1 <br />SINGLE FLUSH DOOR <br />W <br />H <br />3' <br /> <br />- <br /> <br />2 <br />" <br />FOR PARTITION TYPES <br />THROAT: SEE PLAN <br />HEADER FRAMING PER 11/A5-02 <br />FRAME ANCHOR - <br />PROVIDE (1) FOR EVERY <br />24" OF JAMB LENGTH <br />FASTEN FRAME TO JAMB <br />FRAMING W/ (2) #10 SMS PER <br />ANCHOR <br />WELDED HOLLOW METAL <br />FRAME PER DOOR SCHEDULE <br />GYP. BD. WITH SCHEDULED FINISH, TYP. <br />CONT. SEALANT AT EACH SIDE OF PARTITION <br />INSULATION WHERE OCCURS -SEE <br />PLANS FOR PARTITION TYPES <br />HEADER FRAMING PER 11/A5-02 <br />FASTEN FRAME TO JAMB <br />FRAMING W/ (2) #10 SMS PER <br />ANCHOR <br />KNOCK DOWN METAL FRAME <br />WITH MITRED CORNERS PER <br />DOOR SCHEDULE <br />GYP. BD. WITH SCHEDULED FINISH, TYP. <br />CLIP ON TRIP PER MANUFACTURER <br />INSULATION WHERE OCCURS -SEE <br />PLANS FOR PARTITION TYPES <br />FOR PARTITION TYPES <br />THROAT: SEE PLANS <br />FOR PARTITION TYPES <br />THROAT: SEE PLAN <br />(PER NFPA 80) <br />1/2" MIN. <br />4" <br />TYPICAL DISTANCE FROM <br />ADJACENT PARTITION WHERE <br />OCCURS -SEE PLANS <br />JAMB FRAMING PER 14/A5-02 <br />FRAME ANCHOR - <br />PROVIDE (1) FOR EVERY <br />24" OF JAMB LENGTH <br />FASTEN FRAME TO JAMB <br />FRAMING W/ (2) #10 SMS PER <br />ANCHOR <br />WELDED HOLLOW METAL <br />FRAME PER DOOR SCHEDULE <br />GYP. BD. WITH SCHEDULED FINISH, TYP. <br />CONT. SEALANT AT EACH SIDE OF PARTITION <br />INSULATION WHERE OCCURS -SEE <br />PLANS FOR PARTITION TYPES <br />NOTE: <br />PROVIDE FLOOR ANCHORS FOR FRAMES PER MANUFACTURER'S <br />RECOMMENDATIONS AND PER SPECIFICATIONS <br />UNDERCUT <br />3/4" MAX. <br />CENTER MATERIAL <br />TRANSITION - <br />WELDING ROD <br />UNDER DOOR <br />PANEL <br />(E) FLOOR FINISH <br />SCHEDULED FRAME <br />SCHEDULED DOOR <br />SCHEDULED FLOOR <br />FINISH <br />SCHED. PARTITION <br />A <br />WELDED STEEL 3 PIECE <br />KNOCKDOWN FRAME <br />WITH RETURNS <br />FRAME TYPE: <br />1/2" <br />1/2"1 7/8" <br />VARIES <br />1 7/8" <br />SCHED. PARTITION <br />1/2" <br />1/2"1 7/8" <br />VARIES <br />1 7/8" <br />B <br />WELDED STEEL 3 PIECE <br />KNOCKDOWN FRAME <br />WITH RETURNS AND <br />LEAD-LINING <br />FRAME TYPE: <br />HW-1 (LEAD SHEILDED) <br />QTY ITEM / FUNCTION MODEL FINISH MANUFACTURER <br />1 PASSAGE LOCKSET 9K30N15D-LL 626 BEST ACCESS <br />1 BOTTOM PIVOT L147-20 LESS TOP PIVOT 626 RIXSON <br />2 INTERMEDIATE PIVOT ML 19-20 626 RIXSON <br />3 SILENCERS SR644 BLK IVES <br />1 KICK PLATE K0038 630 TRIMCO <br />1 WALL STOP 1270CV 630 TRIMCO <br />1 CLOSER 8916-AF89-FC-SN2 689 DORMAKABA <br />SEE PHYSICIST REPORT FOR SHIELDING REQUIREMENTS. <br />HW-2 (DRESSING ROOM) <br />QTY ITEM / FUNCTION MODEL FINISH MANUFACTURER <br />1 PASSAGE SET 9K30N15D 626 BEST ACCESS <br />3 HINGES BB1168 652 HAGER <br />1 OCCUPANCY INDICATOR B571 626 SHLAGE <br />1 KICK PLATE K0038 630 TRIMCO <br />1 OVERHEAD HOLDER-STOP #6ADJ 626 RIXSON <br />3 SILENCERS SR64 BLK IVES <br />HW-3 (CARD READER) <br />QTY ITEM / FUNCTION MODEL FINISH MANUFACTURER <br />2 HINGE BB1168 626 HAGGAR <br />1 ELECTRIC HINGE BB1168-ETW 626 HAGGAR <br />1 ELECTRIC LOCKSET 93K30N15D 626 BEST ACCESS <br />1 CLOSER 8916-AF89-FC-SN2 626 DORMAKABA <br />3 SILENCERS SR64 BLK IVES <br />1 CARD READER <br />1 REQUEST TO EXIT <br />1 DOOR POSITION SWITCH <br />SEE SECURITY DRAWINGS, 11/T5-01 <br />HW-4 (STOREROOM LOCK) <br />QTY ITEM / FUNCTION MODEL FINISH MANUFACTURER <br />(3) HINGES TA714 630 MCK <br />(1) STOREROOM LOCK 45H7D 14H 630 BES <br />(1)PERMANENT CORE 1CM7 626 BES <br />(1) OVERHEAD HOLDER 2-SERIES 630 RIX <br />(1) SET SEALS S44D MITRED DKB PEM <br />A.HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH 11B-309.4 <br />B.THE FORCE FOR PUSHING OR PULLING OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL BE AS FOLLOWS 11B-404.2.9 <br />1. INTERIOR HINGED DOORS AND GATES: 5 POUNDS MAXIMUM. <br />2. SLIDING OR FOLDING DOORS: 5 POUNDS MAXIMUM. <br />3. REQUIRED FIRE DOORS: THE MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE <br /> AUTHORITY, NOT TO EXCEED 15 POUNDS <br />4. EXTERIOR HINGED DOOR: 5 POUNDS MAXIMUM. <br />C.SWINGING DOOR AND GATE SURFACES WITHIN 10 INCHES OF THE FINISH FLOOR OR GROUND MEASURED VERTICALLY SHALL <br />HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING THE FULL WIDTH OF THE DOOR OR GATE. PARTS CREATING <br />HORIZONTAL OR VERTICAL JOINTS IN THESE SURFACES SHALL BE WITHIN 1/16 INCH OF THE SAME PLANE AS THE OTHER <br />AND BE FREE OF SHARP OR ABRASIVE EDGES. CAVITIES CREATED BY ADDED KICK PLATES SHALL BE CAPPED. <br />11B-404.2.10 <br />GENERAL NOTES - DOOR ACCESSIBILITY <br />METAL STUD FRAMING. <br />MODIFY AS NEEDED. <br />(N) SILL FRAMING PER 06/A5-02 <br />LEAD SHIELDING IN FRAME. <br />(N) OBSERVATION WINDOW ASSEMBLY. <br />LEAD GLASS, LEAD LINED HM FRAME. <br />COMPLY WITH REQUIREMENTS NOTED IN <br />PHYSICIST REPORT. SEE SHEET Q8-11. <br />ENSURE CONTINUITY OF LEAD LINED <br />SHIELDING PROTECTION. <br />CONTROL ROOM <br />SIDE RADIOLOGY <br />ROOM SIDE <br />RADIOLOGY ROOM SIDE <br />CONTROL ROOM <br />SIDE <br />2" <br />STL. GLASS STOP W/ <br />COUNTERSUNK METAL <br />SCREWS <br />(N) JAMB STUDS <br />FASTEN FRAME TO <br />STUDS W/ (2) #10 <br />S.M.S. PER ANCHOR <br />WELD ANCHORS <br />TO FRAME <br />FASTEN FRAME TO <br />STUDS W/ #12 FLAT <br />HEAD S.M.S. <br />(N) HOLLOW METAL WINDOW <br />FRAME, PROVIDE (3) ANCHORS <br />PER JAMB <br />(N) LEAD GLASS <br />2" <br />SEALANT, BOTH SIDES <br />VERIFY EXISTING <br />THROAT: <br />(N) LEAD SHIELDING IN WALL. <br />EXTEND INTO FRAME <br />(N) LEAD SHIELDING IN FRAME <br />(N) PARTITION <br />(N) OBSERVATION WINDOW ASSEMBLY. <br />LEAD GLASS, LEAD LINED HM FRAME. <br />COMPLY WITH REQUIREMENTS NOTED IN <br />PHYSICIST REPORT. SEE SHEET Q8-11. <br />ENSURE CONTINUITY OF LEAD LINED <br />SHIELDING PROTECTION. <br />FASTEN FRAME TO STUDS W/ <br />(2) #10 S.M.S. PER ANCHOR <br />LEAD SHIELDING IN FRAME. <br />(N) HEADER PER 11/A5-02 <br />(N) CONTINUOUS STUD TRACK <br />ENTIRE LENGTH OF MODIFIED <br />PARTIAL HEIGHT WALL <br />6" <br />CONTROL <br />ROOM SIDE <br />RADIOLOGY <br />ROOM SIDE <br />OBSERVATION WINDOW ASSEMBLY. <br />LEAD GLASS, LEAD LINED HM FRAME. <br />COMPLY WITH REQUIREMENTS NOTED IN <br />PHYSICIST REPORT. SEE SHEET Q8-11. <br />ENSURE CONTINUITY OF LEAD LINED <br />SHIELDING PROTECTION. <br />FASTEN FRAME TO STUDS W/ <br />(2) #10 S.M.S. PER ANCHOR <br />LEAD SHIELDING IN FRAME. <br />HEADER PER 19/A6-01 <br />8". <br />42" . <br />34" . <br />4" 16 GA METAL STUD <br />(400S162-54) @ 16" O.C. <br />SILL FRAMING PER 17/A6-01 <br />LEAD SHIELDING IN FRAME. <br />CONTROL <br />ROOM SIDE <br />RADIOLOGY <br />ROOM SIDE <br />(N) FLOORING AND BASE <br />CONT. 4" 16 GA METAL TRACK <br />(400T162-54) <br />5/8" GYP. BD. <br />7'-0" . <br />5/8" LEAD-LINED GYP. BD. PER <br />PHYSICIST REPORT <br />CONT. 4" 16 GA METAL TRACK <br />(400T162-54) <br />1 <br />SINGLE FIXED <br />WINDOW <br />WINDOW TYPE LEGEND <br />@ SILL <br />34" <br />H <br />W <br />FOR PARTITION TYPES <br />THROAT: SEE PLAN <br />(PER NFPA 80) <br />1/2" MIN. <br />4" <br />TYPICAL DISTANCE FROM <br />ADJACENT PARTITION WHERE <br />OCCURS -SEE PLANS <br />JAMB FRAMING PER <br />FRAME ANCHOR -PROVIDE (1) <br />FOR EVERY 24" OF JAMB LENGTH <br />FASTEN FRAME TO JAMB FRAMING <br />W/ (2) #10 SMS PER ANCHOR <br />WELDED HOLLOW METAL <br />FRAME PER DOOR SCHEDULE <br />GYP. BD. WITH <br />SCHEDULED FINISH, TYP. <br />CONT. SEALANT AT EACH <br />SIDE OF PARTITION <br />INSULATION WHERE <br />OCCURS -SEE PLANS FOR <br />PARTITION TYPES <br />NOTE: <br />PROVIDE FLOOR ANCHORS FOR FRAMES PER MANUFACTURER'S <br />RECOMMENDATIONS AND PER SPECIFICATIONS <br />2" <br />LEAD LINED DOOR <br />LEAD SHIELDING IN FRAME <br />LEAD SHIELDING IN WALL. <br />EXTEND INTO FRAME. <br />GEN RAD ROOM SIDE <br />CORRIDOR SIDE <br />14 <br />A5-02 <br />FOR PARTITION TYPES <br />THROAT: SEE PLAN <br />HEADER FRAMING PER <br />FRAME ANCHOR - <br />PROVIDE (1) FOR EVERY <br />24" OF JAMB LENGTH <br />FASTEN FRAME TO JAMB <br />FRAMING W/ (2) #10 SMS PER <br />ANCHOR <br />WELDED HOLLOW METAL <br />FRAME PER DOOR SCHEDULE <br />GYP. BD. WITH SCHEDULED <br />FINISH, TYP. <br />CONT. SEALANT AT EACH <br />SIDE OF PARTITION <br />INSULATION WHERE <br />OCCURS -SEE PLANS FOR <br />PARTITION TYPES <br />LEAD SHIELDING IN FRAME <br />LEAD LINED DOOR <br />GEN RAD ROOM SIDE CORRIDOR SIDE <br />11 <br />A5-02 <br />TYPICAL DISTANCE FROM <br />ADJACENT PARTITION WHERE <br />OCCURS -SEE PLANS <br />JAMB FRAMING PER 14/A5-02 <br />FASTEN FRAME TO JAMB <br />FRAMING W/ #10 SMS @ 11" <br />O.C., TYP BOTH FACES <br />KNOCK DOWN METAL FRAME <br />WITH MITRED CORNERS PER <br />DOOR SCHEDULE <br />GYP. BD. WITH <br />SCHEDULED FINISH, TYP. <br />INSULATION WHERE <br />OCCURS -SEE PLANS <br />FOR PARTITION TYPES 4" <br />CLIP ON TRIP PER <br />MANUFACTURER <br />LEAD SHIELDING IN FRAME <br />LEAD SHIELDING IN WALL. <br />EXTEND INTO FRAME. <br />R <br />No. <br />F <br />LICENSE <br />STATE <br />D <br />O <br />A RCHITECT <br />C AL IFORNIA <br />STEPHE WHITE <br />RENEWAL <br />DATE <br />C-34829 <br />N <br />08/31/25 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />MATTERPORT LINK: https://my.matterport.com/show/?m=FW21iEbmuii <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br />50 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br />1/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />C:\Users\jpark\Documents\R314412.44 - KP SAN 1st Flr Gen Rad_A22_Central_jhaLWMQW.rvt <br />5/20/2024 10:21:19 AM <br />SOCC 2023 R RAD SAN 1ST FLOOR <br />GEN RAD REPLACEMENT (5284) <br />A6-01 <br />SCHEDULE - DOOR <br />CA361 1 - - <br />CAP028060R314412.44 <br />SANTA ANA MEDICAL OFFICES <br />1900 E. 4TH ST. <br />SANTA ANA, CA 92701 <br />DOOR SCHEDULE <br />DOOR <br />NO.ROOM NAME <br />DOOR FRAME <br />FIRE <br />RATING <br />HDW <br />SET NO. <br />VIEW PANEL <br />COMMENTS <br />SIZE <br />TYPE MATERIAL FINISH TYPE MATERIAL FINISH <br />DETAILS <br />TYPE <br />SIZE <br />W H THK HEAD JAMB SILL W H THK <br />1504 HALLWAY 3' - 0" 7' - 0" 1 3/4" 1 SC/WD PT-1 A STEEL P-2 07/A6-01 09/A6-01 08/A6-01 - 3 - 0" 0" 0" <br />1505 SHELL SPACE 3' - 6" 7' - 0" 1 3/4" 1 SC/WD PT-1 A STEEL P-2 07/A6-01 09/A6-01 08/A6-01 - 4 - 0" 0" 0" <br />1506 IMAGING, GEN 3' - 6" 7' - 0" 1 3/4" 1 SC/WD PT-1 B STEEL P-2 27/A6-01 29/A6-01 28/A6-01 - 1 - 0" 0" 0" THIS DOOR IS LEAD-LINED. REFER TO SHEET Q8-11 FOR <br />ADDITIONAL REQUIREMENTS. <br />1511 DRESSING BOOTH 3' - 0" 7' - 0" 1 3/4" 1 SC/WD PT-1 A STEEL P-2 07/A6-01 09/A6-01 08/A6-01 - 2 - 0" 0" 0" <br />1513 DRESSING BOOTH 3' - 0" 7' - 0" 1 3/4" 1 SC/WD PT-1 A STEEL P-2 07/A6-01 09/A6-01 08/A6-01 - 2 - 0" 0" 0" <br />3/8" = 1'-0"DOOR TYPE LEGEND 20 <br />03DOOR HARDWARE <br />3" = 1'-0"TYPICAL DOOR HEAD - HOLLOW METAL 07 <br />3" = 1'-0"TYPICAL DOOR HEAD - KNOCK DOWN 08 <br />3" = 1'-0"TYPICAL DOOR JAMB - HOLLOW METAL 09 <br />3" = 1'-0"TYPICAL DOOR THRESHOLD - SIMILAR MATERIALS 01 <br />02FRAME TYPE LEGEND <br />3" = 1'-0"LEAD LINED WINDOW - SILL 17 <br />3" = 1'-0"LEAD LINED HM WINDOW JAMB DETAIL 18 <br />3" = 1'-0"LEAD LINED WINDOW - HEAD 19 <br />3" = 1'-0"LEAD LINED WINDOW SECTION 21 <br />GENERAL NOTES: <br />1. SEE FINISH SCHEDUEL ON SHEET I1-11 FOR FINISH DEFINITIONS. <br />2. SEE SPECIFICATIONS -DEVISION 13, AND PHYSICIST REPORT ON SHEET Q8-11 FOR ADDITIONAL INFORMATION. <br />ABBREVIATIONS: <br />AL: <br />AD: <br />CLR: <br />FF: <br />HM: <br />KD: <br />LL: <br />TEMP.GL.: <br />STL: <br /> <br />ALUMINUM <br />ANODIZED <br />CLEAR <br />FACTORY FINISH <br />HOLLOW METAL <br />KNOCK-DOWN FRAME <br />LEAD LINED <br />TEMPERED SAFETY GLASS <br />LIGHT STEEL <br />WINDOW SCHEDULE <br />WINDOW <br />NO.ROOM NAME <br />FRAME GLAZING <br />COMMENTSWIDTH HEIGHT TYPE MATERIAL FINISH <br />HEAD <br />DETAIL <br />JAMB <br />DETAIL <br />SILL <br />DETAIL <br />FIRE <br />RATING TYPE THK <br />1 IMAGING, GENERAL 3' - 0" 3' - 6" 1 HM PT-1 19/A6-01 18/A6-01 17/A6-01 NR LEADED 0' - 0 1/2" THIS WINDOW IS LEAD SHIELDED. REFER TO SHEET Q8-11 FOR ADDITIONAL REQUIREMENTS. <br />3" = 1'-0"LEAD LINED HM DOOR JAMB DETAIL 29 <br />3" = 1'-0"LEAD LINED HM DOOR HEAD DETAIL 27 <br />3" = 1'-0"TYPICAL DOOR JAMB - KNOCK DOWN 28 <br />CITY SUBMITTAL 04/19/2024 <br />BID SET 05/20/2024 <br />1900 E 4th St - <br />1011190678/9/2024