ESR-1308 | Most Widely Accepted and Trusted Page 21 of 21 <br />provided the design and installation are in accordance with the 2018 International Building Code (IBC) provisions noted in <br />the evaluation report, and the additional requirements in Sections 2.2.1 through 2.2.2 of this supplement: <br />2.2.1. Conditions of Use: <br />1. All loads applied shall be determined by a registered structural engineer and shall comply with applicable loads from <br />CBC Chapter 16 and its amendments, and Chapter 16A. <br />2. Section 13.5.6.2 of ASCE 7 shall be revised in accordance with CBC Section 1617.11.16 [DSA-SS/CC] and Section <br />1617A.1.21 [DSA-SS]. <br />3. Design and installation shall comply with the requirements of DSA Interpretation of Regulations (IR) DSA IR 25-2.13 <br />and DSA IR 25-3.13 as applicable. <br />2.2.2. Special Inspection Requirements: <br />1. Periodic special inspection is required, in accordance with Section 1705A.12.5 of the CBC [DSA-SS & DSA-SS/CC]. <br />2. Where gypsum wallboard is used in suspended ceiling installations, additional inspection shall be in accordance with <br />CBC Section 2503.2 [DSA-SS, DSA-SS/CC]. <br />This supplement expires concurrently with the evaluation report, reissued December 2022. <br />2130 E 17th St - <br />10111279406/07/23