Laserfiche WebLink
1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER CEC 310.10(D). <br />2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER CEC310.10(C). <br />3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. <br />4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED. 5.BREAKER/FUSE SIZES CONFORMS TO CEC <br />240.6 CODE SECTION. <br />6.AC GROUNDING ELECTRODE CONDUCTOR SIZED PER CEC 250.66. <br />7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 690.31(A). <br />8.AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON CEC 310.15(B)(2). <br />9.MAX. SYSTEM VOLTAGE CORRECTION IS PER CEC 690.7. <br />10.CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE CEC 310.15(B)(16). <br />SCOPE: <br />2.40 KW DC Roof Mounted <br />PV Electrical System <br />6 - Ureco 400W PV Modules <br />6 - IQ8+ Enphase Microinverters <br />DATE:03/10/2023 <br />SCALE:AS NOTED PAPER SIZE:17"x11" <br />CUSTOMER INFORMATION <br />BUILDING INFO: <br />ONE STORY BUILDING <br />ROOF TYPE: COMPOSITION SHINGLE <br />ROOF STRUCTURE: <br />2''X4'' RAFTERS 24'' O/C <br />MOUNTING SYSTEM: <br />IRONRIDGE RACKING <br />PARCEL NUMBER: 10936105 <br />LOT AREA: 6,272 SQFT <br />LIVING AREA: 1,139 SQFT <br />COMPANY NAME: SKYSOLARPRO <br />ANDREY LITVINOV: #867980 TYPE: C10 <br />DATE: 11/30/2023 <br />ADDRESS: 11208 DONA LOLA DRIVE <br />STUDIO CITY, CA 91604 <br />PHONE: (323) 428-4892 <br />SIGNATURE <br />NAME: PET MARTINEZ <br />ADDRESS: 1705 W CUBBON ST, <br />SANTA ANA, CA 92703 <br />CITY OF SANTA ANA <br />UTILITY: SCE <br />PV-3 <br />WIRE SIZE CALCULATION <br />WIRE TAG#WIRE TYPE <br />AND SIZE <br /> QUANTITY OF <br />WIRES <br />GROUNDING <br />SIZE <br />WIRE <br />AMPACITY TEMPERATURE CONDUIT TYPE ABOVE ROOF TEMP. DERATE <br />FACTOR ADJUSTING FACTOR <br />CORRECTED <br />CONDUCTOR <br />AMP <br />CURRENT <br />AMP <br />A Q CABLE #10 2 #6, BARE CU 40 A 90°Free in the air >3.5 - 12''0.71 1 N/A 28.4 9.1 <br />B THWN-2 #10 <br />(L1,L2)2 #8, EGC CU 40 A 90°3/4'' EMT >3.5 - 12''0.71 1 N/A 28.4 9.1 <br />C THWN-2 #10 <br />(L1,L2,N)3 #8, EGC CU 40 A 90°3/4'' EMT ALONG THE <br />WALL 0.91 1 N/A 36.4 9.1 <br />PV SYSTEM OUTPUT CALCULATION <br />6 IQ8PLUS-72-2-US (CEC) 97.0 % <br />6 <br /> Ureco 400W (FBM400MFG-BB) 400.0 W <br />Pmax (PTC Rating) 367.8 W <br />Max DC Output 6 * 400.0 2.40 KW <br />Max AC Output 6 * 367.8 * 0.970 2.14 KW <br />WIRE AMPACITY <br /># QUANTITY ISC <br /> CONSIDER <br />CONTINUOUS <br />COEFFICIENT <br />CURRENT <br />AMP <br />A 6 1.21 1.25 9.1 <br />B 6 1.21 1.25 9.1 <br />C 6 1.21 1.25 9.1 <br />ELECTRICAL CALCULATION <br />MAIN SERVICE PANEL RATING <br />BUSBAR RATING 100 A <br />MIAN BREAKER 100 A <br />PV BREAKER SIZE 20 A <br />120% RULE <br />MAX ALLOWED FEED 120 A <br />100A ''MB'' + 20A "SOLAR" =120A ≤ 120A MAX <br />1705 W Cubbon St <br />04/14/23