Laserfiche WebLink
Y. <br />Z. <br />AA. <br />BB. <br />CC.Seismic Design, Certification, and Anchoring of Electrical Equipment: <br />1. <br />3. <br />5. <br />2. <br />Terminal Cabinets: <br />Outlet Boxes: <br />1. <br />6. <br />4. <br />3. <br />2. <br />1. <br />3. <br />a. <br />DD. <br />6. <br />8. <br />7. <br />9. <br />Aluminum conductors shall not be used. <br />No conductors carrying 120V or more shall be smaller than #12 AWG. <br />X. <br />2. <br />1. <br />Junction and Pullboxes: <br />For fixtures, boxes shall be galvanized, one-piece drawn steel, knockout type equipped with 3/8" fixture studs <br />and plaster rings where required. <br />Trenching and Backfilling: Contractor shall be responsible for trenching and backfilling. Refer to applicable <br />trenching and backfilling specifications for complete requirements. <br />Contractor shall include all costs in the base bid for labor, materials, all special inspections and structural <br />engineering design necessary to meet the Seismic Design Requirements for Non-structural Components <br />(Chapter 13, ASCE/SEI 7-16 Minimum Design loads for Buildings and Other Structures) as required by IBC, or <br />CBC where adopted, Section 1617A and as related to the installation of all electrical equipment furnished <br />under this contract. See Specific Project Site Seismic Criteria on architectural and/or structural plans which <br />include Building Occupancy Category, Seismic Design Category, Design Spectral Response Acceleration <br />(SDS), Height factor ratio (z/h) and Site Class. Non-structural Component Importance Factor (IP) for a particular <br />component shall be determined based on the following criteria: <br />Painting: Terminal cabinets, panels, junction boxes, pull boxes, etc., and conduit installed in public view shall be <br />painted with colors selected by the Architect to match the subject surface. Refer to painting section of the <br />specifications for additional requirements. <br />All terminal cabinets and terminal cabinet barriered sections shall be labeled by the cabinet or cabinet section <br />use (i.e. CATV, Security, etc.). Labels shall be Micarta type as specified elsewhere in these specifications. <br />Unless otherwise noted, all termination blocks and cables shall be labeled per ANSI/EIA 606 standard. <br />Terminal cabinets shall be installed complete with full-length skirts of the same construction and finish as the <br />terminal cabinet. <br />Provide each terminal cabinet with a full size mounting backplate. <br />Terminal cabinets shall be fabricated of hot dipped galvanized code gauge sheet metal for flush or surface <br />mounting, complete with barriered sections, a door for each vertically barriered section, and sizes as indicated <br />on plan. Doors shall be hinged and lockable. Locks shall be keyed to match the branch circuit panelboards. <br />Terminal cabinet trims shall match the branch circuit panels. <br />Plywood Backboards: Where indicated for telephone or communications system terminals or other equipment <br />assemblies, provide backboards of size indicated. Use 3/4" thick x 8' tall (length per plans), Douglas Fir, void-free, <br />kiln-dried, fire-rated plywood finished on one side and prime coat painted on all surfaces with finish coat of enamel <br />paint, color by architect. Leave one (1) fire-rating stamp/sheet exposed for inspection. <br />See drawings for floor box installation notes and specifications. <br />For exposure to weather, damp locations, or surface mounting, outlet boxes shall be heavy cast aluminum or <br />cast iron with threaded hubs; covers shall be watertight with gaskets and non-ferrous screws. <br />For locations where standard boxes are not suitable due to number and size of conduit to be terminated, <br />special boxes shall be designed to fit space or meet other requirements and submitted for approval. <br />For convenience outlets, wall switches, or other devices, outlet boxes shall be galvanized one-piece drawn <br />steel, knockout type 4" x 4" x 2-1/8" minimum size with plaster rings as required. <br />For in-grade applications, junction and pull boxes shall be pre-cast concrete or molded fiberglass <br />manufactured by Christy, Brooks-Jensen, or Utility Vault Co. Fiberglass boxes shall: <br />For outside, damp or surface locations, boxes shall be NEMA 3R heavy cast aluminum or cast iron with <br />removable, gasketed, non-ferrous machine screw secured covers. <br />For interior dry locations, boxes shall be NEMA 1 galvanized one-piece drawn steel, knockout type, with <br />removable, machine screw secured covers. <br />Wire-pulling compounds used as lubricants in installing conductors in raceways shall only be "Polywater J". <br />No oil, grease, graphite, or similar substances may be used. Pulling of #1/0 or larger conductors shall be done <br />with an approved cable pull machine. Other methods; e.g. using vehicles or block and tackle to install <br />conductors are not acceptable. <br />All color-coding for #12 through #6 AWG conductor shall be as identified above. Conductors #4 AWG and <br />larger shall be identified by utilizing phase tape at each termination. <br />All boxes shall be sized for the number and sizes of conductors and conduits entering the box and equipped <br />with plaster rings where required. <br />4. <br />Be used only in landscape planter areas that are not subject to damage from lawnmowers, tractors and <br />other machinery. <br />Not be used in lawn or turf areas. <br />Not exceed 11" W x 17" L in size unless required to be larger to meet code requirements. <br />a. <br />b. <br />c. <br />All boxes located in traffic areas shall be traffic rated.5. <br />Where mounted outdoors, terminal cabinets shall be NEMA 3R, weatherproof complete with gaskets and <br />required sealant to prevent moisture from entering the terminal cabinet. <br />4. <br />3.1 <br />A. <br />3. <br />4. <br />Installation of Conduit and Outlet Boxes: <br />PREPARATION AND INSTALLATION <br />PART 3 - EXECUTION <br />Intermediate metal conduit (IMC), is approved for use in all locations as approved for GRC or EMT and in <br />accordance with NEC, or CEC where adopted, Article 342. <br />Flexible steel conduit shall only be permitted to be used at light fixture outlets and connections to vibrating <br />electrical equipment. All flexible steel conduit runs shall be less than 6'-0". Except when concealed in walls or <br />other structural elements, all outdoor installation shall be made using liquid-tight flex with approved fittings. <br />Include a separate insulated green ground conductor sized per NEC in each conduit. Other uses of flexible <br />conduit shall be allowed only as approved in writing by the Engineer. <br />All conduit installed in the dry walls or ceilings of a building shall be steel tube (EMT), aluminum tube (EMT), or <br />intermediate Metal Conduit (IMC). Flexible conduit shall not be used in lieu of EMT, IMC or rigid conduit <br />except as noted herein. <br />Galvanized rigid conduit (GRC) or intermediate metal conduit (IMC) shall be used as follows: <br />When considered exposed to damage by the local AHJ. <br />When installed in concrete and masonry. The use of ENT in CMU walls and parking structures may be <br />allowed only as directed in writing by the Engineer. Request for ENT substitution must be made prior to <br />bid and in accordance with pre-bid substitution request requirements of these specifications. <br />When noted on the drawings. <br />When installed in wet or damp locations and of a trade size where listed-raintight fittings, connectors, <br />couplings, etc. are unavailable. <br />When required by NEC or CEC Article 517.13 <br />1. <br />2. <br />a. <br />b. <br />c. <br />d. <br />e. <br />5.Flexible liquid-tight conduit shall be installed in lieu of the flexible steel where required by NEC, or CEC where <br />adopted, in damp and wet location, where exposed to weather, in refrigerated area (65 Deg. F or less), and/or <br />between seismic joints. All rotating electrical equipment shall be supplied with flexible, liquid-tight conduit with <br />appropriate slack and shall not exceed thirty-six (36) inches. Include a separate insulated green ground <br />conductor sized per NEC in each conduit. Other uses of liquid-tight flexible conduit shall be allowed as <br />approved in writing by the Engineer on a case by case basis. <br />3.Provide a 1-1/2" high housekeeping pad above finished floor/finished for service equipment. Prior to pad <br />rough-in, Contractor shall verify serving utility company's maximum meter height requirements and, if <br />necessary, adjust height of housekeeping pad to comply with those requirements. In indoor applications, the <br />pad shall be flush with the face of the switchgear. In outdoor applications, the housekeeping pad shall extend <br />a minimum of 4 feet from the front of switchgear's weatherproof enclosure. Confirm pad dimensions with local <br />inspector prior to forming pad to ensure any local code interpretations/conditions are met regarding <br />housekeeping pads. <br />Provide a minimum 3" high housekeeping pad above finished floor/finished grade for all floor-mounted <br />switchgear, switchboards, distribution boards, transformers, motor control centers, etc., flush with the face of <br />the equipment. Located in mechanical central plant(s), other mechanical spaces, and located outdoors, pads <br />shall be flush with the face of the equipment. Confirm pad dimensions with local inspector prior to forming pad <br />to ensure any local code interpretations/conditions are met regarding housekeeping pads. <br />1. <br />G.House Keeping Pads: <br />i.Lightning Protection Systems and antennas. <br />11.Where conduit is underground, under slabs or grade, exposed to the weather, or in wet locations, make joints <br />liquid tight and gas tight. <br />Underground conduits, which terminate inside building(s) below grade, such as in a basement level, or <br />which slope so that water might flow into interior building spaces, shall be sealed at the point of <br />penetration with a modular conduit seal (Link-Seal or equal by Rox Systems). Conduit/conduit sealing <br />system penetrations of waterproofing membranes/systems on existing structures shall be completely <br />restored as required to maintain membrane/system manufacturer and installer warrantee for the <br />installation. All conduits shall be provided with a 4% slope away from buildings. All conduits shall be <br />installed such that the water cannot accumulate in the conduit and such that water drains into the nearest <br />manhole, pull box or vault and not into the facility. In instances where grade changes or elevation <br />differences prevent sloping of conduit away from a building into the nearest manhole, pull box or vault or <br />where accumulation of water in a manhole, pull box or vault may result in water traveling into the facility, <br />conduits shall be sealed internally at each end of each conduit using conduit sealing bushing, sized as <br />required for the conductors contained within the conduit (O-Z Gedney #CSBG 100psig withstand or <br />equal). In all cases, install plugs or caps in spare (empty) conduits at both ends of each conduit <br />(Jackmoon or equal) preventing both water and gas from entering the facility via the conduits. <br />e. <br />Where underground conduit passes under a building slab, concrete encasement may not be required, <br />except as required above, contact the Engineer for written direction prior to omitting any encasement. <br />d. <br />c.In all cases, where any conduit(s) pass under a building slab or footing, the electrical contractor will <br />provide a Bentonite clay or concrete barrier that conforms to the height and width of the trench excavation <br />extending a minimum of 24" on either side of the foundation. In all cases, where conduit(s) pass through <br />a sleeve in a footing or other foundation element, the electrical contractor will provide a Bentonite clay or <br />concrete barrier between the sleeve and the conduit(s) surrounding the conduit(s) for the entire depth of <br />the sleeve. The barrier is required to prevent passage of moisture under or through the slab or footing via <br />the trench or sleeve. <br />b.For all communications conduits 2" and larger, and feeders 100A or greater, provide with a minimum 3", <br />(2,000 LB) concrete envelope, 2" minimum separation between conduits, installed at depth of not less <br />than 24" below grade. (Provide concrete encasement and/or greater minimum conduit depth as required <br />by the Utility Companies.) Conduit separation within a duct bank shall be maintained using plastic <br />spacers located at 5'-0" intervals. Where power and communication conduits are run in a common trench, <br />a 12" minimum separation shall be maintained between power and communication conduits or as required <br />by Utility Companies. Where concrete encasement is not required by serving utlities for a utility-only duct <br />bank, provide free draining sand bedding suitable to acheive 95% relative compaction based on ASTM <br />D1557 using 6" lifts or directed by Utility Company Standards. <br />a.Underground conduit shall be Schedule 40 PVC (polyvinyl chloride) unless otherwise indicated elsewhere <br />in these specifications or as required per NEC, or CEC where adopted, Article 517.13. <br />The following additional requirements shall apply to underground conduits: <br />3. <br />2. <br />1. <br />Firestopping:F. <br />Each fire stop assembly/system shall have an "F" and/or "T" rating as required by each condition requiring fire <br />stopping. Each fire stop assembly/system shall have a current UL listing, as indicated in the latest edition of <br />the UL Fire Resistance Directory. Contractor shall verify acceptability of all fire stopping methods and system <br />selections with the authority having jurisdiction prior to installation. The Contractor shall install each firestop <br />assembly/system in accordance with the manufacturer's printed instructions <br />The Contractor shall be responsible for furnishing all material, labor, equipment, and services in conjunction <br />with the selection and installation of a complete, fully functioning, code compliant, UL-listed, fire stop <br />assembly/system(s) as required by project conditions. <br />6. <br />31. <br />8. <br />8. <br />7. <br />9. <br />10. <br />1. <br />2. <br />D. <br />3. <br />32. <br />34. <br />33. <br />35. <br />36. <br />37. <br />4. <br />5. <br />6. <br />7. <br />E. <br />END OF SECTION <br />1. <br />a. <br />2. <br />B.Installation of 600V Conductors: <br />4. <br />5. <br />All electrical wire, including signal circuits, shall be installed in conduit. <br />9. <br />10. <br />38. <br />13. <br />14. <br />12. <br />16. <br />17. <br />18. <br />6. <br />C.Grounding/Bonding: <br />1. <br />d. <br />c. <br />b. <br />a. <br />Exposed metal in maintenance holes, hand holes. <br />Raised Flooring. <br />h. <br />g. <br />f. <br />e. <br />3. <br />Transformers, Inverters, UPS, PDU, RDC, Transfer Switch and Generator Systems. <br />Telephone distribution equipment. <br />Non-current carrying metal parts of fixed equipment. <br />Panel boards, Distribution boards, Switchgear and Switchboards. <br />Neutral or identified conductors of interior wiring system. <br />Conduit, raceways and cable trays. <br />a. <br />4.Grounding System Connection: <br />b. <br />5. <br />c.Mechanical connectors shall not be used. <br />a. <br />19.Seismic Conduit Support: <br />20. <br />3-1/2" to 4" <br />CONDUIT SIZE <br />1/2" to 3" <br />MAXIMUM SPACING <br />6'-0" <br />8'-0" <br />21. <br />23. <br />22. <br />24. <br />25. <br />26. <br />28. <br />27. <br />29. <br />30. <br />Prefabricated Equipment: Installation of all prefabricated items and equipment shall conform to the requirements <br />of the manufacturer's specifications and installation instruction pamphlets. Where code requirements affect <br />installation of materials and equipment, the more stringent requirements, code or manufacturer's instructions <br />and/or specifications, shall govern the work. <br />The location of all power supply connection and/or terminations to the mechanical equipment is approximate. <br />The exact locations of these terminations shall be verified with other trades during construction. <br />It is the Contractor's responsibility to verify with the drawings of other trades regarding the extent of his <br />responsibility for mechanical equipment. The bid must include a sum sufficient to cover the cost of the <br />installation. <br />Unless otherwise noted, the Contractor shall furnish and install all conduit, boxes, wires, etc., for line voltage <br />wiring and low voltage wiring. <br />Provide power supplies to all plumbing and mechanical equipment, including, but not limited to, equipment <br />furnished and installed by Owner or Contractor, such as heating and air conditioning equipment, pumps, <br />boilers, auto valves and water coolers, etc. The installation shall produce a complete and operable system. <br />The location of all conduit terminations to the equipment is approximate. The exact location of these conduit <br />terminations shall be located and installed as directed by the Mechanical or Plumbing Contractor. <br />Power supplies to individual items of equipment shall be terminated in a suitable outlet or junction box <br />adjacent to the respective item of equipment, or a junction box provided by the manufacturer or the equipment <br />and directed by the Mechanical Contractor. Allow sufficient lengths of conductor at each location to permit <br />connection to the individual equipment without breaking the wire run. <br />An electric power supply, including conduit, any necessary junction and/or outlet boxes and conductors and <br />connection shall be furnished and installed by the Contractor for each item or mechanical equipment. <br />Line Voltage and Low Voltage Power Supplies to all Mechanical Equipment Including Plumbing, Heating and Air <br />Conditioning Units: <br />Building grounding system resistance to ground shall not exceed 25 ohms unless otherwise noted and should <br />be confirmed by testing. <br />Motors: Connect the ground conductor to the conduit with an approved grounding bushing, and to the metal <br />frame with a bolted solderless lug. Bolts, screws and washers shall be bronze or cadmium plated steel. <br />Ductwork: Provide a flexible ground strap, No. 6 AWG equivalent, at each flexible duct connection at each air <br />handler, exhaust fan, and supply fan, and install to preclude vibration. <br />Clean the contact surfaces of all ground connections prior to making connections. <br />Provide separate green equipment ground conductor in all electrical raceways to effectively ground all fixtures, <br />panels, controls, motors, disconnect switches, exterior lighting standards, and non current-carrying metallic <br />enclosures. Use bonding jumpers, grounding bushings, lugs, busses, etc., for this purpose. Connect the <br />equipment ground to the building system ground. Use the same size equipment ground conductors as phase <br />conductors, up through #10 AWG. Use NEC (or CEC where adopted) Table 250.122 for conductor size with <br />phase conductors #8 and larger, if not shown on the Drawings. <br />Isolated Ground Receptacles shall have an insulated ground wire connected between the receptacle and the <br />panelboard isolated ground bus. Unless otherwise noted, this ground wire shall not be grounded at any other <br />point, and shall be distinguished from other ground wires by a continuous yellow stripe. <br />Exothermic weld-type connectors shall be 'Cadweld' manufactured by Erico Products, or approved equal, <br />designed specifically for the intended connection. <br />Compression connectors shall be unplated copper, manufactured by Burndy, or approved equal, designed <br />specifically for the intended connection. <br />Use of Ground Rods: Furnish and install required number of 3/4" x 10' copper clad ground rods to meet <br />specified resistance, all required grounding wires, conduit and clamps. The size of the grounding conductors <br />shall be not less than that set forth in the latest edition of the California Code of Regulations, Title 24, State of <br />California and NEC (or CEC where adopted), unless otherwise indicated. Rods shall be installed such that at <br />least 10 feet of length is in contact with the soil. Where rock bottom is encountered, the electrode shall be <br />driven at an oblique angle not to exceed 45 degrees from vertical or shall be buried in a trench that is at least <br />30 inches deep. The upper end of the electrode shall be flush with or below ground level unless the above <br />ground end and the grounding electrode conductor attachments are protected against physical damage. <br />Unless otherwise noted, connection to the grounding electrode conductor may be by compression type or <br />exothermic process connector. Mechanical connectors shall not be used. <br />Provide grounding and bonding for entire electric installation as shown on plans, as listed herein, and as <br />required by applicable codes. Included, but not limited to, are items that require grounding/bonding: <br />Conductor Support: Provide conductor supports as required by codes and recommended by cable <br />manufacturer. Where required, provide cable supports in vertical conduits and provide lower end of conduit <br />with a ventilator. <br />For 20A branch circuit wiring, increase #12 conductors to #10 for 120V circuits longer than 100 feet and for <br />277V circuits longer than 150 feet. <br />Install UL approved fixture wire from all lighting fixture lamp sockets into fixture outlet or junction box. <br />Utilize pre-insulated "winged" spring type connectors, 3M Company "Performance Plus" #O/B or #R/Y or <br />equal and as required for splices and taps in conductors #6 AWG and smaller. When a spring connector <br />is used in an underground environment or when subject to moisture, utilize a 3M Company Scotchcast <br />3507G epoxy resin connector sealing pack to seal the spring connector. THE USE OF PUSH-WIRE <br />CONNECTORS (e.g. "WAGO" OR EQUIVALENT) IS STRICTLY PROHIBITED. <br />All circuits and feeder wires for all systems shall be continuous from overcurrent protective device or switch to <br />terminal or farthest outlet. No joints shall be made except in pull, junction or outlet boxes, or in panel or <br />switchboard gutters. <br />Tag all empty conduits at each accessible end with a permanent tag identifying the purpose of the conduit, <br />footage end-to-end, and the location of the other end. In wet, corrosive outdoor or underground locations, use <br />brass, bronze, or copper 16 gauge tags secured to conduit ends with #16 or larger galvanized wire. Inscribe <br />on the tags, with steel punch dies, clear and complete identifying information. <br />Except as otherwise indicated on the drawings or elsewhere in these specifications, bends in feeder and <br />branch circuit conduit 2 inches or larger shall have a radius or curvature of the inner edge, equal to not less <br />than ten (10) times the internal diameter of the conduit. Except where sweeping vertically into a building <br />where sweep radius equals ten (10) times conduit diameter, underground communications and building <br />interconnect conduits 3 inches or larger shall have a minimum 12'-6" radius or curvature of the inner edge. For <br />the serving utilities, radius bends shall be made per their respective specifications. <br />Seal all conduits where termination is subject to moisture or where conduit penetrates exterior wall, floor or <br />roof, in refrigerated areas, classified (hazardous areas) and as indicated on the drawings. <br />Where conduits or wireways cross seismic joints, provide approved flexible conduit connection or approved <br />expansion/deflection fitting to allow for displacement of conduit in all three axes. Connection shall allow for <br />movement in accordance with design of seismic joint. Non-flexible raceways crossing expansion joints or <br />other areas of possible structural movement shall make provision for 3-way movement at such points by <br />means of expansion/deflection fittings. Fittings shall be installed in the center of their axes of movement and <br />shall not be deflected to make part of a conduit bend, or compressed or extended to compensate for incorrect <br />conduit length. Install flexible conduit connection(s) or approved expansion/deflection fitting(s) complete with <br />ground jumpers. Where necessary, provide approved expansion joints to allow for thermal expansion and <br />contraction of conduit(s). Install expansion joints complete with ground jumpers. <br />All exposed conduits and support hardware shall be painted to match the finish of the wall or ceiling to which it <br />is supported. <br />All multiple conduit runs within suspended ceilings shall be suspended from building structure by means of <br />unistrut hangers/racks. Conduit shall not be allowed to lay on ceiling or be supported from ceiling suspension <br />wires or other suspension system. Support conduit to structure above suspended ceilings 8" minimum above <br />ceiling to allow removal of ceiling tile. Maintain two inch clearance above recessed light fixtures. <br />Provide nylon or a 1/8-inch O.D. polyethylene rope, rated at 250 pounds tensile strength, in all conduits more <br />than 5 feet in length left empty for future use. Not less than 5 feet of rope shall be left at each end of the <br />conduit. Tag all lines with a plastic tag at each end indicating the termination/stub location of the opposite end <br />of the conduit. <br />All conduit entries to outdoor mounted panels, cabinets, boxes, etc., shall be made using Myers "SCRU-TITE" <br />hubs Series ST. <br />All boxes installed outdoors shall be suitable for outdoor installations, gasketed, screw cover, and painted as <br />directed by the Architect with weatherproof paint to match building. <br />All boxes shall be covered with outlet box protector, Appleton SB-CK, or similar device/method to keep <br />dirt/debris from entering box, conduit or panels. If dirt/debris does get in, it shall be removed prior to pulling <br />wires. <br />Except where below grade, sleeves shall be installed where conduit passes through masonry or concrete walls <br />and shall be 24 gauge galvanized steel no more than 1/2" greater in diameter than the outside diameter of the <br />conduit. When located in non-rated structures, caulk conduit sleeve with stone wool. When located in fire <br />rated structures, provide UL listed fire stopping system. See fire stopping section of this specification for <br />additional requirements. <br />Surface mounted pull boxes, terminal cabinets, junction boxes, panel boards etc., shall be attached to walls <br />using appropriate screws, fasteners, backing plates, stud blocking, etc., as detailed on architectural and/or <br />structural drawings. If architectural and/or structural drawings are not provided on the project, Contractor shall <br />provide all necessary mounting hardware and backing support to comply with local building code requirements <br />and any additional requirements imposed by the local Authority-Having-Jurisdiction. <br />Junction Boxes that do not contain any device(s) shall be located in storage rooms, electrical closets or above <br />accessible ceilings, not in hard lid ceilings or other forms of inaccessible ceilings. Place boxes which must be <br />exposed to public view in a location approved by the Owner's Project Manager. Provide covers or plates to <br />match adjacent surfaces as approved by the Owner's Project Manager. <br />Recessed boxes shall not be mounted back-to-back in any wall; minimum offset shall be 24 inches. <br />Outlet boxes on metal studs shall be attached to metal hangers, tack welded or screwed to studs; On wood <br />studs attachment shall be with wood screws, nails are not acceptable. <br />Locate wall outlet of the same type at same level in all rooms, except where otherwise noted. <br />Open knockouts in outlet boxes only where required for inserting conduit. <br />All conduit runs shall be installed parallel or perpendicular to walls, structural members, or intersection of <br />vertical planes and ceilings. Field made bends and offset shall be avoided where possible. Crushed or <br />deformed raceway shall not be installed. <br />All conduit shall be supported in such a manner that it is securely attached to the structure of the building. <br />Attachment is to be capable of supporting the tributary weight of conduit and contents in any direction. <br />Maximum spacing of support and braces are to be as follows: <br />Nail-in conduit supports, one-piece set screw type conduit clamps or perforated iron for supporting conduit <br />shall not be used. <br />Where conduit racks are used, the rack shall consist of two piece conduit clamps attached to galvanized steel <br />slotted channels, properly secured via threaded rods attached directly to the building structure. <br />All conduit shall be supported at intervals not less than 6'-0" and within 12" from any outlet and at each side of <br />bends and elbows. Conduit supports shall be galvanized, heavy stamped, two-hole conduit clamp properly <br />secured. <br />All metal conduit in masonry and concrete and where concealed under floor slabs shall have joints painted <br />with thread compound prior to makeup. <br />Where conductors enter a raceway or a raceway in a cabinet, pull box, junction box, or auxiliary gutter, the <br />conductors shall be protected by a plastic bushing type fitting providing a smoothly rounded insulating surface. <br />No running threads will be permitted in locations exposed to the weather, in concrete or underground. Special <br />union fittings shall be used in these locations. <br />The ends of all conduits shall be cut square, carefully reamed out to full size and shall be shouldered in fitting. <br />Conduit shall be run so as not to interfere with other piping, fixtures or equipment. <br />Unless otherwise noted above, provide a minimum 1-1/2" high housekeeping pad above finished floor/finished <br />grade for all interior floor-mounted switchgear, distribution boards, transformers, motor control centers, transfer <br />switches, etc., flush with the face of the equipment. All housekeeping pad heights are as measured from <br />finished floor or grade. Confirm pad dimensions with local inspector prior to forming pad to ensure any local <br />code interpretations/conditions are met regarding housekeeping pads. <br />2. <br />4.All housekeeping pads located in, on, or attached to a building shall be seismically braced/connected to the <br />building structure. <br />39. <br />Provide J-box above accessible ceiling prior to running MC cable within partitions or walls. J-box shall be <br />permanently labeled with panel identification and circuit numbers contained within. <br />a. <br />Overhead MC cable runs shall generally follow building lines to provide a neat and workmanlike <br />installation. <br />b. <br />Provide code-sized J-boxes to accommodate MC cable splicing in general. For systems furniture <br />poke-through feeds utilizing MC cable, transition from MC cables to conduit and wire near the panelboard <br />in the TI accessible ceiling space on the floor below the panel board via code-sized gutter(s). Utilize UL <br />listed, insulated barrier strips with recessed screw heads (Ideal #89-6?? series or equal) fastened within <br />the gutter(s), terminate MC conductors on one side of the strip(s) and individual conductors in conduit <br />from the panel board(s) on the other side of the strip(s). Label each terminal strip(s) with panel <br />designation. Label each phase conductor with circuit number using wire markers (ideal or equal). Wire <br />nuts are not an acceptable alternative to the terminal strips in these underfloor transition locations. <br />Provide (1) spare 3/4" conduit from each gutter to its respective panelboard. <br />c. <br />MC cable shall not run directly into panelboards, distribution boards or electrical rooms.d. <br />MC cabling shall be provided with its own code-approved ceiling support wires, cable hangers, individual <br />spring steel support clips, steel trapeze hangers, threaded rods or dedicated #10 AWG drop wire. Cable <br />supports shall be fastened to concrete slabs, beams, joists or other structural members of the building. In <br />no case shall MC cable rest on ceilings, suspended ceilings or structures. Do not support MC cable using <br />ceiling support wires. The use of nylon cable ties to support MC cable is not allowed. <br />e. <br />Use lock or spring nut MC cable fittings.f. <br />Cable runs shall be continuous from wiring device to wiring device - no intermediate splicing J-boxes <br />allowed. <br />g. <br />When terminating or splicing at a junction, outlet, or switch box, cut the cable with an armored cable rotary <br />cutter such that 6" of free conductors remain for connections or splices. Use screw-in or spring lock <br />connector and ensure a proper bonding by firmly tightening the connector to both the box and cable. <br />Insert an anti-short bushing at cable ends to protect conductors from abrasion and use insulated <br />connectors. <br />h. <br />MC Cable bend radius shall not be less than seven (7) times the external diameter of the cable.i. <br />MC cables passing through fire-rated walls or floors shall be firestopped as required with a UL listed <br />system. See firestopping requirements outlined elsewhere in this specification for additional <br />requirements. <br />j. <br />Installation shall not exceed code requirements for total current carrying conductors in multiple MC cable <br />runs bundled together into a single MC cable hanger or strap, unless support device is specifically listed <br />for such purpose. Neutrals shall be counted as current carrying conductors. <br />k. <br />Maintain MC cable clearance of at least 6" from hot water and any other high temperature pipes. Maintain <br />at least 12" clearance between MC cable(s) and telecommunication conduits and cables. MC cable shall <br />cross telecommunication cables and conduits at right angles. <br />l. <br />MC cabling shall not be run through exposed ceilings, where open grid conditions exist, exposed on walls, <br />or exposed to view. See Power Plan and Lighting Plan General Notes for additional requirements. <br />m. <br />Installation of Metal Clad (MC) Cable (when use is permitted in the Allowed Specification Deviations Section or <br />Deductive/Additive Alternate Pricing Section generally located on the symbols list drawing). <br />Rigid metallic conduit installed underground or embedded in concrete shall be 1" trade size minimum and shall <br />be wrapped with 20 mil polyvinyl chloride plastic tape. PVC conduit installed underground or imbedded in <br />concrete shall be 3/4" minimum trade size. <br />6. <br />Each fire stop assembly/system shall be labeled with fire stop manufacturer-furnished label on each side of the <br />fire stopping systems depicting UL number, etc. <br />i.All PVC conduit shall be glued for a water and gas tight installation. The Contractor shall use appropriate <br />solvent on all joints prior to gluing conduit and fittings together. <br />7.Where required for providing an Electrical Circuit Protective System to comply with NEC, or CEC where <br />adopted, Articles 695 and 700, utilize UL Listed 2-hour fire-rated, MC cable or UL Listed 2-hour fire-rated <br />RHH/RHW conductors in conduit. <br />40. <br />When approved for use in the Allowed Specification Deviations Section or Deductive/Additive Alternate <br />Pricing Section, generally located on the symbols list drawing, 1/2" and 3/4" trade size ENT shall be <br />allowed for concealed lighting branch circuits, receptacle branch circuits and miscellaneous signal system <br />circuits within concrete floors, walls and columns within parking structures. <br />a. <br />ENT conduit shall meet the requirements of Underwriters Laboratories Standards 1479 and 1653, NEMA <br />TC-13, and be UL-listed. <br />b. <br />All ENT conduit, ENT fittings, ENT boxes and ENT accessories shall be UL listed and manufactured by <br />the same manufacturer so as to form a complete ENT system. ENT systems shall only be used if they are <br />listed for use in fire resistance rated concrete floors and ceilings with resistance ratings as indicated <br />elsewhere in the project plans. ENT System shall comply with NEC, or CEC where adopted, Article 362. <br />c. <br />All ENT fittings and ENT boxes shall be concrete-tight listed without the use of tape. Additionally, ENT <br />fittings shall be constructed of high-impact PVC and able to resist ENT conduit pull out forces of a <br />minimum of 175 lbs. ENT fittings with fewer than 6 locking tabs for ENT connection shall utilize <br />manufacturer-approved glue as additional protection from fitting/conduit separation. ENT conduit to rigid <br />conduit transition fittings shall be equipped with set screw fittings on the rigid conduit side of the fitting. <br />ENT to metal box fittings shall be equipped with a threaded end and lock washer. <br />d. <br />Where tubing enters a box, fitting or other enclosure provide a bushing or adapter to protect conductors <br />from abrasion unless the box, fitting, or enclosure design provides equivalent protection. <br />e. <br />ENT junction boxes shall have brass screw inserts and shall be rated to support lighting fixtures weighing <br />less than 50 lbs. <br />f. <br />Concrete tight metal boxes shall be used to support pendant hung fixtures or fixtures over 50 lbs.g. <br />ENT shall be provided in continuous lengths between junction boxes without use of in-line splices or <br />connectors and shall be clearly marked/labeled at least every 10-feet. <br />h. <br />All ENT conduit containing electrical branch circuits shall contain a code-sized equipment ground <br />conductor. <br />i. <br />ENT shall transition to EMT, IMC, RMC, or rigid PVC, as appropriate or as called out elsewhere in this <br />specification, for all exposed conduits within/on/under a parking structure. <br />j. <br />ENT shall transition to appropriately sized PVC expansion joint(s) at all structure expansion or seismic <br />joints. <br />k. <br />ENT shall be securely fastened and supported every 2 - 3 ft. and within 1 ft. of every junction box and <br />fitting to prevent movement and sag. <br />l. <br />ENT shall be routed straight without sags, or excessive bending. Where bends are required, comply with <br />Table 362.24 of the NEC for minimum radius of bends. Number of bends shall not exceed quantity <br />allowed by code where used for power and lighting branch circuit and/or feeder conductors. Where <br />utilized for communications system conductors (phones, data cabling, etc.) number of bends shall not <br />exceed the equivalent of (2) 90 degree bends with conduit length no more than 100 feet without <br />installation of a TIA 569-compliant pull box. <br />m. <br />Installation of Electrical Nonmetallic Tubing (ENT) Cable (when use is permitted in the Allowed Specification <br />Deviations Section or Deductive/Additive Alternate Pricing Section generally located on the symbols list <br />drawing). <br />Separation of ENT from fitting(s), excessive sags or deflections in ENT runs that prevent pulling of wire, <br />and other ENT system product or system installation failures/errors, shall be corrected by saw cutting and <br />patching as necessary at no additional cost to the Owner. Use of surface mounted conduits and junction <br />boxes as a repair method is unacceptable. <br />n. <br />Empty ENT runs shall be provided with a nylon pull string.o. <br />Coordinate installation of raceway with structural steel and other structural members. Do not cut, notch or <br />otherwise alter structural members without obtaining approval in writing from the Structural Engineer of <br />Record. <br />p. <br />No more than (2) 3/4" ENT conduits may cross each other within a horizontal concrete slab without <br />obtaining approval in writing from the Structural Engineer of Record. <br />q. <br />2.In multi-occupancy buildings, Contractor shall bond metal water piping systems installed in, under or attached <br />to a building and/or structure serving individual occupancies where the piping system(s) are metallically <br />isolated from each other. Per NEC, or CEC where adopted, ART. 250.104(A)(2) and (3), the bonding <br />conductor shall be sized per Table 250.122 and connected to the switchboard/panelboard serving that <br />suite/occupancy. <br />j.Metal piping installed in or attached to a building/structure. <br />k.Metallically isolated structural steel. <br />l.Metallically isolated underground metal water piping. <br />m.Elevator hydraulic piston/lift case. <br />5.Outlet boxes used for support of ceiling fans shall be galvanized, one-piece drawn steel, knockout type <br />equipped with bracing bars and plaster rings where required and listed for ceiling fan support use. Such boxes <br />shall be labeled and capable of supporting ceiling fan weights up to 70 pounds. <br />Isolated Ground Conductors: Green with continuous Yellow striped. <br />3. <br />5. <br />4. <br />= <br />= <br />2) <br />1) <br />Phase B <br />Phase A <br />= <br />= <br />= <br />5) <br />4) <br />Switchlegs <br />Neutral <br />Phase C3) <br />Power 208/120V, 3PH, 4W: <br />Blue <br />White or White with Phase Color Tracer <br />Black <br />Red <br />= <br />= <br />2) <br />1) <br />Phase B <br />Phase A <br />= <br />= <br />= <br />3) <br />4) <br />5) <br />Phase C <br />Neutral <br />Switchlegs <br />Power 480/277V, 3PH, 4W: <br />Orange <br />Grey or Grey with Phase Color Tracer <br />Yellow <br />Brown <br />Travelers6)=Purple with Black stripe or Pink <br />= <br />Ground Conductors: Green <br />Fire Alarm System: As recommended by the manufacturer <br />Travelers6)Purple with Black stripe or Pink. <br />a. <br />b. <br />c. <br />e. <br />Systems Conductor Color Coding: <br />Purple (Switchlegs shall also be identified separately by numerical tags). <br />Purple (Switchlegs shall also be identified separately by numerical tags) <br />Wire and cable shall be factory color-coded by integral pigmentation with a separate color for each phase and <br />neutral. Each system shall be color-coded and it shall be maintained throughout. <br />Wire and cable shall be new, manufactured not more than six (6) months prior to installation, shall have size, <br />type of insulation, voltage rating and manufacturer's name permanently marked on outer covering at regular <br />intervals. <br />2.Type THHN/THWN-2 thermoplastic, 600V, UL approved, dry and wet locations rated at 90 degrees Celsius, <br />for conductors of all sizes from #12 AWG up to and including 1000 kcmil. RHH/RHW insulation is allowed only <br />to provide an Electrical Circuit Protective System to comply with NEC, or CEC where adopted, Articles 695 and <br />700. <br />All conductors shall be copper. Provide stranded conductor for #10 AWG and larger or when making flexible <br />connections to vibrating machinery. Use compression "fork" type connectors or transition to solid conductors <br />when connecting to switches, receptacles, etc. <br />V. <br />1. <br />600V Conductors - Wire and Cable: <br />1. <br />W. <br />See drawings for Medium Voltage Cable Schedule and Specifications. <br />Medium Voltage Conductors (greater than 600V): <br />IP=1.0: Non-life safety, Non-structural Components in an Occupancy Category IV Facility not required for <br />continued operations of the facility or in any other Occupancy Category Facility where component failure <br />will not impair continued operation of the facility. <br />b.IP=1.5: Designated Seismic Systems are those non-structural components in any Occupancy Category IV <br />facility (except as noted above) or that are a part of any code-defined Critical, Life Safety, Emergency and <br />Legally Required Standby Electrical System. Additionally, those non-structural components containing <br />hazardous materials shall be classified as Designated Seismic Systems. While Designated Seismic <br />Systems are generally identified on the plans, they may include items such as Generators, Automatic <br />Transfer Switches, UPS units and all associated electrical distribution equipment and components <br />necessary for the designated seismic system to form a complete and operable system. The Contractor <br />shall ultimately be responsible for identifying Designated Seismic Systems. For any electrical component <br />either identified on the plans or determined by the contractor to be a Designated Seismic System, all line <br />and load side electrical distribution systems supporting that Designated Seismic System (including, but <br />not limited to, feeders, panel boards switchboards, transformers, all related component supports and <br />attachments, etc.) shall be considered a part of the designated seismic system for the purposes of <br />code-compliance and seismic certification. <br />c.z/h - Height factor ratio: See plans for respective equipment locations. <br />j.All underground conduit work shall conform to the Federal, State and Local Safety Orders or Rules <br />regarding excavations, trenches and related earthwork. For projects in California, refer to the California <br />Code of Regulations, Title 8, Construction Code Sections 1540 and 1541 for additional requirements. <br />2. <br />a. <br />b. <br />c. <br />d. <br />e. <br />Provide a delegated-design submittal for each of the following seismic-restraint systems to be used as <br />required: <br />Restraint Channel Bracings consisting of MFMA-4, shop-or field-fabricated bracing assembly made of <br />slotted steel channels with accessories for attachment to braced component at one end and to building <br />structure at the other end, with other matching components, and with corrosion-resistant coating; rated in <br />tension, compression, and torsion forces. <br />Restraint Cables consisting of ASTM A 603 galvanized-steel cables. End connections made of steel <br />assemblies with thimbles, brackets, swivel, and bolts designed for restraining cable service, with a <br />minimum of two clamping bolts for cable engagement. <br />Seismic-Restraint Accessories consisting of hanger rod/hanger rod stiffener assemblies, multifunctional <br />steel connectors for attaching hangers to rigid channel bracings and/or restraint cables, bushings for floor <br />and wall-mounted equipment, anchor bolts, and resilient isolation washers and bushings. <br />Mechanical Anchor Bolts consisting of drilled-in and stud-wedge or female-wedge type in zinc-coated steel <br />for interior applications and stainless steel for exterior applications. Select anchor bolts with strength <br />required for anchor and as tested according to ASTM E 488. <br />Adhesive Anchor Bolts consisting of drilled-in and capsule anchor system containing resin and <br />accelerator, or injected polymer or hybrid mortar adhesive. Provide specific LEED-compatible, <br />environmentally-friendly resins and adhesives on all LEED projects. Provide anchor bolts and hardware <br />with zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor <br />bolts with strength required for anchor and as tested according to ASTM E 488. <br />The contractor shall engage a qualified testing agency to perform tests and inspections as listed in other <br />Project Specifications, but as a minimum shall include at least four of each type and size of installed anchors <br />and fasteners selected by Architect. Schedule tests with Owner, through Architect, before connecting <br />anchorage device to restrained component (unless post connection testing has been approved), and with at <br />least seven days' advance notice. Obtain Architect's approval before transmitting test loads to structure. <br />Provide temporary load-spreading members as required. Test to 90 percent of rated proof load of device. <br />Prepare and submit test and inspections reports. <br />Multiple Raceways or Cables: Secure raceways and cables to trapeze member with clamps approved for <br />application by OSHPD or an agency acceptable to authorities having jurisdiction. <br />Install seismic-restraint devices using methods approved by OSHPD or an agency acceptable to authorities <br />having jurisdiction providing required submittals for component. <br />Install flexible connections in runs of raceways, cables, wireways, cable trays, and busways where they cross <br />seismic joints, where adjacent sections or branches are supported by different structural elements, and where <br />connection is terminated to equipment that is anchored to a different structural element from the one <br />supporting them as they approach equipment. Flexible connection limitations of the NEC, or CEC where <br />adopted, shall apply. <br />Coordinate the location of embedded connection hardware with supported equipment attachment and <br />mounting points and with requirements for concrete reinforcement and formwork specified elsewhere in the <br />project specifications. <br />Any pre-approval and evaluation documentation shall have a California Office of Statewide Health Planning <br />and Development (OSHPD) Special Seismic Certification Preapproval (OSP) demonstrating horizontal and <br />vertical load testing and analysis showing maximum seismic-restraint ratings, by ICC-ES or another agency <br />acceptable to authorities having jurisdiction. Ratings based on independent testing are preferred to ratings <br />based on calculations. If preapproved ratings are not available, submittals based on independent testing are <br />preferred. Calculations (including combining shear and tensile loads) that support seismic-restraint designs <br />must be signed and sealed by a qualified professional engineer. <br />Submittal shall include design calculations and details for selecting seismic restraints complying with <br />performance requirements, design criteria, and analysis data signed and sealed by the contractor's structural <br />engineer responsible for their preparation. Calculations shall include, but not be limited to, static and dynamic <br />loading caused by equipment weight, operation, and seismic and, if applicable, wind forces required to select <br />seismic and, if applicable, wind restraints and for designing vibration isolation bases. Provide seismic and <br />wind-restraint detailing to support system selection, arrangement of restraints, attachment locations, methods, <br />and spacings with all components identified to include their strengths, directions and values of forces <br />transmitted to the structure during seismic events and association with vibration isolation devices. Sizes of <br />components shall be selected so strength will be adequate to carry present static and seismic loads to <br />accommodate 25% spare future capacity within specified loading limits. <br />3. <br />4. <br />5. <br />6. <br />7. <br />9. <br />8. <br />6. <br />7.Conduit unions shall be "Erickson" couplings, or approved equal. The use of running threads will not be <br />permitted. <br />Flexible steel conduit connectors shall be a malleable iron clamp or squeeze type or steel twist-in type with <br />insulated throat. The finish shall be zinc or cadmium plating. <br />All interior and exterior EMT fittings, connectors and couplings, 2" and smaller, installed in exposed or <br />concealed locations that are considered by the AHJ to be wet or damp locations, shall be raintight-listed, steel, <br />zinc or cadmium plated, threadless, compression, steel locking ring type with insulated throat. If <br />raintight-listed, EMT fittings, connectors and couplings are unavailable for a given trade size or if conduit is <br />installed in an area subject to damage - provide rigid metallic or intermediate metallic conduits, fittings, <br />connectors and couplings as required. <br />5. <br />1. <br />2. <br />3. <br />U.Fittings: <br />Connector, coupling, locknut, bushings and caps used with rigid conduit shall be steel, threaded and <br />thoroughly galvanized. Bushings shall be insulated. <br />Metallic condulet covers shall have the same finish as the fitting and shall be provided for the opening of each <br />fitting where conductors do not pass through the cover. <br />Condulet type fittings shall be smooth inside and out, taper threaded with integral insulating bushing and of the <br />shapes, sizes and types required to facilitate installation or removal of wires and cables from the conduit and <br />tubing system. These fittings shall be of metal, smooth inside and out, thoroughly galvanized, and sherardized <br />cadmium plated. <br />UON all interior EMT fittings, connectors and couplings installed in concealed locations, areas not considered <br />to be wet or damp locations by the AHJ, or areas not subject to physical damage, shall be steel, zinc or <br />cadmium plated, threadless, compression, steel locking ring type with insulated throat. Where suitable for use, <br />steel set screw fittings are allowed for trade sizes of 2" and smaller. Insulated throat is not required for fittings, <br />connectors and couplings 1" and smaller. <br />4. <br />PVC conduit shall not be run in walls except where approved by the Engineer prior to bid in limited instances <br />that may include concrete or CMU walls used in site retaining, parking structures, or exterior equipment yard <br />or enclosure walls, etc. <br />3.Thoroughly clean all conduit and wire-ways and see that all parts are perfectly dry before pulling any wires. <br />15.Where conduit extends through roof to equipment on roof area, the Contractor shall provide flashing material <br />compatible with the roofing system as required by the roofing specifications or as required by the Owner's roof <br />warranty. This flashing shall be delivered to the roofing Contractor for installation. The actual location of all <br />such roof penetrations and outlets shall be verified by the Architect/Owner. Contractor to verify type of flashing <br />prior to bid and include all costs. <br />g.All underground conduits with circuits rated at 40A or greater and all underground communications <br />conduits shall be provided with a metallic marker tape located 12" below the finished grade. <br />Include a separate insulated green ground conductor sized per NEC, or CEC where adopted, in each <br />underground electrical feeder/branch circuit. <br />f. <br />Where underground conduits sweep into/through slabs, utilize PVC 90 degree sweeps that transition, via <br />female PVC adapter to GRC coupling mounted flush in slab. GRC couplings shall be 1/2 lap taped with <br />20 mil tape. If the distance of the conduit run between a sweep and the next connecting sweep, pullbox, <br />vault or manhole exceeds 150 ft then the sweep shall be concrete encased. Exceptions: <br />h. <br />Communications conduits shown terminating at a finished floor shall have an additional 4" high GRC <br />nipple equipped with a bushing, removable conduit plug, labeling tag and pull rope. Tie off pull rope <br />to conduit plug. <br />1) <br />Utility conduit sweeps shall be installed per the requirements of the respective utility company.2) <br />2) <br />1) <br />When located in an interior environment, the splice shall be made with an ILSCO or equal dual rated, <br />insulated splicer-reducer connector or multi-tap connector listed for use with 75/90 degree Celsius <br />rated conductors. <br />When located in an underground environment or when subject to moisture, the splice shall be made <br />with compression connector and sealed by a 3M, or equal, PST cold shrink connector insulator. <br />Wires #4 AWG and larger AWG shall be joined together as follows:b. <br />c.Connections to busbar shall be made with dual-rated copper/aluminum one-piece compression lugs. <br />Paralleled conductor connections shall be by mechanical lugs. <br />Use of MC-AP, "MC All Purpose" or MC cabling where the interlocked armor sheath forms all or a portion <br />of the equipment grounding conductor is expressly prohibited. <br />n. <br />tk1sc project number: B2305501.000 <br />drawn by:checked by: <br />drawing no.: <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />pl <br />a <br />n <br />n <br />i <br />n <br />g <br />in <br />t <br />e <br />r <br />i <br />o <br />r <br />s <br />tB <br />P <br />/ <br />A <br />r <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />46 <br />1 <br />1 <br /> <br />T <br />e <br />l <br />l <br />e <br />r <br /> <br />A <br />v <br />e <br />n <br />u <br />e <br />Ne <br />w <br />p <br />o <br />r <br />t <br /> <br />B <br />e <br />a <br />c <br />h <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />6 <br />0 <br />ph <br />: <br /> <br />9 <br />4 <br />9 <br />. <br />6 <br />7 <br />3 <br />. <br />0 <br />3 <br />0 <br />0 <br />consultant <br />agency <br />owner <br />date: <br />drawing title: <br />description:date:Rev: <br />tBP project number : <br />architect <br />THIS DRAWING AND THE DESIGNS, DEPICTIONS, IDEAS AND OTHER INFORMATION <br />CONTAINED HEREIN CONSTITUTE UNPUBLISHED WORK OF tBP/ARCHITECTURE AND <br />SHALL REMAIN THE PROPERTY OF tBP/ARCHITECTURE IN PERPETUITY. NO PART <br />THEREOF SHALL BE REPRODUCED, DISCLOSED, DISTRIBUTED, SOLD, PUBLISHED OR <br />OTHERWISE USED IN ANY WAY WITHOUT THE ADVANCED EXPRESS WRITTEN CONSENT <br />OF tBP/ARCHITECTURE. <br />ph: 714.667.2700 <br />SANTA ANA, CA 92701 <br />20 CIVIC CENTER PLAZA <br />SANTA ANA PLANNING AND BUILDING AGENCY <br /># <br />DA <br />N <br />C <br />E <br /> <br />S <br />T <br />U <br />D <br />I <br />O <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />L <br />I <br />F <br />O <br />R <br />N <br />I <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />12 <br />0 <br />2 <br /> <br />W <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />MA <br />T <br />E <br />R <br /> <br />D <br />E <br />I <br /> <br />H <br />I <br />G <br />H <br /> <br />S <br />C <br />H <br />O <br />O <br />L <br />21125.00 <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />L <br />I <br />F <br />O <br />R <br />N <br />I <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />12 <br />0 <br />2 <br /> <br />W <br /> <br />E <br />D <br />I <br />N <br />G <br />E <br />R <br /> <br />A <br />V <br />E <br />MA <br />T <br />E <br />R <br /> <br />D <br />E <br />I <br /> <br />H <br />I <br />G <br />H <br /> <br />S <br />C <br />H <br />O <br />O <br />L <br />21125.00 <br />09/06/2023 <br />11870 Pierce Street, Suite 160 <br />Riverside, California 92505 <br />951.299.4160 www.tk1sc.com <br />Project Leader - Bill Voller <br />tk1sc Job #: B2305501.000 <br />Electrical Lead - Marie Rothenberger <br />City Submittal 09/06/23- <br />ELECTRICAL <br />SPECIFICATIONS <br />E5-2 <br />21159.00 <br />1202 W Edinger <br />Ave10/3/2024