01
<br />12 AWG PV WIRE, COPPER
<br />6 AWG BARE, COPPER
<br />FREE AIR
<br />N/A
<br />20A
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />MAX OUTPUT PER BRANCH (125%)
<br />MODULES / MICROINVERTERS TO JUNCTION BOX
<br />9B5
<br />B4
<br />9B6
<br />9
<br />01 02
<br />JU
<br />N
<br />C
<br />T
<br />I
<br />O
<br />N
<br />
<br />B
<br />O
<br />X
<br />NE
<br />M
<br />
<br />3
<br />R
<br />,
<br />
<br />U
<br />L
<br />
<br />L
<br />I
<br />S
<br />T
<br />E
<br />D
<br />B4
<br />B5
<br />B6
<br />MICROINVERTERS
<br />BRANCH 4-6
<br />IQ COMBINER
<br />W/ ENPHASE ENVOY
<br />240/120 V 1Ø, 3W
<br />20A
<br />20A
<br />20A
<br />PV AC DISCONNECT
<br />60A, 240V, NEMA 3R
<br />VISIBLE/LOCKABLE
<br />LABELLED ACD
<br />3B
<br />TO UTILITY GRID
<br />(OVERHEAD)
<br />M 400A
<br />(E)125A
<br />(E) 400A MAIN SERVICE PANEL
<br />240/120 V 1Ø, 3W
<br />BUS RATING: 400A
<br />MCB RATING: 400A
<br />INTERCONNECTION STRATEGY:
<br />LOAD SIDE 705.12(B)(3)(2)
<br />METER NUMBER:
<br />222013-114661
<br />(E) GROUNDING
<br />ELECTRODE
<br />15A
<br />ENVOY
<br />COMMS
<br />3B
<br />50A
<br />04
<br />COMMS
<br />(E) 125A
<br />SUB PANEL
<br />240/120 V 1Ø, 3W
<br />05
<br />60A
<br />(N) FRANKLIN WH
<br />AGATE
<br />240/120 V 1Ø, 3W
<br />MAIN BUS: 200A
<br />(N) 100A BATTERY
<br />SUB PANEL
<br />240/120 V 1Ø, 3W
<br />30A
<br />30A
<br />[x2] (N) BATTERIES
<br />FRANKLINWH APOWER
<br />CAPACITY: 13.6 kWH (EACH)
<br />#1
<br />06
<br />COMMS
<br />#2
<br />COMMS
<br />CONDUCTOR: 10 AWG, THWN-2, Cu
<br />GROUND:8 AWG, THWN-2, Cu
<br />CONDUIT:0.75" EMT
<br />06
<br />60A FUSES
<br />VISIBLE/LOCKABLE
<br />LABELED ACD
<br />ESS AC DISCONNECT
<br />60A FUSED
<br />240V, NEMA 3R
<br />9B2
<br />B1
<br />9B3
<br />10
<br />01
<br />02
<br />JU
<br />N
<br />C
<br />T
<br />I
<br />O
<br />N
<br />
<br />B
<br />O
<br />X
<br />NE
<br />M
<br />
<br />3
<br />R
<br />,
<br />
<br />U
<br />L
<br />
<br />L
<br />I
<br />S
<br />T
<br />E
<br />D
<br />B1
<br />B2
<br />B3
<br />MICROINVERTERS
<br />BRANCH 1-3
<br />IQ COMBINER
<br />W/ ENPHASE ENVOY
<br />240/120 V 1Ø, 3W
<br />20A
<br />20A
<br />20A
<br />PV AC DISCONNECT
<br />60A, 240V, NEMA 3R
<br />VISIBLE/LOCKABLE
<br />LABELLED ACD
<br />3A
<br />15A
<br />ENVOY
<br />COMMS
<br />3A
<br />(E) SUB PANEL
<br />240/120 V 1Ø, 3W
<br />BUS RATING: 125A
<br />EX
<br />I
<br />S
<br />T
<br />I
<br />N
<br />G
<br />60A
<br />125A
<br />SUB MCB
<br />(E)125A
<br />(E)100A
<br />BUILDING G
<br />BUILDING H
<br />PV SYSTEM COMPONENTS
<br />INV1
<br />M MODULES (55) HANWHA QCELLS
<br /> Q.TRON BLK M-G2+ 425
<br />MICROINVERTERS (55)ENPHASE IQ8A-72-2-US
<br />[240] [SI1-JUN20]
<br />PV COMPONENT NOTES
<br />1. PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN PER CEC 690.12
<br />2. ENPHASE MICROINVERTERS ARE MODULE-LEVEL RSD COMPLIANT
<br />02
<br />10 AWG THWN-2, COPPER
<br />8 AWG THWN-2, COPPER
<br />0.75" EMT
<br />6 (2 PER BRANCH)
<br />20A
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />MAX OUTPUT PER BRANCH (125%)
<br />JUNCTION BOX TO PV BRANCH BREAKERS
<br />8 AWG THWN-2, COPPER
<br />8 AWG THWN-2, COPPER
<br />0.75" EMT
<br />3
<br />40.60A
<br />50.75A
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />CONTINUES CURRENT
<br />MAX CURRENT (125%)
<br />3A IQ COMBINER TO SUB PANEL
<br />8 AWG THWN-2, COPPER
<br />8 AWG THWN-2, COPPER
<br />0.75" EMT
<br />3
<br />39.15A
<br />48.94A
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />CONTINUOUS CURRENT
<br />MAX CURRENT (125%)
<br />3B IQ COMBINER TO AGATE
<br />3 AWG THWN-2, COPPER
<br />8 AWG THWN-2, COPPER
<br />1" EMT
<br />3
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />04 AGATE TO MSP
<br />1 AWG THWN-2, COPPER
<br />6 AWG THWN-2, COPPER
<br />EXITING
<br />3
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />05 AGATE TO SUB PANEL
<br />INFINITY SOLAR, INC.
<br />749 N MAIN ST.
<br />ORANGE, CA 92868
<br />PHONE: (714) 880-8089
<br />LIC NO.: C10 - 824287
<br />TIM POLUJANCEWICZ
<br />ELECTRICAL & CONDUIT NOTES
<br />A. MAIN PANEL UPGRADES. A TYPE 1 OR TYPE 2 SURGE PROTECTION DEVICE
<br />SHALL BE INSTALLED FOR THE NEW MSP EITHER AS AN INTEGRAL PART OF THE
<br />SERVICE EQUIPMENT OR LOCATED IMMEDIATELY ADJACENT THERETO.
<br />[NEC 230.67]
<br />B. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR
<br />PURPOSE. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON
<br />MINIMUM CODE REQUIREMENT AND ARE NOT MEANT TO LIMIT UP-SIZING AS
<br />REQUIRED BY FIELD CONDITIONS.
<br />C. CONDUIT RACEWAYS SHALL BE PROVIDED WITH EXPANSION FITTINGS TO
<br />COMPENSATE FOR THERMAL EXPANSION AND CONTRACTION. [NEC 110 (B) AND
<br />110.14 (D)]
<br />D. PROVIDE PULL BOXES AND/OR EXPANSION OR DEFLECTION FITTINGS FOR
<br />THE ROOFTOP CONDUITS TO ACCOMMODATE THERMAL EXPANSION AND
<br />CONTRACTION. [NEC 300.7(B)]
<br />E. ALL CONDUCTORS AND CONDUITS ON THE ROOF SHALL BE INSTALLED A
<br />MINIMUM DISTANCE ABOVE THE ROOF TO THE BOTTOM OF THE RACEWAY OR
<br />CABLE OF 7/8" IN. (INCLUDING CABLES UNDERNEATH MODULES AND RACKING).
<br />F. ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND
<br />IDENTIFIED FOR USE IN DIRECT SUNLIGHT AND FOR THE APPLICATION. [NEC
<br />690.31(C) THROUGH (F), 310.10(D)]
<br />G. EXPOSED CONDUCTORS WITHIN THE PV ARRAY SHALL BE PV WIRE/CABLE,
<br />OR TYPE USE-2, OR TYPE RHW-2 (UL 4703 & 854 LISTED) [NEC 690.31(C)(1)]
<br />H. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN TIGHT AND
<br />APPROVED FOR USE IN WET LOCATIONS. (NEC 314.15)
<br />I. DC WIRING INSIDE A BUILDING MUST BE IN METAL RACEWAYS, METAL-CLAD
<br />CABLE, OR METAL ENCLOSURES. [NEC 690.31(D)]
<br />J. EQUIPMENT GROUNDING CONDUCTOR (EGC) SMALLER THAN #6-AWG SHALL
<br />BE PROTECTED FROM PHYSICAL DAMAGE BY AN IDENTIFIED RACEWAY OR
<br />CABLE ARMOR, UNLESS INSTALLED WITHIN HOLLOW SPACES OF THE FRAMING
<br />MEMBERS OF BUILDINGS OR STRUCTURES AND WHERE NOT SUBJECT TO
<br />PHYSICAL DAMAGE. [NEC 250.120(C)]
<br />K. CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE
<br />NOT LOCATED UNDER THE MODULES, MUST BE PROTECTED. [NEC 300.4]
<br />L. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE
<br />REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY
<br />FIELD CONDITIONS.
<br />6 AWG THWN-2, COPPER
<br />8 AWG THWN-2, COPPER
<br />0.75" EMT
<br />2
<br />CONDUCTOR
<br />GROUND
<br />CONDUIT
<br />CURRENT-CARRYING CONDUCTORS
<br />06 BATTERY SUB PANEL TO AGATE
<br />BATTERY BACKUP CALCULATIONS
<br />BATTERY OUTPUT: 60A
<br />PV OUTPUT (125%):50.75A
<br />TOTAL OUTPUT:110.75A
<br />MAX ALLOWED BACKFEED:
<br />400A X 1.2 - 400A = 80A
<br />80A < 110.75A (PCS REQ.)
<br />BATTERY BACKUP CALCULATIONS
<br />PV WIRE SCHEDULE
<br />SEE CALCULATIONS PAGE FOR FULL WIRE AND CONDUIT CALCULATIONS
<br />ADDITIONAL NOTES
<br />DRAWN BY:
<br />PAPER: 11X17 (ANSI B)DATE:
<br />DESIGN LEAD:
<br />DESIGNED BY SOLAR DEPLOYED, LLC.
<br />931 10TH ST #114, MODESTO, CA 95354
<br />209-671-2001 | HELLO@SOLARDEPLOYED.COM
<br />SIGNATURE:
<br />CHECKED BY:
<br />6/27/2024
<br />T.M.
<br />E.V.A.B.
<br />SHEET NAME:
<br />NEW PV SYSTEM
<br /> 23.375 kW DC (STC-DC) | 21.287 kW (CEC-AC)
<br />SARAH HAMMARSTROM
<br />403 N SUSAN ST,
<br />SANTA ANA, CA 92703
<br />APN: 198-261-34
<br />SHEET NO.:
<br />ENGINEER OF RECORD
<br />LINE DIAGRAM PV.04
<br />B
<br />403 N Susan St #G
<br />& H10/21/2024
|