A-1&3&5 <br />A-1,3,5 <br />A-1+3+5 <br />P, ORPB <br />a,b <br />C <br />B <br />A <br />FLEXIBLE CONNECTION AS REQUIRED. NUMBER OF CONDUCTORS AS REQUIRED. VERIFY CONNECTION REQUIREMENTS WITH MANUFACTURER <br />PRIOR TO ROUGH-IN. <br />UTILITY COMPANY METER. PROVIDE "CT's" AND "PT's" AS REQUIRED, REFER TO SINGLE LINE DIAGRAM. <br />NON-FUSED DISCONNECT SWITCH, HP RATED AND WEATHERPROOF AS REQUIRED. PROVIDE FINAL CONNECTION TO UNIT <br />EQUIPMENT. SEE MOTORIZED EQUIPMENT SCHEDULE FOR DISCONNECT SIZES. <br />FUSED DISCONNECT SWITCH, HP RATED, OR COMBINATION MOTOR STARTER/DISCONNECT SWITCH WITH FUSES PER <br />EQUIPMENT MANUFACTURER AND WEATHERPROOF AS REQUIRED. PROVIDE FINAL CONNECTION TO UNIT EQUIPMENT. SEE <br />MOTORIZED EQUIPMENT SCHEDULE FOR DISCONNECT AND STARTER SIZES. <br />S - PROJECTION SCREEN <br />RL - ROTARY LOCK KEY TYPE <br />BRANCH CIRCUIT SYMBOLS <br />P - PILOT LIGHT <br />M - MOTOR STARTING <br />LV - LOW VOLTAGE <br />a, b, c, ETC. - DESIGNATES QUANTITY OF SWITCHES AT EACH LOCATION. <br />R - REMOTE CONTROL <br />2 - DOUBLE POLE <br />K - KEY OPERATED <br />3 - THREE WAY <br />4 - FOUR WAY <br />PB - PUSHBUTTON <br />SS= PROVIDE SOLID STATE CIRCUIT BREAKER <br />CLCB= CURRENT LIMITING CIRCUIT BREAKER <br />SHUNT= PROVIDE SHUNT TRIP MECHANISM <br />GFP= GROUND FAULT PROTECTION <br />JUNCTION BOX, 4S MINIMUM OR AS REQUIRED BY N.E.C., OR CEC, WHERE ADOPTED. MOUNTED IN ACCESSIBLE CEILING SPACE <br />PER PLAN FOR FLEXIBLE CONNECTION TO PRE-WIRED FURNITURE SYSTEM. MOUNT FLUSH IN FLOOR WHEN INDICATED IN A <br />FLOOR BOX SYMBOL. WHEN SHOWN WITH A DIAGONAL SLASH, THE LAST GENERAL RECEPTACLE CIRCUIT ON THE HOME-RUN <br />CALL OUT SHALL BE CONTROLLED BY THE OCCUPANCY SENSOR. COORDINATE CONTROLLED CIRCUIT CONNECTION <br />REQUIREMENTS WITH FURNITURE SYSTEM MANUFACTURER PRIOR TO ROUGH-IN. SEE DISTRIBUTED LIGHTING CONTROLS FOR <br />ADDITIONAL REQUIREMENTS. <br />POWER SYMBOLS <br />SHUNT= PROVIDE SHUNT TRIP MECHANISM <br />CLF= CURRENT LIMITING FUSE <br />GFP= GROUND FAULT PROTECTION <br />JUNCTION BOX, WALL MOUNTED AT +18-INCHES A.F.F. OR AS NOTED. 4S/DP MINIMUM OR AS REQUIRED BY N.E.C. OR CEC, <br />WHERE ADOPTED. <br />JUNCTION BOX, MOUNTED IN ACCESSIBLE CEILING FOR APPLICATION DENOTED ON PLAN. 4S/DP MINIMUM OR AS REQUIRED <br />BY N.E.C. OR CEC, WHERE ADOPTED. <br />JUNCTION BOX, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. 4S/DP MINIMUM OR AS REQUIRED BY N.E.C., <br />OR CEC, WHERE ADOPTED. <br />JUNCTION BOX, WALL MOUNTED AT +18-INCHES A.F.F., 4S/DP MINIMUM OR AS REQUIRED BY N.E.C., OR CEC, WHERE ADOPTED, <br />FOR FLEXIBLE CONNECTION TO PREWIRED FURNITURE SYSTEM. WHEN SHOWN WITH A DIAGONAL SLASH, THE LAST GENERAL <br />RECEPTACLE CIRCUIT ON THE HOME-RUN CALLOUT SHALL BE CONTROLLED BY THE OCCUPANCY SENSOR. COORDINATE <br />CONTROLLED CIRCUIT CONNECTION REQUIREMENTS WITH FURNITURE SYSTEM MANUFACTURER PRIOR TO ROUGH-IN. SEE <br />DISTRIBUTED LIGHTING CONTROLS FOR ADDITIONAL REQUIREMENTS. <br />SURFACE MOUNTED MULTI-OUTLET ASSEMBLY. REFER TO GENERAL PRODUCT SPECIFICATIONS. PROVIDE ALL COMPONENTS <br />NECESSARY FOR A COMPLETE INSTALLATION. <br />THERMOSTAT OUTLET BOX, PROVIDE 1/2" C.O. TO RESPECTIVE MECHANICAL UNIT. <br />EXHAUST FAN, OR MOTOR LOAD. REFER TO MECHANICAL, PLUMBING OR KITCHEN DRAWINGS FOR SPECIFIC LOAD <br />REQUIREMENTS OR AS NOTED. <br />FLUSH MOUNTED ELECTRICAL PANELBOARD OR LOAD CENTER. REFER TO PANEL SCHEDULE. <br />SURFACE MOUNTED ELECTRICAL PANELBOARD OR LOAD CENTER. REFER TO PANEL SCHEDULE. <br />DISTRIBUTION SWITCHBOARD. REFER TO SINGLE LINE DIAGRAM. <br />TRANSFORMER, REFER TO SINGLE LINE DIAGRAM. <br />HOME RUN TO PANEL. LETTER DESIGNATES PANEL, NUMBERS INDICATE CIRCUITS. HASH MARKS INDICATE NUMBER OF CONDUCTORS IN CONDUIT <br />RUN, #12 AWG MINIMUM UNLESS OTHERWISE NOTED. <br />HOME RUN TO PANEL. LETTER DESIGNATES PANEL, NUMBERS INDICATE CIRCUITS WITH SEPARATE NEUTRALS. "&" INDICATES SEPARATE <br />NEUTRALS. <br />HOME RUN TO PANEL. LETTER DESIGNATES PANEL, NUMBERS INDICATE CIRCUITS. "+" INDICATES SEPARATE #10 NEUTRAL THROUGHOUT BRANCH <br />CIRCUIT. HASH MARK " " INDICATES AN ISOLATED GROUND CONDUCTOR. <br />CONCEALED CONDUIT OR BRANCH CIRCUIT UNLESS OTHERWISE NOTED. 1/2" CONDUIT MINIMUM, (2) #12 AWG CONDUCTORS MINIMUM. <br />CONDUIT OR BRANCH CIRCUIT CONCEALED BELOW GRADE, 3/4" CONDUIT MINIMUM WITH (2) 12 AWG CONDUCTORS MINIMUM AND A CODE SIZED <br />EQUIPMENT GROUND. <br />SURFACE-MOUNTED CONDUIT OR BRANCH CIRCUIT UNLESS OTHERWISE NOTED. 1/2" CONDUIT MINIMUM, (2) #12 AWG CONDUCTORS MINIMUM. <br />INDICATES FINAL CONNECTION TO A LIGHTING FIXTURE, NUMBER OF CONDUCTORS AS REQUIRED. <br />SITE LIGHTING FIXTURE SYMBOLS DEPICTED WITH CAPITAL LETTER(S) ADJACENT TO RESPECTIVE SYMBOL(S) INDICATE(S) LIGHT FIXTURE MOUNTING BASE DETAIL(S). <br />SEE LIGHTING FIXTURE SCHEDULE FOR FIXTURE SYMBOL INFORMATION. <br />LIGHTING FIXTURE CALL OUT, NUMBER(S) AND/OR UPPER CASE LETTER(S) (i.e. "1") INDICATES FIXTURE TYPE (REFER TO LIGHTING <br />FIXTURE SCHEDULE). LOWER CASE LETTER (i.e. "a") ADJACENT TO FIXTURE TYPE INDICATES BALLAST OPTION (SEE GENERAL <br />LIGHTING FIXTURE SCHEDULE NOTES). <br />CIRCUIT BREAKER: "A" REPRESENTS CIRCUIT BREAKER AMPERE RATING, "B" REPRESENTS NUMBER OF POLES AND "C" <br />REPRESENTS MISCELLANEOUS BREAKER FEATURES. <br />FUSIBLE SWITCH: "A" REPRESENTS SWITCH/FRAME AMPERE RATING, "B" REPRESENTS THE FUSE AMPERE RATING, "C" <br />INDICATES NUMBER OF POLES AND "D" REPRESENTS MISCELLANEOUS FUSE/SWITCH FEATURES. <br />SINGLE POLE SWITCHES, WALL MOUNTED. SUBSCRIPTS AT SYMBOL INDICATE THE FOLLOWING: <br />NOTE: ALL WALL SWITCHES CONTROLLING EMERGENCY CIRCUITS SHALL BE ENGRAVED WITH "EMERGENCY". <br />EMERGENCY POWER OFF STATION, WALL MOUNTED PER EPO SYSTEM DETAIL. <br />PULLBOX, SIZED PER N.E.C. OR AS NOTED. <br />GROUND CONNECTION, SIZE AS INDICATED OR AS REQUIRED. <br />TANDEM WIRING CONNECTION. <br />CONDUIT STUB OUT, CAP, MARK AND RECORD ON AS-BUILT DRAWINGS <br />CONDUIT CONTINUATION. <br />CONDUIT/ BRANCH CIRCUIT/FEEDER CONTINUATION DOWN WALL TO FLOOR BELOW <br />CONDUIT/ BRANCH CIRCUIT/FEEDER CONTINUATION UP WALL TO FLOOR ABOVE <br />ALL WALL-MOUNTED EQUIPMENT MOUNTING HEIGHTS SHALL BE VERIFIED PRIOR TO ROUGH-IN PER <br />REQUIREMENTS OF THE DEVICE ALIGNMENT AND MOUNTING HEIGHT DETAILS AND SPECIFICATIONS. <br />WALL MOUNTED DEVICE MOUNTING HEIGHT NOTE: <br />WET LOCATION-LISTED (RAINTITE-IN-USE) RECEPTACLE - SEE ELECTRICAL SPECIFICATION FOR ADDITIONAL INFORMATION.WP-B <br />J <br />J <br />J <br />T <br />T <br />1a <br />J <br />A <br />B <br />C <br />D <br />S <br />M <br />F <br />LO= PROVIDE PERMANENT LOCK-OPEN (OFF) HARDWARE <br />LC= PROVIDE PERMANENT LOCK-CLOSED (ON) HARDWARE <br />ALL RECEPTACLE OUTLETS SHOWN WITH A DIAGONAL SLASH SHALL BE CONTROLLED BY OCCUPANCY SENSOR OR LIGHTING CONTROL PANEL. <br />SEE DISTRIBUTED LIGHTING CONTROLS FOR ADDITIONAL REQUIREMENTS. WHERE DOUBLE DUPLEX RECEPTACLE OUTLETS ARE INDICATED AS <br />CONTROLLED, ONLY A SINGLE DUPLEX RECEPTACLE OUTLET (NON-IG, NON-GCFI TYPE) SHALL BE CONTROLLED. WITHIN ANY CONTROLLED <br />DUPLEX RECEPTACLE OUTLET, ONLY ONE RECEPTACLE SHALL BE CONTROLLED. NOTE THAT FOR FLOOR BOXES OR POKE-THRU DEVICES, THE <br />ASSOCIATED CONTROL RELAY MAY NEED TO BE LOCATED WITHIN THE ELECTRICAL ROOM WHERE THE CONTROLLED CIRCUIT ORIGINATES. <br />J <br />JJ <br />J <br />DUPLEX RECEPTACLES WITH TWO 5V, 3.6A USB CHARGING PORTS. PROVIDE COLOR AS REQUIRED IN 15A OR 20A <br />CONFIGURATION AND/OR TAMPER RESISTANT AND/OR HOSPITAL GRADE AS REQUIRED BY PLANS AND THE WIRING DEVICES <br />SECTION OF THE GENERAL ELECTRICAL SPECIFICATIONS. (PASS & SEYMOUR OR EQUAL BY HUBBELL OR LEVITON.) <br />QUAD RECEPTACLES WITH TWO 5V, 3.6A USB CHARGING PORTS. PROVIDE COLOR AS REQUIRED IN 15A OR 20A <br />CONFIGURATION AND/OR TAMPER RESISTANT AND/OR HOSPITAL GRADE AS REQUIRED BY PLANS AND THE WIRING DEVICES <br />SECTION OF THE GENERAL ELECTRICAL SPECIFICATIONS. (PASS & SEYMOUR OR EQUAL BY HUBBELL OR LEVITON.) <br />DUPLEX RECEPTACLE, ONE HALF SWITCHED, FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX <br />SYMBOL. <br />SIMPLEX RECEPTACLE FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />SPECIAL RECEPTACLE FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />DUPLEX RECEPTACLE FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />DUPLEX, ISOLATED GROUND RECEPTACLE, FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX <br />SYMBOL. <br />DOUBLE DUPLEX RECEPTACLE FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />DUPLEX RECEPTACLE, WALL MOUNTED. <br />DOUBLE DUPLEX RECEPTACLE, WALL MOUNTED. <br />DUPLEX, GFCI RECEPTACLE, WALL MOUNTED. WP INDICATES WEATHERPROOF, A, B OR C INDICATES THE TYPE OF COVER, <br />REFER TO THE GENERAL PRODUCT SPECIFICATIONS. <br />DOUBLE DUPLEX, WALL MOUNTED, WITH (1) GFCI RECEPTACLE AND (1) DUPLEX RECEPTACLE CONNECTED ON LOAD SIDE OF <br />GFCI. WP INDICATES WEATHERPROOF, A, B OR C INDICATES THE TYPE OF COVER, REFER TO THE GENERAL PRODUCT <br />SPECIFICATIONS. <br />DUPLEX RECEPTACLE, ONE HALF SWITCHED, WALL MOUNTED. <br />DUPLEX, ISOLATED GROUND RECEPTACLE, WALL MOUNTED. <br />SIMPLEX RECEPTACLE, WALL MOUNTED. <br />SPECIAL RECEPTACLE, WALL MOUNTED. REFER TO PLAN NOTES. <br />COMBINATION DOUBLE DUPLEX: ONE ISOLATED GROUND DUPLEX RECEPTACLE AND ONE DUPLEX RECEPTACLE, WALL <br />MOUNTED. <br />COMBINATION DOUBLE DUPLEX: ONE ISOLATED GROUND DUPLEX RECEPTACLE AND ONE DUPLEX RECEPTACLE, MOUNTED <br />FLUSH IN CEILING - MOUNT FLUSH IN FLOOR WHEN INDICATED IN FLOOR BOX SYMBOL. <br />DUPLEX RECEPTACLE, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. <br />DOUBLE DUPLEX RECEPTACLE, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. <br />DUPLEX, GFCI RECEPTACLE, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. WP INDICATES WEATHERPROOF, A, B <br />OR C INDICATES THE TYPE OF COVER, REFER TO THE GENERAL PRODUCT SPECIFICATIONS. <br />DOUBLE DUPLEX, WALL MOUNTED 6-INCHES ABOVE COUNTER OR SPLASH, WITH (1) GFCI RECEPTACLE AND (1) DUPLEX <br />RECEPTACLE CONNECTED ON LOAD SIDE OF GFCI. WP INDICATES WEATHERPROOF, A, B OR C INDICATES THE TYPE OF <br />COVER, REFER TO THE GENERAL PRODUCT SPECIFICATIONS. <br />DUPLEX RECEPTACLE, BOTTOM HALF SWITCHED, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. <br />DUPLEX, ISOLATED GROUND RECEPTACLE, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. <br />COMBINATION DOUBLE DUPLEX: ONE ISOLATED GROUND DUPLEX RECEPTACLE AND ONE DUPLEX RECEPTACLE, WALL <br />MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. <br />SIMPLEX RECEPTACLE, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. <br />SPECIAL RECEPTACLE, WALL MOUNTED AT 6-INCHES ABOVE COUNTER OR SPLASH. REFER TO PLAN NOTES. <br />1,3a <br />1,3a <br />1,3a <br />COMBINATION DOUBLE DUPLEX: TWO ISOLATED GROUND RECEPTACLES, WALL MOUNTED. <br />COMBINATION DOUBLE DUPLEX FLUSH IN CEILING: TWO ISOLATED GROUND RECEPTACLES - MOUNT FLUSH IN FLOOR WHEN <br />INDICATED IN FLOOR BOX SYMBOL. <br />COMBINATION DOUBLE DUPLEX: TWO ISOLATED GROUND DUPLEX RECEPTACLES, WALL MOUNTED AT 6-INCHES ABOVE <br />COUNTER OR SPLASH. <br />FIRE ALARM SYSTEM SYMBOLS <br />SIGNAL SYSTEM SYMBOLS <br />PROJECT SPECIFIC SYMBOLS <br />CCTV SYSTEM SYMBOLS <br />GROUNDGRD <br />PA PUBLIC ADDRESS <br />UNDERGROUND PULL SECTION <br />VOLTAGE DROP <br />UNINTERRUPTABLE POWER SYSTEM <br />TRANSFORMER <br />VARIABLE AIR VOLUME <br />SHORT CIRCUIT CURRENT <br />TRANSIENT VOLTAGE SURGE <br />STRUCTURED CABLING SYSTEM <br />ROOT MEAN SQUARE <br />RECEPTACLE <br />WEATHERPROOF <br />UNLESS OTHERWISE NOTED <br />VOLT AMPERES <br />RIGID GALVANIZED STEEL <br />600 VOLTS AND LESS <br />TELEPHONE AND DATA <br />REFRIGERATOR <br />VD <br />U.P.S. or UPS <br />XFMR <br />VAV <br />VA <br />V <br />W <br />WP <br />VOLTS <br />WIRE <br />U.G.P.S. <br />SCC <br />T.V.S.S. <br />SCS <br />RMS <br />REF <br />RGS <br />SQ. <br />TV <br />TC <br />TEL/DATA <br />U.O.N. <br />TYP <br />REC, RECEPT <br />SECONDARY <br />SQUARE <br />TYPICAL <br />TELEVISION <br />TIMECLOCK <br />MERCURY VAPOR <br />POWER DISTRIBUTION UNIT <br />POLY VINYL CHLORIDE <br />PLUMBING CONTRACTOR <br />PERCENT IMPEDANCE <br />NOT TO SCALE <br />NATIONAL ELECTRICAL <br />MINIMUM CIRCUIT AMPS <br />MOTOR CIRCUIT PROTECTOR <br />NON AUTOMATIC DISCONNECT <br />MANUFACTURER <br />THOUSAND CIRCULAR MILS <br />MOTOR CONTROL CENTER <br />METAL HALIDE <br />POTENTIAL TRANSFORMER <br />FURNISH, INSTALL AND CONNECT <br />OVER 600 VOLTS <br />NORMALLY OPENED <br />NORMALLY CLOSED <br />NOT IN CONTRACT <br />OWNER FURNISHED, <br />PDU <br />PVC <br />P.C. <br />%Z <br />N.T.S. <br />OFCI <br />NL <br />NO. or # <br />PC <br />PH. or ø <br />PRIMARY <br />PT <br />PROVIDE <br />P POLE <br />NUMBER <br />PHASE <br />PHOTOCELL <br />NIGHT LIGHT <br />NEMA <br />MCA <br />MIN. <br />MCP <br />MCC <br />MCM <br />NEC <br />MTD <br />MW <br />MFR. <br />MH <br />NO <br />NC <br />NF <br />NIC <br />MOUNTED <br />MICROWAVE <br />NON-FUSED <br />MINIMUM <br />MECHANICAL CONTRACTOR <br />MAXIMUM OVERCURRENT PROTECTION <br />KILOWATT HOUR <br />GROUND FAULT CIRCUIT INTERRUPTER <br />GROUND FAULT PROTECTION <br />GROUNDING ELECTRODE CONDUCTOR <br />HEATING AIR CONDITIONING <br />LONG CONTINUOUS LOAD <br />KILOVOLT AMPERES <br />HIGH PRESSURE SODIUM <br />ISOLATED GROUND <br />JUNCTION BOX <br />DEGREE KELVIN <br />HIGH INTENSITY DISCHARGE <br />HEIGHT, WIDTH, DEPTH, LENGTH <br />HAND-OFF-AUTO <br />HORSEPOWER <br />LOW PRESSURE SODIUM <br />MAIN CIRCUIT BREAKER <br />MAIN LUGS ONLY <br />HEATING, VENTILATING AND AIR <br />M.C. <br />MOCP <br />M/M <br />M <br />KWH <br />LCL <br />KW <br />KVA <br />LPS <br />MAX. <br />MCB <br />MV <br />MLO <br />MAXIMUM <br />METER MAIN <br />METER <br />KILOWATT <br />GFCI <br />GFP <br />GE or GEC <br />HACR <br />HOA <br />HVAC <br />H.,W.,D.,L. <br />HPS <br />HP <br />HID <br />I/G <br />JBOX <br />K <br />IN. or ''INCHES <br />ANNOTATIONS <br />S <br />V <br />V <br />M <br />TV <br />AVERAGEAVG <br />CURRENT TRANSFORMER <br />CURRENT LIMITING FUSE <br />CONTROL POWER TRANSFORMER <br />CONDUIT ONLY, COMPLETE WITH <br />CIRCUIT BREAKER <br />COMBINATION SMOKE FIRE DAMPER <br />CURRENT LIMITING CIRCUIT BREAKER <br />DISTRIBUTION <br />ENERGY MANAGEMENT CONTROL SYSTEM <br />ELECTRICAL METALLIC TUBING <br />ELECTRIC WATER COOLER <br />ELECTRICAL NON-METALLIC TUBING <br />ELECTRICAL CONTRACTOR <br />EMERGENCY POWER OFF <br />END-OF-LINE CIRCUIT TERMINATOR <br />EQUIPMENT GROUND (GREEN) <br />EXISTING DEVICE TO REMAIN <br />EXPLOSION PROOF <br />FULL LOAD AMPS <br />EXHAUST FAN <br />DIST <br />EMS <br />EMT <br />ENT <br />EWC <br />E.C. <br />E.P.O. <br />E-O-L <br />(E) <br />EGC or EG or E/G <br />EP <br />FA or F.A. <br />FLA <br />FT or ' <br />EF <br />FEET <br />FIRE ALARM <br />C <br />C.O. <br />BR <br />BLDG <br />CB <br />CIRC., CKT. <br />CSFD <br />DIA <br />CT <br />CLF <br />CPT <br />CLCB <br />DISC <br />CONN CONNECTED <br />DIAMETER <br />DISCONNECT <br />CONDUIT <br />BUILDING <br />CIRCUIT <br />BRANCH <br />AMERICAN WITH DISABILITIES ACT <br />4" SQUARE BY 2-1/8" DEEP BOX <br />ABOVE FINISH FLOOR <br />AMPERES INTERRUPTING CAPACITY <br />AMERICAN WIRE GAUGE <br />AMP FRAME, AMP TRIP <br />AMP SWITCH, AMP FUSE <br />AUTOMATIC TRANSFER SWITCH <br />ABOVE FINISH GRADE <br />ABBREVIATIONS <br />A.F.F. <br />4S/DP <br />ADA <br />AS/AF <br />AF/AT <br />A.I.C. or AIC <br />AMP, A <br />AWG <br />ATS <br />A.F.G. <br />AMPERE <br />C <br />B <br />SECURITY ALARM SYSTEM SYMBOLS <br />TELEPHONE OUTLET BOX, FLUSH MOUNTED IN CEILING - MOUNT FLUSH IN FLOOR <br />WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />DATA OUTLET BOX FLUSH MOUNTED IN CEILING - MOUNT FLUSH IN FLOOR WHEN <br />INDICATED IN A FLOOR BOX SYMBOL. <br />COMBINATION TELEPHONE AND DATA OUTLET BOX FLUSH MOUNTED IN CEILING - <br />MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />COMBINATION TELEPHONE AND DATA OUTLET BOX MOUNTED IN ACCESSIBLE CEILING <br />SPACE OR IN FLOOR BOX PER PLAN FOR FLEXIBLE CONNECTION TO FURNITURE <br />SYSTEM. VERIFY CONNECTION REQUIREMENTS WITH MANUFACTURER PRIOR TO <br />ROUGH-IN - MOUNT FLUSH IN FLOOR WHEN INDICATED IN A FLOOR BOX SYMBOL. <br />TELEPHONE/DATA SYMBOLS <br />CONCEALED TELEPHONE/DATA CONDUIT RUN, 1-INCH CONDUIT ONLY (MIN). SEE <br />TABLE FOR CONDUIT SIZE VARIATIONS. <br />IN A RATED WALL, PROVIDE (1) 4S/DP BOX WITH (2) 1-1/4" C.O. AND (1) 4S/DP BOX <br />WITH (1) 1-1/4" C.O. WITH PULL STRINGS IN EACH CONDUIT TO ACCESSIBLE <br />CEILING. PROVIDE 1-1/4" BUSHINGS AT CONDUIT ENDS. UTILIZE CADDY #RBS <br />SERIES BOX MOUNTING BRACKET TO MAINTAIN BOX ALIGNMENT (EQUAL BY B-LINE <br />OR RAYCO). UTILIZE FIRESTOPPING SYSTEM PADS RATED FOR USE ON THE INSIDE <br />OR OUTSIDE OF THE BOX (STI OR EQUAL) AS REQUIRED TO MAINTAIN RATING OF <br />WALL OR MEMBRANE. REFER TO ARCHITECTURAL PLANS FOR WALL <br />CONSTRUCTION/TYPE AND CEILING CONDITIONS. <br />IN A NON-RATED INSULATED WALL, OR NON-RATED UNINSULATED WALL, PROVIDE <br />A 2-GANG MUD RING OR CADDY #RBS SERIES BOX MOUNTING BRACKET (EQUAL BY <br />B-LINE OR RAYCO) WITH (2) 1-1/2"C.O. WITH PULL STRING TO ACCESSIBLE CEILING. <br />PROVIDE 1-1/2" BUSHINGS AT CONDUIT ENDS. REFER TO ARCHITECTURAL PLANS <br />FOR WALL CONSTRUCTION/TYPE AND CEILING CONDITIONS. <br />- <br />- <br />T4 = 2" C.O.T3 = 1-1/2" C.O.T2 = 1-1/4" C.O. <br />COMBINATION TELEPHONE AND DATA OUTLET, WALL MOUNTED AT +18-INCHES A.F.F. <br />FOR FLEXIBLE CONNECTION TO FURNITURE SYSTEM. PROVIDE THE FOLLOWING: <br />SEE FIRE ALARM OR CENTRAL MONITORING SYSTEM DRAWINGS FOR FIRE ALARM SYMBOLS. <br />SFD SMOKE FIRE DAMPER <br />NATS <br />NATIONAL ELECTRICAL CODE <br />AUTHORITY HAVING JURISDICTIONAHJ <br />CEC CALIFORNIA ELECTRICAL CODE <br />INTERMEDIATE DISTRIBUTION FRAMEIDF <br />MAIN DISTRIBUTION FRAMEMDF <br />BDF BUILDING DISTRIBUTION FRAME <br />SHEET METAL AND AIR COND.SMACNA <br />THOUSAND CIRCULAR MILSKCMIL <br />REQUIRED SPECIFICATION DEVIATIONS <br />THE FOLLOWING ITEM(S) ARE REQUIRED DEVIATIONS FROM THE DRAWINGS AND SPECIFICATIONS AND <br />SHOULD BE INCLUDED AS PART OF THE BASE BID. THESE DEVIATIONS ARE AT THE DIRECTION OF THE <br />OWNER: <br />THE FOLLOWING ITEM(S) ARE ALLOWED DEVIATIONS FROM THE DRAWINGS AND SPECIFICATIONS. <br />THESE DEVIATIONS ARE AT THE DIRECTION OF THE OWNER: <br />ALLOWED SPECIFICATION DEVIATIONS <br />DEDUCTIVE/ADDITIVE ALTERNATE PRICING <br />IN ADDITION TO ANY DEDUCTIVE OR ADDITIVE LINE ITEM PRICING CALLED FOR ON THE DRAWING OR IN <br />THE SPECIFICATIONS, CONTRACTOR SHALL PROVIDE SEPARATE LINE ITEM DEDUCTIVE/ADDITIVE <br />ALTERNATE PRICING FOR EACH OF THE FOLLOWING ITEM(S): <br />NONE <br />NONE <br />NONE <br />CONTRACTOR'S NAT'L ASSOC. <br />(SYMMETRICAL)CONDITIONING <br />MANUFACTURER'S ASSOCIATION <br />CONTRACTOR INSTALLED <br />SUPPRESSION <br />PULLSTRING <br />REFRIGERATION <br />SA <br />WALL MOUNTED CLOCK. FIELD VERIFY MOUNTING HEIGHT PRIOR TO INSTALLATION. "B" <br />INDICATES BATTERY OPERATED CLOCK. "D" INDICATES DIGITAL CLOCK, "NO LETTER" <br />INDICATES ANALOG CLOCK. REFER TO SPECIFICATIONS. <br />CONCEALED CLOCK CONDUIT RUN 1/2" CONDUIT, OR AS NOTED, WITH CONDUCTORS PER <br />SPECIFICATIONS. <br />TV OUTLET, WALL MOUNTED. STUB A 3/4" C.O. UP 6" ABOVE THE ACCESSIBLE CEILING AND <br />PROVIDE BUSHING. <br />TV OUTLET FLUSH CEILING MOUNTED. <br />CONCEALED TELEVISION CONDUIT RUN, 3/4" CONDUIT, OR AS NOTED, WITH CONDUCTORS <br />- REFER TO SPECIFICATIONS. <br />MICROPHONE OUTLET, WALL MOUNTED. PROVIDE 3/4" C.O. (WITH PULL ROPE) UP TO 6" <br />ABOVE ACCESSIBLE CEILING SPACE. PROVIDE BUSHING AT EACH END. <br />MICROPHONE OUTLET, FLUSH CEILING MOUNTED. <br />CONCEALED MICROPHONE CONDUIT RUN, 3/4" CONDUIT, OR AS NOTED, WITH <br />CONDUCTORS - REFER TO SPECIFICATIONS. <br />SURFACE WALL MOUNTED SPEAKER, "V" INDICATES VOLUME CONTROL. <br />SURFACE MOUNTED SPEAKER , "V" INDICATES VOLUME CONTROL. <br />FLUSH WALL MOUNTED SPEAKER , "V" INDICATES VOLUME CONTROL. <br />CEILING FLUSH MOUNTED SPEAKER , "V" INDICATES VOLUME CONTROL. <br />VOLUME CONTROL, WALL MOUNTED. <br />CONCEALED SPEAKER CONDUIT RUN 3/4" CONDUIT, OR AS NOTED, WITH CONDUCTORS - <br />REFER TO SPECIFICATIONS. <br />V <br />V <br />PANEL CALLOUT, "A" INDICATES PANELBOARD OR EQUIPMENT DESIGNATION. <br />MECHANICAL EQUIPMENT CALLOUT, "AC" INDICATES UNIT TYPE AND "2" INDICATES <br />UNIT NUMBER. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION AND <br />ELECTRICAL REQUIREMENTS. <br />DETAIL CALLOUT, "3" INDICATES DETAIL NUMBER "E-1" INDICATES SHEET NUMBER. <br />PLAN NOTE REFERENCE, REFER TO NOTES ON SHEET, OR AS DIRECTED. <br />REVISION REFERENCE. <br />WYE CONFIGURATION DELTA CONFIGURATION GROUND <br />VIDEO MANAGEMENT SYSTEM - CCTV HEADEND - SEE SPECIFICATIONS. <br />CCTV WORKSTATION AND MONITOR - SEE SPECIFICATIONS. <br />CCTV FIXED POSITION CAMERA - SEE SPECIFICATIONS. <br />CCTV PAN/TILT CAMERA - SEE SPECIFICATIONS. <br />CCTV SYSTEM BRANCH CIRCUIT PER CCTV SYSTEM RISER DIAGRAM AND/OR <br />SPECIFICATIONS. <br />"W" = <br />"P" = <br />TELEPHONE OUTLET BOX, WALL MOUNTED. STUB A 1" C.O. UP 6" ABOVE THE <br />ACCESSIBLE CEILING AND PROVIDE A BUSHING. 4S/DP MINIMUM WITH SINGLE GANG <br />RING. <br />WALL MOUNTED PHONE <br />PUBLIC (PAY) PHONE. VERIFY ALL REQUIREMENTS WITH THE TELEPHONE <br />UTILITY COMPANY. PROVIDE 1" C.O. (MIN) TO THE MAIN TELEPHONE <br />BACKBOARD. MOUNTING HEIGHT AS REQUIRED. <br />DATA OUTLET BOX, WALL MOUNTED. STUB A 1" C.O. UP 6-INCHES ABOVE THE <br />ACCESSIBLE CEILING AND PROVIDE A BUSHING. 4S/DP MINIMUM WITH SINGLE GANG <br />RING. <br />COMBINATION TELEPHONE AND DATA OUTLET BOX, WALL MOUNTED. STUB A 1" C.O. <br />UP 6-INCHES ABOVE THE ACCESSIBLE CEILING AND PROVIDE A BUSHING. 4S/DP <br />MINIMUM WITH SINGLE GANG RING. <br />TELEPHONE OUTLET BOX, WALL MOUNTED 6-INCHES ABOVE COUNTER OR SPLASH. <br />STUB A 1" C.O. UP 6-INCHES ABOVE THE ACCESSIBLE CEILING AND PROVIDE A <br />BUSHING. 4S/DP MINIMUM WITH SINGLE GANG RING. <br />DATA OUTLET BOX, WALL MOUNTED 6-INCHES ABOVE COUNTER OR SPLASH. STUB A <br />1" C.O. UP 6-INCHES ABOVE THE ACCESSIBLE CEILING AND PROVIDE A BUSHING. <br />4S/DP MINIMUM WITH SINGLE GANG RING. <br />COMBINATION TELEPHONE AND DATA OUTLET BOX, WALL MOUNTED 6-INCHES ABOVE <br />COUNTER OR SPLASH. STUB A 1" C.O. UP 6-INCHES ABOVE THE ACCESSIBLE CEILING <br />AND PROVIDE A BUSHING. 4S/DP MINIMUM WITH SINGLE GANG RING. <br />T1 <br />FLUSH MOUNTED, LOCKABLE TERMINAL CABINET WITH TERMINAL STRIPS AS <br />REQUIRED. <br />SURFACE MOUNTED, LOCKABLE TERMINAL CABINET WITH TERMINAL STRIPS AS <br />REQUIRED. <br />TELEPHONE TERMINAL BACKBOARD SIZED AS NOTED, REFER TO SYSTEM GROUND <br />DETAIL. <br />SECURITY ALARM CONTROL PANEL - SEE SPECIFICATIONS. <br />SECURITY SYSTEM POWER SUPPLY - SEE SPECIFICATIONS. <br />SECURITY ALARM PASSIVE INFRARED MOTION SENSOR - SEE SPECIFICATIONS. <br />SECURITY ALARM DUAL TECHNOLOGY MOTION SENSOR - SEE SPECIFICATIONS. <br />SECURITY ALARM ULTRASONIC MOTION SENSOR - SEE SPECIFICATIONS. <br />SECURITY ALARM DOOR CONTACT - SEE SPECIFICATIONS. <br />SECURITY ALARM PANIC BUTTON - SEE SPECIFICATIONS. <br />SECURITY ALARM KEY PAD - SEE SPECIFICATIONS. <br />SECURITY ALARM GLASS BREAK INDICATOR - SEE SPECIFICATIONS. <br />SECURITY ALARM SYSTEM BRANCH CIRCUIT PER SECURITY ALARM RISER DIAGRAM <br />AND/OR SPECIFICATIONS. <br />(R) <br />(ER) <br />DENOTES RELOCATED DEVICE <br />EXISTING DEVICE TO BE RELOCATED <br />(D)EXISTING DEVICE TO BE DEMOLISHED <br />CBC CALIFORNIA BUILDING CODE <br />LIGHTINGLTG, LTS <br />LINEAR FEETLF, L.F. <br />INTERNATIONAL BUILDING CODEIBC <br />TV <br />TV <br />M <br />2 <br />4 <br />3 <br />E-1 <br />AC <br />2 <br />A <br />CC <br />CCVMS <br />CCWS <br />SACP <br />SPS <br />ID <br />DT <br />UD <br />DC <br />PB <br />KP <br />GB <br />M <br />S <br />S <br />V <br />S <br />S <br />BJ BONDING JUMPER <br />SSBJ SUPPLY SIDE BONDING JUMPER <br />SBJ SYSTEM BONDING JUMPER <br />MAIN BONDING JUMPERMBJ <br />LOCATION. <br />OCCUPANCY SENSOR/LIGHTING CONTROL SYSTEM CONTROLLED RECEPTACLE RELAY. WHERE LETTER DESIGNATION "a" <br />REPRESENTS OCCUPANCY SENSOR/LIGHTING CONTROL SYSTEM CONTROL ZONE. SEE THE DISTRIBUTED LIGHTING CONTROL <br />SPECIFICATION FOR MORE INFORMATION. <br />R a <br />LIGHTING SYMBOLS <br />1,3 <br />1,3 <br />1,3 <br />DIMMING PANEL CONTROL STATIOND.P.C.S. <br />INTEGRATED DIMMING CONTROL PANELI.D.C.S. <br />SHORT CIRCUIT CURRENT RATINGSCCR <br />AVAILABLE FAULT CURRENTA.F.C. or AFC <br />ABOVE CEILING MOUNTED SPEAKER , "V" INDICATES VOLUME CONTROL.VSM <br />DAMP LOCATION-LISTED (NOT-RAINTITE-IN-USE) RECEPTACLE - SEE ELECTRICAL SPECIFICATION FOR ADDITIONAL <br />INFORMATION. <br />WP-D <br />DISTRIBUTED ANTENNA SYSTEMDAS <br />LIGHTING CONTROL SYMBOLS <br />y+ <br />y+ <br />WALL MOUNTED SYSTEM-BASED OCCUPANCY SENSOR. <br />AUTOMATIC SWITCHING/STEP-DIMMING DAYLIGHTING CONTROLLER USED TO SWITCH OFF LIGHTS WHEN SUFFICIENT NATURAL LIGHT <br />IS PRESENT. REFER TO THE DLCS SOO FOR TARGET ILLUMINATION VALUE. <br />AUTOMATIC CONTINUOUS DIMMING DAYLIGHTING CONTROLLER USED TO DIM LIGHTS WHEN SUFFICIENT NATURAL LIGHT IS PRESENT. <br />REFER TO THE DLCS SOO FOR TARGET ILLUMINATION VALUE. <br />LOW VOLTAGE MOMENTARY SWITCHES, WALL MOUNTED, FOR MANUAL ON/OFF SWITCHING, DIMMING, AND OVERRIDE CONTROL OF <br />LIGHTING. <br />WALL MOUNTED DIMMER. SEE SINGE POLE SWITCH SYMBOL FOR RELATED SUBSCRIPTS. QUANTITY OF ADJACENT LOWER CASE <br />LETTERS INDICATES QUANTITY OF DIMMERS REQUIRED. PROVIDE DIMMER TYPE TO MATCH INDICATED BALLAST TYPE AND CONTROL <br />REQUIREMENTS. <br />H,AV,DM,P <br />LIGHTING CONTROL SYMBOL SUPERSCRIPT & SUBSCRIPT KEY: <br />1-WAY DIRECTIONAL CEILING MOUNTED, SYSTEM-BASED OCCUPANCY SENSOR. <br />H <br />y WALL MOUNTED STAND ALONE OCCUPANCY SENSOR. <br />y <br />y <br />"y" INDICATES THAT SWITCH LEG "y" TO BE CONFIGURED PER THE SOO. ADJACENT LOWER CASE LETTERS INDICATES QUANTITY OF SWITCHLEGS TO BE <br />CONTROLLED. EXACT CONTROL FUNCTION IS DETERMINED BY THE BALLAST/DRIVER/FIXTURE TYPE. <br />1. <br />H,AV,DM,P <br />y <br />D <br />S <br />D <br />L <br />X <br />SEE THE DISTRIBUTED LIGHTING CONTROL (DLCS) SPECIFICATIONS AND SEQUENCE OF OPERATIONS (SOO) FOR MORE INFORMATION. <br />2. <br />ADJACENT LOWER CASE LETTER(S) INDICATE SWITCH LEG(S) CONTROLLED EXCEPT WHERE "DM" INDICATES DUAL MODE CONTROL SWITCH. <br />ADJACENT "+, ++ AND *" INDICATES PORTION OF SWITCHLEG CONTROLLED BY SENSOR WHERE "+" INDICATES PRIMARY SIDELIT DAYLIT ZONE, "++" <br />INDICATES SECONDARY SIDELIT DAYLIT ZONE, AND "*" INDICATES SKYLIT DAYLIT ZONE. <br />3. <br />K,V <br />y <br />2-WAY DIRECTIONAL CEILING MOUNTED, SYSTEM-BASED OCCUPANCY SENSOR. <br />ADJACENT UPPER CASE LETTER(S) INDICATE THE FOLLOWING: <br />K INDICATES LOCKING SWITCH FOR THE SUBSEQUENT LOWER CASE LETTER. <br />V INDICATES VANDAL RESISTANT SWITCH. <br />P INDICATES CONNECTION TO MOVEABLE PARTITION INTERFACE, SENSOR AND STATUS INDICATOR. <br /> H INDICATES CONNECTION TO HVAC SYSTEM CONTROLS VIA CONTROLLED DRY-CONTACT CLOSURE. <br />AV INDICATES CONNECTION TO A/V CONTROL SYSTEM. <br />DM INDICATES DUAL MODE CONTROL AT CORRIDORS, STAIRWELLS AND WAREHOUSE AISLEWAYS <br />4. <br />LOW VOLTAGE WIRING INTERCONNECTING DLCS COMPONENTS AS REQUIRED. SEE DLCS SPECIFICATIONS FOR MORE INFORMATION. <br />tk1sc project number: B2305501.000 <br />drawn by:checked by: <br />drawing no.: <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />pl <br />a <br />n <br />n <br />i <br />n <br />g <br />in <br />t <br />e <br />r <br />i <br />o <br />r <br />s <br />tB <br />P <br />/ <br />A <br />r <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />46 <br />1 <br />1 <br /> <br />T <br />e <br />l <br />l <br />e <br />r <br /> <br />A <br />v <br />e <br />n <br />u <br />e <br />Ne <br />w <br />p <br />o <br />r <br />t <br /> <br />B <br />e <br />a <br />c <br />h <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />6 <br />0 <br />ph <br />: <br /> <br />9 <br />4 <br />9 <br />. <br />6 <br />7 <br />3 <br />. <br />0 <br />3 <br />0 <br />0 <br />consultant <br />agency <br />owner <br />date: <br />drawing title: <br />description:date:Rev: <br />tBP project number : <br />architect <br />THIS DRAWING AND THE DESIGNS, DEPICTIONS, IDEAS AND OTHER INFORMATION <br />CONTAINED HEREIN CONSTITUTE UNPUBLISHED WORK OF tBP/ARCHITECTURE AND <br />SHALL REMAIN THE PROPERTY OF tBP/ARCHITECTURE IN PERPETUITY. NO PART <br />THEREOF SHALL BE REPRODUCED, DISCLOSED, DISTRIBUTED, SOLD, PUBLISHED OR <br />OTHERWISE USED IN ANY WAY WITHOUT THE ADVANCED EXPRESS WRITTEN CONSENT <br />OF tBP/ARCHITECTURE. <br />ph: 714.667.2700 <br />SANTA ANA, CA 92701 <br />20 CIVIC CENTER PLAZA <br />SANTA ANA PLANNING AND BUILDING AGENCY <br /># <br />DA <br />N <br />C <br />E <br /> <br />S <br />T <br />U <br />D <br />I <br />O <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />L <br />I <br />F <br />O <br />R <br />N <br />I <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />12 <br />0 <br />2 <br /> <br />W <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />MA <br />T <br />E <br />R <br /> <br />D <br />E <br />I <br /> <br />H <br />I <br />G <br />H <br /> <br />S <br />C <br />H <br />O <br />O <br />L <br />21125.00 <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />L <br />I <br />F <br />O <br />R <br />N <br />I <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />12 <br />0 <br />2 <br /> <br />W <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />MA <br />T <br />E <br />R <br /> <br />D <br />E <br />I <br /> <br />H <br />I <br />G <br />H <br /> <br />S <br />C <br />H <br />O <br />O <br />L <br />21125.00 <br />09/06/2023 <br />11870 Pierce Street, Suite 160 <br />Riverside, California 92505 <br />951.299.4160 www.tk1sc.com <br />Project Leader - Bill Voller <br />tk1sc Job #: B2305501.000 <br />Electrical Lead - Marie Rothenberger <br />City Submittal 09/06/23- <br />SYMBOL LIST <br />E0-1 <br />21159.00 <br />1202 W Edinger <br />Ave10/3/2024