LIGHTING PLAN - 2ND FLOOR <br />LEGENDS: <br />: PRIMARY DAYLIGHT ZONE <br />1.EMERGENCY/NL AND EXIT FIXTURES TO BE CONNECTED TO NEARBY ROOM <br />LIGHTING CIRCUIT AHEAD OF LOCAL SWITCH. [2022 CEC 700.12(I)(2)(3)(A)]. <br />2.INTERLOCK RESTROOM LIGHT WITH EXHAUST FAN AND PROVIDE MANUAL <br />MOTOR SWITCH IF NOT PLUG/BUILT-IN. <br />3.GENERAL LIGHTING IN DAYLIT ZONES SHALL BE PROVIDED WITH CONTROLS <br />THAT AUTOMATICALLY ADJUST THE POWER OF THE INSTALLED LIGHTING UP <br />AND DOWN TO KEEP THE TOTAL LIGHT LEVEL STABLE AS THE AMOUNT OF <br />INCOMING DAYLIGHT CHANGES. [2022 CENC 130.1(D)] <br />#KEYED PLAN NOTES: <br />GENERAL NOTES: <br />1.ELECTRICAL EQUIPMENT SHALL BE LISTED BY U.L. OR CITY RECOGNIZED <br />ELECTRICAL TESTING LABORATORY OR APPROVED BY THE CITY <br />DEPARTMENT. <br />2.ALL ELECTRICAL WORK SHALL COMPLY WITH THE [2022 CEC]. <br />3.WIRE SIZE SHALL NOT BE LESS THAN CORRESPONDING CIRCUIT BREAKER <br />RATING AS REQUIRED. [2022 CEC TABLE 310.16] <br />4.CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE [2022 CEC ANNEX C]. <br />5.CONTRACTOR/ELECTRICIAN TO FIELD VERIFY ACTUAL SITE CONDITION <br />/EXACT SERVICE ENTRANCE AND SHALL NOTIFY EOR(S) ANY DISCREPANCY <br />WITH THE PLAN PRIOR TO BIDDING. <br />6.ALL ITEMS LABELED/IDENTIFIED AS EXISTING (IF ANY) ARE SUBJECT TO <br />FIELD VERIFICATION. VERIFY EXISTING CONDITION AND RE-USE. IF NOT <br />EXISTING, PROVIDE PER PLAN. <br />7.OBTAIN APPROVAL ON LOCATION OF SWITCH/DIMMER/SENSOR WITH <br />ARCHITECT/OWNER AT SITE PRIOR TO ROUGH-IN. <br />8.SIGNAGE WILL REQUIRE SEPARATE PERMIT AND SUBMITTAL. <br />9.REFER TO EMERGENCY EXIT ILLUMINATION NOTES FOR EMERGENCY <br />LIGHTING REQUIREMENTS. <br />10.IN OFFICES 250 SQUARE FEET OR SMALLER, MULTIPURPOSE ROOMS OF <br />LESS THAN 1,000 SQUARE FEET, CLASSROOMS OF ANY SIZE, CONFERENCE <br />ROOMS OF ANY SIZE, AND RESTROOMS OF ANY SIZE, LIGHTING SHALL BE <br />CONTROLLED WITH OCCUPANT SENSING CONTROLS TO AUTOMATICALLY <br />SHUT OFF ALL OF THE LIGHTING IN 20 MINUTES OR LESS AFTER THE <br />CONTROL ZONE IS UNOCCUPIED. [2022 CENC 130.1(C)(5)] <br />A.IN AREAS W/ MULTI-LEVEL LIGHTING CONTROLS, THE OCCUPANT <br />SENSING CONTROLS SHALL FUNCTION AS A PARTIAL-ON OCCUPANT <br />SENSING CONTROLS CAPABLE OF AUTOMATICALLY ACTIVATING <br />BETWEEN 50 AND 70 PERCENT OF CONTROLLED LIGHTING POWER <br />B.IN AREAS W/O MULTILEVEL LIGHTING CONTROLS, THE OCCUPANT <br />SENSING CONTROLS SHALL FUNCTION AS A VACANCY SENSING <br />CONTROLS, WHERE ALL LIGHTING RESPONDS TO A MANUAL ON INPUT <br />ONLY. <br />11.IN CORRIDORS AND STAIRWELLS, LIGHTING SHALL BE CONTROLLED BY <br />OCCUPANT SENSING CONTROLS THAT SEPARATELY REDUCE THE LIGHTING <br />POWER IN EACH SPACE BY AT LEAST 50 PERCENT WHEN THE SPACE IS <br />UNOCCUPIED. THE OCCUPANT SENSING CONTROLS SHALL BE CAPABLE OF <br />AUTOMATICALLY TURNING THE LIGHTING FULLY ON ONLY IN THE <br />SEPARATELY CONTROLLED SPACE, AND SHALL BE AUTOMATICALLY <br />ACTIVATED FROM ALL DESIGNED PATHS OF EGRESS. [2022 CENC <br />130.1(C)(6)(C)] <br />12.IN OFFICE SPACES GREATER THAN 250 SQUARE FEET, GENERAL LIGHTING <br />SHALL BE CONTROLLED WITH OCCUPANT SENSING CONTROLS THAT MEET <br />ALL OF THE FOLLOWING: [2022 CENC 130.1(C)(6)(D)] <br />A.THE OCCUPANT SENSING CONTROLS SHALL BE CONFIGURED SO THAT <br />LIGHTING SHALL BE CONTROLLED SEPARATELY IN CONTROL ZONES NOT <br />GREATER THAN 600 SQUARE FEET. FOR LUMINAIRES WITH AN <br />EMBEDDED OCCUPANT SENSOR THAT ARE CAPABLE OF REDUCING <br />POWER INDEPENDENTLY FROM OTHER LUMINAIRES, EACH LUMINAIRE <br />CAN BE CONSIDERED ITS OWN CONTROL ZONE; AND <br />B.IN 20 MINUTES OR LESS AFTER THE CONTROL ZONE IS UNOCCUPIED, <br />THE OCCUPANT SENSING CONTROLS SHALL UNIFORMLY REDUCE <br />LIGHTING POWER IN THE CONTROL ZONE TO BY AT LEAST 80 PERCENT <br />OF FULL POWER. CONTROL FUNCTIONS THAT SWITCH CONTROL ZONE <br />LIGHTS COMPLETELY OFF WHEN THE ZONE IS VACANT MEET THIS <br />REQUIREMENT; AND <br />C.IN 20 MINUTES OR LESS AFTER THE ENTIRE OFFICE SPACE IS <br />UNOCCUPIED, THE OCCUPANT SENSING CONTROLS SHALL <br />AUTOMATICALLY TURN OFF LIGHTING IN ALL CONTROL ZONES IN THE <br />SPACE; AND <br />D.IN EACH CONTROL ZONE, LIGHTING SHALL BE ALLOWED TO <br />AUTOMATICALLY TURN ON TO ANY LEVEL UP TO FULL POWER UPON <br />OCCUPANCY WITHIN THE CONTROL ZONE. WHEN OCCUPANCY IS <br />DETECTED IN ANY CONTROL ZONE IN THE SPACE, THE LIGHTING IN <br />OTHER CONTROL ZONES THAT ARE UNOCCUPIED SHALL OPERATE AT NO <br />MORE THAN 20 PERCENT OF FULL POWER. <br />STAIRCASE 2 <br />STAIRCASE 1 <br />UNISEX 2 <br />OFFICE 2 <br /> C <br />L1 L1 L1 <br />L1 L1 L1 L1 L1 <br />L1 <br />L1 <br />L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 <br />L1 L1 L1 L1 L1 L1 L1 <br />L1 <br />L1 <br />L1 <br />L1 L1 L1 L1 <br />L1 L1 L1 L1 L1 <br />L2 L2 <br />9' <br />- <br />0 <br />" <br />9' <br />- <br />0 <br />" <br />DL <br />DL <br />DL DL <br />DL <br />DL <br />OS <br />D D <br />D D <br />TO DIMMER BELOW <br />TO DIMMER BELOW <br />A-13 A-13 <br />A-13 <br />A-13 <br />A-13 <br />A-13 <br />A-13 <br />X <br />1 <br />EE <br />EE <br />X 1 <br />EE EE <br />EE EE EE EE EE EE <br />EE EE EE <br />OS OS OS OS <br />OS <br />OS <br />OS OS <br />OS <br />OS <br />3 <br />3 <br />33 <br />3 <br />3 <br />2 <br />L1 <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />SHEET TITLE: <br />DATE: SCALE: <br />AN <br />C <br />E <br />N <br />A <br />Y <br /> <br />C <br />O <br />M <br />M <br />E <br />R <br />C <br />I <br />A <br />L <br /> <br />O <br />F <br />F <br />I <br />C <br />E <br />01/11/2024 <br />PLOT DATE: 7/10/2024 1:27:16 PM <br />CD <br />I <br /> <br />Ci <br />r <br />c <br />a <br /> <br />D <br />o <br />m <br />i <br />n <br />i <br /> <br />I <br />n <br />t <br />e <br />r <br />n <br />a <br />t <br />i <br />o <br />n <br />a <br />l <br />, <br /> <br />I <br />n <br />c <br />. <br />En <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />- <br /> <br />C <br />o <br />n <br />s <br />u <br />l <br />t <br />i <br />n <br />g <br />98 <br />9 <br />0 <br /> <br />R <br />e <br />s <br />e <br />a <br />r <br />c <br />h <br /> <br />D <br />r <br />. <br /> <br />S <br />u <br />i <br />t <br />e <br /> <br />1 <br />0 <br />0 <br />, <br /> <br />I <br />r <br />v <br />i <br />n <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />1 <br />8 <br />Ph <br />o <br />n <br />e <br /> <br />( <br />9 <br />4 <br />9 <br />) <br /> <br />5 <br />3 <br />3 <br />- <br />4 <br />1 <br />1 <br />7 <br /> <br />| <br /> <br />d <br />k <br />a <br />n <br />g <br />@ <br />c <br />d <br />i <br />e <br />n <br />g <br />. <br />c <br />o <br />m <br />21 <br />0 <br />W <br />. <br /> <br />1 <br />9 <br />T <br />H <br /> <br />S <br />T <br />R <br />E <br />E <br />T <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />6 <br />DRAWN: CHECKED: <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />V <br />. <br /> <br />0 <br />6 <br />/ <br />2 <br />8 <br />/ <br />2 <br />0 <br />2 <br />4 <br />E101 <br />1/4" = 1'-0" <br />LIGHTING PLAN - <br />2ND FLOOR <br />J.L.H.N. <br />210 W 19th St <br />4/14/2025