RECOMMENDED SPECIFICATION FOR LABELS & <br />PLACARDS; <br />· RED LETTERING W/ WHITE BACKGROUND <br />· LETTER HEIGHT OF 3 8" <br />· LETTERS TO BE CAPITALIZED <br />· ARIAL OR SIMILAR FONT <br />· WEATHER RESISTANT <br />· REFLECTIVE <br />ALL LABELS TO BE PLACED ON THE INTERIOR & <br />EXTERIOR OF EVERY; <br />· DC CONDUIT, RACEWAYS, ENCLOSURES & <br />CABLE ASSEMBLIES; <br />·· EVERY 10' <br />·· W/IN 1' OF EVERY TURN & BEND <br />·· W/IN 1' OF ROOF & CEILING <br />ASSEMBLIES; & <br />·· EVERY WALL & BARRIER <br />DIRECTORY PLACARD MUST BE INSTALLED AT <br />THE MAIN SERVICE PANEL SHOWING <br />LOCATION(S) FOR; <br />· MAIN SERVICE DISCONNECTS <br />· PHOTOVOLTAIC SOLAR INSTALLED <br />· EQUIPMENT INSTALLED <br />SIGNAGE NOTES <br />LEGEND <br />WARNING SIGNAGE PLACEMENT <br />PREPARED BY:DATE: <br />PROJECT #: <br />SHEET NAME: <br />SHEET #: <br />PROPOSED EQUIPMENT:SCOPE OF WORK:HOMEOWNER:CONTRACTOR: <br />DRAWING IS TO ILLUSTRATE TYPICAL PLACEMENT OF <br />PLACARDS & LABELING FOR INSPECTION PURPOSE. <br />PLACEMENT TO BE FIELD VERIFIED FOR ACCURACY <br />PV-S.02 <br />SIGNAGE <br />AC DISCONNECT <br />INVERTER <br />MSP-UTILITY <br />SOLAR MODULES <br />CAUTION <br />DO NOT RELOCATE THIS <br />OVERCURRENT DEVICE <br />DUAL POWER SOURCES <br />UTILITY GRID & <br />PHOTOVOLTAIC SOLAR <br />SOLAR CIRCUIT BREAKER <br />DO NOT RELOCATE THIS <br />OVERCURRENT DEVICE <br />IF GROUND FAULT IS INDICATED, <br />ALL NORMALLY FUNCTIONING <br />CONDUCTORS MAY BE <br />UNGROUNDED & ENERGIZED <br />ELECTRIC SHOCK HAZARD <br />EQUIPMENT IS BEING FED BY <br />MULTIPLE SOURCES. TOTAL <br />RATING OF ALL OVER-CURRENT <br />DEVICES, EXCLUDING MAIN <br />POWER SUPPLY, SHALL NOT <br />EXCEED AMPACITY OF BUSBAR <br />POWER OUTPUT SOURCE <br />CONNECTION <br />WARNING <br />WARNING <br />ELECTRIC SHOCK HAZARD <br />PV SOLAR SYSTEM <br />CONNECTED <br />TERMINALS ON BOTH LINE & LOAD <br />SIDE MAY BE ENERGIZED IN THE <br />OPEN POSITION <br />ELECTRIC SHOCK HAZARD RATED AC OUTPUT CURRENT 40.59A <br /> RATED AC OPERATING VOLTAGE 240V <br />PHOTOVOLTAIC SYSTEM <br />AC DISCONNECT <br />UTILITY <br />PV ARRAY <br />J-BOX <br />AC <br />DISCONNECT <br />EQUIPMENT TO BE <br />HUNG @ <br />36" - 75" <br />O.C. MAX. <br />(ABOVE GRADE) <br />MAIN SERVICE PANEL <br />UTILITY METER <br />RAPID SHUTDOWN <br />SWITCH FOR <br />SOLAR PV SYSTEM <br />INVERTER <br />PHOTOVOLTAIC SYSTEM <br />DC DISCONNECT <br /> MAX. SYSTEM CURRENT 42A <br /> MAX. SYSTEM VOLTAGE 480V <br /> MAX. RATED OUTPUT CURRENT 15A <br /> FOR CHRG. CNTLR. (IF INSTALLED) <br />DIRECTORY MAP <br />PLACE ON MSP - UTILITY; CEC 705.10 <br />DUAL POWER SOURCES <br />PLACE ON MSP - UTILITY; NEC 705.12(B)(3) <br />DC CONDUCTORS <br />PLACE ON MSP - UTILITY; NEC 690.35(F) <br />DO NOT ADD LOADS <br />PLACE ON COMB. PANEL - SUB-PANEL; <br />NEC 690.33(E)(2) <br />PV SYSTEM CONNECTED <br />PLACE ON MSP - UTILITY <br />SOLAR C/B - DO NOT RELOCATE <br />PLACE NEAR OCPD IN MAIN <br />JUNCTION BOX (AC) <br />PLACE ON J-BOXES <br />POWER SOURCE OUTPUT <br />PLACE ON MSP-UTILITY; CEC 705.12 (B)(2)(3)(B) <br />DC DISCONNECT RATING <br />PLACE ON DISCONNECT; CEC 690.52 <br />AC DISCONNECT RATING <br />PLACE ON DISCONNECT; CEC 690.52 <br />DO NOT EXCEED BUSBAR <br />PLACE ON MSP - UTILITY; CEC 705.12(B)(2)(3)(C) <br />DO NOT TOUCH TERMINALS <br />PLACE ON MSP - UTILITY; CEC 690.13(B) <br />GROUND FAULT <br />PLACE ON MSP - UTILITY; NEC 690.35(F) <br />· RAPID SHUTDOWN (STRING) <br />· RAPID SHUTDOWN SWITCH <br />PLACEMENT NO LESS THEN 3' OF DISCONNECT; <br />CEC 690.56 - SEC. 690.56(3) <br />· DERATE WARNING <br />· DERATE (#A) <br />PLACE ON MSP-UTILITY <br />*USE WHEN MAIN BREAKER IS DE-RATED <br />CAUTION SOLAR CIRCUIT <br />PLACE EVERY 10', BEFORE & AFTER EVERY BEND; <br />CEC 690.31(G)(3) <br />DC CONDUCTORS TO THIS PV <br />SOLAR SYSTEM MAY BE <br />UNGROUNDED & ENERGIZED <br />ELECTRIC SHOCK HAZARD <br />AC DISCONNECT <br />CAUTION SOLAR CIRCUIT <br />JUNCTION BOX - DC <br />DC DISCONNECT <br />INVERTER #1 <br />ADDITIONAL POWER SOURCE BEING SUPPLIED TO THIS <br />BUILDING WITH DISCONNECTS AS SHOWN: <br />WARNING <br />WARNING <br />WARNING <br />2329 PARK DR. - SANTA ANA - 92707 <br />WARNING <br />WARNING <br />TURN RAPID SHUTDOWN <br />SWITCH TO THE "OFF" <br />POSITION TO SHUTDOWN PV <br />SYSTEM & REDUCE SHOCK <br />HAZARD IN THE ARRAY <br />SOLAR ELECTRIC <br />PV PANELS <br />PV SOLAR SYSTEM <br />EQUIPPED WITH <br />RAPID SHUTDOWN <br />N <br /> xxxA <br />LARSUN SOLAR <br />CSLB: #583458 (C-46) <br />ADDRESS: 439 E HARRISON ST. UNIT E <br />CITY|ZIP: CORONA | CA | 92879 <br />PHONE: (951) 298-9007 <br />best solar <br />3/15/2022 <br />HP-102 <br />INSTALL A NEW 10.56kW (DC)|9.74kW(AC)|9.76kW (CEC AC) PV SOLAR SYSTEM ON AN <br />(E) RESIDENTIAL ROOF. ALL WORK TO BE CONDUCTED UNDER AN ACTIVE CSLB LICENSE <br />& SHALL ADHERE TO ALL FEDERAL|STATE|LOCAL LAWS & CODES. PLEASE REFERENCE <br />ALL CODE(S) THROUGHOUT THIS PLAN SET FOR FULL COMPLIANCE. <br />THE ROD SELLON RESIDENCE <br />2329 PARK DR. <br />SANTA ANA | CA | 92707 <br />APN #: 14014234 <br />ALL-AMERICAN <br />SOLAR SERVICES <br />L.L.C. <br />x AJC <br /> (24) M SOLAR: HC 144BB-440W MOD. <br /> (24) SOLAREDGE: P485 OPTMZR. <br /> (1) SOLAREDGE: SE10000H-US INV. <br />2329 S. Park Drive <br />06/03/22