Laserfiche WebLink
GENERAL NOTES: <br />POWER PLAN - 1ST FLOOR <br />1.ELECTRICAL EQUIPMENT SHALL BE LISTED BY U.L. OR CITY RECOGNIZED <br />ELECTRICAL TESTING LABORATORY OR APPROVED BY THE CITY <br />DEPARTMENT. <br />2.ALL ELECTRICAL WORK SHALL COMPLY WITH THE [2022 CEC]. <br />3.WIRE SIZE SHALL NOT BE LESS THAN CORRESPONDING CIRCUIT BREAKER <br />RATING AS REQUIRED. [2022 CEC TABLE 310.16] <br />4.CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE [2022 CEC ANNEX C]. <br />5.CONTRACTOR/ELECTRICIAN TO FIELD VERIFY ACTUAL SITE CONDITION <br />/EXACT SERVICE ENTRANCE AND SHALL NOTIFY EOR(S) ANY DISCREPANCY <br />WITH THE PLAN PRIOR TO BIDDING. <br />6.ALL ITEMS LABELED/IDENTIFIED AS EXISTING (IF ANY) ARE SUBJECT TO FIELD <br />VERIFICATION. VERIFY EXISTING CONDITION AND RE-USE. IF NOT EXISTING, <br />PROVIDE PER PLAN. <br />7.COORDINATE LOCATIONS/HEIGHTS OF RECEPTACLES FOR ELECTRICAL <br />DEVICES WITH ARCHITECT AND EQUIPMENT VENDER PRIOR TO ROUGH-IN. <br />8.ALL NEW ELECTRICAL EQUIPMENT (IF ANY) DIMENSIONS TO BE VERIFIED <br />WITH EQUIPMENT MANUFACTURER/VENDER PRIOR TO PURCHASE. <br />9.GFCI PROTECTION: ALL 125V THROUGH 250V RECEPTACLES SUPPLIED BY <br />1-PHASE BRANCH CIRCUITS, 50 AMPERES OR LESS, AND ALL RECEPTACLES <br />SUPPLIED BY 3-PHASE BRANCH CIRCUITS RATED 150 VOLTS OR LESS TO <br />GROUND, 100 AMPERES OR LESS, INSTALLED IN THE FOLLOWING LOCATIONS <br />SHALL HAVE GFCI PROTECTION FOR PERSONNEL. [2022 CEC 210.8(B)] <br />A.BATHROOMS <br />B.KITCHENS OR AREAS WITH A SINK AND PREM. PROVISION FOR COOKING <br />C.ROOFTOPS/OUTDOORS <br />D.SINKS - WITHIN 6FT FROM THE TOP INSIDE EDGE OF THE SINK <br />E.GARAGES, UNFINISHED AREAS OF BASEMENTS OR SIMILAR AREAS <br />10.FOR ALL PERMANENTLY CONNECTED APPLIANCES RATED OVER 300VA, THE <br />CIRCUIT BREAKER CAPABLE OF BEING LOCKED IN THE OPEN POSITION <br />SHALL BE PROVIDED UNLESS LOCATION OF THE BREAKER IS WITHIN THE <br />SIGHT OR SEPARATE DISCONNECTING MEANS IS PROVIDED. [2022 CEC <br />110.25, 422.31(B)] <br />11.RECEPTACLES OF 15 AND 20 AMPERES, 125 AND 250 VOLTS INSTALLED IN A <br />WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF (WP) <br />AND IS LISTED/IDENTIFIED AS “EXTRA DUTY”. THE RECEPTACLES SHALL BE <br />GFCI PROTECTED. [CEC 2022 210.8(B)(4), 406.9(B)] <br />KEYED PLAN NOTES:# <br />1.VERIFY/COORDINATE EXACT LOCATION FOR ELECTRICAL EQUIPMENTS AND <br />PROVIDE/MAINTAIN MINIMUM CLEARANCE. [2022 CEC 110.26] <br />2.ONE OUTLET/DUPLEX RECEPTACLE TO BE CONTROLLED BY OCC./VACANCY <br />SENSOR FROM ROOM LIGHTS OR SEPARATE SENSOR. RECEPTACLE SHALL <br />BE LABELED AS CONTROLLED WITH PREMANENT AND DURABLE MARKING. <br />[2022 CENC130.5(D)] <br />3.PROVIDE GFCI/WATERPROOF/WEATHER RESISTANT RECEPTACLE WITHIN <br />25FT OF HEATING, AC, AND REFRIGERATION EQUIPMENT. <br />4.REFER TO MECHANICAL PLAN AND HVAC SYSTEM CONNECTION SCHEDULE <br />FOR EXACT LOCATIONS, SPECS AND INSTALLATION REQUIREMENTS. <br />5.VERIFY EXACT ELECTRICAL INSTALLATION REQUIREMENTS WITH <br />MANUFACTURER AND PROVIDE PER RECOMMENDATION. <br />HVAC SYSTEM CONNECTION SCHEDULE <br />EQUIPMENT CIRCUIT <br />DESIGNATION VOLT/PHASE FEEDER DISCONNECT <br />HP-1 A-20/22 208V/1PH 3#8, #10GND- 3/4"C 40AF/60AS/2P <br />HP-2 A-24/26 208V/1PH 3#8, #10GND- 3/4"C 40AF/60AS/2P <br />HP-3 A-28/30 208V/1PH 3#8, #10GND- 3/4"C 40AF/60AS/2P <br />FC-1 A-8/10 208V/1PH 3#12, #12GND- 3/4"C 15AF/30AS/2P <br />MECHANICAL EQUIPMENT NOTES: <br />1.PROVIDE OVERCURRENT PROTECTION AND BRANCH CIRCUITS PER UL LISTED <br />REQUIREMENTS FOR EQUIPMENT SERVED. REFER TO MANUFACTURER DATA <br />AND EQUIPMENT CUT-SHEETS FOR ROUGH-IN LOCATIONS OF ELECTRICAL <br />CONNECTIONS AND INTERCONNECTIONS FOR ALL EQUIPMENT. COORDINATE <br />EXACT NAMEPLATE DATA OF EQUIPMENT BEING INSTALLED WITH MECHANICAL <br />CONTRACTOR. <br />2.SWITCHES USED AS DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT <br />OF EQUIPMENT. PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. <br />NON-FUSED DISCONNECT IS ACCEPTABLE INSTEAD OF SPECIFIED FUSE TYPE. <br />3.ADJUST SIZE OF CONDUCTORS AS NEEDED COMPENSATE FOR VOLTAGE DROP. <br />VOLTAGE DROP SHALL NOT EXCEED 3% FOR BRANCH CIRCUITS. <br />4.REFER TO MECHANICAL PLAN FOR MORE INFO. <br />5.IF EXISTING UNITS ARE RE-USED, EXISTING DISCONNECT/FUSE/BREAKER TO BE <br />RE-USED OR REPLACED WITH SAME RATING. VERIFY EXISTING CONDITION IN <br />FIELD. <br />STAIRCASE 2 <br />STAIRCASE 1 <br />TRASH ENCLOSURE <br />OFFICE 1 <br />UNISEX 1 <br />T CA-7 <br />A-2 <br />A-32 <br />PANEL <br />"A" <br />MAIN SWITCHBOARD "MS" <br />1 <br />1 <br />22 <br />2 <br />2 <br />2 <br />3 <br />HP <br />2 <br />HP <br />1 <br />HP <br />1 <br />FC <br />(ON CEILING) <br />WR/WP WR/WP <br />A-6 <br />33 <br />4 <br />4 4 4 <br />J #10 <br />INSTA <br />HOT <br />A-25 <br />RESTR <br />5 <br />DIST.P.S. <br />METER/MAIN <br />2 <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />SHEET TITLE: <br />DATE: SCALE: <br />AN <br />C <br />E <br />N <br />A <br />Y <br /> <br />C <br />O <br />M <br />M <br />E <br />R <br />C <br />I <br />A <br />L <br /> <br />O <br />F <br />F <br />I <br />C <br />E <br />01/11/2024 <br />PLOT DATE: 7/10/2024 1:27:12 PM <br />CD <br />I <br /> <br />Ci <br />r <br />c <br />a <br /> <br />D <br />o <br />m <br />i <br />n <br />i <br /> <br />I <br />n <br />t <br />e <br />r <br />n <br />a <br />t <br />i <br />o <br />n <br />a <br />l <br />, <br /> <br />I <br />n <br />c <br />. <br />En <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />- <br /> <br />C <br />o <br />n <br />s <br />u <br />l <br />t <br />i <br />n <br />g <br />98 <br />9 <br />0 <br /> <br />R <br />e <br />s <br />e <br />a <br />r <br />c <br />h <br /> <br />D <br />r <br />. <br /> <br />S <br />u <br />i <br />t <br />e <br /> <br />1 <br />0 <br />0 <br />, <br /> <br />I <br />r <br />v <br />i <br />n <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />1 <br />8 <br />Ph <br />o <br />n <br />e <br /> <br />( <br />9 <br />4 <br />9 <br />) <br /> <br />5 <br />3 <br />3 <br />- <br />4 <br />1 <br />1 <br />7 <br /> <br />| <br /> <br />d <br />k <br />a <br />n <br />g <br />@ <br />c <br />d <br />i <br />e <br />n <br />g <br />. <br />c <br />o <br />m <br />21 <br />0 <br />W <br />. <br /> <br />1 <br />9 <br />T <br />H <br /> <br />S <br />T <br />R <br />E <br />E <br />T <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />6 <br />DRAWN: CHECKED: <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />V <br />. <br /> <br />0 <br />6 <br />/ <br />2 <br />8 <br />/ <br />2 <br />0 <br />2 <br />4 <br />E200 <br />1/4" = 1'-0" <br />POWER PLAN - <br />1ST FLOOR <br />J.L.H.N. <br />210 W 19th St <br />4/14/2025