Laserfiche WebLink
Service Voltage <br />240 <br />Section 220.82 Dwelling Unit <br />Part #1 - Section 220.82(B)(1) General Lighting/Receptacles @ 3 VA per sq ft: <br />Amps Box A (VA) <br />20.5 4920 <br />Part #2 - Section 220.82(B)(3)a, b, c, d - Appliances and Dedicated Circuits: <br />Size in VA Size in VA <br />1500 <br />1500 <br />1500 <br />1000 <br />600 <br />1000 <br />1600 <br />3840 <br />7680 <br />Amps Box B (VA) <br />84.25 20220 <br />Total VA from Parts #1 and #2 combined:Box A + Box B =25140 <br />Total VA 25140 <br />First 10000 VA @ 100%10000 Remaining VA @ 40% <br />Remaining VA =15140 15140 x 40% =6056 VA <br />Adding First 10000 VA, if possible 10000 VA <br />Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:16056 VA <br />Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:66.90 Amps <br />Part #3 - Section 220.82(C) Heating and A/C loads: <br />*Combine the larger loads of either the Heating or the A/C loads togther <br />100% of all the Heating or A/C loads in VA:0 VA <br />100% of all the Heating or A/C loads in Amps:0.00 A <br />VA Volts Amps <br />Parts #1 & #2 16056 240 66.90 <br />Part #3 0 240 0.00 <br />Total VA for all Parts:16,056 <br />Totals Service/Feeder Load 66.90 <br />Dedicated circuit Dedicated circuit <br />Article 220 - Dedicated Backup Panel Calculation Job Code <br />901 Westwood Ave Santa Ana CA US 92703 <br />109R-901GUER2 <br />Building Square Footage VA (watts)Amps <br />House 1640.00 4920 20.50 <br />Total for Part #1: <br />Laundry <br />Appliance Circuit - 1 <br />Appliance Circuit - 2 <br />Dishwasher <br />Disposal <br />Refrigerator <br />Microwave <br />Other <br />Other <br />Totals for Part #2: <br />Totals from all Parts