Y.
<br />Z.
<br />AA.
<br />BB.
<br />CC.Seismic Design, Certification, and Anchoring of Electrical Equipment:
<br />1.
<br />3.
<br />5.
<br />2.
<br />Terminal Cabinets:
<br />Outlet Boxes:
<br />1.
<br />6.
<br />4.
<br />3.
<br />2.
<br />1.
<br />3.
<br />a.
<br />DD.
<br />6.
<br />8.
<br />7.
<br />9.
<br />Aluminum conductors shall not be used.
<br />No conductors carrying 120V or more shall be smaller than #12 AWG.
<br />X.
<br />2.
<br />1.
<br />Junction and Pullboxes:
<br />For fixtures, boxes shall be galvanized, one-piece drawn steel, knockout type equipped with 3/8" fixture studs
<br />and plaster rings where required.
<br />Trenching and Backfilling: Contractor shall be responsible for trenching and backfilling. Refer to applicable
<br />trenching and backfilling specifications for complete requirements.
<br />Contractor shall include all costs in the base bid for labor, materials, all special inspections and structural
<br />engineering design necessary to meet the Seismic Design Requirements for Non-structural Components
<br />(Chapter 13, ASCE/SEI 7-16 Minimum Design loads for Buildings and Other Structures) as required by IBC, or
<br />CBC where adopted, Section 1617A and as related to the installation of all electrical equipment furnished
<br />under this contract. See Specific Project Site Seismic Criteria on architectural and/or structural plans which
<br />include Building Occupancy Category, Seismic Design Category, Design Spectral Response Acceleration
<br />(SDS), Height factor ratio (z/h) and Site Class. Non-structural Component Importance Factor (IP) for a particular
<br />component shall be determined based on the following criteria:
<br />Painting: Terminal cabinets, panels, junction boxes, pull boxes, etc., and conduit installed in public view shall be
<br />painted with colors selected by the Architect to match the subject surface. Refer to painting section of the
<br />specifications for additional requirements.
<br />All terminal cabinets and terminal cabinet barriered sections shall be labeled by the cabinet or cabinet section
<br />use (i.e. CATV, Security, etc.). Labels shall be Micarta type as specified elsewhere in these specifications.
<br />Unless otherwise noted, all termination blocks and cables shall be labeled per ANSI/EIA 606 standard.
<br />Terminal cabinets shall be installed complete with full-length skirts of the same construction and finish as the
<br />terminal cabinet.
<br />Provide each terminal cabinet with a full size mounting backplate.
<br />Terminal cabinets shall be fabricated of hot dipped galvanized code gauge sheet metal for flush or surface
<br />mounting, complete with barriered sections, a door for each vertically barriered section, and sizes as indicated
<br />on plan. Doors shall be hinged and lockable. Locks shall be keyed to match the branch circuit panelboards.
<br />Terminal cabinet trims shall match the branch circuit panels.
<br />Plywood Backboards: Where indicated for telephone or communications system terminals or other equipment
<br />assemblies, provide backboards of size indicated. Use 3/4" thick x 8' tall (length per plans), Douglas Fir, void-free,
<br />kiln-dried, fire-rated plywood finished on one side and prime coat painted on all surfaces with finish coat of enamel
<br />paint, color by architect. Leave one (1) fire-rating stamp/sheet exposed for inspection.
<br />See drawings for floor box installation notes and specifications.
<br />For exposure to weather, damp locations, or surface mounting, outlet boxes shall be heavy cast aluminum or
<br />cast iron with threaded hubs; covers shall be watertight with gaskets and non-ferrous screws.
<br />For locations where standard boxes are not suitable due to number and size of conduit to be terminated,
<br />special boxes shall be designed to fit space or meet other requirements and submitted for approval.
<br />For convenience outlets, wall switches, or other devices, outlet boxes shall be galvanized one-piece drawn
<br />steel, knockout type 4" x 4" x 2-1/8" minimum size with plaster rings as required.
<br />For in-grade applications, junction and pull boxes shall be pre-cast concrete or molded fiberglass
<br />manufactured by Christy, Brooks-Jensen, or Utility Vault Co. Fiberglass boxes shall:
<br />For outside, damp or surface locations, boxes shall be NEMA 3R heavy cast aluminum or cast iron with
<br />removable, gasketed, non-ferrous machine screw secured covers.
<br />For interior dry locations, boxes shall be NEMA 1 galvanized one-piece drawn steel, knockout type, with
<br />removable, machine screw secured covers.
<br />Wire-pulling compounds used as lubricants in installing conductors in raceways shall only be "Polywater J".
<br />No oil, grease, graphite, or similar substances may be used. Pulling of #1/0 or larger conductors shall be done
<br />with an approved cable pull machine. Other methods; e.g. using vehicles or block and tackle to install
<br />conductors are not acceptable.
<br />All color-coding for #12 through #6 AWG conductor shall be as identified above. Conductors #4 AWG and
<br />larger shall be identified by utilizing phase tape at each termination.
<br />All boxes shall be sized for the number and sizes of conductors and conduits entering the box and equipped
<br />with plaster rings where required.
<br />4.
<br />Be used only in landscape planter areas that are not subject to damage from lawnmowers, tractors and
<br />other machinery.
<br />Not be used in lawn or turf areas.
<br />Not exceed 11" W x 17" L in size unless required to be larger to meet code requirements.
<br />a.
<br />b.
<br />c.
<br />All boxes located in traffic areas shall be traffic rated.5.
<br />Where mounted outdoors, terminal cabinets shall be NEMA 3R, weatherproof complete with gaskets and
<br />required sealant to prevent moisture from entering the terminal cabinet.
<br />4.
<br />3.1
<br />A.
<br />3.
<br />4.
<br />Installation of Conduit and Outlet Boxes:
<br />PREPARATION AND INSTALLATION
<br />PART 3 - EXECUTION
<br />Intermediate metal conduit (IMC), is approved for use in all locations as approved for GRC or EMT and in
<br />accordance with NEC, or CEC where adopted, Article 342.
<br />Flexible steel conduit shall only be permitted to be used at light fixture outlets and connections to vibrating
<br />electrical equipment. All flexible steel conduit runs shall be less than 6'-0". Except when concealed in walls or
<br />other structural elements, all outdoor installation shall be made using liquid-tight flex with approved fittings.
<br />Include a separate insulated green ground conductor sized per NEC in each conduit. Other uses of flexible
<br />conduit shall be allowed only as approved in writing by the Engineer.
<br />All conduit installed in the dry walls or ceilings of a building shall be steel tube (EMT), aluminum tube (EMT), or
<br />intermediate Metal Conduit (IMC). Flexible conduit shall not be used in lieu of EMT, IMC or rigid conduit
<br />except as noted herein.
<br />Galvanized rigid conduit (GRC) or intermediate metal conduit (IMC) shall be used as follows:
<br />When considered exposed to damage by the local AHJ.
<br />When installed in concrete and masonry. The use of ENT in CMU walls and parking structures may be
<br />allowed only as directed in writing by the Engineer. Request for ENT substitution must be made prior to
<br />bid and in accordance with pre-bid substitution request requirements of these specifications.
<br />When noted on the drawings.
<br />When installed in wet or damp locations and of a trade size where listed-raintight fittings, connectors,
<br />couplings, etc. are unavailable.
<br />When required by NEC or CEC Article 517.13
<br />1.
<br />2.
<br />a.
<br />b.
<br />c.
<br />d.
<br />e.
<br />5.Flexible liquid-tight conduit shall be installed in lieu of the flexible steel where required by NEC, or CEC where
<br />adopted, in damp and wet location, where exposed to weather, in refrigerated area (65 Deg. F or less), and/or
<br />between seismic joints. All rotating electrical equipment shall be supplied with flexible, liquid-tight conduit with
<br />appropriate slack and shall not exceed thirty-six (36) inches. Include a separate insulated green ground
<br />conductor sized per NEC in each conduit. Other uses of liquid-tight flexible conduit shall be allowed as
<br />approved in writing by the Engineer on a case by case basis.
<br />3.Provide a 1-1/2" high housekeeping pad above finished floor/finished for service equipment. Prior to pad
<br />rough-in, Contractor shall verify serving utility company's maximum meter height requirements and, if
<br />necessary, adjust height of housekeeping pad to comply with those requirements. In indoor applications, the
<br />pad shall be flush with the face of the switchgear. In outdoor applications, the housekeeping pad shall extend
<br />a minimum of 4 feet from the front of switchgear's weatherproof enclosure. Confirm pad dimensions with local
<br />inspector prior to forming pad to ensure any local code interpretations/conditions are met regarding
<br />housekeeping pads.
<br />Provide a minimum 3" high housekeeping pad above finished floor/finished grade for all floor-mounted
<br />switchgear, switchboards, distribution boards, transformers, motor control centers, etc., flush with the face of
<br />the equipment. Located in mechanical central plant(s), other mechanical spaces, and located outdoors, pads
<br />shall be flush with the face of the equipment. Confirm pad dimensions with local inspector prior to forming pad
<br />to ensure any local code interpretations/conditions are met regarding housekeeping pads.
<br />1.
<br />G.House Keeping Pads:
<br />i.Lightning Protection Systems and antennas.
<br />11.Where conduit is underground, under slabs or grade, exposed to the weather, or in wet locations, make joints
<br />liquid tight and gas tight.
<br />Underground conduits, which terminate inside building(s) below grade, such as in a basement level, or
<br />which slope so that water might flow into interior building spaces, shall be sealed at the point of
<br />penetration with a modular conduit seal (Link-Seal or equal by Rox Systems). Conduit/conduit sealing
<br />system penetrations of waterproofing membranes/systems on existing structures shall be completely
<br />restored as required to maintain membrane/system manufacturer and installer warrantee for the
<br />installation. All conduits shall be provided with a 4% slope away from buildings. All conduits shall be
<br />installed such that the water cannot accumulate in the conduit and such that water drains into the nearest
<br />manhole, pull box or vault and not into the facility. In instances where grade changes or elevation
<br />differences prevent sloping of conduit away from a building into the nearest manhole, pull box or vault or
<br />where accumulation of water in a manhole, pull box or vault may result in water traveling into the facility,
<br />conduits shall be sealed internally at each end of each conduit using conduit sealing bushing, sized as
<br />required for the conductors contained within the conduit (O-Z Gedney #CSBG 100psig withstand or
<br />equal). In all cases, install plugs or caps in spare (empty) conduits at both ends of each conduit
<br />(Jackmoon or equal) preventing both water and gas from entering the facility via the conduits.
<br />e.
<br />Where underground conduit passes under a building slab, concrete encasement may not be required,
<br />except as required above, contact the Engineer for written direction prior to omitting any encasement.
<br />d.
<br />c.In all cases, where any conduit(s) pass under a building slab or footing, the electrical contractor will
<br />provide a Bentonite clay or concrete barrier that conforms to the height and width of the trench excavation
<br />extending a minimum of 24" on either side of the foundation. In all cases, where conduit(s) pass through
<br />a sleeve in a footing or other foundation element, the electrical contractor will provide a Bentonite clay or
<br />concrete barrier between the sleeve and the conduit(s) surrounding the conduit(s) for the entire depth of
<br />the sleeve. The barrier is required to prevent passage of moisture under or through the slab or footing via
<br />the trench or sleeve.
<br />b.For all communications conduits 2" and larger, and feeders 100A or greater, provide with a minimum 3",
<br />(2,000 LB) concrete envelope, 2" minimum separation between conduits, installed at depth of not less
<br />than 24" below grade. (Provide concrete encasement and/or greater minimum conduit depth as required
<br />by the Utility Companies.) Conduit separation within a duct bank shall be maintained using plastic
<br />spacers located at 5'-0" intervals. Where power and communication conduits are run in a common trench,
<br />a 12" minimum separation shall be maintained between power and communication conduits or as required
<br />by Utility Companies. Where concrete encasement is not required by serving utlities for a utility-only duct
<br />bank, provide free draining sand bedding suitable to acheive 95% relative compaction based on ASTM
<br />D1557 using 6" lifts or directed by Utility Company Standards.
<br />a.Underground conduit shall be Schedule 40 PVC (polyvinyl chloride) unless otherwise indicated elsewhere
<br />in these specifications or as required per NEC, or CEC where adopted, Article 517.13.
<br />The following additional requirements shall apply to underground conduits:
<br />3.
<br />2.
<br />1.
<br />Firestopping:F.
<br />Each fire stop assembly/system shall have an "F" and/or "T" rating as required by each condition requiring fire
<br />stopping. Each fire stop assembly/system shall have a current UL listing, as indicated in the latest edition of
<br />the UL Fire Resistance Directory. Contractor shall verify acceptability of all fire stopping methods and system
<br />selections with the authority having jurisdiction prior to installation. The Contractor shall install each firestop
<br />assembly/system in accordance with the manufacturer's printed instructions
<br />The Contractor shall be responsible for furnishing all material, labor, equipment, and services in conjunction
<br />with the selection and installation of a complete, fully functioning, code compliant, UL-listed, fire stop
<br />assembly/system(s) as required by project conditions.
<br />6.
<br />31.
<br />8.
<br />8.
<br />7.
<br />9.
<br />10.
<br />1.
<br />2.
<br />D.
<br />3.
<br />32.
<br />34.
<br />33.
<br />35.
<br />36.
<br />37.
<br />4.
<br />5.
<br />6.
<br />7.
<br />E.
<br />END OF SECTION
<br />1.
<br />a.
<br />2.
<br />B.Installation of 600V Conductors:
<br />4.
<br />5.
<br />All electrical wire, including signal circuits, shall be installed in conduit.
<br />9.
<br />10.
<br />38.
<br />13.
<br />14.
<br />12.
<br />16.
<br />17.
<br />18.
<br />6.
<br />C.Grounding/Bonding:
<br />1.
<br />d.
<br />c.
<br />b.
<br />a.
<br />Exposed metal in maintenance holes, hand holes.
<br />Raised Flooring.
<br />h.
<br />g.
<br />f.
<br />e.
<br />3.
<br />Transformers, Inverters, UPS, PDU, RDC, Transfer Switch and Generator Systems.
<br />Telephone distribution equipment.
<br />Non-current carrying metal parts of fixed equipment.
<br />Panel boards, Distribution boards, Switchgear and Switchboards.
<br />Neutral or identified conductors of interior wiring system.
<br />Conduit, raceways and cable trays.
<br />a.
<br />4.Grounding System Connection:
<br />b.
<br />5.
<br />c.Mechanical connectors shall not be used.
<br />a.
<br />19.Seismic Conduit Support:
<br />20.
<br />3-1/2" to 4"
<br />CONDUIT SIZE
<br />1/2" to 3"
<br />MAXIMUM SPACING
<br />6'-0"
<br />8'-0"
<br />21.
<br />23.
<br />22.
<br />24.
<br />25.
<br />26.
<br />28.
<br />27.
<br />29.
<br />30.
<br />Prefabricated Equipment: Installation of all prefabricated items and equipment shall conform to the requirements
<br />of the manufacturer's specifications and installation instruction pamphlets. Where code requirements affect
<br />installation of materials and equipment, the more stringent requirements, code or manufacturer's instructions
<br />and/or specifications, shall govern the work.
<br />The location of all power supply connection and/or terminations to the mechanical equipment is approximate.
<br />The exact locations of these terminations shall be verified with other trades during construction.
<br />It is the Contractor's responsibility to verify with the drawings of other trades regarding the extent of his
<br />responsibility for mechanical equipment. The bid must include a sum sufficient to cover the cost of the
<br />installation.
<br />Unless otherwise noted, the Contractor shall furnish and install all conduit, boxes, wires, etc., for line voltage
<br />wiring and low voltage wiring.
<br />Provide power supplies to all plumbing and mechanical equipment, including, but not limited to, equipment
<br />furnished and installed by Owner or Contractor, such as heating and air conditioning equipment, pumps,
<br />boilers, auto valves and water coolers, etc. The installation shall produce a complete and operable system.
<br />The location of all conduit terminations to the equipment is approximate. The exact location of these conduit
<br />terminations shall be located and installed as directed by the Mechanical or Plumbing Contractor.
<br />Power supplies to individual items of equipment shall be terminated in a suitable outlet or junction box
<br />adjacent to the respective item of equipment, or a junction box provided by the manufacturer or the equipment
<br />and directed by the Mechanical Contractor. Allow sufficient lengths of conductor at each location to permit
<br />connection to the individual equipment without breaking the wire run.
<br />An electric power supply, including conduit, any necessary junction and/or outlet boxes and conductors and
<br />connection shall be furnished and installed by the Contractor for each item or mechanical equipment.
<br />Line Voltage and Low Voltage Power Supplies to all Mechanical Equipment Including Plumbing, Heating and Air
<br />Conditioning Units:
<br />Building grounding system resistance to ground shall not exceed 25 ohms unless otherwise noted and should
<br />be confirmed by testing.
<br />Motors: Connect the ground conductor to the conduit with an approved grounding bushing, and to the metal
<br />frame with a bolted solderless lug. Bolts, screws and washers shall be bronze or cadmium plated steel.
<br />Ductwork: Provide a flexible ground strap, No. 6 AWG equivalent, at each flexible duct connection at each air
<br />handler, exhaust fan, and supply fan, and install to preclude vibration.
<br />Clean the contact surfaces of all ground connections prior to making connections.
<br />Provide separate green equipment ground conductor in all electrical raceways to effectively ground all fixtures,
<br />panels, controls, motors, disconnect switches, exterior lighting standards, and non current-carrying metallic
<br />enclosures. Use bonding jumpers, grounding bushings, lugs, busses, etc., for this purpose. Connect the
<br />equipment ground to the building system ground. Use the same size equipment ground conductors as phase
<br />conductors, up through #10 AWG. Use NEC (or CEC where adopted) Table 250.122 for conductor size with
<br />phase conductors #8 and larger, if not shown on the Drawings.
<br />Isolated Ground Receptacles shall have an insulated ground wire connected between the receptacle and the
<br />panelboard isolated ground bus. Unless otherwise noted, this ground wire shall not be grounded at any other
<br />point, and shall be distinguished from other ground wires by a continuous yellow stripe.
<br />Exothermic weld-type connectors shall be 'Cadweld' manufactured by Erico Products, or approved equal,
<br />designed specifically for the intended connection.
<br />Compression connectors shall be unplated copper, manufactured by Burndy, or approved equal, designed
<br />specifically for the intended connection.
<br />Use of Ground Rods: Furnish and install required number of 3/4" x 10' copper clad ground rods to meet
<br />specified resistance, all required grounding wires, conduit and clamps. The size of the grounding conductors
<br />shall be not less than that set forth in the latest edition of the California Code of Regulations, Title 24, State of
<br />California and NEC (or CEC where adopted), unless otherwise indicated. Rods shall be installed such that at
<br />least 10 feet of length is in contact with the soil. Where rock bottom is encountered, the electrode shall be
<br />driven at an oblique angle not to exceed 45 degrees from vertical or shall be buried in a trench that is at least
<br />30 inches deep. The upper end of the electrode shall be flush with or below ground level unless the above
<br />ground end and the grounding electrode conductor attachments are protected against physical damage.
<br />Unless otherwise noted, connection to the grounding electrode conductor may be by compression type or
<br />exothermic process connector. Mechanical connectors shall not be used.
<br />Provide grounding and bonding for entire electric installation as shown on plans, as listed herein, and as
<br />required by applicable codes. Included, but not limited to, are items that require grounding/bonding:
<br />Conductor Support: Provide conductor supports as required by codes and recommended by cable
<br />manufacturer. Where required, provide cable supports in vertical conduits and provide lower end of conduit
<br />with a ventilator.
<br />For 20A branch circuit wiring, increase #12 conductors to #10 for 120V circuits longer than 100 feet and for
<br />277V circuits longer than 150 feet.
<br />Install UL approved fixture wire from all lighting fixture lamp sockets into fixture outlet or junction box.
<br />Utilize pre-insulated "winged" spring type connectors, 3M Company "Performance Plus" #O/B or #R/Y or
<br />equal and as required for splices and taps in conductors #6 AWG and smaller. When a spring connector
<br />is used in an underground environment or when subject to moisture, utilize a 3M Company Scotchcast
<br />3507G epoxy resin connector sealing pack to seal the spring connector. THE USE OF PUSH-WIRE
<br />CONNECTORS (e.g. "WAGO" OR EQUIVALENT) IS STRICTLY PROHIBITED.
<br />All circuits and feeder wires for all systems shall be continuous from overcurrent protective device or switch to
<br />terminal or farthest outlet. No joints shall be made except in pull, junction or outlet boxes, or in panel or
<br />switchboard gutters.
<br />Tag all empty conduits at each accessible end with a permanent tag identifying the purpose of the conduit,
<br />footage end-to-end, and the location of the other end. In wet, corrosive outdoor or underground locations, use
<br />brass, bronze, or copper 16 gauge tags secured to conduit ends with #16 or larger galvanized wire. Inscribe
<br />on the tags, with steel punch dies, clear and complete identifying information.
<br />Except as otherwise indicated on the drawings or elsewhere in these specifications, bends in feeder and
<br />branch circuit conduit 2 inches or larger shall have a radius or curvature of the inner edge, equal to not less
<br />than ten (10) times the internal diameter of the conduit. Except where sweeping vertically into a building
<br />where sweep radius equals ten (10) times conduit diameter, underground communications and building
<br />interconnect conduits 3 inches or larger shall have a minimum 12'-6" radius or curvature of the inner edge. For
<br />the serving utilities, radius bends shall be made per their respective specifications.
<br />Seal all conduits where termination is subject to moisture or where conduit penetrates exterior wall, floor or
<br />roof, in refrigerated areas, classified (hazardous areas) and as indicated on the drawings.
<br />Where conduits or wireways cross seismic joints, provide approved flexible conduit connection or approved
<br />expansion/deflection fitting to allow for displacement of conduit in all three axes. Connection shall allow for
<br />movement in accordance with design of seismic joint. Non-flexible raceways crossing expansion joints or
<br />other areas of possible structural movement shall make provision for 3-way movement at such points by
<br />means of expansion/deflection fittings. Fittings shall be installed in the center of their axes of movement and
<br />shall not be deflected to make part of a conduit bend, or compressed or extended to compensate for incorrect
<br />conduit length. Install flexible conduit connection(s) or approved expansion/deflection fitting(s) complete with
<br />ground jumpers. Where necessary, provide approved expansion joints to allow for thermal expansion and
<br />contraction of conduit(s). Install expansion joints complete with ground jumpers.
<br />All exposed conduits and support hardware shall be painted to match the finish of the wall or ceiling to which it
<br />is supported.
<br />All multiple conduit runs within suspended ceilings shall be suspended from building structure by means of
<br />unistrut hangers/racks. Conduit shall not be allowed to lay on ceiling or be supported from ceiling suspension
<br />wires or other suspension system. Support conduit to structure above suspended ceilings 8" minimum above
<br />ceiling to allow removal of ceiling tile. Maintain two inch clearance above recessed light fixtures.
<br />Provide nylon or a 1/8-inch O.D. polyethylene rope, rated at 250 pounds tensile strength, in all conduits more
<br />than 5 feet in length left empty for future use. Not less than 5 feet of rope shall be left at each end of the
<br />conduit. Tag all lines with a plastic tag at each end indicating the termination/stub location of the opposite end
<br />of the conduit.
<br />All conduit entries to outdoor mounted panels, cabinets, boxes, etc., shall be made using Myers "SCRU-TITE"
<br />hubs Series ST.
<br />All boxes installed outdoors shall be suitable for outdoor installations, gasketed, screw cover, and painted as
<br />directed by the Architect with weatherproof paint to match building.
<br />All boxes shall be covered with outlet box protector, Appleton SB-CK, or similar device/method to keep
<br />dirt/debris from entering box, conduit or panels. If dirt/debris does get in, it shall be removed prior to pulling
<br />wires.
<br />Except where below grade, sleeves shall be installed where conduit passes through masonry or concrete walls
<br />and shall be 24 gauge galvanized steel no more than 1/2" greater in diameter than the outside diameter of the
<br />conduit. When located in non-rated structures, caulk conduit sleeve with stone wool. When located in fire
<br />rated structures, provide UL listed fire stopping system. See fire stopping section of this specification for
<br />additional requirements.
<br />Surface mounted pull boxes, terminal cabinets, junction boxes, panel boards etc., shall be attached to walls
<br />using appropriate screws, fasteners, backing plates, stud blocking, etc., as detailed on architectural and/or
<br />structural drawings. If architectural and/or structural drawings are not provided on the project, Contractor shall
<br />provide all necessary mounting hardware and backing support to comply with local building code requirements
<br />and any additional requirements imposed by the local Authority-Having-Jurisdiction.
<br />Junction Boxes that do not contain any device(s) shall be located in storage rooms, electrical closets or above
<br />accessible ceilings, not in hard lid ceilings or other forms of inaccessible ceilings. Place boxes which must be
<br />exposed to public view in a location approved by the Owner's Project Manager. Provide covers or plates to
<br />match adjacent surfaces as approved by the Owner's Project Manager.
<br />Recessed boxes shall not be mounted back-to-back in any wall; minimum offset shall be 24 inches.
<br />Outlet boxes on metal studs shall be attached to metal hangers, tack welded or screwed to studs; On wood
<br />studs attachment shall be with wood screws, nails are not acceptable.
<br />Locate wall outlet of the same type at same level in all rooms, except where otherwise noted.
<br />Open knockouts in outlet boxes only where required for inserting conduit.
<br />All conduit runs shall be installed parallel or perpendicular to walls, structural members, or intersection of
<br />vertical planes and ceilings. Field made bends and offset shall be avoided where possible. Crushed or
<br />deformed raceway shall not be installed.
<br />All conduit shall be supported in such a manner that it is securely attached to the structure of the building.
<br />Attachment is to be capable of supporting the tributary weight of conduit and contents in any direction.
<br />Maximum spacing of support and braces are to be as follows:
<br />Nail-in conduit supports, one-piece set screw type conduit clamps or perforated iron for supporting conduit
<br />shall not be used.
<br />Where conduit racks are used, the rack shall consist of two piece conduit clamps attached to galvanized steel
<br />slotted channels, properly secured via threaded rods attached directly to the building structure.
<br />All conduit shall be supported at intervals not less than 6'-0" and within 12" from any outlet and at each side of
<br />bends and elbows. Conduit supports shall be galvanized, heavy stamped, two-hole conduit clamp properly
<br />secured.
<br />All metal conduit in masonry and concrete and where concealed under floor slabs shall have joints painted
<br />with thread compound prior to makeup.
<br />Where conductors enter a raceway or a raceway in a cabinet, pull box, junction box, or auxiliary gutter, the
<br />conductors shall be protected by a plastic bushing type fitting providing a smoothly rounded insulating surface.
<br />No running threads will be permitted in locations exposed to the weather, in concrete or underground. Special
<br />union fittings shall be used in these locations.
<br />The ends of all conduits shall be cut square, carefully reamed out to full size and shall be shouldered in fitting.
<br />Conduit shall be run so as not to interfere with other piping, fixtures or equipment.
<br />Unless otherwise noted above, provide a minimum 1-1/2" high housekeeping pad above finished floor/finished
<br />grade for all interior floor-mounted switchgear, distribution boards, transformers, motor control centers, transfer
<br />switches, etc., flush with the face of the equipment. All housekeeping pad heights are as measured from
<br />finished floor or grade. Confirm pad dimensions with local inspector prior to forming pad to ensure any local
<br />code interpretations/conditions are met regarding housekeeping pads.
<br />2.
<br />4.All housekeeping pads located in, on, or attached to a building shall be seismically braced/connected to the
<br />building structure.
<br />39.
<br />Provide J-box above accessible ceiling prior to running MC cable within partitions or walls. J-box shall be
<br />permanently labeled with panel identification and circuit numbers contained within.
<br />a.
<br />Overhead MC cable runs shall generally follow building lines to provide a neat and workmanlike
<br />installation.
<br />b.
<br />Provide code-sized J-boxes to accommodate MC cable splicing in general. For systems furniture
<br />poke-through feeds utilizing MC cable, transition from MC cables to conduit and wire near the panelboard
<br />in the TI accessible ceiling space on the floor below the panel board via code-sized gutter(s). Utilize UL
<br />listed, insulated barrier strips with recessed screw heads (Ideal #89-6?? series or equal) fastened within
<br />the gutter(s), terminate MC conductors on one side of the strip(s) and individual conductors in conduit
<br />from the panel board(s) on the other side of the strip(s). Label each terminal strip(s) with panel
<br />designation. Label each phase conductor with circuit number using wire markers (ideal or equal). Wire
<br />nuts are not an acceptable alternative to the terminal strips in these underfloor transition locations.
<br />Provide (1) spare 3/4" conduit from each gutter to its respective panelboard.
<br />c.
<br />MC cable shall not run directly into panelboards, distribution boards or electrical rooms.d.
<br />MC cabling shall be provided with its own code-approved ceiling support wires, cable hangers, individual
<br />spring steel support clips, steel trapeze hangers, threaded rods or dedicated #10 AWG drop wire. Cable
<br />supports shall be fastened to concrete slabs, beams, joists or other structural members of the building. In
<br />no case shall MC cable rest on ceilings, suspended ceilings or structures. Do not support MC cable using
<br />ceiling support wires. The use of nylon cable ties to support MC cable is not allowed.
<br />e.
<br />Use lock or spring nut MC cable fittings.f.
<br />Cable runs shall be continuous from wiring device to wiring device - no intermediate splicing J-boxes
<br />allowed.
<br />g.
<br />When terminating or splicing at a junction, outlet, or switch box, cut the cable with an armored cable rotary
<br />cutter such that 6" of free conductors remain for connections or splices. Use screw-in or spring lock
<br />connector and ensure a proper bonding by firmly tightening the connector to both the box and cable.
<br />Insert an anti-short bushing at cable ends to protect conductors from abrasion and use insulated
<br />connectors.
<br />h.
<br />MC Cable bend radius shall not be less than seven (7) times the external diameter of the cable.i.
<br />MC cables passing through fire-rated walls or floors shall be firestopped as required with a UL listed
<br />system. See firestopping requirements outlined elsewhere in this specification for additional
<br />requirements.
<br />j.
<br />Installation shall not exceed code requirements for total current carrying conductors in multiple MC cable
<br />runs bundled together into a single MC cable hanger or strap, unless support device is specifically listed
<br />for such purpose. Neutrals shall be counted as current carrying conductors.
<br />k.
<br />Maintain MC cable clearance of at least 6" from hot water and any other high temperature pipes. Maintain
<br />at least 12" clearance between MC cable(s) and telecommunication conduits and cables. MC cable shall
<br />cross telecommunication cables and conduits at right angles.
<br />l.
<br />MC cabling shall not be run through exposed ceilings, where open grid conditions exist, exposed on walls,
<br />or exposed to view. See Power Plan and Lighting Plan General Notes for additional requirements.
<br />m.
<br />Installation of Metal Clad (MC) Cable (when use is permitted in the Allowed Specification Deviations Section or
<br />Deductive/Additive Alternate Pricing Section generally located on the symbols list drawing).
<br />Rigid metallic conduit installed underground or embedded in concrete shall be 1" trade size minimum and shall
<br />be wrapped with 20 mil polyvinyl chloride plastic tape. PVC conduit installed underground or imbedded in
<br />concrete shall be 3/4" minimum trade size.
<br />6.
<br />Each fire stop assembly/system shall be labeled with fire stop manufacturer-furnished label on each side of the
<br />fire stopping systems depicting UL number, etc.
<br />i.All PVC conduit shall be glued for a water and gas tight installation. The Contractor shall use appropriate
<br />solvent on all joints prior to gluing conduit and fittings together.
<br />7.Where required for providing an Electrical Circuit Protective System to comply with NEC, or CEC where
<br />adopted, Articles 695 and 700, utilize UL Listed 2-hour fire-rated, MC cable or UL Listed 2-hour fire-rated
<br />RHH/RHW conductors in conduit.
<br />40.
<br />When approved for use in the Allowed Specification Deviations Section or Deductive/Additive Alternate
<br />Pricing Section, generally located on the symbols list drawing, 1/2" and 3/4" trade size ENT shall be
<br />allowed for concealed lighting branch circuits, receptacle branch circuits and miscellaneous signal system
<br />circuits within concrete floors, walls and columns within parking structures.
<br />a.
<br />ENT conduit shall meet the requirements of Underwriters Laboratories Standards 1479 and 1653, NEMA
<br />TC-13, and be UL-listed.
<br />b.
<br />All ENT conduit, ENT fittings, ENT boxes and ENT accessories shall be UL listed and manufactured by
<br />the same manufacturer so as to form a complete ENT system. ENT systems shall only be used if they are
<br />listed for use in fire resistance rated concrete floors and ceilings with resistance ratings as indicated
<br />elsewhere in the project plans. ENT System shall comply with NEC, or CEC where adopted, Article 362.
<br />c.
<br />All ENT fittings and ENT boxes shall be concrete-tight listed without the use of tape. Additionally, ENT
<br />fittings shall be constructed of high-impact PVC and able to resist ENT conduit pull out forces of a
<br />minimum of 175 lbs. ENT fittings with fewer than 6 locking tabs for ENT connection shall utilize
<br />manufacturer-approved glue as additional protection from fitting/conduit separation. ENT conduit to rigid
<br />conduit transition fittings shall be equipped with set screw fittings on the rigid conduit side of the fitting.
<br />ENT to metal box fittings shall be equipped with a threaded end and lock washer.
<br />d.
<br />Where tubing enters a box, fitting or other enclosure provide a bushing or adapter to protect conductors
<br />from abrasion unless the box, fitting, or enclosure design provides equivalent protection.
<br />e.
<br />ENT junction boxes shall have brass screw inserts and shall be rated to support lighting fixtures weighing
<br />less than 50 lbs.
<br />f.
<br />Concrete tight metal boxes shall be used to support pendant hung fixtures or fixtures over 50 lbs.g.
<br />ENT shall be provided in continuous lengths between junction boxes without use of in-line splices or
<br />connectors and shall be clearly marked/labeled at least every 10-feet.
<br />h.
<br />All ENT conduit containing electrical branch circuits shall contain a code-sized equipment ground
<br />conductor.
<br />i.
<br />ENT shall transition to EMT, IMC, RMC, or rigid PVC, as appropriate or as called out elsewhere in this
<br />specification, for all exposed conduits within/on/under a parking structure.
<br />j.
<br />ENT shall transition to appropriately sized PVC expansion joint(s) at all structure expansion or seismic
<br />joints.
<br />k.
<br />ENT shall be securely fastened and supported every 2 - 3 ft. and within 1 ft. of every junction box and
<br />fitting to prevent movement and sag.
<br />l.
<br />ENT shall be routed straight without sags, or excessive bending. Where bends are required, comply with
<br />Table 362.24 of the NEC for minimum radius of bends. Number of bends shall not exceed quantity
<br />allowed by code where used for power and lighting branch circuit and/or feeder conductors. Where
<br />utilized for communications system conductors (phones, data cabling, etc.) number of bends shall not
<br />exceed the equivalent of (2) 90 degree bends with conduit length no more than 100 feet without
<br />installation of a TIA 569-compliant pull box.
<br />m.
<br />Installation of Electrical Nonmetallic Tubing (ENT) Cable (when use is permitted in the Allowed Specification
<br />Deviations Section or Deductive/Additive Alternate Pricing Section generally located on the symbols list
<br />drawing).
<br />Separation of ENT from fitting(s), excessive sags or deflections in ENT runs that prevent pulling of wire,
<br />and other ENT system product or system installation failures/errors, shall be corrected by saw cutting and
<br />patching as necessary at no additional cost to the Owner. Use of surface mounted conduits and junction
<br />boxes as a repair method is unacceptable.
<br />n.
<br />Empty ENT runs shall be provided with a nylon pull string.o.
<br />Coordinate installation of raceway with structural steel and other structural members. Do not cut, notch or
<br />otherwise alter structural members without obtaining approval in writing from the Structural Engineer of
<br />Record.
<br />p.
<br />No more than (2) 3/4" ENT conduits may cross each other within a horizontal concrete slab without
<br />obtaining approval in writing from the Structural Engineer of Record.
<br />q.
<br />2.In multi-occupancy buildings, Contractor shall bond metal water piping systems installed in, under or attached
<br />to a building and/or structure serving individual occupancies where the piping system(s) are metallically
<br />isolated from each other. Per NEC, or CEC where adopted, ART. 250.104(A)(2) and (3), the bonding
<br />conductor shall be sized per Table 250.122 and connected to the switchboard/panelboard serving that
<br />suite/occupancy.
<br />j.Metal piping installed in or attached to a building/structure.
<br />k.Metallically isolated structural steel.
<br />l.Metallically isolated underground metal water piping.
<br />m.Elevator hydraulic piston/lift case.
<br />5.Outlet boxes used for support of ceiling fans shall be galvanized, one-piece drawn steel, knockout type
<br />equipped with bracing bars and plaster rings where required and listed for ceiling fan support use. Such boxes
<br />shall be labeled and capable of supporting ceiling fan weights up to 70 pounds.
<br />Isolated Ground Conductors: Green with continuous Yellow striped.
<br />3.
<br />5.
<br />4.
<br />=
<br />=
<br />2)
<br />1)
<br />Phase B
<br />Phase A
<br />=
<br />=
<br />=
<br />5)
<br />4)
<br />Switchlegs
<br />Neutral
<br />Phase C3)
<br />Power 208/120V, 3PH, 4W:
<br />Blue
<br />White or White with Phase Color Tracer
<br />Black
<br />Red
<br />=
<br />=
<br />2)
<br />1)
<br />Phase B
<br />Phase A
<br />=
<br />=
<br />=
<br />3)
<br />4)
<br />5)
<br />Phase C
<br />Neutral
<br />Switchlegs
<br />Power 480/277V, 3PH, 4W:
<br />Orange
<br />Grey or Grey with Phase Color Tracer
<br />Yellow
<br />Brown
<br />Travelers6)=Purple with Black stripe or Pink
<br />=
<br />Ground Conductors: Green
<br />Fire Alarm System: As recommended by the manufacturer
<br />Travelers6)Purple with Black stripe or Pink.
<br />a.
<br />b.
<br />c.
<br />e.
<br />Systems Conductor Color Coding:
<br />Purple (Switchlegs shall also be identified separately by numerical tags).
<br />Purple (Switchlegs shall also be identified separately by numerical tags)
<br />Wire and cable shall be factory color-coded by integral pigmentation with a separate color for each phase and
<br />neutral. Each system shall be color-coded and it shall be maintained throughout.
<br />Wire and cable shall be new, manufactured not more than six (6) months prior to installation, shall have size,
<br />type of insulation, voltage rating and manufacturer's name permanently marked on outer covering at regular
<br />intervals.
<br />2.Type THHN/THWN-2 thermoplastic, 600V, UL approved, dry and wet locations rated at 90 degrees Celsius,
<br />for conductors of all sizes from #12 AWG up to and including 1000 kcmil. RHH/RHW insulation is allowed only
<br />to provide an Electrical Circuit Protective System to comply with NEC, or CEC where adopted, Articles 695 and
<br />700.
<br />All conductors shall be copper. Provide stranded conductor for #10 AWG and larger or when making flexible
<br />connections to vibrating machinery. Use compression "fork" type connectors or transition to solid conductors
<br />when connecting to switches, receptacles, etc.
<br />V.
<br />1.
<br />600V Conductors - Wire and Cable:
<br />1.
<br />W.
<br />See drawings for Medium Voltage Cable Schedule and Specifications.
<br />Medium Voltage Conductors (greater than 600V):
<br />IP=1.0: Non-life safety, Non-structural Components in an Occupancy Category IV Facility not required for
<br />continued operations of the facility or in any other Occupancy Category Facility where component failure
<br />will not impair continued operation of the facility.
<br />b.IP=1.5: Designated Seismic Systems are those non-structural components in any Occupancy Category IV
<br />facility (except as noted above) or that are a part of any code-defined Critical, Life Safety, Emergency and
<br />Legally Required Standby Electrical System. Additionally, those non-structural components containing
<br />hazardous materials shall be classified as Designated Seismic Systems. While Designated Seismic
<br />Systems are generally identified on the plans, they may include items such as Generators, Automatic
<br />Transfer Switches, UPS units and all associated electrical distribution equipment and components
<br />necessary for the designated seismic system to form a complete and operable system. The Contractor
<br />shall ultimately be responsible for identifying Designated Seismic Systems. For any electrical component
<br />either identified on the plans or determined by the contractor to be a Designated Seismic System, all line
<br />and load side electrical distribution systems supporting that Designated Seismic System (including, but
<br />not limited to, feeders, panel boards switchboards, transformers, all related component supports and
<br />attachments, etc.) shall be considered a part of the designated seismic system for the purposes of
<br />code-compliance and seismic certification.
<br />c.z/h - Height factor ratio: See plans for respective equipment locations.
<br />j.All underground conduit work shall conform to the Federal, State and Local Safety Orders or Rules
<br />regarding excavations, trenches and related earthwork. For projects in California, refer to the California
<br />Code of Regulations, Title 8, Construction Code Sections 1540 and 1541 for additional requirements.
<br />2.
<br />a.
<br />b.
<br />c.
<br />d.
<br />e.
<br />Provide a delegated-design submittal for each of the following seismic-restraint systems to be used as
<br />required:
<br />Restraint Channel Bracings consisting of MFMA-4, shop-or field-fabricated bracing assembly made of
<br />slotted steel channels with accessories for attachment to braced component at one end and to building
<br />structure at the other end, with other matching components, and with corrosion-resistant coating; rated in
<br />tension, compression, and torsion forces.
<br />Restraint Cables consisting of ASTM A 603 galvanized-steel cables. End connections made of steel
<br />assemblies with thimbles, brackets, swivel, and bolts designed for restraining cable service, with a
<br />minimum of two clamping bolts for cable engagement.
<br />Seismic-Restraint Accessories consisting of hanger rod/hanger rod stiffener assemblies, multifunctional
<br />steel connectors for attaching hangers to rigid channel bracings and/or restraint cables, bushings for floor
<br />and wall-mounted equipment, anchor bolts, and resilient isolation washers and bushings.
<br />Mechanical Anchor Bolts consisting of drilled-in and stud-wedge or female-wedge type in zinc-coated steel
<br />for interior applications and stainless steel for exterior applications. Select anchor bolts with strength
<br />required for anchor and as tested according to ASTM E 488.
<br />Adhesive Anchor Bolts consisting of drilled-in and capsule anchor system containing resin and
<br />accelerator, or injected polymer or hybrid mortar adhesive. Provide specific LEED-compatible,
<br />environmentally-friendly resins and adhesives on all LEED projects. Provide anchor bolts and hardware
<br />with zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor
<br />bolts with strength required for anchor and as tested according to ASTM E 488.
<br />The contractor shall engage a qualified testing agency to perform tests and inspections as listed in other
<br />Project Specifications, but as a minimum shall include at least four of each type and size of installed anchors
<br />and fasteners selected by Architect. Schedule tests with Owner, through Architect, before connecting
<br />anchorage device to restrained component (unless post connection testing has been approved), and with at
<br />least seven days' advance notice. Obtain Architect's approval before transmitting test loads to structure.
<br />Provide temporary load-spreading members as required. Test to 90 percent of rated proof load of device.
<br />Prepare and submit test and inspections reports.
<br />Multiple Raceways or Cables: Secure raceways and cables to trapeze member with clamps approved for
<br />application by OSHPD or an agency acceptable to authorities having jurisdiction.
<br />Install seismic-restraint devices using methods approved by OSHPD or an agency acceptable to authorities
<br />having jurisdiction providing required submittals for component.
<br />Install flexible connections in runs of raceways, cables, wireways, cable trays, and busways where they cross
<br />seismic joints, where adjacent sections or branches are supported by different structural elements, and where
<br />connection is terminated to equipment that is anchored to a different structural element from the one
<br />supporting them as they approach equipment. Flexible connection limitations of the NEC, or CEC where
<br />adopted, shall apply.
<br />Coordinate the location of embedded connection hardware with supported equipment attachment and
<br />mounting points and with requirements for concrete reinforcement and formwork specified elsewhere in the
<br />project specifications.
<br />Any pre-approval and evaluation documentation shall have a California Office of Statewide Health Planning
<br />and Development (OSHPD) Special Seismic Certification Preapproval (OSP) demonstrating horizontal and
<br />vertical load testing and analysis showing maximum seismic-restraint ratings, by ICC-ES or another agency
<br />acceptable to authorities having jurisdiction. Ratings based on independent testing are preferred to ratings
<br />based on calculations. If preapproved ratings are not available, submittals based on independent testing are
<br />preferred. Calculations (including combining shear and tensile loads) that support seismic-restraint designs
<br />must be signed and sealed by a qualified professional engineer.
<br />Submittal shall include design calculations and details for selecting seismic restraints complying with
<br />performance requirements, design criteria, and analysis data signed and sealed by the contractor's structural
<br />engineer responsible for their preparation. Calculations shall include, but not be limited to, static and dynamic
<br />loading caused by equipment weight, operation, and seismic and, if applicable, wind forces required to select
<br />seismic and, if applicable, wind restraints and for designing vibration isolation bases. Provide seismic and
<br />wind-restraint detailing to support system selection, arrangement of restraints, attachment locations, methods,
<br />and spacings with all components identified to include their strengths, directions and values of forces
<br />transmitted to the structure during seismic events and association with vibration isolation devices. Sizes of
<br />components shall be selected so strength will be adequate to carry present static and seismic loads to
<br />accommodate 25% spare future capacity within specified loading limits.
<br />3.
<br />4.
<br />5.
<br />6.
<br />7.
<br />9.
<br />8.
<br />6.
<br />7.Conduit unions shall be "Erickson" couplings, or approved equal. The use of running threads will not be
<br />permitted.
<br />Flexible steel conduit connectors shall be a malleable iron clamp or squeeze type or steel twist-in type with
<br />insulated throat. The finish shall be zinc or cadmium plating.
<br />All interior and exterior EMT fittings, connectors and couplings, 2" and smaller, installed in exposed or
<br />concealed locations that are considered by the AHJ to be wet or damp locations, shall be raintight-listed, steel,
<br />zinc or cadmium plated, threadless, compression, steel locking ring type with insulated throat. If
<br />raintight-listed, EMT fittings, connectors and couplings are unavailable for a given trade size or if conduit is
<br />installed in an area subject to damage - provide rigid metallic or intermediate metallic conduits, fittings,
<br />connectors and couplings as required.
<br />5.
<br />1.
<br />2.
<br />3.
<br />U.Fittings:
<br />Connector, coupling, locknut, bushings and caps used with rigid conduit shall be steel, threaded and
<br />thoroughly galvanized. Bushings shall be insulated.
<br />Metallic condulet covers shall have the same finish as the fitting and shall be provided for the opening of each
<br />fitting where conductors do not pass through the cover.
<br />Condulet type fittings shall be smooth inside and out, taper threaded with integral insulating bushing and of the
<br />shapes, sizes and types required to facilitate installation or removal of wires and cables from the conduit and
<br />tubing system. These fittings shall be of metal, smooth inside and out, thoroughly galvanized, and sherardized
<br />cadmium plated.
<br />UON all interior EMT fittings, connectors and couplings installed in concealed locations, areas not considered
<br />to be wet or damp locations by the AHJ, or areas not subject to physical damage, shall be steel, zinc or
<br />cadmium plated, threadless, compression, steel locking ring type with insulated throat. Where suitable for use,
<br />steel set screw fittings are allowed for trade sizes of 2" and smaller. Insulated throat is not required for fittings,
<br />connectors and couplings 1" and smaller.
<br />4.
<br />PVC conduit shall not be run in walls except where approved by the Engineer prior to bid in limited instances
<br />that may include concrete or CMU walls used in site retaining, parking structures, or exterior equipment yard
<br />or enclosure walls, etc.
<br />3.Thoroughly clean all conduit and wire-ways and see that all parts are perfectly dry before pulling any wires.
<br />15.Where conduit extends through roof to equipment on roof area, the Contractor shall provide flashing material
<br />compatible with the roofing system as required by the roofing specifications or as required by the Owner's roof
<br />warranty. This flashing shall be delivered to the roofing Contractor for installation. The actual location of all
<br />such roof penetrations and outlets shall be verified by the Architect/Owner. Contractor to verify type of flashing
<br />prior to bid and include all costs.
<br />g.All underground conduits with circuits rated at 40A or greater and all underground communications
<br />conduits shall be provided with a metallic marker tape located 12" below the finished grade.
<br />Include a separate insulated green ground conductor sized per NEC, or CEC where adopted, in each
<br />underground electrical feeder/branch circuit.
<br />f.
<br />Where underground conduits sweep into/through slabs, utilize PVC 90 degree sweeps that transition, via
<br />female PVC adapter to GRC coupling mounted flush in slab. GRC couplings shall be 1/2 lap taped with
<br />20 mil tape. If the distance of the conduit run between a sweep and the next connecting sweep, pullbox,
<br />vault or manhole exceeds 150 ft then the sweep shall be concrete encased. Exceptions:
<br />h.
<br />Communications conduits shown terminating at a finished floor shall have an additional 4" high GRC
<br />nipple equipped with a bushing, removable conduit plug, labeling tag and pull rope. Tie off pull rope
<br />to conduit plug.
<br />1)
<br />Utility conduit sweeps shall be installed per the requirements of the respective utility company.2)
<br />2)
<br />1)
<br />When located in an interior environment, the splice shall be made with an ILSCO or equal dual rated,
<br />insulated splicer-reducer connector or multi-tap connector listed for use with 75/90 degree Celsius
<br />rated conductors.
<br />When located in an underground environment or when subject to moisture, the splice shall be made
<br />with compression connector and sealed by a 3M, or equal, PST cold shrink connector insulator.
<br />Wires #4 AWG and larger AWG shall be joined together as follows:b.
<br />c.Connections to busbar shall be made with dual-rated copper/aluminum one-piece compression lugs.
<br />Paralleled conductor connections shall be by mechanical lugs.
<br />Use of MC-AP, "MC All Purpose" or MC cabling where the interlocked armor sheath forms all or a portion
<br />of the equipment grounding conductor is expressly prohibited.
<br />n.
<br />tk1sc project number: B2305501.000
<br />drawn by:checked by:
<br />drawing no.:
<br />ar
<br />c
<br />h
<br />i
<br />t
<br />e
<br />c
<br />t
<br />u
<br />r
<br />e
<br />pl
<br />a
<br />n
<br />n
<br />i
<br />n
<br />g
<br />in
<br />t
<br />e
<br />r
<br />i
<br />o
<br />r
<br />s
<br />tB
<br />P
<br />/
<br />A
<br />r
<br />c
<br />h
<br />i
<br />t
<br />e
<br />c
<br />t
<br />u
<br />r
<br />e
<br />46
<br />1
<br />1
<br />
<br />T
<br />e
<br />l
<br />l
<br />e
<br />r
<br />
<br />A
<br />v
<br />e
<br />n
<br />u
<br />e
<br />Ne
<br />w
<br />p
<br />o
<br />r
<br />t
<br />
<br />B
<br />e
<br />a
<br />c
<br />h
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />6
<br />6
<br />0
<br />ph
<br />:
<br />
<br />9
<br />4
<br />9
<br />.
<br />6
<br />7
<br />3
<br />.
<br />0
<br />3
<br />0
<br />0
<br />consultant
<br />agency
<br />owner
<br />date:
<br />drawing title:
<br />description:date:Rev:
<br />tBP project number :
<br />architect
<br />THIS DRAWING AND THE DESIGNS, DEPICTIONS, IDEAS AND OTHER INFORMATION
<br />CONTAINED HEREIN CONSTITUTE UNPUBLISHED WORK OF tBP/ARCHITECTURE AND
<br />SHALL REMAIN THE PROPERTY OF tBP/ARCHITECTURE IN PERPETUITY. NO PART
<br />THEREOF SHALL BE REPRODUCED, DISCLOSED, DISTRIBUTED, SOLD, PUBLISHED OR
<br />OTHERWISE USED IN ANY WAY WITHOUT THE ADVANCED EXPRESS WRITTEN CONSENT
<br />OF tBP/ARCHITECTURE.
<br />ph: 714.667.2700
<br />SANTA ANA, CA 92701
<br />20 CIVIC CENTER PLAZA
<br />SANTA ANA PLANNING AND BUILDING AGENCY
<br />#
<br />DA
<br />N
<br />C
<br />E
<br />
<br />S
<br />T
<br />U
<br />D
<br />I
<br />O
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />L
<br />I
<br />F
<br />O
<br />R
<br />N
<br />I
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />7
<br />12
<br />0
<br />2
<br />
<br />W
<br />
<br />E
<br />D
<br />I
<br />N
<br />G
<br />E
<br />R
<br />
<br />A
<br />V
<br />E
<br />MA
<br />T
<br />E
<br />R
<br />
<br />D
<br />E
<br />I
<br />
<br />H
<br />I
<br />G
<br />H
<br />
<br />S
<br />C
<br />H
<br />O
<br />O
<br />L
<br />21125.00
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />L
<br />I
<br />F
<br />O
<br />R
<br />N
<br />I
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />7
<br />12
<br />0
<br />2
<br />
<br />W
<br />
<br />E
<br />D
<br />I
<br />N
<br />G
<br />E
<br />R
<br />
<br />A
<br />V
<br />E
<br />MA
<br />T
<br />E
<br />R
<br />
<br />D
<br />E
<br />I
<br />
<br />H
<br />I
<br />G
<br />H
<br />
<br />S
<br />C
<br />H
<br />O
<br />O
<br />L
<br />21125.00
<br />09/06/2023
<br />11870 Pierce Street, Suite 160
<br />Riverside, California 92505
<br />951.299.4160 www.tk1sc.com
<br />Project Leader - Bill Voller
<br />tk1sc Job #: B2305501.000
<br />Electrical Lead - Marie Rothenberger
<br />City Submittal 09/06/23-
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />E5-2
<br />21159.00
<br />1202 W Edinger
<br />Ave10/3/2024
|