Laserfiche WebLink
LIGHTING FIXTURE SCHEDULE <br />SYMBOL DESCRIPTION LAMP VOLT WATT <br />LED RECESSED DOWNLIGHT, DIMMABLE, HIGH EFFICACY <br />LITHONIA LDN6 SERIES OR APPROVED EQUAL LED 120 18 <br />LED WALL SCONE, HIGH EFFICACY W/ PHOTO SENSOR/ASTRONOMICAL TIME CLOCK <br />WAC LIGHTING WS-W52610 SERIES OR APPROVED EQUAL LED 120 12 <br />EE LIGHT FIXTURE WITH 90 MINUTES EMERGENCY BATTERY PACK <br />VERIFY WITH MANUFACTURER FOR OPTION/INVERTER IF NOT AVAILABLE ---120 --- <br />X LED EXIT SIGN WITH 90 MINUTES BATTERY PACK <br />LITHONIA EXR LED M6 OR EQUIVALENT ---120 --- <br />120V, SINGLE POLE, MAX 3% VOLTAGE DROP <br />LENGTH OF RUN <br />COPPER <br />COPPER <br />COPPER <br />COPPER <br />COPPER <br />ALUMINUM <br />ALUMINUM <br />AMP LOAD200'150'100'50'25' <br />14 <br />12 <br />10 <br />1 <br />1/0 <br />3/0 <br />250 <br />12 <br />12 <br />10 <br />1 <br />1/0 <br />3/0 <br />250 <br />10 <br />8 <br />6 <br />1 <br />2/0 <br />3/0 <br />300 <br />8 <br />6 <br />4 <br />2/0 <br />4/0 <br />300 <br />600 <br />6 <br />4 <br />4 <br />4/0 <br />300 <br />500 <br />900 <br />15 AMP <br />20AMP <br />30 AMP <br />100 AMP <br />100 AMP <br />200 AMP <br />200 AMP <br />NOTE: <br />THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT <br />CONDUCTORS TO THE FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT. <br />TYPICAL ELECTRICAL DEVICE MOUNTING HEIGHTS <br />SCALE <br />NTS <br />48" <br />DISC. SW. <br />CL. <br />72" MAX <br />12" MIN <br />ELECTRICAL PANEL <br />44" <br />G <br />18" <br />72"44" <br />CLOCK <br />48" <br />WITHIN 18" <br />WITHIN 60" <br />80" <br />EXIT E <br />F I R <br />18" <br />96" <br />84" <br />44" <br />24" <br />EX <br />T <br />E <br />R <br />I <br />O <br />R <br /> <br />R <br />E <br />C <br />E <br />P <br />T <br />A <br />C <br />L <br />E <br />G <br />26" <br />FINISH FLOOR <br />NOTES: <br />1.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL TELEVISION OUTLETS WITH THE ARCHITECT <br />PRIOR TO INSTALLATION. <br />2.ALL DEVICES SHOWN ON THIS DETAIL ARE FOR REFERENCES OF MOUNTING HEIGHTS ONLY. THE ELECTRICAL CONTRACTOR <br />SHALL FIELD ADJUST THE HEIGHTS OF THE DEVICES AS REQUIRED FOR PROPER MOUNTING OF THE DEVICES. <br />3.ALL DEVICES REQUIRED FOR THIS PROJECT MAY NOT APPEAR ON THIS DETAIL. ALL ITEMS SHOWN ON THIS DETAIL MAY NOT <br />B REQUIRED OF THIS PROJECT. <br />4.FIRE ALARM HORN/STROBES ARE TO BE MOUNTED NO HIGHER THAN 96" AND NO LOWER THAN 80" ON CENTER. <br />G <br />36" <br />GFCI <br />DRYER <br />WASHER <br />GFCI <br />GFCI <br />STACKABLE <br />WASHER & DRYER <br />48" <br />50" (MAX) <br />TO TOP <br />OF BOX <br />WP/ <br />GFCI <br />1 <br />SINGLE LINE DIAGRAM NOTES <br />1.CONTRACTOR/ELECTRICIAN TO FIELD VERIFY ACTUAL SITE CONDITION <br />/EXACT SERVICE ENTRANCE AND SHALL NOTIFY EOR(S) ANY DISCREPANCY <br />WITH THE PLAN PRIOR TO BIDDING. <br />2.CONTRACTOR TO VERIFY ALL EQUIPMENT DIMENSIONS AND CLEARANCES <br />WITH FIELD CONDITION PRIOR TO ORDERING EQUIPMENT. <br />3.ALL EQUIPMENT TO BE LISTED BY A RECOGNIZED TESTING AGENCY. <br />TERMINALS TO BE RATED FOR ALUMINUM AND COPPER WIRE. <br />4.CONTRACTOR TO OBTAIN A FAULT CURRENT LETTER FROM UTILITY <br />COMPANY PRIOR TO PURCHASE OF ANY EQUIPMENT (IF ANY) FOR AIC <br />VERIFICATION. EQUIPMENT CUTSHEETS AND FAULT CURRENT LETTER TO BE <br />PROVIDED UPON INSPECTION. <br />5.IF APPLICABLE, ALL NEW CIRCUIT BREAKERS INSTALLED ON EXISTING <br />PANEL/SWITCHBOARD SHALL MATCH THE HIGHEST EXISTING AIC RATED <br />BREAKER WITHIN THAT PANEL/BOARD. INSPECTOR TO VERIFY HIGHEST AIC <br />RATING AT THE SITE. <br />6.MAIN SERVICE DISCONNECT AMPERAGE MUST BE PERMANENTLY MARKED <br />7.ALL SYSTEM TO BE FULLY RATED SYSTEM. IF SYSTEM IS SERIES RATED, ALL <br />COMPONENTS MUST BE FROM THE SAME MANUFACTURER. LISTED BREAKER <br />COMBINATIONS SHALL BE AVAILABLE TO THE AUTHORITY HAVING <br />JURISDICTION UPON REQUEST. <br />8.IF APPLICABLE, ALL EQUIPMENT LABELED/IDENTIFIED AS EXISTING, ARE <br />SUBJECT TO FIELD VERIFICATION. <br />9.ARC-FLASH HAZARD WARNING FIELD MARKING TO BE PROVIDED ON <br />ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, PANEL BOARDS, METER <br />SOCKET ENCLOSURES AND MCC THAT ARE IN OTHER THAN DWELLING UNITS. <br />[2022 CEC 110.21(B)] <br />NOTES: <br />1.FIXTURE SHALL HAVE MIN. OF 10 YEARS MANUFACTURER WARRANTY ON ALL COMPONENTS. <br />2.FIXTURES SHALL HAVE APPROPRIATE U.L. LABEL (i.c., DAMP OR WET) AS REQUIRED BY CODES AND ORDINANCES. <br />3.FIXTURES SHALL INCLUDE ALL ACCESSORIES FOR INSTALLATION ACCORDING TO MANUFACTURER'S SHOP <br />DRAWINGS AND AS REQUIRED BY CODES AND LOCAL ORDINANCES. <br />4.PRIOR TO ORDERING ANY LIGHTING EQUIPMENT, THE CONTRACT OR SHALL COORDINATE ALL FIXTURE <br />LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND CEILING CAVITY DEPTHS. <br />5.ALL LAMPS SHALL BE PROVIDED AND INSTALLED ACCORDING TO THE ATTACHED FIXTURE SCHEDULE AND <br />SPECIFICATIONS. ENSURE COMPATIBILITY BETWEEN FIXTURE, LAMP(S) AND BALLAST(S). <br />6.CONTRACTOR SHALL VERIFY FIXTURE VOLTAGES AND CEILING TRIM COMPATIBILITY PRIOR TO ORDERING <br />FIXTURE. <br />7.PROVIDE APPROVED FIRE-RATED ENCLOSURES FOR ALL LIGHTING FIXTURES LOCATED IN FIRE-RATED CEILINGS. <br />8.LIGHTING FIXTURE CATALOG NUMBERS ARE SERIES TYPE ONLY. PROVIDE ALL NECESSARY HARDWARE AS <br />REQUIRED BY THE SPECIFICATIONS, DRAWINGS, AND PROJECT CONDITIONS FOR A COMPLETE INSTALLATION. <br />9.ALL FIXTURES SHALL BE ORDERED WITH APPROPRIATE BALLAST(S) THAT HAVE U.L. AND CBM LABELS. PROVIDE <br />MULTIPLE BALLASTS FOR DUAL-LEVEL SWITCHING AND WIRING AS INDICATED ON THE PLANS. <br />10.ENSURE COMPATIBILITY OF ALL LIGHTING SYSTEM COMPONENTS, ESPECIALLY DIMMED SYSTEMS. FIXTURES, <br />LAMPS, BALLAST(S), AND DIMMING SYSTEMS/INDIVIDUAL CONTROLS MUST BE FACTORY CERTIFIED COMPATIBLE <br />FOR FULL RANGE OF DIMMING COMPATIBILITY. <br />11.LIGHTING FIXTURE MANUFACTURER & MODEL IS FOR REFERENCE ONLY. FIXTURE SHALL BE SELECTED BY <br />ARCHITECT. POWER AND QUALITY SHALL BE SPECIFICATION GRADE. <br />SINGLE LINE DIAGRAM <br />FEEDER CHART <br />(E)/(N)FEEDER SIZE <br />S400 (N)3#600- 3 1/2"C (BY UTILITY) <br />100 (N)3#1, #8GND- 1 1/2"C <br /># <br />100 <br />TYP. (2) <br />(N) <br />100A <br />2P <br />TYP. (2) <br />(N) PANEL <br />"R1/R2" <br />M <br />(N) PANEL <br />"HP" <br />100 <br />(N) <br />100A <br />2P <br />M <br />(N) UTILITY COMPANY <br />SECONDARY FEEDER <br />(N) <br />400A <br />2P <br />S400 <br />G <br />N <br />BLDG <br />STRUCT <br />STEEL <br />UFER <br />GND <br />GND <br />ROD <br />COLD <br />WTR <br />PIPE <br />(N)#2/0GND <br />GROUND LEVEL <br />TYP. (2) <br />D= <br />1 <br />0 <br />' <br />Is <br />c <br />= <br />1 <br />6 <br />, <br />8 <br />8 <br />0 <br />A <br />%V <br />D <br />= <br />0 <br />. <br />1 <br />4 <br />% <br />Isc=20,911 <br />(N) RESIDENTIAL METER STACK "MS" <br />400A, 120/240V, 1Ø, 3W <br />22K AIC RATING, NEMA 1 ENCLOSURE <br />100 <br />TYP. (2) <br />(N) <br />100A <br />2P <br />TYP. (2) <br />(N) PANEL <br />"R3/R4" <br />M TYP. (2) <br />100 <br />(N) <br />100A <br />2P <br />(N) PANEL <br />"R5" <br />M <br />(N) PANEL <br />"R6" <br />100 <br />M <br />(N) <br />100A <br />2P <br />TYP. (2) <br />(N) PANEL <br />"R7/R8" <br />100 <br />M <br />TYP. (2) <br />(N) <br />100A <br />2P <br />TYP. (2) <br />TYP. (2) <br />(N) PANEL <br />"R9/R10" <br />100 <br />M <br />TYP. (2) <br />(N) <br />100A <br />2P <br />TYP. (2) <br />2ND LEVEL <br />ROOF LEVEL <br />BUILDING STRUCTURAL <br />STEEL NEC 250.52 <br />BARE COPPER GROUNDING <br />CONDUCTOR NEC 250-66 <br />(TYPICAL) <br />CADWELD <br />(TYPICAL) <br />BARE COPPER GROUNDING <br />ELECTRODE BONDED TO <br />MINIMUM OF 20'-0" OF <br />1/2" REBAR IN BUILDING <br />WALL FOOTING PER NEC <br />250.52 <br />3/4"x10' GROUND <br />ROD NEC 250.52 <br />VALVE, <br />METER <br />OR UNION <br />SUPPLY <br />SIDE <br />JUMPER <br />BOND TO UNDERGROUND METALLIC <br />COLD WATER PIPE WITHIN 5FT OF <br />SERVICE ENTRANCE (PROVIDE SIMILAR <br />CONNECTION <br />TO FIRE PROTECTION WATER <br />SERVICE ENTRANCE) <br />NEC 250.52 <br />MAIN SERVICE ENTRANCE ALL GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH ARTICLE 250.50 OF <br />THE NATIONAL ELECTRICAL CODE, BOND THE NEUTRAL AT THE SERVICE ENTRANCE <br />EQUIPMENT <br />GROUNDING ELECTRODE SYSTEM DETAIL <br />SCALE <br />NTS <br />2 <br />SELF TAPPING <br />SCREWS <br />STANDARD COLORS: <br />1. NORMAL POWER - BLACK BACKGROUND, WHITE LETTERS <br />2. EMERGENCY POWER - RED BACKGROUND, WHITE LETTERING <br />NAMEPLATES ARE REQUIRED ON ALL PANELBOARDS, STARTERS <br />AND DISCONNECT SWITCHES. <br />PANELBOARD <br />PANEL "X" <br />PANELBOARD <br />DESIGNATION <br />ALL PANELS SHALL BE LABELED ON INSIDE OF DOOR WITH <br />LIST OF CIRCUITS AND THEIR APPROPRIATE NAMES. <br />3" <br />1" <br />EACH PANEL SCHEDULE TO INDICATE THE SOURCE OF POWER <br />TO THE PANEL. THE LABEL SHALL BE PERMANENTLY AFFIXED. <br />NAMEPLATE <br />(TYPICAL) <br />ENGRAVED LAMACOID, <br />5/32 INCH LETTERS <br />PANEL BOARD NAMEPLATE DETAIL <br />SCALE <br />NTS <br />3 <br />120V GFCI BREAKER WIRING DIAGRAM <br />SCALE <br />NTS <br />4 <br />D= <br />3 <br />0 <br />' <br />Is <br />c <br />= <br />1 <br />2 <br />, <br />1 <br />8 <br />3 <br />A <br />%V <br />D <br />= <br />0 <br />. <br />2 <br />5 <br />% <br />D= <br />9 <br />5 <br />' <br />Is <br />c <br />= <br />6 <br />, <br />3 <br />9 <br />8 <br />A <br />%V <br />D <br />= <br />1 <br />. <br />3 <br />3 <br />% <br />INSPECTION NOTES <br />A.TOTAL ACCESS SHALL BE PROVIDED FOR ALL INSPECTIONS. [CBC 110.1] PER <br />2022 CALIFORNIA ELECTRICAL CODE (CEC) SECTION90.4, THE AHJ HAS THE <br />RESPONSIBILITY TO ENFORCE THE CEC REQUIREMENTS.THIS REQUIREMENT <br />REQUIRES INSPECTIONS AT DIFFERENT STAGES OF WORK TO ENSURE <br />COMPLIANCE PRIOR TO ANY WORK BEING COVERED OR CLOSED OR <br />OTHERWISE UNABLE TO BE PROPERLY INSPECTED. <br />B.EQUIPMENT INSTALLED SUCH AS RECEPTACLE OUTLETS, SWITCHES, <br />LUMINAIRES FIXED APPLIANCES, SUBPANELS, AND OVERCURRENT <br />PROTECTIVE DEVICES MUST BE INSTALLED PER THE CEC REQUIREMENTS. <br />ADDITIONALLY, OTHER CODES HAVE SEPARATE REQUIREMENTS (2022 CAEC, <br />CALGREEN, CALIFORNIA FIRE CODE. ALL CODE REQUIREMENTS MUST BE <br />CONSIDERED DURING CONSTRUCTION AND INSPECTION. <br />C.CEC 110.12 SPECIFIES THE REQUIREMENTS FOR INSTALLATIONS. NEAT AND <br />WORKMANLIKE INSTALLATIONS ARE MANDATORY; ANY UNUSED OPENINGS <br />ARE TO BE PROPERLY CLOSED, AND THE INTEGRITY OF ELECTRICAL <br />EQUIPMENT MUST BE MAINTAINED. ANY DAMAGED CONDUCTORS, PARTS OR <br />EQUIPMENT MUST BE REPLACED OR RETURNED TO CONDITIONS THAT <br />EXISTED DURING THEIR MANUFACTURE AND LISTING. <br />D.ELECTRICAL SUBPANELS AND RELATED EQUIPMENT MUST BE PROPERLY <br />INSTALLED. THE CEC HAS SPECIFIC REQUIREMENTS THAT ARE FOUND IN <br />ARTICLE 408 AMONGST OTHER CEC REQUIREMENTS. PANELS MUST MEET THE <br />PENETRATION REQUIREMENTS WHEN INSTALLED IN FIRE-RATED STRUCTURE. <br />L1 <br />L2 <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />SHEET TITLE: <br />DATE: SCALE: <br />GA <br />R <br />F <br />I <br />E <br />L <br />D <br /> <br />R <br />E <br />S <br />T <br />O <br />R <br />A <br />T <br />I <br />O <br />N <br /> <br />/ <br /> <br />R <br />E <br />M <br />O <br />D <br />E <br />L <br />03/05/2023 <br />PLOT DATE: 9/12/2024 5:11:23 PM <br />CD <br />I <br /> <br />Ci <br />r <br />c <br />a <br /> <br />D <br />o <br />m <br />i <br />n <br />i <br /> <br />I <br />n <br />t <br />e <br />r <br />n <br />a <br />t <br />i <br />o <br />n <br />a <br />l <br />, <br /> <br />I <br />n <br />c <br />. <br />En <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />- <br /> <br />C <br />o <br />n <br />s <br />u <br />l <br />t <br />i <br />n <br />g <br />98 <br />9 <br />0 <br /> <br />R <br />e <br />s <br />e <br />a <br />r <br />c <br />h <br /> <br />D <br />r <br />. <br /> <br />S <br />u <br />i <br />t <br />e <br /> <br />1 <br />0 <br />0 <br />, <br /> <br />I <br />r <br />v <br />i <br />n <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />1 <br />8 <br />Ph <br />o <br />n <br />e <br /> <br />( <br />9 <br />4 <br />9 <br />) <br /> <br />5 <br />3 <br />3 <br />- <br />4 <br />1 <br />1 <br />7 <br /> <br />| <br /> <br />d <br />k <br />a <br />n <br />g <br />@ <br />c <br />d <br />i <br />e <br />n <br />g <br />. <br />c <br />o <br />m <br />82 <br />9 <br /> <br />N <br /> <br />G <br />A <br />R <br />F <br />I <br />E <br />L <br />D <br /> <br />S <br />T <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />1 <br />DRAWN: CHECKED: <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />V <br />. <br /> <br />0 <br />4 <br />/ <br />2 <br />7 <br />/ <br />2 <br />0 <br />2 <br />3 <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />V <br />. <br /> <br />0 <br />9 <br />/ <br />2 <br />8 <br />/ <br />2 <br />0 <br />2 <br />3 <br />IN <br />S <br />P <br />E <br />C <br />T <br />I <br />O <br />N <br /> <br />R <br />E <br />V <br />. <br /> <br />0 <br />6 <br />/ <br />1 <br />9 <br />/ <br />2 <br />0 <br />2 <br />4 <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />V <br />. <br /> <br />0 <br />9 <br />/ <br />0 <br />4 <br />/ <br />2 <br />0 <br />2 <br />4 <br />N.T.S. <br />E001 <br />SINGLE LINE <br />DIAGRAM/ <br />SCHEDULES <br />J.L.L.N. <br />HOLD- 829 N <br />Garfield St1/15/2025