SECTION 095113 - ACOUSTICAL PANEL CEILINGS <br />PART 1 - GENERAL <br />1.1 RELATED DOCUMENTS <br />A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND <br />SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS, APPLY TO <br />THIS SECTION. <br />1.2 SUMMARY <br />A. SECTION INCLUDES ACOUSTICAL PANELS AND EXPOSED SUSPENSION SYSTEMS FOR <br />INTERIOR CEILINGS. <br />B. PRODUCTS FURNISHED, BUT NOT INSTALLED UNDER THIS SECTION, INCLUDE <br />ANCHORS, CLIPS, AND OTHER CEILING ATTACHMENT DEVICES TO BE CAST IN <br />CONCRETE. <br />1.3 ACTION SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />1.4 DELIVERY, STORAGE, AND HANDLING <br />A. DELIVER ACOUSTICAL PANELS, SUSPENSION-SYSTEM COMPONENTS, AND ACCESSORIES <br />TO PROJECT SITE AND STORE THEM IN A FULLY ENCLOSED, CONDITIONED SPACE WHERE <br />THEY WILL BE PROTECTED AGAINST DAMAGE FROM MOISTURE, HUMIDITY, <br />TEMPERATURE EXTREMES, DIRECT SUNLIGHT, SURFACE CONTAMINATION, AND OTHER <br />CAUSES. <br />B. BEFORE INSTALLING ACOUSTICAL PANELS, PERMIT THEM TO REACH ROOM <br />TEMPERATURE AND A STABILIZED MOISTURE CONTENT. <br />1.5 FIELD CONDITIONS <br />A. ENVIRONMENTAL LIMITATIONS: DO NOT INSTALL ACOUSTICAL PANEL CEILINGS UNTIL <br />SPACES ARE ENCLOSED AND WEATHERTIGHT, WET-WORK IN SPACES IS COMPLETE <br />AND DRY, WORK ABOVE CEILINGS IS COMPLETE, AND AMBIENT TEMPERATURE AND <br />HUMIDITY CONDITIONS ARE MAINTAINED AT THE LEVELS INDICATED FOR PROJECT WHEN <br />OCCUPIED FOR ITS INTENDED USE. <br />1. PRESSURIZED PLENUMS: OPERATE VENTILATION SYSTEM FOR NOT LESS THAN <br />48 HOURS BEFORE BEGINNING ACOUSTICAL PANEL CEILING INSTALLATION. <br />PART 2 - PRODUCTS <br />2.1 MANUFACTURERS <br />A. SOURCE LIMITATIONS: OBTAIN EACH TYPE OF ACOUSTICAL CEILING PANEL AND ITS <br />SUPPORTING SUSPENSION SYSTEM FROM SINGLE SOURCE FROM SINGLE <br />MANUFACTURER. <br />2.2 PERFORMANCE REQUIREMENTS <br />A. SURFACE-BURNING CHARACTERISTICS: COMPLY WITH ASTM E 84; TESTING BY A <br />QUALIFIED TESTING AGENCY. IDENTIFY PRODUCTS WITH APPROPRIATE MARKINGS OF <br />APPLICABLE TESTING AGENCY. <br />1. FLAME-SPREAD INDEX: CLASS B ACCORDING TO ASTM E 1264. <br />2. SMOKE-DEVELOPED INDEX: 450 OR LESS. <br />B. FIRE-RESISTANCE RATINGS: COMPLY WITH ASTM E 119; TESTING BY A QUALIFIED <br />TESTING AGENCY. IDENTIFY PRODUCTS WITH APPROPRIATE MARKINGS OF APPLICABLE <br />TESTING AGENCY. <br />1. INDICATE DESIGN DESIGNATIONS FROM UL OR FROM THE LISTINGS OF <br />ANOTHER QUALIFIED TESTING AGENCY. <br />2.3 ACOUSTICAL PANELS <br />A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS <br />BY ONE OF THE FOLLOWING: <br />1. ARMSTRONG WORLD INDUSTRIES, INC. <br />2. OR EQUAL <br />B. REFER TO FINISH SCHEDULE <br />2.4 METAL SUSPENSION SYSTEM <br />A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS <br />BY ONE OF THE FOLLOWING: <br />1. ARMSTRONG WORLD INDUSTRIES, INC. <br />2. OR EQUAL <br />B. METAL SUSPENSION-SYSTEM STANDARD: PROVIDE MANUFACTURER'S STANDARD, <br />DIRECT-HUNG, METAL SUSPENSION SYSTEM AND ACCESSORIES ACCORDING TO ASTM <br />C 635/C 635M AND DESIGNATED BY TYPE, STRUCTURAL CLASSIFICATION, AND FINISH <br />INDICATED. <br />C. WIDE-FACE, CAPPED, DOUBLE-WEB ALUMINUM SUSPENSION SYSTEM: MAIN AND CROSS <br />RUNNERS ROLL FORMED FROM ALUMINUM SHEET; PREPAINTED, WITH PREFINISHED <br />15/16-INCH- WIDE ALUMINUM CAPS ON FLANGES. <br />1. STRUCTURAL CLASSIFICATION: HEAVY-DUTY SYSTEM. <br />2. END CONDITION OF CROSS RUNNERS: BUTT-EDGE TYPE. <br />3. FACE DESIGN: FLAT, FLUSH. <br />4. CAP MATERIAL: ALUMINUM. <br />5. CAP FINISH: PAINTED WHITE. <br />2.5 ACCESSORIES <br />A. ATTACHMENT DEVICES: SIZE FOR FIVE TIMES THE DESIGN LOAD INDICATED IN ASTM C <br />635/C 635M, TABLE 1, "DIRECT HUNG," UNLESS OTHERWISE INDICATED. COMPLY WITH <br />SEISMIC DESIGN REQUIREMENTS. <br />B. WIRE HANGERS, BRACES, AND TIES: PROVIDE WIRES AS FOLLOWS: <br />1. STAINLESS-STEEL WIRE: ASTM A 580/A 580M, TYPE 304, NONMAGNETIC, AT <br />KITCHENS AND LAUNDRY. <br />2. SIZE: WIRE DIAMETER SUFFICIENT FOR ITS STRESS AT THREE TIMES <br />HANGER DESIGN LOAD (ASTM C 635/C 635M, TABLE 1, "DIRECT HUNG") WILL <br />BE LESS THAN YIELD STRESS OF WIRE, BUT NOT LESS THAN 0.135-INCH- <br />DIAMETER WIRE. <br />C. HANGER RODS: MILD STEEL, ZINC COATED OR PROTECTED WITH RUST-INHIBITIVE PAINT. <br />D. ANGLE HANGERS: ANGLES WITH LEGS NOT LESS THAN 7/8 INCH WIDE; FORMED WITH <br />0.04-INCH- THICK, GALVANIZED-STEEL SHEET COMPLYING WITH ASTM A 653/A 653M, <br />G90 COATING DESIGNATION; WITH BOLTED CONNECTIONS AND 5/16-INCH- DIAMETER <br />BOLTS. <br />2.6 METAL EDGE MOLDINGS AND TRIM <br />A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS <br />BY ONE OF THE FOLLOWING: <br />1. ARMSTRONG WORLD INDUSTRIES, INC. <br />2. OR EQUAL <br />B. ROLL-FORMED, SHEET-METAL EDGE MOLDINGS AND TRIM: TYPE AND PROFILE <br />INDICATED OR, IF NOT INDICATED, MANUFACTURER'S STANDARD MOLDINGS FOR EDGES <br />AND PENETRATIONS THAT COMPLY WITH SEISMIC DESIGN REQUIREMENTS; FORMED <br />FROM SHEET METAL OF SAME MATERIAL, FINISH, AND COLOR AS THAT USED FOR <br />EXPOSED FLANGES OF SUSPENSION-SYSTEM RUNNERS. <br />1. EDGE MOLDINGS SHALL FIT ACOUSTICAL PANEL EDGE DETAILS AND <br />SUSPENSION SYSTEMS INDICATED AND MATCH WIDTH AND CONFIGURATION OF <br />EXPOSED RUNNERS UNLESS OTHERWISE INDICATED. <br />2. FOR LAY-IN PANELS WITH REVEAL EDGE DETAILS, PROVIDE STEPPED EDGE <br />MOLDING THAT FORMS REVEAL OF SAME DEPTH AND WIDTH AS THAT FORMED <br />BETWEEN EDGE OF PANEL AND FLANGE AT EXPOSED SUSPENSION MEMBER. <br />3. FOR CIRCULAR PENETRATIONS OF CEILING, PROVIDE EDGE MOLDINGS <br />FABRICATED TO DIAMETER REQUIRED TO FIT PENETRATION EXACTLY. <br />PART 3 - EXECUTION <br />3.1 EXAMINATION <br />A. EXAMINE SUBSTRATES, AREAS, AND CONDITIONS, INCLUDING STRUCTURAL FRAMING TO <br />WHICH ACOUSTICAL PANEL CEILINGS ATTACH OR ABUT, WITH INSTALLER PRESENT, FOR <br />COMPLIANCE WITH REQUIREMENTS SPECIFIED IN THIS AND OTHER SECTIONS THAT <br />AFFECT CEILING INSTALLATION AND ANCHORAGE AND WITH REQUIREMENTS FOR <br />INSTALLATION TOLERANCES AND OTHER CONDITIONS AFFECTING PERFORMANCE OF <br />ACOUSTICAL PANEL CEILINGS. <br />B. EXAMINE ACOUSTICAL PANELS BEFORE INSTALLATION. REJECT ACOUSTICAL PANELS <br />THAT ARE WET, MOISTURE DAMAGED, OR MOLD DAMAGED. <br />C. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN <br />CORRECTED. <br />3.2 PREPARATION <br />A. MEASURE EACH CEILING AREA AND ESTABLISH LAYOUT OF ACOUSTICAL PANELS TO <br />BALANCE BORDER WIDTHS AT OPPOSITE EDGES OF EACH CEILING. AVOID USING <br />LESS-THAN-HALF-WIDTH PANELS AT BORDERS UNLESS OTHERWISE INDICATED, AND <br />COMPLY WITH LAYOUT SHOWN ON REFLECTED CEILING PLANS. <br />B. LAYOUT OPENINGS FOR PENETRATIONS CENTERED ON THE PENETRATING ITEMS. <br />3.3 INSTALLATION <br />A. INSTALL ACOUSTICAL PANEL CEILINGS ACCORDING TO ASTM C 636/C 636M, AND <br />MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />1. FIRE-RATED ASSEMBLY: INSTALL FIRE-RATED CEILING SYSTEMS ACCORDING <br />TO TESTED FIRE-RATED DESIGN. <br />B. SUSPEND CEILING HANGERS FROM BUILDING'S STRUCTURAL MEMBERS AND AS <br />FOLLOWS: <br />1. INSTALL HANGERS PLUMB AND FREE FROM CONTACT WITH INSULATION OR <br />OTHER OBJECTS WITHIN CEILING PLENUM THAT ARE NOT PART OF <br />SUPPORTING STRUCTURE OR OF CEILING SUSPENSION SYSTEM. <br />2. SPLAY HANGERS ONLY WHERE REQUIRED AND, IF PERMITTED WITH <br />FIRE-RESISTANCE-RATED CEILINGS,TO MISS OBSTRUCTIONS; OFFSET <br />RESULTING HORIZONTAL FORCES BY BRACING, COUNTERSPLAYING, OR <br />OTHER EQUALLY EFFECTIVE MEANS. <br />3. WHERE WIDTH OF DUCTS AND OTHER CONSTRUCTION WITHIN CEILING PLENUM <br />PRODUCES HANGER SPACINGS THAT INTERFERE WITH LOCATION OF HANGERS <br />AT SPACINGS REQUIRED TO SUPPORT STANDARD SUSPENSION-SYSTEM <br />MEMBERS, INSTALL SUPPLEMENTAL SUSPENSION MEMBERS AND HANGERS IN <br />FORM OF TRAPEZES OR EQUIVALENT DEVICES. <br />4. SECURE WIRE HANGERS TO CEILING-SUSPENSION MEMBERS AND TO <br />SUPPORTS ABOVE WITH A MINIMUM OF THREE TIGHT TURNS. CONNECT <br />HANGERS DIRECTLY TO STRUCTURE OR TO INSERTS, EYE SCREWS, OR OTHER <br />DEVICES THAT ARE SECURE AND APPROPRIATE FOR SUBSTRATE AND THAT <br />WILL NOT DETERIORATE OR OTHERWISE FAIL DUE TO AGE, CORROSION, OR <br />ELEVATED TEMPERATURES. <br />5. SECURE FLAT, ANGLE, CHANNEL, AND ROD HANGERS TO STRUCTURE, <br />INCLUDING INTERMEDIATE FRAMING MEMBERS, BY ATTACHING TO INSERTS, <br />EYE SCREWS, OR OTHER DEVICES THAT ARE SECURE AND APPROPRIATE FOR <br />BOTH THE STRUCTURE TO WHICH HANGERS ARE ATTACHED AND THE TYPE OF <br />HANGER INVOLVED. INSTALL HANGERS IN A MANNER THAT WILL NOT CAUSE <br />THEM TO DETERIORATE OR FAIL DUE TO AGE, CORROSION, OR ELEVATED <br />TEMPERATURES. <br />6. DO NOT SUPPORT CEILINGS DIRECTLY FROM PERMANENT METAL FORMS OR <br />FLOORDECK. FASTEN HANGERS TO CAST-IN-PLACE HANGER INSERTS, POST- <br />INSTALLED MECHANICAL OR ADHESIVE ANCHORS, OR POWER-ACTUATED <br />FASTENERS THATEXTENDTHROUGH FORMS INTO CONCRETE. <br />7. WHEN STEEL FRAMING DOES NOT PERMIT INSTALLATION OF HANGER WIRES <br />AT SPACING REQUIRED, INSTALL CARRYING CHANNELS OR OTHER <br />SUPPLEMENTAL SUPPORT FOR ATTACHMENT OF HANGER WIRES. <br />8. DO NOT ATTACH HANGERS TO STEEL DECK TABS. <br />9. DO NOT ATTACH HANGERS TO STEEL ROOF DECK. ATTACH HANGERS TO <br />STRUCTURALMEMBERS. <br />10. SPACE HANGERS NOT MORE THAN 48 INCHES O.C. ALONG EACH MEMBER <br />SUPPORTED DIRECTLY FROM HANGERS UNLESS OTHERWISE INDICATED; <br />PROVIDE HANGERS NOT MORE THAN 8 INCHES FROM ENDS OF EACH MEMBER. <br />11. SIZE SUPPLEMENTAL SUSPENSION MEMBERS AND HANGERS TO SUPPORT <br />CEILING LOADS WITHIN PERFORMANCE LIMITS ESTABLISHED BY REFERENCED <br />STANDARDS. <br />C. SECURE BRACING WIRES TO CEILING SUSPENSION MEMBERS AND TO SUPPORTS WITH A <br />MINIMUM OF FOUR TIGHT TURNS. SUSPEND BRACING FROM BUILDING'S STRUCTURAL <br />MEMBERS AS REQUIRED FOR HANGERS, WITHOUT ATTACHING TO PERMANENT METAL <br />FORMS, STEEL DECK, OR STEEL DECK TABS. FASTEN BRACING WIRES INTO CONCRETE <br />WITH CAST-IN-PLACE OR POSTINSTALLED ANCHORS. <br />D. INSTALL EDGE MOLDINGS AND TRIM OF TYPE INDICATED AT PERIMETER OF ACOUSTICAL <br />CEILING AREA AND WHERE NECESSARY TO CONCEAL EDGES OF ACOUSTICAL PANELS. <br />1. APPLY ACOUSTICAL SEALANT IN A CONTINUOUS RIBBON CONCEALED ON <br />BACK OF VERTICAL LEGS OF MOLDINGS BEFORE THEY ARE INSTALLED. <br />2. SCREW ATTACH MOLDINGS TO SUBSTRATE AT INTERVALS NOT MORE THAN <br />16 INCHES O.C. AND NOT MORE THAN 3 INCHES FROM ENDS. MITER CORNERS <br />ACCURATELY AND CONNECT SECURELY. <br />3. DO NOT USE EXPOSED FASTENERS, INCLUDING POP RIVETS, ON MOLDINGS <br />AND TRIM. <br />E. INSTALL SUSPENSION-SYSTEM RUNNERS SO THEY ARE SQUARE AND SECURELY <br />INTERLOCKED WITH ONE ANOTHER. REMOVE AND REPLACE DENTED, BENT, OR <br />KINKED MEMBERS. <br />F. INSTALL ACOUSTICAL PANELS WITH UNDAMAGED EDGES AND FIT ACCURATELY INTO <br />SUSPENSION-SYSTEM RUNNERS AND EDGE MOLDINGS. SCRIBE AND CUT PANELS AT <br />BORDERS AND PENETRATIONS TO PROVIDE PRECISE FIT. <br />1. ARRANGE DIRECTIONALLY PATTERNED ACOUSTICAL PANELS AS FOLLOWS: <br />A. INSTALL PANELS WITH PATTERN RUNNING IN ONE DIRECTION <br />PARALLEL TO SHORT AXIS OF SPACE. <br />2. FOR SQUARE-EDGED PANELS, INSTALL PANELS WITH EDGES FULLY HIDDEN <br />FROM VIEW BY FLANGES OF SUSPENSION-SYSTEM RUNNERS AND MOLDINGS. <br />3. FOR REVEAL-EDGED PANELS ON SUSPENSION-SYSTEM RUNNERS, INSTALL <br />PANELS WITH BOTTOM OF REVEAL IN FIRM CONTACT WITH TOP SURFACE OF <br />RUNNER FLANGES. <br />4. FOR REVEAL-EDGED PANELS ON SUSPENSION-SYSTEM MEMBERS WITH <br />BOX-SHAPED FLANGES, INSTALL PANELS WITH REVEAL SURFACES IN FIRM <br />CONTACT WITH SUSPENSION-SYSTEM SURFACES AND PANEL FACES FLUSH <br />WITH BOTTOM FACE OF RUNNERS. <br />5. PAINT CUT EDGES OF PANEL REMAINING EXPOSED AFTER INSTALLATION; <br />MATCH COLOR OF EXPOSED PANEL SURFACES USING COATING <br />RECOMMENDED IN WRITING FOR THIS PURPOSE BY ACOUSTICAL PANEL <br />MANUFACTURER. <br />6. INSTALL HOLD-DOWN AND IMPACT CLIPS IN AREAS INDICATED; SPACE <br />ACCORDING TO PANEL MANUFACTURER'S WRITTEN INSTRUCTIONS UNLESS <br />OTHERWISE INDICATED. <br />A. HOLD-DOWN CLIPS: SPACE 24 INCHES O.C. ON ALL CROSS RUNNERS. <br />7. PROTECT LIGHTING FIXTURES AND AIR DUCTS ACCORDING TO REQUIREMENTS <br />INDICATED FOR FIRE-RESISTANCE-RATED ASSEMBLY. <br />3.4 ERECTION TOLERANCES <br />A. SUSPENDED CEILINGS: INSTALL MAIN AND CROSS RUNNERS LEVEL TO A TOLERANCE OF <br />1/8 INCH IN 12 FEET, NON-CUMULATIVE. <br />B. MOLDINGS AND TRIM: INSTALL MOLDINGS AND TRIM TO SUBSTRATE AND LEVEL WITH <br />CEILING SUSPENSION SYSTEM TO A TOLERANCE OF 1/8 INCH IN 12 FEET, NON- <br />CUMULATIVE. <br />3.5 FIELD QUALITY CONTROL <br />A. SPECIAL INSPECTIONS: OWNER WILL ENGAGE A QUALIFIED SPECIAL INSPECTOR TO <br />PERFORM THE FOLLOWING SPECIAL INSPECTIONS: <br />1. PERIODIC INSPECTION DURING THE INSTALLATION OF SUSPENDED CEILING <br />GRIDS ACCORDING TO ASCE/SEI 7. <br />B. TESTING AGENCY: OWNER WILL ENGAGE A QUALIFIED TESTING AGENCY TO PERFORM <br />TESTS AND INSPECTIONS. <br />C. PERFORM THE FOLLOWING TESTS AND INSPECTIONS OF COMPLETED INSTALLATIONS <br />OF ACOUSTICAL PANEL CEILING HANGERS AND ANCHORS AND FASTENERS IN <br />SUCCESSIVE STAGES AND WHEN INSTALLATION OF CEILING SUSPENSION SYSTEMS ON <br />EACH FLOOR HAS REACHED 20 PERCENT COMPLETION, BUT NO PANELS HAVE BEEN <br />INSTALLED. DO NOT PROCEED WITH INSTALLATIONS OF ACOUSTICAL PANEL CEILING <br />HANGERS FOR THE NEXT AREA UNTIL TEST RESULTS FOR PREVIOUSLY COMPLETED <br />INSTALLATIONS OF ACOUSTICAL PANEL CEILING HANGERS SHOW COMPLIANCE WITH <br />REQUIREMENTS. <br />1. WITHIN EACH TEST AREA, TESTING AGENCY WILL SELECT ONE OF EVERY 10 <br />POWER-ACTUATED FASTENERS AND POSTINSTALLED ANCHORS USED TO <br />ATTACH HANGERS TO CONCRETE AND WILL TEST THEM FOR 200 LBF OF <br />TENSION; IT WILL ALSO SELECT ONE OF EVERY TWO POSTINSTALLED ANCHORS <br />USED TO ATTACH BRACING WIRES TO CONCRETE AND WILL TEST THEM FOR <br />440 LBF OF TENSION. <br />2. WHEN TESTING DISCOVERS FASTENERS AND ANCHORS THAT DO NOT COMPLY <br />WITH REQUIREMENTS, TESTING AGENCY WILL TEST THOSE ANCHORS NOT <br />PREVIOUSLY TESTED UNTIL 20 PASS CONSECUTIVELY AND THEN WILL RESUME <br />INITIAL TESTING FREQUENCY. <br />D. PREPARE TEST AND INSPECTION REPORTS. <br />3.6 CLEANING <br />A. CLEAN EXPOSED SURFACES OF ACOUSTICAL PANEL CEILINGS, INCLUDING TRIM, EDGE <br />MOLDINGS, AND SUSPENSION-SYSTEM MEMBERS. COMPLY WITH MANUFACTURER'S <br />WRITTEN INSTRUCTIONS FOR CLEANING AND TOUCHUP OF MINOR FINISH DAMAGE. <br />B. REMOVE AND REPLACE CEILING COMPONENTS THAT CANNOT BE SUCCESSFULLY <br />CLEANED AND REPAIRED TO PERMANENTLY ELIMINATE EVIDENCE OF DAMAGE. <br />SECTION 09 6500 - RESILIENT FLOORING <br />PART 1 - GENERAL <br />1.1 ACTION SUBMITTALS: <br />A. PRODUCT DATA: INDICATE PRODUCT CHARACTERISTICS AND INSTALLATION <br />REQUIREMENTS, INCLUDING MANUFACTURER'S RECOMMENDED ADHESIVES AND <br />MAINTENANCE INSTRUCTIONS. <br />B. SAMPLES: SUBMIT FULL SIZE SAMPLES FOR EACH TYPE COLOR AND PATTERN OF <br />FLORRING AND ACCESSORY REQUIRED. <br />1.2 QUALITY ASSURANCE: <br />A. APPLICABLE STANDARDS, AS REFERENCED HEREIN: ASTM INTERNATIONAL (ASTM). <br />1.3 PROJECT/SITE CONDITIONS: <br />A. ENVIRONMENTAL REQUIREMENTS: <br />1. MAINTAIN TEMPERATURE IN SPACE TO RECEIVE RESILIENT MATERIALS AT NOT <br />LESS THAN 70 DEGREES F. FOR NOT LESS THAN 24 HOURS BEFORE, DURING <br />AND FOR 48 HOURS AFTER INSTALLATION. <br />2. MAINTAIN MINIMUM TEMPERATURE OF 55 DEGREES F. AFTER FLOORING IS <br />INSTALLED, EXCEPT AS SPECIFIED ABOVE, FOR DURATION OF PROJECT. <br />B. DELIVER VINYL FLOORING AND BASE PRODUCTS TO JOBSITE A MINIMUM OF 24 HOURS <br />PRIOR TO USE. UNROLL VINYL BASE AND LOW PERCENTAGE RUBBER AND ALLOW TO <br />RELAX FOR 24 HOURS PRIOR TO USING. <br />C. PROTECTION: PROTECT FINISHED FLOORING, BASE AND ACCESSORIES FROM <br />STAINING, MARRING OR OTHER PHYSICAL DAMAGE BY WORK OF OTHER TRADES. <br />COVER OR MASK SURFACES AS REQUIRED. <br />PART 2 - PRODUCTS <br />2.1 RUBBER BASE: <br />A. ACCEPTABLE MANUFACTURERS: <br />1. BASIS OF DESIGN; JOHNSONITE, INC. <br />2. ROPPE CORP. <br />3. BURKE FLOORING, A DIV. OF BURKE INDUSTRIES <br />B. CHARACTERISTICS: <br />1. TYPE: MINIMUM 48% RUBBER, 100% VULCANIZED; MEETING ASTM <br />F1861-08(2012), TYPE TS THERMOSET VULCANIZED RUBBER SBR. <br />2. LENGTH: MINIMUM 120'-0" ROLLS. <br />3. THICKNESS: 1/8". <br />4. HEIGHT: 4"; TOP SET COVE BASE. <br />5. STYLE AND COLOR: AS INDICATED IN FINISH SCHEDULE IN DRAWINGS. <br />2.2 SHEET FLOORING WITH BACKING: <br />A. ACCEPTABLE MANUFACTURERS: <br />1. NORA SYSTEMS. <br />2. ARMSTRONG WORLD INDUSTRIES, INC. <br />3. SHAW CONTRACT. <br />4. TARKETT. <br />B. TYPE: MEETING ASTM F1303-04(2009). <br />1. TYPE: HETEROGENEOUS, TYPE I, GRADE 1 <br />2. WEAR-LAYER THICKNESS: 0.022 IN. <br />3. OVERALL THICKNESS: 0.080 IN. <br />4. BACKING CLASS: CLASS A. <br />5. FINISH: UV-CURED POLYURETHANE. <br />6. SIZE: 6 FT. X 82 FT. <br />7. COLORS AND PATTERNS: AS INDICATED IN FINISH SCHEDULE IN DRAWINGS. <br />C. FIRE RESISTANCE: CRITICAL RADIENT FLUX MEETING CLASS I, 0.45 WATTS/CM^2 WHEN <br />TESTED IN ACCORD WITH ASTM E648-10. SMOKE DEVELOPMENT OF 450 OR LESS WHEN <br />TESTED IN ACCORD WITH ASTM E662-12. <br />2.3 ACCESSORIES: <br />A. ACCEPTABLE MANUFACTURERS: <br />1. BURKE FLOORING PRODUCTS, A DIV. OF BURKE INDUSTRIES. <br />2. MARLEY FLEXCO (USA), INC. <br />3. JOHNSONITE, INC. <br />4. R. C. MUSSON RUBBER CO. <br />5. ROPPE CORP. <br />B. REDUCERS: <br />1. MATERIAL: RUBBER <br />2. THICKNESS: SAME AS ABUTTING FLOOR MATERIALS. <br />3. WIDTH(S): 1", UNLESS INDICARTED OTHERWISE. <br />4. EDGES: TAPERED. <br />5. COLORS: SUBMIT SAMPLE FOR ARCHITECT'S APPROVAL <br />2.4 INSTALLATION MATERIALS: <br />A. LEVELING COMPOUND: ACCEPTABLE PRODUCTS: AS SPECIFIED IN SECTION 03 8215. <br />B. ADHESIVES: WATER-RESISTANT TYPES AND BRANDS OF ADHESIVE RECOMMENDED BY <br />FLOORING MATERIAL MANUFACTURER'S PRODUCT DATA FOR INSTALLATION <br />CONDITIONS INDICATED. <br />1. VOC CONTENT: ADHESIVES SHALL HAVE A VOC CONTENT LESS THAN THE <br />CURRENT VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY MANAGEMENT <br />DISTRICT (SCAQMD) RULE #1113, ARCHITECTURAL COATINGS, RULES IN <br />EFFECT JANUARY 1, 2004. <br />C. CHEMICAL-BONDING COMPOUND: MANUFACTURER'S PRODUCT FOR CHEMICALLY <br />BONDING SEAMS. <br />1. VOC CONTENT: VOC CONTENT LESS THAN THE CURRENT VOC CONTENT LIMITS <br />OF SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD) RULE #1113, <br />ARCHITECTURAL COATINGS, RULES IN EFFECT JANUARY 1, 2004. <br />PART 3 - EXECUTION <br />3.1 PREPARATION: <br />A. PREPARE SURFACES TO RECEIVE RESILIENT MATERIAL IN ACCORD WITH FLOORING <br />MANUFACTURER'S INSTRUCTIONS. <br />B. GRIND HIGH AREAS AND FILL DEPRESSIONS WITH LEVELING COMPOUND WHERE <br />REQUIRED TO PRODUCE SMOOTH INSTALLATION AND FOR PROPER ALIGNMENT OF <br />RESILIENT FLOORING WITH ADJACENT FLOORING MATERIALS. <br />C. PERFORM BOND AND MOISTURE TESTS ON SUBFLOORS IN ACCORD WITH ASTM F2170-11 <br />AND RESILIENT FLOORING MANUFACTURER'S PRODUCT DATA, TO DETERMINE IF <br />SURFACES ARE ACCEPTABLE TO RECEIVE SPECIFIED RESILIENT FLOORING PRODUCTS. <br />CORRECT CONDITIONS DETRIMENTAL TO RESILIENT FLOORING INSTALLATION PRIOR <br />TO STARTING INSTALLATION. <br />D. REMOVE DIRT, OIL, GREASE OR OTHER FOREIGN MATTER FROM SURFACES TO RECEIVE <br />FLOOR COVERING OR ACCESSORIES. <br />3.2 APPLICATION OF ADHESIVES: <br />A. MIX AND APPLY ADHESIVES IN ACCORD WITH RESILIENT MATERIAL MANUFACTURER'S <br />PRODUCT DATA. APPLY WITH NOTCHED TROWEL OR OTHER TOOLS AS RECOMMENDED <br />BY ADHESIVE MANUFACTURER. <br />2.7 JOINT MATERIALS AND ADHESIVES: <br />A. STANDARD GYPSUM BOARD PRODUCTS: <br />1. JOINT TAPE: MEETING ASTM C475-12, PERFORATED PAPER TYPE. <br />2. JOINT COMPOUND: MEETING ASTM C475-12, READY-MIXED TAPE EMBEDMENT <br />AND TOPPING COMPOUNDS, VINYL-BASED. <br />B. MOLD AND MOISTURE RESISTANT PAPER FACED GYPSUM BOARD: JOINT TAPE AND <br />JOINT COMPOUND SHALL BE IN ACCORD WITH RECOMMENDATIONS OF BOARD <br />MANUFACTURER'S PRODUCT DATA. <br />C. JOINT TAPE FOR GLASS MAT-FACED BOARD: FIBERGLASS TAPE, AS HEREIN SPECIFIED. <br />2.8 ACCESSORIES: <br />A. ACCESSORIES SHALL COMPLY WITH ASTM C1047-10A <br />B. CORNER REINFORCEMENT: VINYL CORP., "RIGID VINYL DRYWALL & VENEER <br />ACCESSORIES, MODEL CBD125 CORNER BEADS"; LEAD-FREE, VIRGIN VINYL COMPOUNDS <br />CORNER BEADS WITH 1-1/4" X 1-1/4" PERFORATED FLANGES. <br />C. METAL JAMB, CEILING AND CASING TRIM: MANUFACTURER'S STANDARD "L" AND "U" <br />SHAPED GALVANIZED MEMBERS WITH FINE EXPANDED MESH FLANGES; "MUD-IN" TYPE <br />FOR FINISHING WITH JOINT COMPOUNDS. <br />D. TIE WIRE: MINIMUM 18 GA. GALVANIZED, ANNEALED STEEL WIRE. <br />E. SPECIAL TRIM SHAPES: <br />1. ACCEPTABLE MANUFACTURERS; SUBJECT TO COMPLIANCE WITH SPECIFIED <br />REQUIREMENTS: <br />A. FRY REGLET CORP. <br />B. GORDON, INC. <br />C. PITTCON INDUSTRIES, INC. <br />2. CHARACTERISTICS: <br />A. MATERIAL: MANUFACTURER'S STANDARD ALUMINUM ALLOW. <br />B. FINISH: PAINTED FINISH, COLOR SELECTED BY ARCHITECT. <br />C. SHAPES: AS INDICATED ON DRAWINGS. <br />PART 3 - EXECUTION <br />3.1 FRAMING AND FURRING INSTALLATION: <br />A. EXCEPT WHERE STRINGENT REQUIREMENTS ARE SPECIFIED, INSTALL FRAMING AND <br />FURRING IN ACCORD WITH ASTM C754-11, GYPSUM ASSOCIATION REQUIREMENTS AND <br />MANUFACTURER'S PRODUCT DATA. <br />B. RUNNERS: <br />1. ATTACH RUNNER TRACKS AT FLOOR AND UNDERSIDE OF STRUCTURAL DECK <br />WITH SPECIFIED FASTENERS. PROVIDE SLIP JOINT ATTACHMENTS TO MEET <br />DEFLECTION CRITERIA AND MANUFACTURER'S CALCULATIONS AT THE <br />FOLLOWING LOCATIONS: <br />A. TALL PARTITIONS. <br />B. FULL-HEIGHT, FLOOR-TO-FLOOR OR FLOOR-TO-DECK PARTITIONS. <br />C. ALL PARTITIONS SUBJECT TO DEFLECTION. <br />2. WHERE PARTITIONS ARE INDICATED TO STOP AT FINISH CEILING, ATTACH TO <br />CEILING SUSPENSION SYSTEM USING 1/8" TOGGLE BOLTS OR SHEET METAL <br />SCREWS SPACED AT 1'-4" O.C., MAXIMUM, WHERE PARTITION ALIGNS WITH <br />CEILING GRID. WHERE PARTITION DOES NOT ALIGN WITH GRID, ATTACH AT <br />EACH INTERSECTION WITH GRID. <br />C. STUDS: <br />1. POSITION FULL LENGTH STUDS VERTICALLY, ENGAGING FLOOR AND CEILING <br />RUNNERS. <br />A. SPACE STUDS AS INDICATED ON DRAWINGS. <br />B. SPACE STUDS NOT TO EXXCEED 1'-4" O.C. FOR PARTITIONS TO FRP <br />PANELS. <br />2. PROVIDE JUMBO STUDS AT INTERIOR AND EXTERIOR CORNERS, PARTITION <br />TERMINATION AND ADJACENT TO DOOR AND BORROWED LITE OPENINGS IN <br />PARTITIONS. <br />3. SECURE ABUTTING AND INTERSECTING WALLS WITH FASTENERS THROUGH <br />STUD FLANGES. <br />4. FOR HORIZONTAL REINFORCEMENT AT DOOR AND BORROWED LITE FRAMES, <br />INSTALL CUT-TO-LENTH RUNNER SECTIONS WITH SLIT FLANGES SECURED TO <br />STUDS. <br />5. INSTALL ACOUSTICAL TAPE ON METAL STUDS WHICH ABUT OTHER STUDS OR <br />DISSIMILAR SURFACES IN WALLS TO RECEIVE SOUND ATTENUATION BLANKETS. <br />D. AT LOCATIONS OF ATTACHMENTS TO METAL-FRAMED GYPSUM BOARD PARTITIONS, <br />PROVIDE MINIMUM 16GA. STEEL PLATE FOR ATTACHMENT. ATTACH TO METAL FRAMING <br />AS INDIACTED ON DRAWINGS. <br />3.2 GENERAL BOARD APPLICATION: <br />A. EXCEPT WHERE MORE STRINGENT REQUIREMENT ARE SPECIFIED, INSTALL GYPSUM <br />BOARD IN ACCORD WITH ASTM C840-11, GA-216 AND MANUFACTURER'S PRODUCT DATA. <br />B. INSTALL CEILING PANELS ACROSS FRAMING TO MINIMIZE THE NUMBER OF ABUTTING END <br />JOINTS AND TO AVOID ABUTTING END JOINTS IN CENTRAL AREA OF EACH CEILING. <br />STAGGER ABUTTING END JOINTS OF ADJACENT PANELS NOT LESS THAN ONE FRAMING <br />MEMBER. <br />C. USE GYPSUM BOARD OF MAXIMUM LENGTHS TO MINIMIZE END JOINTS. STAGGER END <br />JOINTS. <br />D. ABUT GYPSUM BOARDS WITHOUT FORCING. FIT ENDS AND EDGES OF BOARD. DO NOT <br />PLACE BUTT ENDS AGAINST TAPERED EDGES. <br />E. SUPPORT ENDS AND EDGES OF GYPSUM BOARD PANELS ON FRAMING OR FURRING <br />MEMBERS, EXCEPT FOR FACE LAYER OF DOUBLE LAYER WORK. <br />F. INSTALL GYPSUM BOARD ACCESSORIES IN ACCORD WITH GYPSUM BOARD <br />MANUFACTURER'S PRODUCT DATA AND AS FOLLOWS: <br />1. CORNER BEAD: INSTALL VINYL CORNER BEADS AT EXTERNAL CORNERS. <br />2. METAL TRIM SHAPES: AT EXPOSED EDGE OF GYPSUM BOARD AT DOOR AND <br />WINDOW OPENINGS, AT INTERSECTIONS WITH OTHER MATERIALS AND AT <br />INTERSECTION OF WALLS WITH CEILINGS. <br />3. INSTALL CORNER BEADS AND METAL TRIM SHAPES TO FRAMING SYSTEM WITH <br />MECHANICAL ANCHORS. <br />G. INSTALL ACOUSTICAL SEALANT AT SOUND-RATED PARTITIONS: <br />1. SEAL PARTITION PERIMETER WITH CONTINUOUS 1/4" MINIMUM ROUND BEAD OF <br />ACOUSTICAL SEALANT APPLIED TO EACH LEG OF RUNNERS, INCLUDING THOSE <br />USED AT PARTITION INTERSECTIONS WITH DISSIMILAR WALL CONSTRUCTION. <br />2. INSTALL GYPSUM BOARD WITH 1/8" PERIMETER RELIEF COMPRESSING SEALANT <br />TO FORM PERMANENT AIRTIGHT SEAL. <br />3. WHERE SLIP JOINT ATTACHMENTS ARE REQUIRED AT TOP OF PARTITIONS, FILL <br />RESULTING JOINT BETWEEN DRYWALL AND ADJACENT STRUCTURE WITH <br />ACOUSTICAL SEALANT TO FORM PERMANENT AIR TIGHT SEAL. <br />4. APPLY ACOUSTICAL SEALANT AROUND CUTOUTS SUCH AS AT ELECTRICAL <br />BOXES, PLUMBING PENETRATIONS, MEDICINE CABINETS, HEATING DUCTS AND <br />COLD AIR RETURNS TO FORM PERMANENT AIRTIGHT SEAL. (SEALANT SHALL <br />NOT BE USED AS A FIRE STOPPING MATERIAL.) <br />H. INSTALL MOLD-MOISTURE RESISTANT GYPSUM BOARD IN DAMP, MOIST LOCATIONS. <br />I. CONTINUE REQUIRED COMPONENTS OF FIRE-RATED AND ACOUSTICALLY RATED WALL <br />ASSEMBLY TO OVERHEAD STRUCTURE. APPLY JOINT TAPE AND ONE COAT OF <br />COMPOUND TO GYPSUM BOARD JOINTS CONCEALED FROM VIEW IN COMPLETED WORK. <br />J. IDENTIFICATION: <br />1. FIRE, WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE <br />PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS <br />SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR <br />STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY HAVING <br />JURISDICTION. <br />2. SUCH IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING AND IN <br />CONCEALED SPACES. <br />3. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "_____ HOUR FIRE AND <br />SMOKE BARRIER - PROTECT ALL OPENINGS." <br />K. ALLOWABLE TOLERANCES IN FRAMED GYPSUM BOARD CONSTRUTION. <br />1. POSITION: + - 1/4" MAXIMUM VARIATION FROM DESIGN POSITIOIN. <br />2. ALIGNMENT: 1/8" IN 8'-0"; 1/4" MAXIMUM IN ANY CONTINOUS WALL, LINE OR <br />SURFACE. <br />3. SURFACE PLANE: 1/8" IN 12-0"; 1/16" IN 1'-0", MAXIMUM VARIATION IN TRUE <br />SURFACE <br />PLANE. <br />4. SURFACE SMOOTHNESS: NO JOINT OR FASTENER LOCATION, ROUGHNESS OR <br />BLEMISH DISCERNIBLE AFTER APPLICATION OF FINISH WHEN VIEWED AT ANY <br />ANGLE FROM A DISTANCE OF 5'-0" UNDER OCCUPANCY LIGHTING CONDITIONS, <br />WITH SURFACE PREPARATION AS SPECIFIED IN PAINTING AND COATING <br />SECTION. <br />L. ALLOWABLE TOLERANCES IN SUSPENDED GYPSUM BOARD FURRING SYSTEM CEILINGS: <br />1. DEFLECTION: SUSPENSION SYSTEM COMPONENTS, HANGERS AND FASTENING <br />DEVICES SUPPORTING LIGHTING FIXTURES, CEILING GRILLES AND ACOUSTICAL <br />UNITS SHALL HAVE MAXIMUM DEFLECTION OF 1/360 OF SPAN WHEN TESTED IN <br />ACCORD WITH ASTM C635-07. <br />2. BOW, CAMBER AND TWIST: NOT EXCEEDING TOLERANCES ESTABLISHED BY <br />ASTM C635-07. <br />3. VARIATION FROM LEVEL IN FINISHED CEILING: 1/8" IN 12'-0". <br />4. VARIATION IN PLANE OF ADJACENT GYPSUM BOARD PANELS PRIOR TO JOINT <br />TREATMENT: 1/16". <br />3.3 SINGLE LAYER APPLICATION: <br />A. CEILING: APPLY GYPSUM BOARD WITH LONG DIMENSION AT RIGHT ANGLES TO FRAMING. <br />TERMINATE EDGES OF GYPSUM BOARD RUNNING PARALLEL TO FRAMING ON FRAMING <br />MEMBERS. <br />B. WALLS: <br />1. APPLY GYPSUM BOARD VERTICALLY AND HORIZONTALLY AT CONTRACTOR'S <br />OPTION, EXCEPT AS REQUIRED BY GYPSUM BOARD MANUFACTURER'S <br />PRODUCT DATA FOR SYSTEM DESIGNS, INCLUDING FIRE-RATED AND <br />ACOUSTICALLY-RATED <br />PARTITIONS. <br />2. STAGGER END JOINTS IN OPPOSITE SIDES OF PARTITIONS. <br />3. TERMINATE EDGES OF GYPSUM BOARD RUNNING PARALLEL TO FRAMING, <br />FURRING ON FRAMING OR FURRING MEMBERS. <br />C. FASTENING: ATTACH GYPSUM BOARD USING FASTENERS SPECIFIED AT SPACING <br />REQUIRED BY MANUFACTURER'S PRODUCT DATA. <br />3.4 JOINT TREATMENT: <br />A. FINISH LEVELS SHALL BE IN ACCORD WITH THE "RECOMMENDED SPECIFICATON: LEVELS <br />OF GYPSUM BOARD FINISH" AS PUBLISHED JOINTLY BY THE GYPSUM ASSOCIATION, <br />AWCI, CISCA, AND PDCA. <br />B. FINISH LEVEL 1; JOINT TREATMENT FOR NON-PUBLIC, NON-SERVICE AREAS TO RECEIVE <br />NO FURTHER FINISH, INCLUDING STORAGE AREAS: APPLY JOINT COMPOUND TO JOINTS <br />AND ANGLES IN GYPSUM BOARD AND EMBED JOINT TAPE. SURFACE SHALL BE FREE OF <br />EXCESS JOINT COMPOUND; TOOL MARKS AND RIDGES ARE ACCEPTABLE. <br />C. FINISH LEVEL 2; JOINT TREATMENT FOR AREAS INDICATED TO RECEIVE NO FURTHER <br />FINISH; APPLY JOINT COMPOUND TO JOINTS, ANGLES, FASTENER HEADS AND <br />ACCESSORIES. EMBED JOINT TAPE. APPLY ONE ADDITIONAL COAT OR COMPOUND OVER <br />TAPE. APPLY ONE COAT OF COMPOUND TO FASTENER DEPRESSIONS. SURFACES SHALL <br />BE FREE OF EXCESS JOINT COMPOUND; TOOL MARKS AND RIDGES ARE ACCEPTABLE. <br />D. FINISH LEVEL 4; JOINT TREATMENT FOR AREAS INDICATED TO RECEIVE SEMI-GLOSS AND <br />EGGSHELL PAINT FINISHES: <br />1. APPLY JOINT COMPOUND TO JOINTS, ANGLES, FASTENER HEADS AND <br />ACCESSORIES. EMBED JOINT TAPE. APPLY THREE ADDITIONAL COATS OF <br />COMPOUND OVER TAPE, FEATHEREDGING AND SANDING EACH COAT. <br />2. APPLY MINIMUM OF THREE COATS OF COMPOUND TO FASTENER DEPRESSIONS, <br />SANDING EACH COAT AND BRINGING TO LEVEL PLANE WITH GYPSUM BOARD <br />SURFACE. <br />3. ALL JOINT COMPOUND SHALL BE FREE OF TOOL MARKS AND RIDGES. <br />E. FASTENER POP: DRIVE NEW FASTENER APPROXIMATELY 1-1/2" FROM POPPED FASTENER <br />AND REPAIR TO MATCH GYPSUM BOARD FINISH. <br />F. FILL CRACKS WITH JOINT COMPOUND AND SAND SMOOTH AND FLUSH. <br />G. DUST SURFACES AND LEAVE READY FOR DECORATION. JOINT AND FASTENER <br />TREATMENT SHALL BE INDISTINGUISHABLE IN FINISHED WORK. <br />END OF SECTION <br />B. PROVIDE SAFETY PRECAUTIONS DURING MIXING AND APPLICATIONS AS RECOMMENDED <br />BY ADHESIVE MANUFACTURER. <br />C. APPLY ADHESIVE TO ONLY THAT AREA WHICH CAN BE COVERED BY RESILIENT <br />MATERIAL WITHIN THE RECOMMENDED WORKING TIME OF THE ADHESIVE. <br />1. REMOVE ADHESIVE WHICH DRIES OR FILMS OVER. <br />2. DO NOT SOIL WALLS, BASES OR ADJACENT AREAS WITH ADHESIVES. <br />3. REMOVE SPILLED OR MISPLACED MATERIALS. <br />3.3 INSTALLATION OF VINYL SHEET FLOORING: <br />A. WORKMANSHIP: <br />1. INSTALL SHEET MATERIAL IN ACCORD WITH RFCI SPECIFICATIONS IS-1 AND <br />WITH FLOORING MANUFACTURER'S PRODUCT DATA. <br />2. CUT SHEET MATERIAL IN LENGTHS AND SIZES REQUIRED; COMPLY WITH <br />MANUFACTURER'S CUTTIG AND FITTING INSTRUCTIONS. <br />3. LAY CUT SHEETS FLAT AND ALLOW TO ACCLIMATIZE TO ROOM TEMPERATURE <br />PRIOR TO SECURING IN PLACE. <br />B. APPLY FULL BED OF ADHESIVE UNIFORMLY OVER EXPOSED SUBFLOOR. TURN SHEET <br />BACK INTO WET ADHESIVE. <br />C. WORK OUT WRINKLES AND AIR POCKETS. ROLL MATERIAL IN TWO DIRECTIONS <br />STARTING AT CENTER OF SHEET. <br />3.4 INSTALLATION OF BASE: <br />A. WORKMANSHIP: <br />1. UNROLL BASE MATERIAL AND ALLOW TO RELAX FOR 24 HOURS, MINIMUM, <br />PRIOR TO INSTALLATION. CUT INTO LENGTHS FOR MINIMUM NUMBER OF <br />JOINTS. DOUBLE-CUT ADJOINING LENGTHS. <br />2. INSTALL WITH TIGHT BUTT JOINTS WITH NO JOINT WIDTHS GREATER THAN <br />1/64". <br />B. TOP-SER BASE: <br />1. APPLY ADHESIVE AND ADHERE TO VERTICAL SURFACES. <br />2. PRESS DOWN SO THAT BOTTOM EDGE FOLLOWS FLOOR PROFILE. <br />3. FORM INTERNAL CORNERS USING PREMOLDED CORNERS. <br />4. FORM EXTERNAL CORNERS USING PREMOLDED CORNERS. <br />5. SCRIBE BASE TO ABUTTING MATERIALS. <br />3.5 ACCESSORY INSTALLATION: <br />A. CUT MATERIALS TO LENGTHS AND SIZES INDICATED. <br />B. RESILIENT REDUCERS: <br />1. APPLY ADHESIVES AND BOND TO SUBSTRATE. <br />2. CENTER AND REDUCERS IN DOOR OPENINGS. <br />3. FIT EDGE TO DOOR FRAME JAMBS WITHOUT VISIBLE GAPS OR CRACKS. <br />4. FIT EDGES TO ABUTTING FLOOR MATERIALS FOR FLUSH FIT. <br />3.6 CLEANING: <br />A. UPON COMPLETION OF INSTALLATION, CLEAN SURFACES USING A NEUTRAL CLEANER <br />ACCEPTABLE TO MATERIAL MANUFACTURER. <br />B. JUST PRIOR TO DATE OF SUBSTANTIAL COMPLETION, BUFF NO-WAX FLOORS USING <br />BUFFING COMPOUND FOR NO-WAX FINISH. FOR INDICATED FLOORING TYPES, APPLY <br />TWO COATS OF NON-SLIP WAX TO CLEAN WAXABLE FLOOR SURFACES AND BUFF. <br />3.7 MAINTENANCE MATERIAL: <br />A. SALVAGE SCRAPS FROM INSTALLATION OF SHEET FLOORING GOODS OVER THREE SQ. <br />FT. IN AREA AND OVER 1'-0" IN WIDTH FOR OWNER'S USE. <br />END OF SECTION <br />SECTION 09 9000 - PAINTING AND COATING <br />PART 1 - GENERAL <br />1.1 SUMMARY: <br />A. WORK OF THIS SECTION INCLUDES: <br />1. TOUCHING UP OF SHOP-APPLIED PRIME COATS. <br />2. PREPARATION OF SURFACES TO RECEIVE FINISHES. <br />3. PAINTING, OR OTHERWISE FINISHING OF SURFACES, EXCEPT AS OTHERWISE <br />INDICATED. <br />B. RELATED WORK SPECIFIED ELSEWHERE: <br />1. SHOP-APPLIED PRIMER COATS. <br />2. JOINT SEALANTS. <br />3. PIPING IDENTIFICATON. <br />4. PREFINISHED ITEMS. <br />1.2 DEFINITIONS: <br />A. STANDARD COATING TERMS: AS DEFINED IN ASTM D16-12. <br />B. COMMERCIAL: PAINTER GRADE PRODUCTS. <br />C. DFT: DRY FILM THICKNESS OF THE COATING. <br />D. PREMIUM: BEST QUALITY PRODUCT (TOP OF THE LINE): <br />E. VOC: VOLATILE ORGANIC COMPOUNDS FOUND IN PRIMERS, PAINTS, SEALERS AND <br />STAINS. VOC LEVELS ARE DESIGNATED IN GRAMS PER LITER (g/L). <br />1.3 PERFORMANCE REQUIREMENTS: <br />A. DFT FOR EACH PRIMER, PAINT, SEALER AND STAIN SHALL BE AS RECOMMENDED BY <br />PRODUCT MANUFACTURER'S PRODUCT DATA. <br />B. VOC CONTENT: PAINTS, PRIMERS, AND SEALERS SHALL HAVE A VOC CONTENT LESS <br />THAN THE CURRENT VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY <br />MANAGEMENT DISTRICT (SCAQMD) RULE #1113, ARCHITECTURAL COATINGS, RULES IN <br />EFFECT JANUARY 1, 2004. <br />1.4 ACTION SUBMITTALS: <br />A. PRODUCT DATA: <br />1. SUBMIT COMPLETE LIST OF PRODUCTS PROPOSED FOR USE AT LEAST 30 DAYS <br />PRIOR TO COMMENCEMENT OF PAINTING WORK. <br />2. INDICATE MANUFACTURER, BRAND NAME, QUALITY, TYPE, AND SHEEN FOR <br />EACH TYPE OF PAINT AND FOR EACH SURFACE TO BE FINISHED. INDICATE VOC <br />RATING AND COMPLIANCE WITH APPLICABLE REGULATIONS. <br />3. INDICATE MANUFACTURER'S INSTRUCTIONS REGARDING MIXING, SURFACE <br />PREPARATION AND APPLICATION. INCLUDE APPLICATION RATES, FILM <br />THICKNESS AND REQUIRED PRIMERS. <br />4. INTENT OF CONTRACTOR TO USE PRODUCTS SPECIFIED DOES NOT RELIEVE <br />HIM FROM HIS RESPONSIBILITIES OF SUBMITTING PRODUCT LIST. <br />B. VERIFICATION SAMPLES: SUBMIT TWO SETS OF SELECTED COLOR SAMPLES FROM <br />PAINT MANUFACTURER FOR ARCHITECT'S REVIEW AND ACCEPTANCE. <br />1.5 QUALITY ASSURANCE: <br />A. APPLICABLE STANDARDS: <br />1. ASTM INTERNATIONAL (ASTM), AS REFERENCED HEREIN. <br />2. ENVIRONMENTAL PROTECTION AGENCY (EPA), VOLATILE ORGANIC <br />COMPOUNDS (VOC) STANDARDS AS REQUIRED BY LOCAL CODES AND <br />REGULATIONS. <br />1.6 DELIVERY, STORAGE AND HANDLING: <br />A. DELIVERY: DELIVER MATERIALS TO PROJECT SITE READY-MIXED IN ORIGINAL <br />CONTAINERS WITH LABELS INTACT; LABELS BEARING MANUFACTURER'S NAME, PAINT <br />TYPE, COLOR AND RECOMMENDED INSTALLATION AND REDUCING PROCEDURES. <br />B. STORAGE AND HANDLING: <br />1. STORE MATERIALS IN LOCATION ACCEPTABLE TO ARCHITECT. <br />2. MAINTAIN NEAT, CLEAN CONDITIONS IN STORAGE AREA; REMOVE RAGS AND <br />WASTE MATERIALS AT END OF EACH DAY'S WORK. <br />3. CLOSE CONTAINERS AT END OF DAY'S WORK. LEAVE NO MATERIALS OPEN. <br />1.7 PROJECT/ SITE CONDITIONS: <br />A. ENVIRONMENTAL REQUIREMENTS: <br />1. COMPLY WITH MANUFACTURER'S PRODUCT DATA AS TO ENVIRONMENTAL <br />CONDITIONS UNDER WHICH MATERIALS MAY BE APPLIED. <br />2. APPLY NO MATERIALS IN SPACES WHERE DUST IS BEING GENERATED. <br />3. COMPLY WITH APPLICABLE VOC REGULATIONS. <br />B. PROTECTION: COVER FINISHED WORK OF OTHER TRADES AND SURFACES NOT BEING <br />PAINTED CONCURRENTLY AND PREFINISHED ITEMS. <br />C. SAFETY PRECAUTIONS: <br />1. PROVIDE TEMPORARY FIRE PROTECTION EQUIPMENT IN MATERIALS STORAGE <br />AREA. <br />2. PROHIBIT SMOKING IN STORAGE AREA. <br />PART 2 - PRODUCTS <br />2.1 MANUFACTURERS: <br />A. ACCEPTABLE MANUFACTURERS: EXCEPT AS OTHERWISE NOTED, PRODUCTS SPECIFIED <br />AS A STANDARD OF QUALITY ARE MANUFACTURED BY BENJAMIN MOORE CO. <br />PRODUCTS OF THE FOLLOWING MANUFACTURERS SIMILAR IN TYPE AND QUALITY ARE <br />ACCEPTABLE FOR USE, SUBJECT TO APPROVAL OF PRODUCT LIST: <br />1. FRAZEE PAINT. <br />2. DUNN-EDWARDS CORPORATION. <br />3. SHERWIN-WILLIAMS. <br />B. WHERE PRODUCTS OTHER THAN THOSE OF THE MANUFACTURER LISTED AS THE <br />STANDARD OF QUALITY ARE SPECIFIED IN PAINTING SCHEDULE, SUCH PRODUCTS HAVE <br />BEEN SELECTED TO ACHIEVE SPECIFIC RESULTS AND SUBSTITUTIONS WILL BE <br />ALLOWED ONLY IN ACCORD WITH PRODUCT SUBSTITUTION PROCEDURES SECTION. <br />2.2 PAINTING MATERIALS: <br />A. MISCELLANEOUS MATERIALS: <br />1. PAINT THINNERS AND TINTS SHALL BE PRODUCTS OF SAME MANUFACTURER <br />AS PAINTS OR APPROVED BY HIM FOR USE WITH HIS PRODUCTS. <br />2. SHELLAC, TURPENTINE, PATCHING COMPOUNDS AND SIMILAR MATERIALS <br />REQUIRED FOR EXECUTION OF WORK SHALL BE PURE, BEST QUALITY <br />PRODUCTS. <br />B. PAINT AND STAIN COLORS SHALL BE AS INDICATED ON FINISH SCHEDULE WITH FINAL <br />APPROVAL BASED ON BRUSH-OUT SUBMITTAL. <br />PART 3 - EXECUTION <br />3.1 PREPARATION: <br />A. INCLUDE PAINTING REQUIRED BY PROJECT EXCEPT FOR PREFINISHED ITEMS AND <br />SPECIAL FINISHES AS SPECIFIED IN OTHER SECTIONS. <br />B. EXISTING SURFACES: <br />1. FOR PREVIOUSLY PAINTED SURFACES, REMOVE DIRT, DEBRIS AND CHALK BY <br />WASHING WITH DETERGENT AND WATER. <br />2. PREVIOUSLY PAINTED METAL SURFACES TO REMAIN SHALL BE WIRE-BRUSHED <br />AND CLEANED OF EXISTING PAINT AND RUST. <br />3. TREAT MILDEWED SURFACES WITH A SOLUTION OF ONE QUART <br />HYPOCHLORITE BLEACH TO A HALF CUP OF DETERGENT TO ONE GALLON <br />WATER. RINSE AND ALLOW TO DRY PRIOR TO PAINTING. <br />4. SCRAPE OR USE APPROPRIATE MEANS TO REMOVE ALL LOOSE, PEELING, <br />FLAKING, OR MARGINALLY ADHERING PAINT FROM THE SURFACE. FEATHER <br />SAND EDGES AS NECESSARY. <br />5. REPAIR OR REPLACE CAULKING WHERE NEEDED. <br />6. AFTER CLEANING, GLOSSY SURFACES SHALL BE DULLED BY SANDING. <br />REMOVE ALL SANDING DUST FROM THE SURFACE AFTER SANDING HAS TAKEN <br />PLACE. <br />7. PREPARE BARE AREAS AS NEW SURFACES, AND STOP PRIME OR FILL THOSE <br />AREAS WITH THE APPROPRIATE PRIMER OR FILLER. <br />8. PATCH OR REPAIR ALL CRACKS OR VOIDS WITH THE APPROPRIATE PATCHING <br />COMPOUND AND SAND SMOOTH AS NECESSARY. <br />9. SPOT PRIME ALL PATCHED AREAS WITH THE APPROPRIATE PRIMER PRIOR TO <br />FINISHING. <br />10. IF AFTER CLEANING CHALKY SURFACES CHALK RESIDUE IS STILL PRESENT, <br />PRIME THE ENTIRE SURFACE WITH THE PROPER BONDING PRIMER TO INSURE <br />GOOD ADHESION OF THE TOPCOAT TO THE SUBSTRATE. <br />C. WHERE FINISH MATERIALS ABUT OR ARE ABUTTED BY DISSIMILAR MATERIALS, CAULK <br />JOINTS IN ACCORD WITH JOINT SEALANTS SECTION. <br />D. GYPSUM BOARD: <br />1. FILL NARROW, SHALLOW CRACKS AND SMALL HOLES WITH PATCHING <br />COMPOUND, ALLOW TO DRY AND SAND SMOOTH WITHOUT RAISING NAP OF <br />GYPSUM BOARD PAPER. <br />2. GYPSUM BOARD SHALL BE FINISHED AS SPECIFIED IN GYPSUM BOARD <br />SECTION PRIOR TO PAINTING. <br />E. FERROUS METALS: <br />1. WIRE-BRUSH OR SANDPAPER TO REMOVE RUST AND MILL SCALE. <br />2. SOLVENT-CLEAN WITH XYLOL TO REMOVE GREASE, OIL AND CONTAMINANTS. <br />WIPE DRY WITH CLEAN CLOTH. <br />3.2 APPLICATIOIN: <br />A. APPLY PAINT ONLY WHEN MOISTURE CONTENT OF SURFACES IS WITHIN LIMITS <br />RECOMMENDED IN PRODUCT DATA. APPLY PAINT MATERIALS USING CLEAN BRUSHES, <br />ROLLERS OR SPRAYING EQUIPMENT. <br />B. APPLY MATERIALS AT RATE NOT EXCEEDING THAT RECOMMENDED IN PRODUCT DATA <br />FOR SURFACE BEING PAINTED, LESS TEN PERCENT FOR LOSSES. <br />C. COMPLY WITH PRODUCT DATA FOR DRYING TIME BETWEEN COATS. <br />D. SAND AND DUST BETWEEN COATS TO REMOVE DEFECTS VISIBLE FROM A DISTANCE OF <br />5'-0". <br />E. FINISH COATS SHALL BE SMOOTH, FREE OF BRUSH MARKS, STREAKS, LAPS OR PILE-UP <br />OF PAINT, SKIPPED OR MISSED AREAS. <br />F. MAKE EDGES OF PAINT ADJOINING OTHER MATERIALS OR COLORS CLEAN AND SHARP <br />WITHOUT OVERLAPPING. <br />G. PRIMER COATS MAY BE OMITTED FOR SURFACES SPECIFIED TO RECEIVE FACTORY- <br />APPLIED PRIMER, IF PRIMER IS COMPATIBLE WITH FINISH COATS. IF PRIMER COATS ARE <br />NOT COMPATIBLE, SUBSTITUTE A BOND COAT AS RECOMMENDED BY PAINT <br />MANUFACTURER FOR SPECIFIED PRIMER COAT. <br />H. WHERE TWO-COAT FINISH IS SPECIFIED, PRIME COAT SHALL BE TINTED TO <br />APPROXIMATE FINISH COLOR. <br />I. WHERE PORTION OF FINISH ON GYPSUM BOARD PARTITION IS DAMAGED OR <br />UNACCEPTABLE, REFINISH ENTIRE SURFACE OF PARTITION. <br />J. SEAL TOPS AND BOTTOMS OF INTERIOR DOORS WITH PRIME COAT ONLY; SIDE EDGES <br />SAME AS FACES. <br />K. REMOVE AND PROTECT HARDWARE, ACCESSORIES, DEVICE PLATES, LIGHTING <br />FIXTURES, FACTORY-FINISHED WORK AND SIMILAR ITEMS, OR PROVIDE IN-PLACE <br />PROTECTION. UPON COMPLETION OF EACH SPACE, REPLACE REMOVED ITEMS. <br />L. PAINT EXPOSED PIPING AND DUCKWORK IN PAINTED SPACES SAME AS ADJACENT <br />WALL SURFACES. <br />M. THE FOLLOWING SURFACES DO NOT REQUIRE PAINTING: <br />1. PREFINISHED AND FACTORY-FINISHED SURFACES AND ITEMS, EXCEPT WHERE <br />INDICATED OTHERWISE. <br />2. CONCEALED DUCKWORK, CONDUIT AND PIPING. <br />3.3 PAINT SCHEDULES: <br />A. INTERIOR PAINT SCHEDULE: <br />1. GYPSUM BOARD: PROVIDE THE FOLLOWING FINISH SYSTEMS OVER INTERIOR <br />GYPSUM BOARD SURFACES: <br />A. LOW-LUSTER ACRYLIC EGGSHELL FINISH: <br />1) FIRST COAT OVER BARE DRYWALL: MOORE #023 FRESH START <br />ACRYLIC LATEX PRIMER 50 g/L 1.3 MILS DFT. <br />2) FIRST COAT OVER PREVIOUSLY PAINTED DRYWALL: MOORE <br />#SXA-110 STIX WATERBORNE BONDING PRIMER 40% VOL <br />SOLIDS, 2.1 MILS DFT. <br />3) SECOND COAT: MOORE #N538 ULTRA SPEC 500, ZERO VOC, <br />ACRYLIC EGGSHELL ENAMEL, 1.8 MILS DFT. <br />4) THIRD COAT: MOORE #N538 ULTRA SPEC 500, ZERO VOC, <br />ACRYLIC EGGSHELL ENAMEL, 1.8 MILS DFT. <br />2. FERROUS METAL: PROVIDE THE FOLLOWING FINISH SYSTEMS OVER NEW AND <br />PREVIOUSLY PAINTED FERROUS METAL: <br />A. SEMI-GLOSS ACRYLIC ENAMEL FINISH: <br />1) FIRST COAT: MOORE #P04 SUPER SPEC HP ACRYLIC METAL <br />PRIMER 54 g/L, 2.3 MILS DFT. <br />2) SECOND COAT: MOORE #P29 SUPER SPEC HP ACRYLIC DTM <br />SEMI-GLOSS ENAMEL, 206 g/L, 2.5 MILS DFT. <br />3) THIRD COAT: MOORE #P29 SUPER SPEC HP ACRYLIC DTM <br />SEMI-GLOSS ENAMEL, 206 g/L, 2.5 MILS DFT. <br />3. ZINC-COATED METAL: PROVIDE THE FOLLOWING FINISH SYSTEMS OVER NEW <br />AND PREVIOUSLY PAINTED INTERIOR ZINC-COATED METAL SURFACES: <br />A. SEMI-GLOSS ACRYLIC ENAMEL FINISH: <br />1) FIRST COAT: MOORE #P04 SUPER SPEC HP ACRYLIC METAL <br />PRIMER 54 g/L, 2.3 MILS DFT. <br />2) SECOND COAT: MOORE #P29 SUPER SPEC HP ACRYLIC DTM <br />SEMI-GLOSS ENAMEL, 206 g/L, 2.5 MILS DFT. <br />3) THIRD COAT: MOORE #P29 SUPER SPEC HP ACRYLIC DTM <br />SEMI-GLOSS ENAMEL, 206 g/L, 2.5 MILS DFT. <br />4. ALUMINUM: PROVIDE THE FOLLOWING FINISH SYSTEMS OVER NEW AND <br />PREVIOUSLY PAINTED INTERIOR ALUMINUM METAL SURFACES: <br />A. SEMI-GLOSS ACRYLIC ENAMEL FINISH: <br />1) FIRST COAT: MOORE #SXA-110 STIX BONDING PRIMER 40% <br />VOL. SOLIDS, 2.1 MILS DFT. <br />2) SECOND COAT: MOORE #P29 SUPER SPEC HP ACRYLIC DTM <br />SEMI-GLOSS ENAMEL, 206 g/L, 2.5 MILS DFT. <br />3) THIRD COAT: MOORE #P29 SUPER SPEC HP ACRYLIC DTM <br />SEMI-GLOSS ENAMEL, 206 g/L, 2.5 MILS DFT. <br />END OF SECTION <br />DIVISION 10 - SPECIALTIES <br />SECTION 10 2123 - CUBICLE TRACK AND CURTAINS <br />PART 1 - GENERAL <br />1.1 SUMMARY: <br />A. WORK OF THIS SECTION INCLUDES CUBICLE CURTAIN TRACK, CURTAINS AND <br />ACCESSORIES. <br />B. RELATED WORK SPECIFIED ELSEWHERE: <br />1. ROUGH CARPENTRY. <br />2. ACOUSTICAL CEILINGS. <br />1.2 SUBMITTALS: <br />A. GENERAL: IN COMPLIANCE WITH SECTION 01 3300 AND AS SPECIFIED HEREIN. <br />B. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT LITERATURE AND INSTALLATION <br />INSTRUCTIONS FOR EACH TYPE OF CUBICLE CURTAIN TRACK, CURTAIN AND <br />INSTALLATION ACCESSORY REQUIRED. INCLUDE METHODS OF INSTALLATION FOR EACH <br />TYPE OF SUPPORTING STRUCTURE. <br />1.3 QUALITY ASSURANCE: <br />A. MANUFACTURER QUALIFICATIONS: FABRICATOR WITH NOT LESS THAN 3 YEARS OF <br />PRODUCTION EXPERIENCE WITH CUBICLE CURTAIN TRACK, CURTAIN SIMILAR TO <br />REQUIREMENTS OF THIS PROJECT. <br />B. INSTALLER QUALIFICATIONS: FIRM SPECIALIZING IN CUBICLE CURTAIN TRACKS WITH NOT <br />LESS THAN 2 YEARS OF EXPERIENCE IN INSTALLATION OF PRODUCTS SIMILAR TO THAT <br />REQUIRED FOR THIS PROJECT. <br />1.4 DELIVERY, STORAGE AND HANDLING: <br />A. COMPLY WITH INSTRUCTIONS AND RECOMMENDATIONS OF MANUFACTURER FOR <br />SPECIAL DELIVERY, STORAGE, AND HANDLING REQUIREMENTS. <br />B. DELIVER MATERIAL TO PROJECT SITE ON PROTECTIVE WRAPPINGS AND CONTAINERS, <br />CLEARLY LABELED WITH IDENTIFICATION OF MANUFACTURER. STORE MATERIALS IN <br />PACKAGES, INSIDE WELL-VENTILATED AREA PROTECTED FROM WEATHER, MOISTURE, <br />SOILING, AND TEXTURE TEMPERATURE AND HUMIDITY. <br />1.5 SEQUENCING AND SCHEDULING: <br />A. SEQUENCE CUBICLE CURTAIN TRACK, CURTAIN INSTALLATION WITH OTHER WORK TO <br />MINIMIZE POSSIBILITY OF DAMAGE AND SOILING DURING REMAINDER OF CONSTRUCTION <br />PERIOD. <br />PART 2 - PRODUCTS <br />2.1 MANUFACTURERS: <br />A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS OF ONE OF THE FOLLOWING: <br />1. BASIS OF DESIGN: GENERAL CUBICLE COMPANY, INC. <br />2. KIRSCH. <br />3. INPRO CORP. <br />4. AR NELSON. <br />2.2 TRACK MATERIALS: <br />A. PROVIDE CUBICLE CURTAIN TRACK CONFIGURATIONS AS SHOWN ON DRAWINGS, <br />EQUIPPED WITH HARDWARE AS SCHEDULED. <br />B. EXTRUDED-ALUMINUM TRACK: NOT LESS THAN 1-1/4" WIDE BY 3/4" HIGH; WITH MINIMUM <br />WALL THICKNESS OF 0.058". <br />1. CURVED TRACK: FACTORY FABRICATED 14" RADIUS BENDS. <br />2. TRACK FINISH: WHITE BAKED ENAMEL. <br />C. PROVIDE TRACK ACCESSORIES AS REQUIRED. <br />D. TRACK ACCESSORIES: FABRICATE SPLICES, END CAPS, CONNECTORS, END STOPS, <br />COUPLING AND JOINING SLEEVES, WALL FLANGES, BRACKETS, CEILING CLIPS, AND <br />OTHER ACCESSORIES FROM SAME MATERIAL AND WITH SAME FINISH AS TRACK. <br />1. SUSPENDED TRACK SUPPORT: NOT LESS THAN 7/8" O.D. TUBE. <br />2. END STOP: REMOVABLE WITH CARRIER HOOK. <br />3. SPLICING CLAMP: ANODIZED SLEEVE SECURING JOINED SECTIONS OF TRACK. <br />4. CURVES: TRACK CHANNEL BENT TO 12" RADIUS. <br />5. SPLICE LOCATIONS: PROVIDE CONTINUOUS TRACK ASSEMBLIES WITHOUT <br />SPLICES WHEREVER POSSIBLE. WHERE SPLICES ARE UNAVOIDABLE, LOCATE <br />SPLICES NO CLOSER THAN 12" FROM THE END OF A CURVED SECTION, NOR <br />CLOSER THAN 12" TO THE END OF THE TRACK. <br />6. ROLLER CARRIER: BASIS OF DESIGN IS GENERAL IFC-100. <br />7. CURTAIN ACCESSORIES: PROVIDE TRACK ACCESSORIES TO FACILITATE USE OF <br />CURTAINS. <br />2.3 CUBICLE CURTAINS: <br />A. CUBICLE CURTAIN: <br />1. BASIS OF DESIGN: ICP MEDICAL <br />2. ALTERNATE: OWNER APPROVED EQUAL. <br />PART 3 - EXECUTION <br />3.1 EXAMINATION: <br />A. EXAMINE AREAS AND CONDITIONS WHERE CURTAIN TRACK, CURTAIN WILL BE <br />INSTALLED. DO NOT PROCEED UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN <br />CORRECTED. ONCE THE CONTRACTOR ACCEPTS AND COMMENCES THE INSTALLATION <br />IN A ROOM OR AREA, THE CONTRACTOR SHALL REPAIR AND CORRECT DAMAGES TO THE <br />BUILDING CONSTRUCTION RESULTING FROM HIS INSTALLATION OPERATIONS. <br />3.2 PREPARATION: <br />A. PRIOR TO INSTALLATION OF CUBICLE CURTAIN TRACK AND CURTAINS, CLEAN <br />SUBSTRATE TO REMOVE DUST, DEBRIS, AND LOOSE PARTICLES. <br />B. COORDINATE MOUNTING OF TRACK WITH REFLECTED CEILING PLAN TO AVOID CONFLICT <br />WITH LIGHTS, AND OTHER CEILING MOUNTED DEVICES. <br />C. VERIFY THAT MATERIALS ARE THOSE SPECIFIED BEFORE INSTALLING. <br />3.3 INSTALLATION: <br />A. INSTALL CUBICLE CURTAIN TRACK, CURTAIN UNITS IN MANNER INDICATED TO COMPLY <br />WITH FABRICATOR'S INSTRUCTIONS. SECURE AT PROPER HEIGHT AND LOCATION <br />RELATIVE TO ADJOINING RELATED WORK. SECURELY ANCHOR UNITS WITH PROPER <br />ANCHORAGES, SUITED TO CEILING LEVEL, SURFACE MOUNTING. <br />B. SECURE TRACK TO CEILING WITH FASTENERS APPROPRIATE FOR SUBSTRATE AT <br />MINIMUM 3'-0" INTERVALS. PROVIDE TRACK ACCESSORIES AS REQUIRED. <br />C. MAKE PROVISIONS FOR UNENCUMBERED OPERATION OF HARDWARE. <br />3.4 FIELD QUALITY CONTROL: <br />A. TEST OPERATION OF EACH CUBICLE CURTAIN TRACK, CURTAIN AND ADJUST THOSE <br />WHICH DO NOT OPERATE SMOOTHLY. <br />3.5 ADJUSTING: <br />A. RETURN TO PROJECT SITE 6 MONTHS AFTER THE ARCHITECT'S FINAL CERTIFICATE, RE- <br />HANG ANY CUBICLE CURTAIN UNITS WHICH REQUIRE MINOR ADJUSTMENT; RE-HEM <br />CUBICLE CURTAIN UNITS WHICH HAVE STRETCHED. <br />3.6 CLEANING AND PROTECTION: <br />A. REMOVE SURPLUS MATERIALS, RUBBISH, AND DEBRIS RESULTING FROM INSTALLATION <br />UPON COMPLETION OF WORK, AND LEAVE AREAS OF INSTALLATION IN NEAT, CLEAN <br />CONDITION. <br />B. PROTECT TESTED AND INSTALLED UNITS TO ENSURE OPTIMUM OPERATING CONDITIONS <br />WITHOUT DAMAGE, BLEMISHES OR INDICATION OF USE AT COMPLETION OF PROJECT. <br />REPAIR OR REPLACE DAMAGED, SOILED OR OTHERWISE DEFECTED UNITS. <br />END OF SECTION <br />SECTION 10 2600 - WALL PROTECTION <br />PART 1 - GENERAL <br />1.1 SUMMARY: <br />A. WORK OF THIS SECTION INCLUDES: <br />1. WALL PROTECTION <br />B. RELATED WORK SPECIFIED ELSEWHERE: GYPSUM BOARD. <br />1.2 REFERENCES: <br />A. ASTM INTERNATIONAL (ASTM) <br />B. INTERNATIONAL BUILDING CODE (IBC) <br />C. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA); LIFE SAFETY CODE. <br />D. UNDERWRITERS LABORATORIES (UL). <br />1.3 ACTION SUBMITTALS: <br />A. PRODUCT DATA: SUBMIT PRODUCT DATA AND DETAILED SPECIFICATIONS FOR EACH <br />SYSTEM COMPONENT AND INSTALLATION ACCESSORY REQUIRED, INCLUDING <br />INSTALLATION METHODS FOR EACH TYPE OF SUBSTRATE. <br />B. SAMPLES: SAMPLES FOR VERIFICATION PURPOSES: SUBMIT 12" LONG SAMPLE OF EACH <br />MODEL SPECIFIED AND AS PROPOSED FOR THIS WORK, FOR VERIFICATION OF GUARD. <br />1.4 QUALITY ASSURANCE: <br />A. INSTALLER QUALIFICATIONS: ENGAGE AN INSTALLER WHO HAS NO LESS THAN 3 YEARS <br />EXPERIENCE IN INSTALLATION OF SYSTEMS SIMILAR IN COMPLEXITY TO THOSE <br />REQUIRED FOR THIS PROJECT. <br />B. MANUFACTURER'S QUALIFICATIONS: NOT LESS THAN 5 YEARS EXPERIENCE IN THE <br />PRODUCTION OF SPECIFIED PRODUCTS AND A RECORD OF SUCCESSFUL IN-SERVICE <br />PREFORMANCE. <br />C. CODE COMPLIANCE: ASSEMBLIES SHALL CONFORM TO APPLICABLE CODES INCLUDING <br />IBC, AND LIFE SAFETY. <br />D. FIRE PERFORMANCE CHARACTERISTICS: PROVIDE WALL PROTECTION SYSTEM <br />COMPONENTS WITH UL LABEL INDICATING THAT THEY ARE IDENTICAL TO THOSE TESTED <br />IN ACCORD WITH ASTM E84-12A FOR CLASS 1 CHARACTERISTICS LISTED BELOW" <br />1. FLAME SPREAD: 25 OR LESS <br />2. SMOKE DEVELOPED: 450 OR LESS. <br />E. IMPACT STRENGTH: PROVIDE ASSEMBLED WALL PROTECTION UNITS THAT HAVE BEEN <br />TESTED IN ACCORD WITH THE APPLICABLE PROVISIONS OF ASTM F476-84(2002) <br />F. CHEMICAL AND STAIN RESISTANCE: PROVIDE WALL PROTECTION SYSTEM COMPONENTS <br />WITH CHEMICAL AND STAIN RESISTANCE IN ACCORDANCE WITH ASTM D1308-02(2007). <br />G. COLOR MATCH: PROVIDE WALL PROTECTION COMPONENTS THAT ARE COLOR MATCHED <br />IN ACCORDANCE WITH THE FOLLOWING: <br />1. DELTA ECMC OF NO GREATER THAN 1.0 USING CIELAB COLOR SPACE. <br />H. SINGLE SOURCE RESPONSIBILITY: PROVIDE ALL COMPONENTS OF THE WALL <br />PROTECTION SYSTEM MANUFACTURED BY THE SAME COMPANY TO ENSURE <br />COMPATIBILITY OF COLOR, TEXTURE AND PHYSICAL PROPERTIES. <br />1.5 DELIVERY, STORAGE AND HANDLING: <br />A. DELIVER MATERIALS TO THE PROJECT SITE IN UNOPENED ORIGINAL FACTORY <br />PACKAGING CLEARLY LABELED TO SHOW MANUFACTURER. <br />B. STORE MATERIALS IN ORIGINAL, UNDAMAGED PACKAGING IN A COOL, DRY PLACE OUT <br />OF DIRECT SUNLIGHT AND EXPOSURE TO THE ELEMENTS. MAINTAIN A MINIMUM ROOM <br />TEMPERATURE OF 40 DEGREES F. AND A MAXIMUM TEMPERATURE OF 100 DEGREES F. <br />C. STORE MATERIAL FLAT. <br />1.6 PROJECT CONDITIONS: <br />A. ACCLIMATE MATERIALS IN AN ENVIRONMENT OF 65 DEGREES TO 75 DEGREES FOR AT <br />LEAST 24 HOURS PRIOR TO BEGINNING INSTALLATION. <br />B. INSTALLATION AREAS SHALL BE ENCLOSED AND WEATHERPROOFED BEFORE <br />INSTALLATION COMMENCES. <br />PART 2 - PRODUCTS <br />2.1 CORNER GUARDS: <br />A. ENGINEERING PETG: HIGH IMPACT ACROVYN 4000 WITH NOMINAL .040" THICKNESS. <br />B. ALUMINUM EXTRUSIONS: ALLOY AND TEMPER RECOMMENDED BY MANUFACTURER <br />FOR TYPE OF USE AND FINISH INDICATED, BUT WITH NOT LESS THAN STRENGTH AND <br />DURABILITY PROPERTIES SPECIFIED IN ASTM B221-12A FOR ALLOY 6063-T5. <br />C. FASTENERS: ALUMINUM, NONMAGNETIC STAINLESS-STEEL, OR OTHER NONCORROSIVE <br />METAL SCREWS, BOLTS, AND OTHER FASTENERS COMPATIBLE WITH ITEMS BEING <br />FASTENED. USE SECURITY-TYPE FASTENERS WHERE EXPOSED TO VIEW. <br />D. ADHESIVE: AS RECOMMENDED BY IMPACT-RESISTANT PLASTIC WALL PROTECTION <br />MANUFACTURER'S PRODUCT DATA AND WITH A VOC CONTENT LESS THAN THE CURRENT <br />VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD) <br />RULE #1113, ARCHITECTURAL COATINGS, RULES IN EFFECT JANUARY 1, 2004. <br />E. REFER TO FINISH SCHEDULE. <br />2.2 FABRICATION: <br />A. FABRICATE IMPACT-RESISTANT WALL PROTECTION UNITSTO COMPLY WITH <br />REQUIREMENTS INDICATED FOR DESIGN, DIMENSIONS, AND MEMBER SIZES, <br />INCLUDING THICKNESSES OF COMPONENTS. <br />B. ASSEMBLE COMPONENTS IN FACTORY TO GREATEST EXTENT POSSIBLE TO MINIMIZE <br />FIELD ASSEMBLY. DISASSEMBLE ONLY AS NECESSARY FOR SHIPPING AND HANDLING. <br />C. FABRICATE COMPONENTS WITH TIGHT SEAMS AND JOINTS WITH EXPOSED EDGES <br />ROLLED. PROVIDE SURFACES FREE OF WRINKLES, CHIPS, DENTS, UNEVEN COLORATION, <br />AND OTHER IMPERFECTIONS. FABRICATE MEMBERS AND FITTINGS TO PRODUCE FLUSH, <br />SMOOTH, AND RIGID HAIRLINE JOINTS. <br />PART 3 - EXECUTION <br />3.1 EXAMINATION: <br />A. EXAMINE SUBSTRATES AND WALL AREAS, WITH INSTALLER PRESENT, FOR <br />COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION TOLERANCES AND OTHER <br />CONDITIONS AFFECTING PERFORMANCE OF WORK. <br />B. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN <br />CORRECTED. <br />3.2 PREPARATION: <br />A. COMPLETE FINISHING OPERATIONS, INCLUDING PAINTING , BEFORE INSTALLING <br />IMPACT-RESISTANT WALL PROTECTION SYSTEM COMPONENTS. <br />B. BEFORE INSTALLATION, CLEAN SUBSTRATE TO REMOVE DUST, DEBRIS, AND LOOSE <br />PARTICLES. <br />3.3 INSTALLATION: <br />A. GENERAL: INSTALL IMPACT-RESISTANCE HANDRAILS UNITS LEVEL, PLUMB, AND TRUE <br />TO LINE WITHOUT DISTORTIONS. DO NOT USE MATERIALS WITH CHIPS, CRACKS, VOIDS, <br />STAINS, OR OTHER DEFECTS THAT MIGHT BE VISIBLE IN THE FINISHED WORK. <br />3.4 CLEANING: <br />A. IMMEDIATELY AFTER COMPLETION OF INSTALLATION, CLEAN PLSTIC COVERS AND <br />ACCESSORIES USING A STANDARD, AMMONIA-BASED, HOUSEHOLD CLEANING AGENT. <br />B. REMOVE EXCESS ADHESIVE USING METHODS AND MATERIALS RECOMMENDED IN <br />MANUFACTURER'S PRODUCT DATA. <br />END OF SECTION <br />DIVISION 11 THRU 21 <br />(NO SECTIONS REQUIRED) <br />DIVISION 22 <br />PROVIDED ON PLUMBING DRAWINGS <br />DIVISION 23 <br />PROVIDED ON MECHANICAL DRAWINGS <br />DIVISION 24 <br />(NO SECTIONS REQUIRED) <br />DIVISION 25 <br />(NO SECTIONS REQUIRED) <br />DIVISION 26 <br />PROVIDED ON ELECTRICAL DRAWINGS <br />DIVISION 27 THRU 49 <br />(NO SECTIONS REQUIRED) <br />R <br />No. <br />F <br />LICENSE <br />STATE <br />D <br />O <br />A RCHITECT <br />C AL IFORNIA <br />STEPHE WHITE <br />RENEWAL <br />DATE <br />C-34829 <br />N <br />08/31/25 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />MATTERPORT LINK: https://my.matterport.com/show/?m=FW21iEbmuii <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br />50 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br />1/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />C:\Users\jpark\Documents\R314412.44 - KP SAN 1st Flr Gen Rad_A22_Central_jhaLWMQW.rvt <br />5/20/2024 10:23:29 AM <br />SOCC 2023 R RAD SAN 1ST FLOOR <br />GEN RAD REPLACEMENT (5284) <br />G0-04 <br />SPECIFICATIONS <br />CA361 1 <br />CAP028060R314412.44 <br />SANTA ANA MEDICAL OFFICES <br />1900 E. 4TH ST. <br />SANTA ANA, CA 92701 <br />CITY SUBMITTAL 04/19/2024 <br />BID SET 05/20/2024 <br />1900 E 4th St - <br />1011190678/9/2024