Laserfiche WebLink
4' - 0"8' - 0" <br />12 <br />' <br /> <br />- <br /> <br />0 <br />" <br />6' <br /> <br />- <br /> <br />0 <br />" <br />FIXED END <br />FREE END <br />FR <br />E <br />E <br /> <br />E <br />N <br />D <br />FI <br />X <br />E <br />D <br /> <br />E <br />N <br />D <br />FROM SPLAY <br />WIRE TO WALL <br />CROSS RUNNERS,TYP. <br />CONT. MAIN RUNNER <br />AT 4'-0" O.C., TYP. <br />4 WAY 45 DEG. DIAGONAL <br />12 GA. WIRE BRACING W/ <br />COMPRESSION STRUT <br />LOCATED ON MAIN <br />RUNNER <br />PER DETAIL: <br />12 GA. <br />VERTICAL <br />HANGER WIRES <br />AT 4'-0" EA. <br />WAY <br />NOTE: <br />1. CEILING GRID MAY BE ATTACHED TO NOT MORE THAN TWO (2) ADJACENT WALLS AND MUST <br />BE AT LEAST 3/4" FREE OF OTHER WALLS. <br />2. LOCATE COMPRESSION STRUT FOR EA. 96 S.F. <br />03/A5-04 <br />FIXTURE <br />SUSPENSION PER <br />DETAIL:04/A5-04 <br />24 GA. CONT. WALL <br />ANGLE, TYP. <br />8" <br /> <br />M <br />A <br />X <br />STABILIZER BARS, <br />CROSS TEES OR <br />STRUTS 8" MAX. FROM <br />WALL TYP. ALONG <br />FREE JOINTS <br />4' - 0" MAX. <br />SUSPENDED CEILINGS: SEISMIC DESIGN FOR CATEGORIES D THROUGH F (ASCE 7): <br />1. SUSPENSION SYSTEM COMPONENTS SHALL COMPLY WITH ASTM C635 AND E580 SECTION 5.1 AS MODIFIED BY CBC 1616A.1.21: <br />• THE CEILING GRID SYSTEM SHALL BE RATED HEAVY DUTY AS DEFINED BY ASTM C635 <br />• HANGER AND BRACING WIRES SHALL BE #12 GAGE (0.106" DIAMETER), SOFT ANNEALED, AND GALVANIZED STEEL WIRES <br />WITH CLASS 1 COATING. THEY MAY BE USED FOR UP TO AND INCLUDING 4'-0"x 4'-0" GRID SPACING ALONG AND <br />ATTACHED TO MAIN RUNNERS. SPLICES ARE NOT PERMITTED IN ANY HANGER WIRE. <br />• MAIN RUNNERS AND CROSS RUNNERS ALONG WITH THEIR SPLICES, INTERSECTION CONNECTORS, AND EXPANSION <br />DEVICES SHALL BE DESIGNED AND CONSTRUCTED TO CARRY A MEAN ULTIMATE TEST LOAD OF NOT LESS THAN 180 <br />LBS. IN COMPRESSION & TENSION, IN ACCORDANCE WITH ASTM 580 SECTION 5.1.2. <br />2. SUSPENSION SYSTEM INSTALLATION, SHALL COMPLY WITH ASTM C636 AND E580 SECTION 5.2: <br />• PROVIDE #12 GAGE HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES OF THE <br />SUPPORT OR WITHIN ONE-FOURTH (1/4) OF THE LENGTH OF THE END TEE, WHICHEVER IS LESS, FOR THE PERIMETER <br />OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF THE END TEE IS EIGHT (8) INCHES <br />OR LESS. <br />• CEILING GRID MEMBERS SHALL BE ATTACHED TO TWO (2) ADJACENT WALLS, IN ACCORDANCE WITH ASTM E580 SECTION <br />5.2.3. CEILING GRID MEMBERS SHALL BE AT LEAST 3/4" INCH CLEAR OF OTHER WALLS. IF WALLS RUN DIAGONAL TO THE <br />CEILING GRID SYSTEM RUNNERS, ONE END OF MAIN AND CROSS RUNNERS SHOULD BE FREE, AND A MINIMUM OF 3/4 <br />INCH CLEAR OF WALL. <br />• THE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT LESS THAN TWO (2) INCHES. USE OF <br />ANGLES WITH SMALLER WIDTHS IN CONJUNCTION WITH PERIMETER CLIPS SHALL REQUIRE AN ALTERNATE METHOD OF <br />COMPLIANCE WITH ADEQUATE JUSTIFICATION AND ARE OUTSIDE THE SCOPE OF THIS PROJECT. <br />• AT THE PERIMETER OF THE CEILING AREA WHERE MAIN OR CROSS RUNNERS ARE NOT CONNECTED TO THE ADJACENT <br />WALL, PROVIDE INTERCONNECTION BETWEEN THE RUNNERS AT THE FREE END TO PREVENT LATERAL SPREADING. A <br />METAL STRUT OR A #16 GAGE WIRE WITH A POSITIVE MECHANICAL CONNECTION TO RUNNER MAY BE USED. WHERE <br />THE PERPENDICULAR DISTANCE FROM THE WALL TO THE FIRST PARALLEL RUNNER IS EIGHT (8) INCHES OR LESS, THIS <br />INTERCONNECTION IS NOT REQUIRED. <br />3. EXPANSION JOINTS, SEISMIC SEPARATIONS, AND PENETRATIONS: <br />• EXPANSION JOINTS SHALL BE PROVIDED IN THE CEILING AT INTERSECTIONS OF CORRIDORS AND AT JUNCTIONS OF <br />CORRIDORS WITH LOBBIES OR OTHER SIMILAR AREAS. <br />• FOR CEILING AREAS EXCEEDING 2500 SQUARE FEET, A SEISMIC SEPARATION JOINT SHALL BE PROVIDED TO DIVIDE THE <br />CEILING INTO AREAS NOT EXCEEDING 2500 SQ. FT. <br />• PENETRATIONS THROUGH THE CEILING FOR SPRINKLER HEADS AND OTHER SIMILAR DEVICES THAT ARE NOT <br />INTEGRALLY TIED TO THE CEILING SYSTEM IN THE LATERAL DIRECTION SHALL HAVE A TWO (2) INCH OVERSIZED RING, <br />SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF ONE (1) INCH IN ALL HORIZONTAL <br />DIRECTIONS. A FLEXIBLE SPRINKLER HOSE FITTING THAT CAN ACCOMMODATE ONE (1) INCH OF CEILING MOVEMENT <br />SHALL BE PERMITTED TO BE USED IN LIEU OF THE OVERSIZED RING, SLEEVE OR ADAPTER. SUCH FLEXIBLE SPRINKLER <br />HOSE SHALL BE ADEQUATELY SUPPORTED FROM SOFFIT SO AS NOT TO EXCEED THE MAXIMUM TRIBUTARY WEIGHT OF <br />THE CEILING. <br />4. CHANGES IN CEILING PLAN ELEVATION SHALL BE PROVIDED WITH POSITIVE BRACING. <br />5. CABLE TRAYS AND ELECTRICAL CONDUITS SHALL BE SUPPORTED INDEPENDENTLY OF THE CEILING. <br />6. SUSPENDED CEILINGS SHALL BE SUBJECT TO THE SPECIAL INSPECTION REQUIREMENTS OF CBC 1707A.6 IN ACCORDANCE <br />WITH ASCE 7-05 SECTION 11A.1.3.9. <br />CEILING FIXTURES, TERMINALS, AND DEVICES: <br />a. CEILING PANELS SHALL NOT SUPPORT ANY LIGHT FIXTURES, AIR TERMINALS/GRILLS, OR OTHER DEVICES(REFERRED <br />TO ALL BY COMMON TERM FIXTURES HERE AFTER). <br />b. ALL FIXTURES SHALL BE MOUNTED IN A MANNER THAT WILL NOT COMPROMISE CEILING PERFORMANCE. <br />c. ALL FIXTURES SHALL BE ATTACHED TO THE SUSPENDED CEILING SYSTEM BY MECHANICAL MEANS, UNLESS <br />INDEPENDENTLY SUPPORTED. THE ATTACHMENT DEVICE SHALL HAVE THE CAPACITY OF 100% OF FIXTURE WEIGHT <br />ACTING IN ANY DIRECTION. A MINIMUM OF TWO ATTACHMENT DEVICES ARE REQUIRED FOR EACH FIXTURE. <br />d. SURFACE MOUNTED FIXTURES SHALL BE ATTACHED TO THE MAIN RUNNER WITH POSITIVE CLAMPING DEVICES MADE <br />OF MATERIAL WITH A MINIMUM 14 GAGE. A NO.12 GAUGE SAFETY WIRES SHALL BE ATTACHED BETWEEN THE <br />CLAMPING DEVICE AND TO THE STRUCTURE ABOVE. IN NO CASE SHALL THE FIXTURES EXCEED THE DESIGN <br />CAPACITY OF THE SUPPORTING MEMBERS. <br />e. ALL FIXTURES WEIGHING LESS THAN OR EQUAL TO 10 LB. SHALL HAVE ONE NO. 12 GAUGE SAFETY WIRE CONNECTED <br />FROM FIXTURE HOUSING TO STRUCTURE ABOVE. IT IS NOT NECESSARY FOR THESE SAFETY WIRES TO BE TAUT. <br />f. ALL FIXTURES WEIGHING GREATER THAN 10 LB BUT LESS THAN OR EQUAL TO 56 LB. SHALL HAVE TWO NO. 12 GAUGE <br />SAFETY WIRE CONNECTED FROM FIXTURE HOUSING TO STRUCTURE ABOVE. IT IS NOT NECESSARY FOR THESE <br />SAFETY WIRES TO BE TAUT. <br />g. ALL FIXTURES WEIGHING GREATER THAN 56 LB. SHALL BE SUPPORTED DIRECTLY FROM STRUCTURE ABOVE BY <br />APPROVED HANGERS. <br />h. PENDENT-HUNG FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE USING NO LESS THAN N0. <br />9-GAUGE WIRE OR AN APPROVED ALTERNATE SUPPORT. THE CEILING SUSPENSION SYSTEM SHALL NOT PROVIDE <br />ANY DIRECT SUPPORT. <br />i. ALL RECESSED OR DROP-IN FIXTURES SHALL BE SUPPORTED DIRECTLY FROM FIXTURE HOUSING TO THE <br />STRUCTURE ABOVE WITH A MINIMUM OF TWO NO. 12 GAUGE WIRES LOCATED AT DIAGONALLY OPPOSITE CORNERS. <br />LEVELING OR POSITIONING OF FIXTURES MAY BE PROVIDED BY CEILING GRID. FIXTURE SUPPORT WIRES MAY BE <br />SLIGHTLY LOOSE TO ALLOW THE FIXTURE TO SEAT IN THE GRID SYSTEM. FIXTURES SHALL NOT BE SUPPORTED <br />FROM MAIN RUNNERS OR CROSS RUNNERS IF THE WEIGHT OF THE FIXTURES CAUSES TOTAL DEAD LOAD TO <br />EXCEED THE DEFLECTION CAPABILITY OF THE CEILING SUSPENSION SYSTEM. <br />(2) 12 GA. SLACK WIRE HANGERS FOR DEVICES THAT <br />WEIGH LESS THAN 56 LBS. (HEAVY DUTY GRID SYSTEM <br />REQUIRED), PLACE ON DIAGONAL CORNERS <br />(2) #8 SMS EA. SIDE <br />HEAVY DUTY GRID SYSTEM <br />HEAVY DUTY GRID SYSTEM HANGER WIRE (WHERE OCCURS)CEILING FIXTURE, <br />TERMINAL, OR <br />DEVICE (56# MAX) <br />LATERAL FORCE BRACING: <br />a. PROVIDE LATERAL-FORCE BRACING ASSEMBLIES CONSISTING OF A STRUT AND FOUR (4) #12 GAGE <br />BRACING WIRES ORIENTED 90 DEGREES FROM EACH OTHER. <br />b. LATERAL-FORCE BRACING ASSEMBLIES SHALL BE SPACED IN ACCORDANCE WITH AND FROM <br />EACH WALL AND AT THE EDGES OF ANY CHANGE OF ELEVATION OF THE CEILING. <br />c. THE SLOPE OF BRACING WIRES MAY BE FROM 10 TO 45 DEGREES BUT MAY NOT EXCEED 45 DEGREES <br />FROM THE PLANE OF THE CEILING AND WIRES SHALL BE TAUT. <br />d. STRUTS SHALL BE ADEQUATE TO RESIST THE VERTICAL COMPONENT INDUCED BY THE BRACING <br />WIRES, AND SHALL NOT BE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB. <br />EXCEPTION: LATERAL FORCE BRACING MAY BE OMITTED FOR SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH <br />A CEILING AREA OF 144 SQ. FT. OR LESS, WHEN PERIMETER SUPPORT IN ACCORDANCE WITH ASTM E580 ARE <br />PROVIDED AND PERIMETER WALLS ARE DESIGNED TO CARRY THE CEILING LATERAL FORCES. <br />4 WAY 45 DEG. <br />DIAGONAL 12 GA. WIRE <br />BRACING FOR TOP <br />ATTACHMENT SEE <br />DETAIL: <br />12 GA. VERTICAL <br />HANGER WIRES AT 4'-0" <br />EA. WAY - FOR TOP <br />ATTACHMENT SEE <br />DETAIL: <br />-/--- <br />-/--- <br />1-1/2" MAX.1-1/2" MAX. <br />TYP. <br />3/4" MIN. <br />1" MAX <br />400S137-33 (20 GA) CENTERED <br />OVER CROSS RUNNER - SLOT <br />END AS NOTED. FOR TOP <br />ATTACHMENT <br />SEE DETAIL:-/--- <br />CROSS RUNNER <br />MAIN RUNNER <br />(2) 1/4" DIA. MACHINE BOLT <br />TYP. <br />3/4" MIN. <br />TYP. <br />10 TO 45° <br />02/A5-04 <br />WALL STUD (20 GA. MIN.) <br />5/8" GYP. BD. <br />(2) #10 SMS TO FRAMING <br />12 GA. HOCL-11 ANGLE CLIP <br />12 GA. CEILING HANGER WIRE <br />WITH 3 TIGHT TURNS IN 3" BOTH <br />ENDS OF WIRE PER DETAIL <br />02/A5-04 <br />1 TO 6 MAX. SLOPE FROM VERTICAL <br />NOTE: <br />1. APPLY DETAIL FOR PERIMETER WIRE ATTACHMENT OR WHERE OBSTRUCTIONS PREVENTS <br />ATTACHMENT TO STRUCTURE ABOVE. <br />2. WALLS SHALL BE DESIGN FOR HANGER FORCES. <br />(E) STRUCTURE <br />CUT STUD FLANGE AND BEND <br />WEB 90 DEG. ATTACH TRACK TO <br />(E) STRUCTURE ABOVE OR NEW <br />2X4 WITH (2) #12X2" FHWS. <br />(E) PLYWOOD DECK <br />400S137-33 (20 GA) - CUT <br />FLANGES AND BEND <br />(E) STRUCTURE <br />12 GA. HANGER WIRE W/ <br />(3) TIGHT TURNS. <br />SPLICES NOT <br />PERMITTED <br />12 GA. BRACE WIRE W/ (3) <br />TIGHT TURNS. SPLICES <br />NOT PERMITTED. <br />3" FLATHEAD HANGER SCREW <br />(ICC ESR-1153) W/ 1 1/2" MIN. <br />PENETRATION <br />(E) PLYWOOD DECK <br />NOTE: <br />COAT ALL COMBUSTIBLE MATERIAL WITHIN THE PLENUM SPACE WITH <br />FLAME STOP IM INTUMESCENT PAINT TO COMPLY WITH CMC 602.2 <br />NO HANGER OR ATTACHEMENTS OF ANY KIND TO BE MADE TO THE <br />EXISTING PLYWOOD ROOF DECK <br />ATTACHMENT OF HANGER AND BRACING WIRES: <br />a. HANGER WIRE LOOPS SHALL BE TIGHTLY WRAPPED AND SHARPLY BENT TO PREVENT ANY VERTICAL MOVEMENT OR <br />ROTATION OF THE MEMBER WITHIN THE LOOPS. <br />b. SPLICES OF WIRES ARE NOT PERMITTED. <br />c. HANGER OR BRACING WIRE ANCHORED TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE <br />DIRECTION OF THE ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE. <br />d. SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST SIX (6) INCHES FROM ALL UNBRACED DUCTS, PIPES <br />CONDUITS, ETC. <br />e. HANGER WIRES SHALL NOT BE ATTACHED TO OR BEND AROUND INTERFERING MATERIAL OR EQUIPMENT. PROVIDE <br />TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT MEMBERS AT OBSTRUCTIONS TO TYPICAL HANGER SPACING. <br />PROVIDE ADDITIONAL HANGERS, STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS, OR <br />DISCONTINUOUS AREAS. <br />f. HANGER WIRES THAT ARE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB SHALL REQUIRE PROJECT <br />SPECIFIC DESIGN. <br />NOTE: <br />1. PROVIDE 12 GAGE HANGER WIRES AR THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES OF <br />THE SUPPORT OR WITHIN ONE-FOURTH (1/4) OF THE LENGTH OF THE END TEE, WHICHEVER IS LESS, FOR THE <br />PERIMETER OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF THE END TEE IS <br />EIGHT (8) INCHES OR LESS. <br />2. NAILS AT ENDS OF HORIZONTAL STRUTS ARE TO BE PLACED WITH NAIL HEAD TOWARD CENTER LINE OF SPAN OF <br />STRUT. <br />3. SPACERS MAY BE SLOTTED APPROVED ANGLES OR CHANNELS WITH "DIAMOND POINTS" OF SPRING STEEL WHICH <br />SNAP TIGHT TO PREVENT MOVEMENT OF STRUT. <br />4. STEEL POP RIVETS SHALL HAVE MINIMUM ALLOWABLE SHEAR STRENGTH OF 120# AND ULTIMATE SHEAR STRENGTH <br />OF 300#. <br />5. REFER TO ICC-ESR-1308. <br />STEEL POP RIVET AT <br />ATTACHED SIDE ONLY <br />MAIN OR <br />CROSS <br />RUNNER <br />HANGER <br />WIRE <br />CEILING <br />PANEL <br />7/8"x1" 24 GA CONT. <br />PERIMETER ANGLE W/ <br />(1) #10 SMS INTO WALL <br />STUDS (24" O.C. MAX) <br />CONT. SLOTTED ANGLE <br />STRUT SPACER W/ <br />HORIZ. 6d RINGSHANK <br />NAIL <br />FREE <br />END <br />FIXED <br />END <br />BERC2 <br />SLIP CLIP <br />8" MAX 8" MAX <br />FURRING CHANNEL SPLICE <br />MAIN RUNNER SPLICE <br />16" <br />12" MIN OVERLAP <br />PROVIDE (4) #8 SMS AT EACH END OF OVERLAP. (8) TOTAL. <br />1-1/2" 16 GA. MAIN RUNNER INSTALLED BACK TO BACK. <br />PROVIDE (2) #8 SMS AT EACH END OF OVERLAP. (4) TOTAL. <br />8" <br />7-1/4" TYP. <br />3/8" TYP. <br />1-1/2" 16 GA. MAIN RUNNER. <br />MIN. <br />8" <br />MAX.SADDLE TIED TO MAIN RUNNERS <br />WITH 16 GAGE TIE WIRE OR A <br />DOUBLE STRAND OF 18 GAGE TIE <br />WIRE <br />LATERAL FORCE BRACING: <br />a. PROVIDE LATERAL-FORCE BRACING ASSEMBLIES CONSISTING OF A STRUT AND FOUR (4) #12 GAGE <br />BRACING WIRES ORIENTED 90 DEGREES FROM EACH OTHER. <br />b. LATERAL-FORCE BRACING ASSEMBLIES SHALL BE SPACED IN ACCORDANCE WITH AND FROM <br />EACH WALL AND AT THE EDGES OF ANY CHANGE OF ELEVATION OF THE CEILING. <br />c. THE SLOPE OF BRACING WIRES MAY BE FROM 10 TO 45 DEGREES BUT MAY NOT EXCEED 45 DEGREES <br />FROM THE PLANE OF THE CEILING AND WIRES SHALL BE TAUT. <br />d. STRUTS SHALL BE ADEQUATE TO RESIST THE VERTICAL COMPONENT INDUCED BY THE BRACING WIRES, <br />AND SHALL NOT BE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB. <br />EXCEPTION: LATERAL FORCE BRACING MAY BE OMITTED FOR SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH <br />A CEILING AREA OF 144 SQ. FT. OR LESS, WHEN PERIMETER SUPPORT IN ACCORDANCE WITH ASTM E580 ARE <br />PROVIDED AND PERIMETER WALLS ARE DESIGNED TO CARRY THE CEILING LATERAL FORCES. <br />4 WAY 45 DEG. <br />DIAGONAL 12 GA. WIRE <br />BRACING FOR TOP <br />ATTACHMENT SEE <br />DETAIL: <br />12 GA. VERTICAL <br />HANGER WIRES AT 4'-0" <br />EA. WAY - FOR TOP <br />ATTACHMENT SEE <br />DETAIL: <br />-/--- <br />-/--- <br />400S137-33 (20 GA) CENTERED OVER <br />CROSS RUNNER - FOR TOP <br />ATTACHMENT SEE DETAIL: <br />-/--- <br />GYP. BD. FINISH <br />FURRING CHANNEL <br />10/A5-04 <br />2" MAX <br />#8 SMS TO PREVENT <br />SLIPPAGE OF BRACE <br />WIRES PARALLEL TO <br />MAIN RUNNER, TYP. <br />(2) #10 SMS <br />3" MAX <br />MAIN RUNNER <br />4' - 0" MAX <br />MAX <br />8' - 0" <br />12' - 0" MAX <br />6'-0" MAX <br />FIXED END <br />FREE END <br />FR <br />E <br />E <br /> <br />E <br />N <br />D <br />FI <br />X <br />E <br />D <br /> <br />E <br />N <br />D <br />FROM SPLAY <br />WIRE TO WALL <br />FURRING CHANNELS,TYP. <br />CONT. MAIN RUNNER <br />AT 4'-0" O.C., TYP. <br />4 WAY 45 DEG. DIAGONAL <br />12 GA. WIRE BRACING W/ <br />COMPRESSION STRUT <br />LOCATED ON MAIN <br />RUNNER <br />PER DETAIL: <br />12 GA. <br />VERTICAL <br />HANGER WIRES <br />AT 4'-0" EA. <br />WAY <br />NOTE: <br />1. CEILING GRID MAY BE ATTACHED TO NOT MORE THAN TWO (2) ADJACENT WALLS AND MUST <br />BE AT LEAST 3/4" FREE OF OTHER WALLS. <br />2. LOCATE COMPRESSION STRUT AND SPLAY WIRES FOR EA. 96 S.F. <br />03/A5-04 <br />FIXTURE <br />SUSPENSION PER <br />DETAIL:12/A5-04 <br />24 GA. CONT. WALL <br />ANGLE, TYP. <br />13 <br />A5-04 <br />14 <br />A5-04 <br />CEILING FIXTURES, TERMINALS, AND DEVICES: <br />a. ALL FIXTURES SHALL BE MOUNTED IN A MANNER THAT WILL NOT COMPROMISE CEILING PERFORMANCE. <br />b. ALL FIXTURES SHALL BE SUPPORTED DIRECTLY BY MAIN RUNNERS OR BY SUPPLEMENTAL FRAMING WHICH IS <br />SUPPORTED BY MAIN RUNNERS AND POSITIVELY ATTACHED WITH SCREWS OR OTHER APPROVED CONNECTORS. <br />c. SURFACE MOUNTED FIXTURES SHALL BE ATTACHED TO A MAIN RUNNER WITH POSITIVE CLAMPING DEVICE MADE OF <br />MATERIAL WITH A MINIMUM 14 GAGE. ROTATIONAL SPRING CLAMPS DO NOT COMPLY. <br />d. ALL FIXTURES WEIGHING LESS THAN OR EQUAL TO 10 LB. SHALL HAVE ONE NO. 12 GAUGE SAFETY WIRE <br />CONNECTED FROM FIXTURE HOUSING TO STRUCTURE ABOVE. IT IS NOT NECESSARY FOR THESE SAFETY WIRES TO <br />BE TAUT. <br />e. ALL FIXTURES WEIGHING GREATER THAN 10 LB BUT LESS THAN OR EQUAL TO 56 LB. SHALL HAVE TWO NO. 12 GAUGE <br />SAFETY WIRE CONNECTED FROM FIXTURE HOUSING TO STRUCTURE ABOVE. IT IS NOT NECESSARY FOR THESE <br />SAFETY WIRES TO BE TAUT. <br />f. ALL FIXTURES WEIGHING GREATER THAN 56 LB. SHALL BE SUPPORTED DIRECTLY FROM STRUCTURE ABOVE BY <br />APPROVED HANGERS. <br />g. PENDENT-HUNG FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE USING NO LESS THAN <br />N0. 9-GAUGE WIRE OR AN APPROVED ALTERNATE SUPPORT. THE CEILING SUSPENSION SYSTEM SHALL NOT <br />PROVIDE ANY DIRECT SUPPORT. <br />h. ALL RECESSED OR DROP-IN FIXTURES SHALL BE SUPPORTED DIRECTLY FROM FIXTURE HOUSING TO THE <br />STRUCTURE ABOVE WITH A MINIMUM OF TWO NO. 12 GAUGE WIRES LOCATED AT DIAGONALLY OPPOSITE CORNERS. <br />LEVELING OR POSITIONING OF FIXTURES MAY BE PROVIDED BY CEILING GRID. FIXTURE SUPPORT WIRES MAY BE <br />SLIGHTLY LOOSE TO ALLOW THE FIXTURE TO SEAT IN THE GRID SYSTEM. FIXTURES SHALL NOT BE SUPPORTED <br />FROM MAIN RUNNERS OR FURRING CHANNELS IF THE WEIGHT OF THE FIXTURES CAUSES TOTAL DEAD LOAD TO <br />EXCEED THE DEFLECTION CAPABILITY OF THE CEILING SUSPENSION SYSTEM. <br />i. ACCESS PANELS SHALL HAVE A PERMANENT WARNING LABEL AS FOLLOWS: <br />1. DO NOT CLIMB, WALK OR CRAWL ON THE GYPSUM BOARD CEILING <br />2. DO NOT STORE OR STOW ANYTHING ON THE GYPSUM BOARD CEILING <br />(2) 12 GA. SLACK WIRE HANGERS <br />FOR DEVICES THAT WEIGH LESS <br />THAN 56 LBS. PLACE ON <br />DIAGONAL CORNERS <br />(2) #10 SMS EA. END GYPSUM BOARD FINISH <br />HANGER WIRE (WHERE OCCURS) <br />CEILING FIXTURE, TERMINAL, OR <br />DEVICE (56# MAX) WITH POSITIVE <br />ATTACHMENT TO MAIN RUNNERS <br />PROVIDE (1) OR MORE <br />SUPPLEMENTAL 150U050-54 AS <br />REQUIRED. SEE GENERAL NOTE b. - <br />CLIP FLANGE AND BEND BACK TO <br />FORM 'L' CLIP <br />#10 SMS AT EACH <br />MAIN RUNNER <br />MAIN RUNNER <br />HANGER <br />WIRE <br />FURRING <br />CHANNEL <br />1"x2" 24 GA CONT. <br />PERIMETER ANGLE W/ <br />(1) #10 SMS INTO <br />WALL STUDS (24" O.C. <br />MAX) <br />FREE <br />END <br />FIXED <br />END <br />6" MAX 6" MAX <br />MIN <br />1" CLR1/2" MIN <br />1/2" MIN <br />4" MAX, TYP <br />#10 SMS AT EACH <br />FURRING CHANNEL <br />MAIN <br />RUNNER <br />HANGER <br />WIRE <br />FURRING <br />CHANNEL <br />1"x2" 24 GA CONT. <br />PERIMETER ANGLE W/ <br />(1) #10 SMS INTO <br />WALL STUDS (24" O.C. <br />MAX) <br />FREE <br />END <br />FIXED <br />END <br />6" MAX 6" MAX <br />MIN <br />1" CLR <br />NO CONNECTION <br />TO FURRING <br />CHANNEL <br />1/2" MIN <br />1/2" MIN <br />1. SUSPENSION SYSTEM COMPONENTS SHALL COMPLY WITH ASTM C754: <br />• MAIN RUNNERS SHALL CONSIST OF 16 GAGE 1-1/2” COLD ROLLED U-CHANNEL 150U050-54 SPACED AT 4’-0” OC MAX. <br />MAIN RUNNERS SHALL BE SUPPORTED BY HANGER WIRES AT 4’-0” OC MAX AND WITHIN 6” FROM EA END. <br />• FURRING CHANNEL SHALL CONSIST OF 25 GAGE 7/8” (HAT) FURRING CHANNELS (087F125-18) AT 2’-0” OC MAX. <br />FURRING CHANNELS SHALL BE SADDLE TIED TO MAIN RUNNERS WITH 16 GAGE TIE WIRE OR A DOUBLE STRAND OF <br />18 GAGE TIE WIRE IN ACCORDANCE WITH <br />• MAIN RUNNERS AND FURRING CHANNELS SHALL BE SPLICED BY LAPPING IN ACCORDANCE WITH <br />• MAIN RUNNERS AND FURRING CHANNELS ALONG WITH THEIR SPLICES, INTERSECTION CONNECTORS, AND <br />EXPANSION DEVICES SHALL BE DESIGNED AND CONSTRUCTED TO CARRY A MEAN ULTIMATE TEST LOAD OF NOT <br />LESS THAN 270 LBS. IN COMPRESSION & TENSION. <br />• HANGER AND BRACING WIRES SHALL BE #12 GAGE (0.106" DIAMETER), SOFT ANNEALED, AND GALVANIZED STEEL <br />WIRES WITH CLASS 1 COATING. THEY MAY BE USED FOR UP TO AND INCLUDING 4'-0"x 4'-0" GRID SPACING ALONG <br />AND ATTACHED TO MAIN RUNNERS. SPLICES ARE NOT PERMITTED IN ANY HANGER WIRE. <br />• WIRE HANGERS SHALL BE SADDLE-TIED AROUND MAIN RUNNERS SO AS TO PREVENT TURNING OR TWISTING OF <br />THE MEMBER. <br />2. SUSPENSION SYSTEM INSTALLATION SHALL COMPLY WITH ASTM C754: <br />• CEILING GRID MEMBERS SHALL BE ATTACHED TO TWO (2) ADJACENT WALLS. MAIN RUNNERS AND FURRING <br />CHANNEL SHALL BE AT LEAST 1 INCH CLEAR OF OTHER WALL AND FURRING SHALL BE AT LEAST 3/4” CLEAR OF <br />OTHER WALL. IF WALLS RUN DIAGONAL TO THE CEILING GRID SYSTEM RUNNERS, ONE END OF MAIN RUNNER AND <br />FURRING SHOULD BE FREE WITH STANDARD CLEARANCES. <br />• THE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT LESS THAN TWO (2) INCHES. <br />3. EXPANSION JOINTS, SEISMIC SEPARATIONS, AND PENETRATIONS: <br />• EXPANSION JOINTS SHALL BE PROVIDED IN THE CEILING AT INTERSECTIONS OF CORRIDORS AND AT JUNCTIONS OF <br />CORRIDORS WITH LOBBIES OR OTHER SIMILAR AREAS. <br />• FOR CEILING AREAS EXCEEDING 2500 SQUARE FEET, A SEISMIC SEPARATION JOINT SHALL BE PROVIDED TO DIVIDE <br />THE CEILING INTO AREAS NOT EXCEEDING 2500 SQ. FT. <br />• PENETRATIONS THROUGH THE CEILING FOR SPRINKLER HEADS AND OTHER SIMILAR DEVICES THAT ARE NOT <br />INTEGRALLY TIED TO THE CEILING SYSTEM IN THE LATERAL DIRECTION SHALL HAVE A TWO (2) INCH OVERSIZED <br />RING, SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF ONE (1) INCH IN ALL <br />HORIZONTAL DIRECTIONS. A FLEXIBLE SPRINKLER HOSE FITTING THAT CAN ACCOMMODATE ONE (1) INCH OF <br />CEILING MOVEMENT SHALL BE PERMITTED TO BE USED IN LIEU OF THE OVERSIZED RING, SLEEVE OR ADAPTER. <br />SUCH FLEXIBLE SPRINKLER HOSE SHALL BE ADEQUATELY SUPPORTED FROM SOFFIT SO AS NOT TO EXCEED THE <br />MAXIMUM TRIBUTARY WEIGHT OF THE CEILING. <br />4. GYPSUM BOARD INSTALLATION SHALL COMPLY WITH ASTM C840-11: <br />• GYPSUM BOARD SHALL CONSIST OF SINGLE-PLY ½” OR 5/8” THICK IN ACCORDANCE WITH ASTM C11-10a. <br />• GYPSUM BOARD SHALL BE INSTALLED PERPENDICULAR TO FURRING WITH SCREWS AT 12" ON CENTER MAXIMUM, IN <br />ACCORDANCE WITH ASTM C840-11. <br />• GYPSUM BOARD SHALL BE ATTACHED TO FURRING/FRAMING WITH ASTM C1002-07 TYPE S (ASTM A568-11b GRADES <br />1018 TO 1022) SCREWS (NOT LESS THAN, N0. 6, WITH MAJOR DIAMETER NOT LESS THAN 0.136 IN). <br />15/A5-04 <br />-/--- <br />NOTE: SEE DETAILS 03 & 04/A5-02 FOR TOP <br />OF SOFFIT CONNECTION <br />(E) DRYWALL CEILING <br />(N) ACOUSTICAL CEILING <br />TILE <br />(E) SUSPENDED CEILING <br />SYSTEM <br />NEW METAL STUD FRAMING <br />(N) DRYWALL SOFFIT <br />R <br />No. <br />F <br />LICENSE <br />STATE <br />D <br />O <br />A RCHITECT <br />C AL IFORNIA <br />STEPHE WHITE <br />RENEWAL <br />DATE <br />C-34829 <br />N <br />08/31/25 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />MATTERPORT LINK: https://my.matterport.com/show/?m=FW21iEbmuii <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br />50 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br />1/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />C:\Users\jpark\Documents\R314412.44 - KP SAN 1st Flr Gen Rad_A22_Central_jhaLWMQW.rvt <br />5/20/2024 10:23:14 AM <br />SOCC 2023 R RAD SAN 1ST FLOOR <br />GEN RAD REPLACEMENT (5284) <br />A5-04 <br />DETAILS - TYPICAL CEILING <br />CA361 1 1 - <br />CAP028060R314412.44 <br />SANTA ANA MEDICAL OFFICES <br />1900 E. 4TH ST. <br />SANTA ANA, CA 92701 <br />1/8" = 1'-0"ACT DIAGRAMATIC CEILING PLAN 02 <br />N/AACT SUSPENDED CEILING NOTES 01 <br />3" = 1'-0"ACT FIXTURE SUSPENSION 04 <br />3" = 1'-0"ACT COMPRESSION STRUT 03 <br />3" = 1'-0"CEILING WIRE AT PERIMETER OBSTRUCTION 06 <br />3" = 1'-0"COMPRESSION STRUT ANCHORAGE 08 <br />3" = 1'-0"SUSPENSION WIRE CONNECTION @ ROOF 07 <br />3" = 1'-0"ACT PERIMETER ATTACHMENT 05 <br />3" = 1'-0"GYP. BD. CEILING - SPLICE DETAILS 15 3" = 1'-0"GYP. BD. COMPRESSION STRUT 11 <br />1/8" = 1'-0"GYP. BD. DIAGRAMATIC CEILING PLAN 10 <br />3" = 1'-0"GYP. BD. FIXTURE SUSPENSION 12 <br />3" = 1'-0"GYP. BD. PERIMETER ATTACHMENT 13 <br />3" = 1'-0"GYP. BD. PERIMETER ATTACHMENT - FURRING 14 <br />N/AGYP. BOARD SUSPENDED CEILING NOTES 093" = 1'-0"CEILING TRANSITION, GYP TO ACT 17 <br />CITY SUBMITTAL 04/19/2024 <br />BID SET 05/20/2024 <br />1900 E 4th St - <br />1011190678/9/2024