B. FIRE-TEST-RESPONSE CHARACTERISTICS: PROVIDE FIRESTOPPING SYSTEM DESIGN
<br />LISTING BY A TESTING AND INSPECTION AGENCY IN ACCORD WITH THE SPECIFIED
<br />UL STANDARDS.
<br />C. ACCEPTABLE INSTALLER SHALL BE:
<br />1. INSTALLER QUALIFICATIONS: A FIRM THAT HAS BEEN APPROVED BY FM
<br />GLOBAL ACCORDING TO FM GLOBAL 4991, "APPROVAL OF FIRESTOP
<br />CONTRACTOR," OR BEEN EVALUATED BY UL AND FOUND TO COMPLY WITH
<br />UL's "QUALIFIED FIRESTOP CONTRACTOR PROGRAM REQUIREMENTS."
<br />2. LICENSED BY STATE OR LOCAL AUTHORITY, WHERE APPLICABLE.
<br />3. SUCCESSFULLY COMPLETED NOT LESS THAN 5 COMPARABLE SCALE
<br />PROJECTS.
<br />D. SINGLE SOURCE RESPONSIBILITY: OBTAIN FIRESTOP SYSTEMS FOR EACH KIND OF
<br />PENETRATION AND CONSTRUCTION CONDITION INDICATED FROM A SINGLE PRIMARY
<br />FIRESTOP SYSTEMS MANUFACTURER.
<br />1. MATERIALS FROM DIFFERENT MANUFACTURER THAN ALLOWED BY TESTED
<br />AND LISTED SYSTEM SHALL NOT BE INTERMIXED IN THE SAME FIRESTOP
<br />SYSTEM OR OPENING.
<br />2. INSTALL TESTED AND LISTED FIRESTOP SYSTEMS BEFORE INSTALLING AN
<br />ENGINEERING JUDGEMENT OR EQUIVALENT FIRE RESISTANCE RATED
<br />ASSEMBLY (EFFRA).
<br />1.6 DELIVERY STORAGE AND HANDLING:
<br />A. DELIVER FIRESTOPPING MATERIALS IN ORIGINAL, UNOPENED CONTAINERS OR PACKAGES
<br />WITH INTACT AND LEGIBLE MANUFACTURER'S LABELS IDENTIFYING PRODUCT AND
<br />MANUFACTURER.
<br />B. STORE AND HANDLE FIRESTOPPING MATERIALS IN ACCORD WITH MANUFACTURER'S
<br />PRODUCT DATA.
<br />1.7 JOB CONDITIONS:
<br />A. COORDINATE FIRESTOPPING INSTALLATION WITH OTHER WORK REQUIRING
<br />PENETRATIONS THROUGH FIRE-RESISTIVE CONSTRUCTION. INSTALL PENETRATING
<br />ELEMENTS PRIOR TO INSTALLATION OF FIRESTOPPING SYSTEMS OR DEVICES.
<br />B. SECURE INSPECTION AND APPROVAL OF FIRESTOPPING WORK BY BUILDING OFFICIALS
<br />PRIOR TO CONCEALMENT.
<br />C. SUPPORT PENETRATING ELEMENTS INDEPENDENTLY OF FIRESTOPPING SYSTEMS OR
<br />DEVICES.
<br />D. DO NOT COVER UP FIRESTOPPING INSTALLATIONS UNTIL OWNER'S INSPECTION AGENCY
<br />OR AUTHORITIES HAVING JURISDICTION HAVE EXAMINED EACH INSTALLATION.
<br />PART 2 - PRODUCTS
<br />2.1 MATERIALS, GENERAL:
<br />A. VOC CONTENT: PENETRATION FIRESTOPPING SEALANTS AND SEALANT PRIMERS SHALL
<br />HAVE A VOC CONTENT LESS THAN THE CURRENT VOC CONTENT LIMITS OF SOUTH
<br />COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD) RULE #1113, ARCHITECTURAL
<br />COATINGS, RULES IN EFFECT JANUARY 1, 2004.
<br />2.2 THROUGH-PENETRATION FIRESTOP SYSTEMS:
<br />A. ACCEPTABLE MANUFACTURERS; SUBJECT TO COMPLIANCE WITH SPECIFIED
<br />REQUIREMENTS:
<br />1. GRACE CONSTRUCTION PRODUCT.
<br />2. HILTI USA.
<br />3. 3M FIRE PROTECTION PRODUCTS.
<br />4. NELSON FIRESTOP PRODUCTS.
<br />5. RECTOR SEAL CORP.
<br />6. SPECIFIED TECHNOLOGIES, INC. (STI).
<br />7. TREMCO, INC.
<br />B. SYSTEM DESCRIPTION: FIELD-CONSTRUCTED FIRESTOPPING FOR PENETRATIONS
<br />THROUGH WALLS AND FLOORS COMPOSED OF SPECIFIED MATERIALS AND ACCESSORIES
<br />ASSEMBLED IN ACCORD WITH THROUGH-PENETRATION FIRESTOPPING SYSTEM
<br />NUMBERS, LISTED IN UL BUILDING MATERIALS DIRECTORY, CURRENT EDITION, AND
<br />TESTED IN ACCORD WITH ASTM E814-11A.
<br />C. MATERIALS: UL CLASSIFIED FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS.
<br />1. FIRESTOP SEALANT: SINGLE-COMPONENT, ELASTOMERIC SILICONE OR
<br />ENDOTHERMIC LATEX SEALANT COMPOUND; SELF-ADHERING, FLEXIBLE AND
<br />WATERTIGHT; NON SAG AND SELF-LEVELING TYPES AS REQUIRED.
<br />2. FIRESTOP FOAM: TWO-PART, ROOM TEMPERATURE VULCANIZING, SILICONE
<br />ELASTOMER, NON-COMBUSTIBLE FOAM VOID SEAL.
<br />3. INTUMESCENT SEALANTS AND PUTTIES: SINGLE-COMPONENT, SYNTHETIC,
<br />ORGANIC/INORGANIC INTUMESCENT ELASTOMERS.
<br />4. INTUMESCENT WRAP STRIPS: ONE-PART, ORGANIC/INORGANIC, INTUMESCENT
<br />ELASTOMERIC SHEET; ALUMINUM FOIL-FACED ONE SIDE.
<br />5. INTUMESCENT COMPOSITE SHEETS: COMPOSITE SHEETS COMPOSED OF
<br />ORGANIC/INORGANIC INTUMESCENT ELASTOMERIC CORE BONDED ON ONE SIDE
<br />TO 28 GA. GALVANIZED STEEL SHEET AND OTHER SIDE REINFORCED WITH
<br />STEEL WIRE MESH, COVERED WITH ALUMINUM FOIL.
<br />6. MINERAL WOOL OR CERAMIC FIBER SAFING: NON-COMBUSTIBLE FIBER TESTED
<br />IN ACCORD WITH ASTM E136-12, WITH MELTING POINT IN EXCESS OF 2000
<br />DEGREES F.; FLAME SPREAD OF 15 MAXIMUM AND 0 SMOKE DEVELOPMENT
<br />WHEN TESTED IN ACCORD WITH ASTM E84-12C. THICKNESS AND DENSITY SHALL
<br />BE AS REQUIRED BY THROUGH-PENETRATION FIRESTOP SYSTEM DESIGNS.
<br />D. ACCESSORIES:
<br />1. PRIMERS, ADHESIVES AND BACKER RODS: AS REQUIRED BY MANUFACTURER'S
<br />PRODUCT DATA AND SYSTEM DESIGNS.
<br />2. FORMING, DAMMING AND PACKING MATERIALS: TYPES AS INDICATED IN
<br />THROUGH-PENETRATION FIRESTOP SYSTEMS.
<br />3. RESTRICTING COLLARS: MANUFACTURER'S STANDARD DESIGN AS REQUIRED
<br />FOR FIRESTOP SYSTEMS.
<br />4. FASTENERS, ANCHOR CLIPS, SLEEVES, CLAMPS, SPACERS, TIES, COVER PLATES
<br />AND MISCELLANEOUS ACCESSORIES: PROVIDE AS REQUIRED BY
<br />MANUFACTURER'S PRODUCT DATA AND IN ACCORD WITH THROUGH-
<br />PENETRATION FIRESTOP SYSTEM DESIGNS.
<br />2.3 THROUGH-PENETRATION FIRESTOP DEVICES:
<br />A. ACCEPTABLE MANUFACTURERS; SUBJECT TO COMPLIANCE WITH SPECIFIED
<br />REQUIREMENTS:
<br />1. GRACE CONSTRUCTION PRODUCTS.
<br />2. HILTI USA.
<br />3. ISOLATEK INTERNATIONAL, INC.
<br />4. NELSON FIRESTOP PRODUCTS.
<br />5. PROSET SYSTEMS, INC.
<br />6. SPECIFIED TECHNOLOGIES, INC. (STI).
<br />7. TREMCO, INC.
<br />B. TYPES: FACTORY-ASSEMBLED, SELF-CONTAINED FIRESTOPPING DEVICES FOR
<br />PENETRATIONS THROUGH WALLS AND FLOORS; UL CLASSIFIED FOR THROUGH-
<br />PENETRATION FIRESTOP DEVICES AS LISTED IN UL BUILDING MATERIALS DIRECTORY,
<br />CURRENT EDITION, AND TESTED IN ACCORD WITH ASTM E-814-11A.
<br />C. ACCESSORIES: PROVIDE SEALANTS, ADHESIVES, FASTENERS, SLEEVES, CLAMPS,
<br />SPACERS, ANCHOR CLIPS, TIES AND ACCESSORIES IN ACCORD WITH MANUFACTURER'S
<br />PRODUCT DATA AND AS REQUIRED FOR COMPLETE INSTALLATION.
<br />2.4 FIRESTOP SEALANTS:
<br />A. ACCEPTABLE PRODUCTS; SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS:
<br />1. GRACE CONSTRUCTION PRODUCTS, FLAMESAFE SILICONE SEALANT.
<br />2. HILTI USA, CP 601S FIRESTOP SEALANT.
<br />3. NELSON FIRESTOP PRODUCTS, CLK.
<br />4. 3M FIRE PROTECTION PRODUCTS, FIRE BARRIER SILICONE SEALANT 2000 N/S
<br />5. RECTOR SEAL CORP., METACAULK 835+.
<br />6. SPECIFIED TECHNOLOGIES, INC. (STI), SPECSEAL PEN 300 SILICONE JOINT
<br />SEALANT.
<br />7. TREMCO, INC., FYRE-SIL.
<br />B. CHARACTERISTICS: SINGLE-COMPONENT, SELF-ADHERING, FLEXIBLE, WATERTIGHT,
<br />ELASTOMERIC SILICONE SEALANT COMPOUND; UL CLASSIFIED. PROVIDE SELF-LEVELING
<br />TYPE FOR HORIZONTAL APPLICATIONS, NON-SAG TYPE FOR ALL OTHER APPLICATIONS.
<br />2.5 SAFING:
<br />A. ACCEPTABLE PRODUCTS; SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS:
<br />1. GENERAL INSULATION COMPANY, FBX SAFING INSULATION.
<br />2. THERMAL CERAMICS, CERABLANKET F.S.
<br />3. THERMAFIBER INC., THERMAFIBER SAFING INSULATION.
<br />B. CHARACTERISTICS:
<br />1. MATERIAL: SEMI-RIGID MINERAL FIBER INSULATION, MEETING ASTM C665-12,
<br />TYPE 1.
<br />2. DENSITY: 4.0 PCF.
<br />3. THICKNESS: AS INDICATED.
<br />4. FACING: UNFACED OR REINFORCED FOIL FACING, BASED ON UL DESIGN
<br />SELECTED.
<br />5. FIRE RESISTANCE PROPERTIES:
<br />A. MELTING POINT: MINIMUM OF 2000 DEGREES F. WHEN TESTED IN
<br />ACCORD WITH ASTM C24-09.
<br />B. NON-COMBUSTIBLE: AS DEFINED BY ASTM E136-12 AND NFPA.
<br />C. FIRE HAZARD CHARACTERISTICS: MAXIMUM FLAME SPREAD OF 15
<br />AND SMOKE DEVELOPMENT OF 5 WHEN TESTED IN ACCORD WITH
<br />ASTM E84-12C (UNFACED).
<br />6. FIRE SAFING: TESTED IN ACCORD WITH ASTM E119-12A WITHOUT
<br />DETERIORATION FOR MINIMUM OF FIVE HOURS IN A SLAB EDGE/SPANDREL
<br />CONFIGURATION.
<br />C. ACCESSORIES:
<br />1. CLIPS: INSULATION MANUFACTURER'S STANDARD GALVANIZED STEEL IMPALING
<br />CLIPS FOR ATTACHMENT OF SAFING.
<br />2. SEALANT: MANUFACTURER'S TESTED SEALANT MATERIAL FOR FOIL-FACED
<br />SMOKE SEAL.
<br />PART 3 - EXECUTION
<br />3.1 PRE-INSTALLATION REQUIREMENTS:
<br />A. PRE-INSTALLATION MEETING: PRIOR TO BEGINNING FIRESTOPPING WORK, A
<br />PRE-INSTALLATION MEETING SHALL BE HELD TO REVIEW WORK TO BE ACCOMPLISHED.
<br />1. CONTRACTOR, ARCHITECT, FIRESTOPPING SYSTEM MANUFACTURER'S
<br />REPRESENTATIVES, INSTALLER AND OTHER SUBCONTRACTORS WHOSE WORK
<br />INVOLVES FIRESTOPPING SHALL BE PRESENT.
<br />2. CONTRACTOR SHALL NOTIFY ALL PARTIES AT LEAST SEVEN DAYS PRIOR TO
<br />TIME FOR MEETING.
<br />3. CONTRACTOR SHALL RECORD MINUTES OF MEETING AND DISTRIBUTE TO
<br />ATTENDING PARTIES.
<br />3.2 EXAMINATION:
<br />A. EXAMINE AREAS TO RECEIVE FIRESTOPPING MATERIALS PRIOR TO BEGINNING WORK.
<br />VERIFY THAT OPENING AREAS AND DIMENSIONS FOR PENETRATIONS TO RECEIVE
<br />FIRESTOPPING SYSTEMS AND DEVICES DO NOT EXCEED DESIGN REQUIREMENTS.
<br />B. REMOVE PROJECTIONS INTERFERING WITH INSTALLATION. PREPARE SURFACES IN
<br />ACCORD WITH MANUFACTURER'S PRODUCT DATA AND UL THROUGH-PENETRATION
<br />FIRESTOP DEVICES NUMBERS.
<br />3.3 PREPARATION:
<br />A. PRIMING: PRIME SUBSTRATES WHERE RECOMMENDED BY FIRESTOPPING MANUFACTURER
<br />USING THAT MANUFACTURER'S RECOMMENDED PRODUCTS AND METHODS. CONFINE
<br />PRIMERS TO AREAS OF BOND. DO NOT ALLOW SPILLAGE AND MIGRATION ONTO EXPOSED
<br />SURFACES.
<br />B. MASKING TAPE: USE MASKING TAPE TO PREVENT FIRESTOPPING FROM CONTACTING
<br />ADJOINING SURFACES THAT WILL REMAIN EXPOSED UPON COMPLETION OF THE WORK.
<br />REMOVE TAPE AS SOON AS IT IS POSSIBLE TO DO SO WITHOUT DISTURBING THE
<br />FIRESTOPPING SEAL WITH SUBSTRATES.
<br />3.4 INSTALLATION:
<br />A. GENERAL:
<br />1. COMPLY WITH MANUFACTURER'S PRODUCT DATA AND UL CLASSIFIED FOR
<br />THROUGH-PENETRATION FIRESTOP DEVICES NUMBERS.
<br />2. INSTALL FIRESTOPPING MATERIALS FITTED TO ADJACENT CONSTRUCTION
<br />TO FILL VOIDS.
<br />3. FIRESTOP PENETRATIONS THROUGH FIRE-RATED WALLS, PARTITIONS, FLOORS
<br />AND FLOOR/CEILING ASSEMBLIES WITH TESTED ASSEMBLIES IN ACCORD WITH
<br />UL 1479 OR WITH A THROUGH-PENETRATION FIRESTOP SYSTEM OR DEVICE
<br />WHEN TESTED IN ACCORD WITH ASTM E814-11A.
<br />4. FIRESTOPPING SHALL COMPLY WITH CODE REQUIREMENTS.
<br />B. FIRE AND SMOKE BARRIER IDENTIFICATION:
<br />1. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
<br />PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS
<br />SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
<br />STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY HAVING
<br />JURISDICTION.
<br />2. SUCH IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING AND IN
<br />CONCEALED SPACES, AND NEAR THE TOP OF THE WALL OR BARRIER IN
<br />UNFINISHED SPACES.
<br />3. SUCH IDENTIFICATION SHALL BE LETTERS A MINIMUM OF 2" (51 mm) HIGH ON
<br />A CONTRASTING BACKGROUND, SPACED AT 12'-0" O.C. MAXIMUM, WITH A
<br />MINIMUM OF ONE PER WALL OR BARRIER. COMPLY WITH CODE REQUIREMENTS.
<br />4. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "______ HOUR FIRE
<br />AND SMOKE BARRIER - PROTECT ALL OPENINGS."
<br />C. THROUGH-PENETRATION FIRESTOP SYSTEMS AND DEVICES:
<br />1. INSTALL AT PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL
<br />CONSTRUCTION, INCLUDING PARTITIONS AND FLOOR/ CEILING ASSEMBLIES,
<br />IN ACCORD WITH MANUFACTURER'S PRODUCT DATA AND UL SYSTEM NUMBERS.
<br />PROVIDE MATERIALS AND ACCESSORIES AS REQUIRED.
<br />2. INSTALL INTUMESCENT TYPE FIRESTOP SYSTEMS WHERE PLASTIC PIPING,
<br />CABLE, CONDUIT AND OTHER COMBUSTIBLE ITEMS, INCLUDING INSULATED
<br />METAL PIPES, PENETRATE FIRE-RATED CONSTRUCTION.
<br />3. AT CONTRACTOR'S OPTION, THROUGH-PENETRATION FIRESTOP DEVICES OF
<br />SIMILAR FUNCTION MAY BE INSTALLED IN LIEU OF FIRESTOP SYSTEMS.
<br />4. DO NOT REMOVE FORMING MATERIALS UNLESS SPECIFIED IN SYSTEM DESIGNS.
<br />D. FIRESTOP SEALANT: SEAL PERIMETERS, VOIDS AND JOINTS OF FIRE-RATED WALLS AND
<br />PARTITIONS,INCLUDING ABUTMENT OF FLOOR AND ROOF OR CEILING STRUCTURE, AND
<br />FLUTES OF METAL DECKING.
<br />1. IF REQUIRED BY UL DESIGN, INSTALL MINERAL WOOL OR CERAMIC FIBER IN
<br />CAVITIES, PACKED FULL AND TIGHT WITH ALLOWANCE FOR SEALANT
<br />INSTALLATION.
<br />2. SEAL BOTH FACES OF WALLS AND PARTITIONS WITH FIRESTOP SEALANT. TOOL
<br />SEALANTFLUSH WITH ADJACENT FINISH.
<br />3. IN ACCORD WITH UL FIRE RESISTANCE DIRECTORY DESIGNS, PACKED CONCRETE
<br />AND MASONRY JOINTS SHALL BE SEALED USING FIRESTOP SEALANT OR USING
<br />SEALANT AS SPECIFIED IN JOINT SEALANTS SECTION.
<br />E. MINERAL FIBER SAFING:
<br />1. INSTALL SAFING IN CAVITIES OF PENETRATIONS THROUGH NON-RATED FLOOR
<br />AND WALL CONSTRUCTION, INCLUDING SPACES AROUND PIPING, CONDUITS,
<br />CABLES AND DUCT PENETRATIONS.
<br />2. INSTALL SAFING IN VOIDS AND JOINTS OF NON-RATED WALLS AND PARTITIONS
<br />ABUTTING METAL DECKING OF FLOOR AND ROOD STRUCTURES. PACK FLUTES
<br />OF METAL DECKING SOLID WITH SAFING MATERIAL.
<br />3. SAFING SHALL BE INSTALLED AT JOINTS AND PENETRATIONS IN NON-RATED
<br />CONSTRUCTION NOT EXPOSED TO VIEW AND CONCEALED IN FINISH WORK.
<br />SECURE SAFING BY COMPRESSING INTO VOIDS OR JOINTS AND USING
<br />MANUFACTURER'S STANDARD CLIPS OR CLOSURE PLATES AS REQUIRED.
<br />F. SEAL VOIDS AND JOINTS OF NON-RATED WALLS AND PARTITIONS ABUTTING CONCRETE
<br />FLOOR AND ROOF CONSTRUCTION USING SEALANT AS SPECIFIED IN OTHER SECTIONS.
<br />3.5 FIELD QUALITY CONTROL:
<br />A. INSPECTION: INDEPENDENT INSPECTION AGENCY EMPLOYED AND PAID BY OWNER , WILL
<br />EXAMINE PENETRATION FIRESTOPPING IN ACCORD WITH ASTM E2174-10 AND
<br />ASTM E2393-10A. INSPECTION AGENCY WILL EXAMINE FIRESTOPPING AND WILL
<br />DETERMINE, IN GENERAL, THAT FIRESTOPPING HAS BEEN INSTALLED IN COMPLIANCE
<br />WITH TESTED AND LISTED FIRESTOP SYSTEM, AND THAT INSTALLATION PROCESS
<br />CONFORMS TO FM 4991 - STANDARD FOR APPROVAL OF FIRESTOP CONTRACTORS OR
<br />UL QUALIFIED FIRESTOP CONTRACTOR PROGRAM.
<br />B. INSPECTOR WILL ADVISE CONTRACTOR OF DEFICIENCIES NOTED WITHIN ONE WORKING
<br />DAY.
<br />C. DO NOT PROCEED TO ENCLOSE FIRESTOPPING WITH OTHER CONSTRUCTION UNTIL
<br />INSPECTION AGENCY HAS VERIFIED FIRESTOP INSTALLATION COMPLIES WITH
<br />REQUIREMENTS OF CONTRACT DOCUMENTS.
<br />D. WHERE DEFICIENCIES ARE FOUND, REPAIR OR REPLACE FIRESTOPPING SO THAT IT
<br />COMPLIES WITH REQUIREMENTS OF TESTED AND LISTED SYSTEM DESIGN.
<br />3.6 CLEANING:
<br />A. CLEAN OFF EXCESS FILL MATERIALS AND SEALANTS ADJACENT TO OPENINGS AND
<br />JOINTS AS WORK PROGRESSES. USE METHODS AND CLEANING MATERIALS APPROVED
<br />BY MANUFACTURERS OF FIRESTOPPING PRODUCTS AND OR ASSEMBLIES IN WHICH
<br />OPENINGS AND JOINTS OCCUR.
<br />B. PROTECT FIRESTOPPING DURING AND AFTER CURING PERIOD FROM CONTACT WITH
<br />CONTAMINATING SUBSTANCES.
<br />END OF SECTION
<br />SECTION 07 9200 - JOINT SEALANTS
<br />PART 1 - GENERAL
<br />1.1 SUMMARY:
<br />A. DEFINITIONS:
<br />1. JOINT SEALANT COMPOUND: A MATERIAL USED IN FILLING JOINTS AND SEAMS,
<br />HAVING PROPERTIES OF ADHESION AND COHESION; NOT REQUIRED TO HAVE
<br />EXTENSIBILITY AND RECOVERY PROPERTIES, GENERALLY FOR APPLICATION IN
<br />INTERIOR JOINTS NOT SUBJECT TO MOVEMENT.
<br />2. CAULK: THE PROCESS OF FILLING JOINTS, WITHOUT REGARD TO TYPE OF
<br />MATERIAL.
<br />3. JOINT FAILURE: A CAULKED JOINT EXHIBITING ONE OR MORE OF THE FOLLOWING
<br />CHARACTERISTICS:
<br />A. AIR AND/OR WATER LEAKAGE.
<br />B. MIGRATION AND/OR REVERSION.
<br />C. LOSS OF ADHESION.
<br />D. LOSS OF COHESION.
<br />E. FAILURE TO CURE.
<br />F. DISCOLORATION.
<br />G. STAINING OF ADJACENT WORK.
<br />H. DEVELOPMENT OF BUBBLES, AIR POCKETS OR VOIDS.
<br />1.2 ACTION SUBMITTALS:
<br />A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DESCRIPTION, INDICATING
<br />CONFORMANCE WITH SPECIFIED REQUIREMENTS AND INSTALLATION INSTRUCTIONS
<br />FOR EACH TYPE OF SEALANT. INDICATE PREPARATION AND PRIMING REQUIREMENTS
<br />FOR EACH SUBSTRATE CONDITION.
<br />B. COLOR SAMPLES:
<br />1. SAMPLES FOR INITIAL INSPECTION: SAMPLES SHALL BE ACTUAL MATERIALS
<br />OR LITERATURE DEPICTING ACTUAL COLORS OF STANDARD COLOR MATERIALS
<br />SHOWING FULL RANGE OF COLORS AVAILABLE FOR EACH PRODUCT EXPOSED
<br />TO VIEW.
<br />2. SUBMIT SAMPLES OF CUSTOM COLOR SEALANT MATERIALS MATCHING COLOR
<br />SAMPLE PROVIDED BY ARCHITECT.
<br />3. SAMPLES FOR VERIFICATION: FOR EACH KIND AND COLOR OF JOINT SEALANT
<br />REQUIRED, PROVIDE SAMPLES WITH JOINT SEALANTS IN 1/2" WIDE JOINTS
<br />FORMED BETWEEN TWO 6" LONG STRIPS OF MATERIAL MATCHING
<br />APPEARANCE OF EXPOSED SURFACES ADJACENT TO JOINT SEALANTS.
<br />1.3 INFORMATIONAL SUBMITTALS:
<br />A. ADHESION COMPATIBILITY TEST RESULTS: SUBMIT A LETTER FROM SEALANT
<br />MANUFACTURER INDICATING ADHESION AND COMPATIBILITY TESTING HAS BEEN
<br />PERFORMED AND THAT MATERIALS ARE COMPATIBLE AND THAT ADHESION IS
<br />ACCEPTABLE. INDICATE REQUIREMENTS FOR PRIMERS OR SPECIAL PREPARATION.
<br />B. SUBSTRATE STAINING TEST RESULTS: SUBMIT A LETTER FROM SEALANT
<br />MANUFACTURER INDICATING THAT SUBSTRATE STAIN TESTING HAS BEEN PERFORMED
<br />ON ACTUAL SAMPLES OF SUBSTRATES INDICATED TO RECEIVE JOINT SEALANT AND
<br />THAT SEALANT WAS FOUND TO BE NON-STAINING TO SUBSTRATE. INDICATE
<br />REQUIREMENTS FOR PRIMERS OR SPECIAL PREPARATION TO MEET NON-STAINING
<br />REQUIREMENTS.
<br />C. JOINT SEALANT SCHEDULE: INCLUDE THE FOLLOWING INFORMATION:
<br />1. JOINT-SEALANT APPLICATION, JOINT LOCATION, AND DESIGNATION.
<br />2. JOINT-SEALANT MANUFACTURER AND PRODUCT NAME.
<br />3. JOINT-SEALANT FORMULATION.
<br />4. JOINT-SEALANT COLOR.
<br />1.4 QUALITY ASSURANCE:
<br />A. APPLICABLE STANDARDS AS REFERENCED HEREIN:
<br />1. ASTM INTERNATIONAL (ASTM).
<br />2. UNITED STATES DEPARTMENT OF AGRICULTURE (USDA).
<br />B. ADHESION COMPATIBILITY TESTS: PERFORM TESTS ON ACTUAL SAMPLES OF
<br />ALUMINUM FRAMING SYSTEM COMPONENTS, TO DETERMINE THAT MATERIALS ARE
<br />COMPATIBLE AND THAT ADHESION IS ACCEPTABLE. IDENTIFY REQUIREMENTS FOR
<br />PRIMERS OR SPECIAL PREPARATION.
<br />C. SUBSTRATE STAINING TEST RESULTS: PERFORM TEST ON ACTUAL SAMPLES OF
<br />STONE VENEER TO RECEIVE JOINT SEALANT TO DETERMINE THAT SEALANT IS
<br />NON-STAINING TO SUBSTRATE. IDENTIFY REQUIREMENTS FOR PRIMERS OR SPECIAL
<br />PREPARATION TO MEET NON-STAINING REQUIREMENTS.
<br />1. TEST POROUS SUBSTANCES IN ACCORD WITH ASTM C1248-08(2012).
<br />2. TEST NON-POROUS SUBSTRATES IN ACCORD WITH ASTM D2203-01(2011).
<br />D. VOC CONTENT OF INTERIOR SEALANTS: SEALANTS AND SEALANT PRIMERS USED
<br />INSIDE THE WEATHERPROOFING SYSTEM SHALL HAVE A VOC CONTENT LESS THAN
<br />THE CURRENT VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY MANAGEMENT
<br />DISTRICT (SCAQMD) RULE #1113, ARCHITECTURAL COATING, RULES IN EFFECT
<br />JANUARY 1, 2004.
<br />E. ARCHITECT RESERVES THE RIGHT TO REJECT WORK NOT IN CONFORMANCE WITH
<br />SELECTED COLORS, BASED UPON SAMPLES SUBMITTED.
<br />1.5 PROJECT/ SITE CONDITIONS:
<br />A. PROTECTION OF ADJACENT SURFACES:
<br />1. PROTECT BY APPLYING MASKING MATERIAL OR MANIPULATING APPLICATION
<br />EQUIPMENT TO KEEP MATERIALS IN JOINT. IF MASKING MATERIALS ARE
<br />USED, ALLOW NO TAPE TO TOUCH CLEANED SURFACES TO RECEIVE SEALANT.
<br />REMOVE TAPE IMMEDIATELY AFTER CAULKING, BEFORE SURFACE SKIN
<br />BEGINS TO FORM.
<br />2. REMOVE MISAPPLIED MATERIALS FROM SURFACES BY USING SOLVENTS
<br />AND METHODS RECOMMENDED BY MANUFACTURER.
<br />3. AT SURFACES FROM WHICH MATERIALS HAVE BEEN REMOVED, RESTORE
<br />TO ORIGINAL CONDITION AND APPEARANCE.
<br />1.6 WARRANTIES:
<br />A. INSTALLER'S WARRANTY: WARRANT WORK TO BE FREE FROM DEFECTS IN MATERIALS
<br />AND WORKMANSHIP, INCLUDING JOINT FAILURE, FOR A PERIOD OF TWO YEARS.
<br />B. WARRANTIES SHALL BEGIN AT DATE OF SUBSTANTIAL COMPLETION.
<br />PART 2 - PRODUCTS
<br />2.1 ONE-PART, NON-SAG POLYURETHANE SEALANT:
<br />A. ACCEPTABLE PRODUCTS:
<br />1. BASF BUILDING PRODUCTS, SONOLASTIC NP-1.
<br />2. PECORA CORP., DYNATROL I-XL.
<br />3. TREMCO, INC., AN RPM COMPANY, VULKEM 116
<br />4. TREMCO, INC., AN RPM COMPANY, DYMONIC.
<br />B. CHARACTERISTICS:
<br />1. TYPE: ONE-PART, NON-SAG POLYURETHANE-BASED SEALANT; MEETING
<br />ASTM C920-11, TYPE S, GRADE NS, CLASS 25, FOR USE NT.
<br />2. COLORS: COLORS AS SELECTED BY ARCHITECT.
<br />2.2 SILICONE BATH SEALANT FOR WET AREAS:
<br />A. ACCEPTABLE PRODUCTS:
<br />1. BASF BUILDING SYSTEMS, OMNIPLUS.
<br />2. DOW CORNING CORP., 786 MILDEW-RESISTANT SILICONE SEALANT.
<br />3. FRANKLIN INTERNATIONAL, TITEBOND KITCHEN & BATH SEALANT.
<br />4. GE ADVANCED MATERIALS, SANITARY SCS1700.
<br />5. PECORA CORP., #898NST SILICONE SANITARY SEALANT.
<br />B. CHARACTERISTICS:
<br />1. TYPE: ONE-PART SILICON RUBBER, MILDEW- AND STAIN-RESISTANT, ACID-
<br />CURING SILICONE SEALANT; MEETING ASTM C920-11, TYPE S, GRADE NS,
<br />CLASS 25, FOR USE NT.
<br />2. COLOR: CLEAR, WHITE OR OFF-WHITE, AS SELECTED BY ARCHITECT.
<br />2.3 TWO-PART POLYURETHANE SEALANT FOR HORIZONTAL TRAFFIC-BEARING PAVEMENTS:
<br />A. ACCEPTABLE PRODUCTS:
<br />1. BASF BUILDING SYSTEMS, SONOLASTIC SL 2.
<br />2. PECORA CORP., UREXPAN NR-200.
<br />3. TREMCO, INC., AN RPM COMPANY, 45 SSL.
<br />B. CHARACTERISTICS:
<br />1. TYPE: TWO-COMPONENT POLYURETHANE SEALANT FOR HORIZONTAL
<br />TRAFFIC-BEARING SURFACES MEETING ASTM C920-11, TYPE M, GRADE P
<br />OR NS, MINIMUM CLASS 25, FOR USE T; SELF-LEVELING FOR FLAT SURFACES
<br />AND NON-SAG FOR SLOPED SURFACES.
<br />2. COLORS: COLORS AS SELECTED BY ARCHITECT.
<br />2.4 SOLVENT-RELEASE-CURING ACRYLIC SEALANT:
<br />A. ACCEPTABLE PRODUCTS:
<br />1. FRANKLIN INTERNATIONAL, TITEBOND PAINTERS PLUS CAULK.
<br />2. SCHNEE-MOREHEAD, INC., ACRYL-R ACRYLIC SEALANT.
<br />3. TREMCO, INC., AN RPM COMPANY, MONO 555.
<br />B. CHARACTERISTICS:
<br />1. TYPE: ONE-PART, ACRYLIC POLYMER SEALANT, MEETING ASTM C1311-11.
<br />2. COLORS: STANDARD COLORS AS SELECTED BY ARCHITECT.
<br />2.5 PAINTABLE ACRYLIC-LATEX JOINT SEALANT:
<br />A. ACCEPTABLE PRODUCTS:
<br />1. BASF BUILDING SYSTEMS, SONOLASTIC SONOLAC.
<br />2. BOSTIK, CHEM-CALK 600.
<br />3. FRANKLIN INTERNATIONAL, TITEBOND PAINTERS CAULK.
<br />4. GE ADVANCED MATERIALS, RCS20.
<br />5. PECORA CORP., AC-20 ACRYLIC LATEX.
<br />6. TREMCO, INC., AN RPM COMPANY, TREMFLEX 834.
<br />B. CHARACTERISTICS: FLEXIBLE, PAINTABLE, NON-STAINING, NON-BLEEDING ACRYLIC LATEX
<br />OR SILICONIZED ACRYLIC EMULSION, MEETING ASTM C834-10, TYPE OP, GRADE NF.
<br />2.6 ACCESSORY MATERIALS:
<br />A. JOINT CLEANER: TYPE RECOMMENDED BY MATERIAL MANUFACTURER FOR
<br />SUBSTRATES INDICATED.
<br />B. JOINT PRIMER/SEALER: TYPE RECOMMENDED BY MATERIAL MANUFACTURER FOR
<br />SUBSTRATES, CONDITIONS AND EXPOSURES INDICATED.
<br />C. BOND BREAKER TAPE: PLASTIC TAPE APPLIED TO CONTACT SURFACES WHERE BOND
<br />TO SUBSTRATE OR JOINT FILLER MUST BE AVOIDED FOR MATERIAL PERFORMANCE.
<br />D. SEALANT BACKER ROD: COMPRESSIBLE ROD STOCK AS RECOMMENDED BY SEALANT
<br />MANUFACTURER FOR COMPATIBILITY WITH SEALANT. PROVIDE SIZE AND SHAPE OF ROD
<br />TO CONTROL JOINT DEPTH.
<br />E. TOOLING AGENT: AGENT RECOMMENDED BY MATERIAL MANUFACTURER TO ENSURE
<br />CONTACT OF MATERIAL WITH INNER JOINT FACES.
<br />PART 3 - EXECUTION
<br />3.1 JOB MOCK-UP:
<br />A. PREPARE, CAULK AND FINISH ONE MOCK-UP SAMPLE OF EACH JOINT CONDITION.
<br />B. SAMPLE JOINTS SHALL BE APPROVED BY ARCHITECT PRIOR TO BEGINNING WORK.
<br />APPROVED, UNDAMAGED MOCK-UP JOINTS SHALL SERVE AS A STANDARD OF QUALITY
<br />FOR THE REMAINDER OF THE WORK.
<br />3.2 JOINT SURFACE PREPARATION:
<br />A. CLEAN JOINTS OF DEBRIS AND PROJECTIONS INCLUDING SHIMS.
<br />B. CLEAN JOINT SURFACES IMMEDIATELY BEFORE CAULKING JOINTS. REMOVE DIRT,
<br />INSECURE COATINGS, MOISTURE AND OTHER SUBSTANCES WHICH WOULD INTERFERE
<br />WITH BOND.
<br />C. ROUGHEN JOINT SURFACES OF NON-POROUS MATERIALS, UNLESS MATERIAL
<br />MANUFACTURER'S PRODUCT DATA INDICATES EQUAL BOND STRENGTH AS POROUS
<br />SURFACES. RUB WITH FINE ABRASIVE CLOTH OR WOOL TO PRODUCE DULL SHEEN.
<br />3.3 APPLICATION:
<br />A. COMPLY WITH JOINT SEALANT MATERIAL MANUFACTURER'S PRODUCT DATA AND ASTM
<br />C1193-09 EXCEPT WHERE MORE STRINGENT REQUIREMENTS ARE SPECIFIED.
<br />B. PRIME JOINT SURFCES WHERE RECOMMENDED BY MATERIAL MANUFACTURER. DO
<br />NOT ALLOW PRIMER/SEALER TO SPILL OR MIGRATE ONTO ADJACENT SURFACES.
<br />C. INSTALL BACKER ROD FOR JOINT SEALANT MATERIALS, EXCEPT WHERE RECOMMENDED
<br />BY MATERIAL MANUFACTURER TO BE OMITTED FOR APPLICATION INDICATED.
<br />1. PLACE BACKER ROD TO MAINTAIN RECOMMENDED SEALANT THICKNESS AND
<br />PROFILE.
<br />2. PLACE ROD AT DEPTH TO PROVIDE SEALANT MANUFACTURER'S
<br />RECOMMENDED SEALANT DEPTH.
<br />3. DO NOT TWIST ROD DURING INSTALLATION.
<br />4. PLACE ROD TO MINIMIZE POSSIBILITY OF EXTRUSION WHEN JOINT IS
<br />COMPRESSED.
<br />5. INSTALL BOND BREAKER TAPE IN LIEU OF BACKER ROD FOR SHALLOW, CLOSED
<br />JOINTS AND AS RECOMMENDED BY MANUFACTURER'S PRODUCT DATA.
<br />D. EMPLOY INSTALLATION TECHNIQUES WHICH WILL ENSURE THAT MATERIALS ARE
<br />DEPOSITED IN UNIFORM, CONTINUOUS RIBBONS WITHOUT GAPS OR AIR POCKETS,
<br />WITH COMPLETE WETTING OF JOINT BOND SURFACES. WHERE HORIZONTAL JOINTS
<br />ARE BETWEEN A HORIZONTAL SURFACE AND A VERTICAL SURFACE, FILL JOINT TO FORM
<br />SLIGHT COVE SO THAT JOINT WILL NOT TRAP MOISTURE AND DEBRIS.
<br />E. DO NOT ALLOW MATERIALS TO OVERFLOW ONTO ADJACENT SURFACES. PREVENT
<br />STAINING OF ADJACENT SURFACES.
<br />F. REMOVE EXCESS AND MISPLACED MATERIALS AS WORK PROGRESSES. CLEAN THE
<br />ADJOINING SURFACES TO REMOVE MISPLACED MATERIALS, WITHOUT DAMAGE TO
<br />ADJACENT SURFACES OR FINISHES.
<br />G. INTERIOR JOINTS: AT INTERIOR JOINTS AND SEAMS AT ABUTTING AND ADJACENT
<br />MATERIALS, RECESS JOINT SEALANT 3/16" IN JOINTS WIDER THAN 1/4". AT JOINTS 1/4"
<br />OR LESS IN WIDTH, TOOL JOINT SEALANT FLUSH.
<br />H. TOOL JOINTS OF NON-SAG SEALANT TO CONCAVE PROFILE AND SMOOTH, UNIFORM
<br />SURFACE, FLUSH WITH EDGES OF SUBSTRATE. MAINTAIN SEALANT DEPTH-TO-WIDTH
<br />RATIO IN ACCORD WITH MANUFACTURER'S PRODUCT DATA.
<br />I. CURE JOINT SEALANTS IN ACCORD WITH MANUFACTURER'S PRODUCT DATA TO OBTAIN
<br />HIGH EARLY BOND STRENGTH, INTERNAL COHESIVE STRENGTH AND SURFACE
<br />DURABILITY. PROTECT UNCURED SURFACES FROM CONTAMINATION AND PHYSICAL
<br />DAMAGE.
<br />3.4 JOINT SEALANT SCHEDULE:
<br />A. INTERIOR JOINTS AT PERIMETER OF WINDOWS AND OF HOLLOW METAL FRAMING:
<br />ONE-PART, NON-SAG POLYURETHANE SEALANT.
<br />B. INTERIOR CONCEALED BEDDING JOINTS AND THRESHOLDS: SOLVENT-RELEASE-CURING
<br />ACRYLIC SEALANT.
<br />C. INTERIOR HORIZONTAL TRAFFIC-BEARING JOINTS, EXCLUDING TILE FLOOR JOINTS:
<br />TWO-PART POLYURETHANE SEALANT.
<br />D. FIRESTOPPED JOINTS: FIRESTOP SEALANT AS SPECIFIED IN FIRESTOPPING SECTION.
<br />E. TYPICAL INTERIOR JOINTS AND SEAMS AT ABUTTING AND ADJACENT MATERIALS
<br />EXCEPT AS SPECIFIED HEREIN: PAINTABLE ACRYLIC-LATEX JOINT SEALANT.
<br />F. INTERIOR JOINTS IN CONJUNCTION WITH FIXTURES AND TILE FINISHES: SILICONE
<br />BATH SEALANT.
<br />END OF SECTION
<br />SECTION 08 1416 - FLUSH WOOD DOORS
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A. SECTION INCLUDES:
<br />1. WOOD DOORS.
<br />B. RELATED REQUIREMENTS:
<br />1. DIVISION 01 - GENERAL REQUIREMENTS.
<br />2. SECTION 09 9000 - PAINTING AND COATING.
<br />1.02 DESIGN REQUIREMENTS
<br />A. DRAWINGS INDICATE SIZES, LOCATIONS AND GENERAL DETAILS OF WOOD DOOR
<br />CONSTRUCTION AND INSTALLATION.
<br />B. REGULATORY REQUIREMENTS:
<br />1. FIRE RATED DOORS SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING
<br />AND CERTIFICATION AGENCY IN ACCORDANCE WITH LOCAL BUILDING CODES
<br />AND ACCEPTABLE TO THE AUTHORITIES HAVING JURISDICTION. THE LISTED
<br />DOORS SHALL MEET OR EXCEED THE REQUIREMENTS OF UL10B, NFPA 252 AND
<br />NFPA 80. ALL DOOR REQUIRING FIRE-RATING SHALL CARRY EITHER A UL OR
<br />ITS (INTERTEK TESTING SERVICES-WARNOCK HERSEY) LABEL.
<br />2. ASTM E2074 – STANDARD TEST METHOD FOR FIRE TESTS OF DOOR
<br />ASSEMBLIES, INCLUDING POSITIVE PRESSURE ON SIDE-HINGED AND PIVOTED
<br />SWINGING DOOR ASSEMBLIES.
<br />1.03 SUBMITTALS
<br />A. SHOP DRAWINGS: SUBMIT SCHEDULES, PLANS, ELEVATIONS AND DETAILS INDICATING
<br />DOOR CONSTRUCTION DETAILS, OPENING IDENTIFICATION SYMBOLS, SIZES, DOOR
<br />TYPE AND GRADE, FIRE CLASSIFICATION, SWING, LIGHT AND LOUVER CUTOUT SIZE
<br />AND LOCATIONS, AND UNDERCUTS.
<br />B. PRODUCT DATA: SUBMIT MANUFACTURERS TECHNICAL DATA FOR EACH SPECIFIED
<br />DOOR TYPE, INCLUDING DETAILS OF WOOD SPECIES, DESIGN AND CONSTRUCTION,
<br />FACTORY FINISHING SPECIFICATIONS AND INSTALLATION INSTRUCTIONS.
<br />C. COLOR/FINISH SAMPLES: SUBMIT SAMPLES OF NOT LESS THAN 4-INCH BY 6-INCH ON
<br />REPRESENTATIVE DOOR FINISH AND SAMPLES OF 3-INCH BY 8-INCH FOR THE EXPOSED
<br />EDGES. EACH SAMPLE SHALL BEAR A LABEL IDENTIFYING THE JOB NAME, ARCHITECT,
<br />CONTRACTOR AND THE WOODWORK INSITUTE FINISH SYSTEM NUMBER.
<br />1.04 QUALITY ASSURANCE
<br />A. WOOD DOORS CONSTRUCTION, MANUFACTURE, AND FABRICATION SHALL CONFORM TO
<br />ANSI/WDMA I.S. 1-A, CUSTOM GRADE, EXTRA HEAVY DUTY GRADE INCLUDING THE
<br />LATEST REVISIONS, AND SPECIAL REQUIREMENTS SPECIFIED.
<br />B. DOORS SHALL BE FABRICATED, HARDWARE FACTORY FITTED AND MACHINED, AND
<br />FACTORY FINISHED, UNLESS NOTED OTHERWISE.
<br />C. WOOD DOOR FINISHES SHALL COMPLY WITH THE ARCHITECTURAL WOODWORK
<br />INSTITUTE STANDARDS.
<br />D. DOORS SHALL BE PRODUCTS OF ONE MANUFACTURER.
<br />E. DOOR MODIFICATIONS ARE NOT PERMITTED, UNLESS REVIEWED BY THE ARCHITECT OF
<br />RECORD.
<br />1.05 DELIVERY, STORAGE AND HANDLING
<br />A. DELIVER MATERIALS IN MANUFACTURERS ORIGINAL, UNOPENED, UNDAMAGED
<br />CONTAINERS WITH IDENTIFICATION LABELS INTACT.
<br />B. DELIVER DOORS TO THE PROJECT SITE ONLY AFTER BUILDING HAS BEEN PROVIDED
<br />WITH DESIGN TEMPERATURE AND HUMIDITY.
<br />C. STORE AND HANDLE IN ACCORDANCE WITH ANSI/WDMA I.S.1-A. STORE DOORS
<br />PROTECTED FROM EXPOSURE TO HARMFUL CONDITIONS AND AT TEMPERATURE AND
<br />HUMIDITY CONDITIONS RECOMMENDED BY THE MANUFACTURER.
<br />1.06 PROJECT CONDITIONS
<br />A. DO NOT INSTALL DOORS UNTIL BUILDING IS ENCLOSED AND AMBIENT CONDITIONS ARE
<br />WITHIN THE TEMPERATURE AND HUMIDITY RANGE RECOMMENDED BY DOOR
<br />MANUFACTURER.
<br />1.07 WARRANTY
<br />A. MANUFACTURER SHALL PROVIDE A LIFE TIME MATERIAL WARRANTY FOR INTERIOR
<br />DOORS.
<br />B. INSTALLER SHALL PROVIDE A TWO YEAR FABRICATION AND INSTALLATION WARRANTY
<br />FOR ALL DOORS.
<br />PART 2 - PRODUCTS
<br />2.01 MANUFACTURERS
<br />A. PROVIDE PRODUCTS MANUFACTURED BY ONE OF THE FOLLOWING:
<br />1. ALGOMA HARDWOOD INC.
<br />2. MARSHFIELD DOOR SYSTEMS.
<br />3. EGGERS INDUSTRIES.
<br />4. OR EQUAL.
<br />2.02 DOOR CONSTRUCTION
<br />A. LAMINATED, SHIELDED CORE, WXR&20PP, 20&MIN.
<br />1. THICKNESS: 1-3/4 INCH.
<br />A. CLEAR FINISH:
<br />1) GRADE: PREMIUM.
<br />2) FACE: PLAIN SLICED WHITE MAPLE.
<br />2. CROSSBANDS: HARDWOOD VENEER OR ENGINEERED HIGH DENSITY
<br />FIBERBOARD, 1/16 INCH THICK.
<br />3. SIDE EDGES: 3/4 INCH, VENEER TO MATCH FACE VENEER, BONDED TO CORE.
<br />FACTORY INSTALL CONCEALED INTUMESCENT SEALS PER UL 10C FOR
<br />POSITIVE PRESSURE FIRE DOORS.
<br />4. TOP AND BOTTOM EDGES: 1&1/8 INCH, BONDED TO CORE. FACTORY INSTALL
<br />INTUMESCENT SEALS AT TOP RAIL PER UL 10C FOR POSITIVE PRESSURE FIRE
<br />DOORS.
<br />5. FACE ASSEMBLY ADHESIVE: TYPE I, WATERPROOF.
<br />6. CORE ASSEMBLY ADHESIVE: TYPE II, WATER&RESISTANT.
<br />7. CORE: BONDED LOW DENSITY STAVED WOOD.
<br />8. MOISTURE STRIPPING: NOT APPLICABLE.
<br />9. SHIELDING: SHEET LEAD BONDED ONE SIDE OR TWO SIDES TO CROSSBAND,
<br />THICKNESS TO CONFORM TO SHIELDING REQUIREMENTS OF WALL IN WHICH
<br />DOOR IS INSTALLED.
<br />10. BLOCKING FOR HARDWARE: FLAME RESISTANT, 6 INCH TOP EDGE FOR
<br />CLOSERS, 5.5 INCHES FOR BOTTOM HARDWARE OR AUTOMATIC CLOSERS
<br />WHERE APPLICABLE, 5 X 18 INCH LOCK BLOCKS, 5.5 INCH CROSS BLOCKING
<br />FOR PANIC HARDWARE, 5 X 12 INCH FOR FLOOR CLOSERS OR PIVOT HINGES
<br />WHERE APPLICABLE.
<br />11. ALGOMA HARDWOODS, INC.'S "ALGOMA GRADE LEAD LINED DOOR, FD 1/3
<br />HOUR"; MARSHFIELD DOOR SYSTEMS, INC.'S "X-RAY DOOR WXR-20"; EGGERS
<br />INDUSTRIES, "LEAD SHIELD DOOR & 20 MINUTE FIRE DOOR.
<br />2.03 FABRICATION
<br />A. FABRICATE FIRE&RATED DOORS IN ACCORDANCE WITH WI QUALITY STANDARDS AND
<br />WDMAI.S.1 & A & LATEST EDITION AND TO UL OR WH REQUIREMENTS. ATTACH
<br />PERMANENT METAL
<br />FIRE & RATING LABEL TO DOOR EDGE, EITHER ON HINGE STILE OR TOP EDGE.
<br />B. PRE & MACHINE DOORS AT FACTORY FOR FINISH HARDWARE. CUTOUTS FOR
<br />HARDWARE IN DOORS HAVING A FIRE RATING OF 20 MINUTES OR MORE SHALL BE
<br />ACCOMPLISHED AT THE FACTORY BEFORE LABELS ARE AFFIXED. PREPARATION SHALL
<br />BE PERFORMED IN ACCORDANCE WITH MANUFACTURER’S INSPECTION SERVICE
<br />PROCEDURE AND UNDER LABEL SERVICE.
<br />C. VENEER: FACE VENEER GRAIN SHALL RUN VERTICALLY; CROSSBAND VENEER RUN
<br />HORIZONTALLY.
<br />2.04 FACTORY FINISH
<br />A. FACTORY FINISH: PREMIUM FINISH, MEET OR EXCEED PERFORMANCE STANDARDS OF
<br />WI SYSTEM CATALYZED POLYURETHANE. FACTORY & FINISHED DOORS SHALL BE
<br />INSTALLED JUST PRIOR TO SUBSTANTIAL COMPLETION.
<br />1. CLEAR FINISH: WI SYSTEM 5, CATALYZED POLYURETHANE.
<br />PART 3 - EXECUTION
<br />3.1 EXAMINATION
<br />A. VERIFY THAT OPENINGS ARE READY TO RECEIVE WORK AND FIELD MEASUREMENTS
<br />ARE AS INDICATED ON SHOP DRAWINGS.
<br />B. BEGINNING OF INSTALLATION MEANS ACCEPTANCE OF EXISTING CONDITIONS.
<br />C. PRODUCT SCHEDULE: FOR HOLLOW-METAL DOORS AND FRAMES, PREPARED BY OR
<br />UNDER THE SUPERVISION OF SUPPLIER, USING SAME REFERENCE NUMBERS FOR
<br />DETAILS AND OPENINGS AS THOSE ON DRAWINGS. COORDINATE WITH FINAL DOOR
<br />HARDWARE SCHEDULE.
<br />1.7 INFORMATIONAL SUBMITTALS
<br />A. PRODUCT TEST REPORTS: FOR EACH TYPE OF HOLLOW-METAL DOOR AND FRAME
<br />ASSEMBLY, FOR TESTS PERFORMED BY A QUALIFIED TESTING AGENCY.
<br />B. OVERSIZE CONSTRUCTION CERTIFICATION: FOR ASSEMBLIES REQUIRED TO BE
<br />FIRE-RATED AND EXCEEDING LIMITATIONS OF LABELED ASSEMBLIES.
<br />1.8 DELIVERY, STORAGE, AND HANDLING
<br />A. DELIVER HOLLOW-METAL DOORS AND FRAMES PALLETIZED, PACKAGED, OR CRATED TO
<br />PROVIDE PROTECTION DURING TRANSIT AND PROJECT-SITE STORAGE. DO NOT USE
<br />NONVENTED PLASTIC.
<br />1. PROVIDE ADDITIONAL PROTECTION TO PREVENT DAMAGE TO
<br />FACTORY-FINISHED UNITS.
<br />B. DELIVER WELDED FRAMES WITH TWO REMOVABLE SPREADER BARS ACROSS BOTTOM
<br />OF FRAMES, TACK WELDED TO JAMBS AND MULLIONS.
<br />C. STORE HOLLOW-METAL DOORS AND FRAMES VERTICALLY UNDER COVER AT PROJECT
<br />SITE WITH HEAD UP. PLACE ON MINIMUM 4-INCH- HIGH WOOD BLOCKING. PROVIDE
<br />MINIMUM 1/4-INCH SPACE BETWEEN EACH STACKED DOOR TO PERMIT AIR CIRCULATION.
<br />PART 2 - PRODUCTS
<br />2.1 MANUFACTURERS
<br />A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />PRODUCTS BY ONE OF THE FOLLOWING:
<br />1. CECO DOOR; ASSA ABLOY.
<br />2. CURRIES COMPANY; ASSA ABLOY.
<br />3. REPUBLIC DOORS AND FRAMES.
<br />4. OR APPROVED EQUAL
<br />B. SOURCE LIMITATIONS: OBTAIN HOLLOW-METAL DOOR AND FRAMES FROM SINGLE
<br />SOURCE FROM SINGLE MANUFACTURER.
<br />2.2 PERFORMANCE REQUIREMENTS
<br />A. FIRE-RATED ASSEMBLIES: COMPLYING WITH NFPA 80 AND LISTED AND LABELED BY A
<br />QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION FOR
<br />FIRE-PROTECTION RATINGS AND TEMPERATURE-RISE LIMITS INDICATED, BASED ON
<br />TESTING AT POSITIVE PRESSURE ACCORDING TO NFPA 252 OR UL 10C.
<br />1. SMOKE- AND DRAFT-CONTROL ASSEMBLIES: PROVIDE ASSEMBLIES WITH
<br />GASKETS LISTED AND LABELED FOR SMOKE AND DRAFT CONTROL BY A
<br />QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING
<br />JURISDICTION, BASED ON TESTING ACCORDING TO UL 1784 AND INSTALLED
<br />IN COMPLIANCE WITH NFPA 105.
<br />B. FIRE-RATED, BORROWED-LITE ASSEMBLIES: COMPLYING WITH NFPA 80 AND LISTED
<br />AND LABELED BY A QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES
<br />HAVING JURISDICTION, FOR FIRE-PROTECTION RATINGS INDICATED, BASED ON
<br />TESTING ACCORDING TO NFPA 257 OR UL 9.
<br />2.3 INTERIOR STANDARD STEEL DOORS AND FRAMES
<br />A. CONSTRUCT HOLLOW-METAL DOORS AND FRAMES TO COMPLY WITH STANDARDS
<br />INDICATED FOR MATERIALS, FABRICATION, HARDWARE LOCATIONS, HARDWARE
<br />REINFORCEMENT, TOLERANCES, AND CLEARANCES, AND AS SPECIFIED.
<br />B. HEAVY-DUTY DOORS AND FRAMES: SDI A250.8, LEVEL 2; SDI A250.4, LEVEL B PROVIDE
<br />AT ALL SCHEDULED INTERIOR DOOR LOCATIONS EXCEPT STAIRWELLS.
<br />1. DOORS:
<br />A. TYPE: AS INDICATED IN THE DOOR SCHEDULE.
<br />B. THICKNESS: AS INDICATED IN THE DOOR SCHEDULE.
<br />C. FACE: AS INDICATED IN THE DOOR SCHEDULE.
<br />D. EDGE CONSTRUCTION: MODEL 2, SEAMLESS.
<br />E. EDGE BEVEL: PROVIDE MANUFACTURER'S STANDARD BEVELED OR
<br />SQUARE EDGES.
<br />F. CORE: MANUFACTURER'S STANDARD.
<br />G. FIRE-RATED CORE: MANUFACTURER'S STANDARD CORE FOR
<br />FIRE-RATED AND TEMPERATURE-RISE-RATED DOORS.
<br />2. FRAMES:
<br />A. MATERIALS: UNCOATED STEEL SHEET, MINIMUM THICKNESS OF
<br />0.059 INCH.
<br />B. SIDELITE AND TRANSOM FRAMES: FABRICATED FROM SAME
<br />THICKNESS MATERIAL AS ADJACENT DOOR FRAME.
<br />C. CONSTRUCTION: FULL PROFILE WELDED.
<br />3. EXPOSED FINISH: PRIME.
<br />2.4 FRAME ANCHORS
<br />A. JAMB ANCHORS:
<br />1. TYPE: ANCHORS OF MINIMUM SIZE AND TYPE REQUIRED BY APPLICABLE
<br />DOOR AND FRAME STANDARD, AND SUITABLE FOR PERFORMANCE LEVEL
<br />INDICATED.
<br />2. QUANTITY: MINIMUM OF THREE ANCHORS PER JAMB, WITH ONE ADDITIONAL
<br />ANCHOR FOR FRAMES WITH NO FLOOR ANCHOR. PROVIDE ONE ADDITIONAL
<br />ANCHOR FOR EACH 24 INCHES OF FRAME HEIGHT ABOVE 7 FEET.
<br />B. FLOOR ANCHORS: PROVIDE FLOOR ANCHORS FOR EACH JAMB AND MULLION THAT
<br />EXTENDS TO FLOOR.
<br />C. FLOOR ANCHORS FOR CONCRETE SLABS WITH UNDERLAYMENT: ADJUSTABLE-TYPE
<br />ANCHORS WITH EXTENSION CLIPS, ALLOWING NOT LESS THAN 2-INCH HEIGHT
<br />ADJUSTMENT. TERMINATE BOTTOM OF FRAMES AT TOP OF UNDERLAYMENT.
<br />D. MATERIAL: ASTM A 879/A 879M, COMMERCIAL STEEL (CS), 04Z COATING DESIGNATION;
<br />MILL PHOSPHATIZED.
<br />1. FOR ANCHORS BUILT INTO EXTERIOR WALLS, STEEL SHEET COMPLYING WITH
<br />ASTM A 1008/A 1008M OR ASTM A 1011/A 1011M; HOT-DIP GALVANIZED
<br />ACCORDING TO ASTM A 153/A 153M, CLASS B.
<br />2.5 MATERIALS
<br />A. COLD-ROLLED STEEL SHEET: ASTM A 1008/A 1008M, COMMERCIAL STEEL (CS), TYPE B;
<br />SUITABLE FOR EXPOSED APPLICATIONS.
<br />B. HOT-ROLLED STEEL SHEET: ASTM A 1011/A 1011M, COMMERCIAL STEEL (CS), TYPE B;
<br />FREE OF SCALE, PITTING, OR SURFACE DEFECTS; PICKLED AND OILED.
<br />C. METALLIC-COATED STEEL SHEET: ASTM A 653/A 653M, COMMERCIAL STEEL (CS), TYPE B.
<br />D. INSERTS, BOLTS, AND FASTENERS: HOT-DIP GALVANIZED ACCORDING TO
<br />ASTM A 153/A 153M.
<br />E. POWER-ACTUATED FASTENERS IN CONCRETE: FASTENER SYSTEM OF TYPE
<br />SUITABLE FOR APPLICATION INDICATED, FABRICATED FROM CORROSION-RESISTANT
<br />MATERIALS, WITH CLIPS OR OTHER ACCESSORY DEVICES FOR ATTACHING
<br />HOLLOW-METAL FRAMES OF TYPE INDICATED.
<br />F. MINERAL-FIBER INSULATION: ASTM C 665, TYPE I (BLANKETS WITHOUT MEMBRANE
<br />FACING); CONSISTING OF FIBERS MANUFACTURED FROM SLAG OR ROCK WOOL;
<br />WITH MAXIMUM FLAME-SPREAD AND SMOKE-DEVELOPED INDEXES OF 25 AND 50,
<br />RESPECTIVELY; PASSING ASTM E 136 FOR COMBUSTION CHARACTERISTICS.
<br />G. GLAZING: COMPLY WITH REQUIREMENTS IN SECTION 088000 "GLAZING."
<br />H. DOOR SILENCERS: 1/2 INCH DIAMETER TAMPER-PROOF GREY RUBBER CONE-SHAPED
<br />PLUGS.
<br />2.6 FABRICATION
<br />A. HOLLOW-METAL FRAMES: FABRICATE IN ONE PIECE EXCEPT WHERE HANDLING AND
<br />SHIPPING LIMITATIONS REQUIRE MULTIPLE SECTIONS. WHERE FRAMES ARE
<br />FABRICATED IN SECTIONS, PROVIDE ALIGNMENT PLATES OR ANGLES AT EACH
<br />JOINT, FABRICATED OF METAL OF SAME OR GREATER THICKNESS AS FRAMES.
<br />1. PROVIDE COUNTERSUNK, FLAT- OR OVAL-HEAD EXPOSED SCREWS AND BOLTS
<br />FOR EXPOSED FASTENERS UNLESS OTHERWISE INDICATED.
<br />2. DOOR SILENCERS: EXCEPT ON WEATHER-STRIPPED FRAMES, DRILL STOPS
<br />TO RECEIVE DOOR SILENCERS AS FOLLOWS. KEEP HOLES CLEAR DURING
<br />CONSTRUCTION.
<br />A. SINGLE-DOOR FRAMES: DRILL STOP IN STRIKE JAMB TO RECEIVE
<br />THREE DOOR SILENCERS.
<br />B. HARDWARE PREPARATION: FACTORY PREPARE HOLLOW-METAL DOORS AND FRAMES
<br />TO RECEIVE TEMPLATED CYLINDRICAL HARDWARE, AND ELECTRICAL WIRING; INCLUDE
<br />CUTOUTS, REINFORCEMENT, DRILLING, AND TAPPING ACCORDING TO
<br />SDI A250.6, THE DOOR HARDWARE SCHEDULE, AND TEMPLATES.
<br />1. REINFORCE DOORS AND FRAMES TO RECEIVE NONTEMPLATED, CYLINDRICAL,
<br />AND SURFACE-MOUNTED DOOR HARDWARE.
<br />2. COMPLY WITH BHMA A156.115 FOR PREPARING HOLLOW-METAL DOORS AND
<br />FRAMES FOR HARDWARE.
<br />2.7 STEEL FINISHES
<br />A. PRIME FINISH: CLEAN, PRETREAT, AND APPLY MANUFACTURER'S STANDARD PRIMER.
<br />1. SHOP PRIMER: MANUFACTURER'S STANDARD, FAST-CURING, LEAD- AND
<br />CHROMATE-FREE PRIMER COMPLYING WITH SDI A250.10; RECOMMENDED
<br />BY PRIMER MANUFACTURER FOR SUBSTRATE; COMPATIBLE WITH
<br />SUBSTRATE AND FIELD-APPLIED COATINGS DESPITE PROLONGED EXPOSURE.
<br />PART 3 - EXECUTION
<br />3.1 PREPARATION
<br />A. REMOVE WELDED-IN SHIPPING SPREADERS INSTALLED AT FACTORY. RESTORE
<br />EXPOSED FINISH BY GRINDING, FILLING, AND DRESSING, AS REQUIRED TO MAKE
<br />REPAIRED AREA SMOOTH, FLUSH, AND INVISIBLE ON EXPOSED FACES. TOUCH UP
<br />FACTORY-APPLIED FINISHES WHERE SPREADERS ARE REMOVED.
<br />B. DRILL AND TAP DOORS AND FRAMES TO RECEIVE NONTEMPLATED, CYLINDRICAL,
<br />AND SURFACE-MOUNTED DOOR HARDWARE.
<br />3.2 INSTALLATION
<br />A. GENERAL: INSTALL HOLLOW-METAL DOORS AND FRAMES PLUMB, RIGID, PROPERLY
<br />ALIGNED, AND SECURELY FASTENED IN PLACE. COMPLY WITH APPROVED SHOP
<br />DRAWINGS AND WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
<br />B. HOLLOW-METAL FRAMES: COMPLY WITH SDI A250.11OR NAAMM-HMMA 840.
<br />1. SET FRAMES ACCURATELY IN POSITION; PLUMBED, ALIGNED, AND BRACED
<br />SECURELY UNTIL PERMANENT ANCHORS ARE SET. AFTER WALL
<br />CONSTRUCTION IS COMPLETE, REMOVE TEMPORARY BRACES WITHOUT
<br />DAMAGE TO COMPLETED WORK.
<br />A. WHERE FRAMES ARE FABRICATED IN SECTIONS, FIELD SPLICE AT
<br />APPROVED LOCATIONS BY WELDING FACE JOINT CONTINUOUSLY;
<br />GRIND, FILL, DRESS, AND MAKE SPLICE SMOOTH, FLUSH, AND
<br />INVISIBLE ON EXPOSED FACES. TOUCH-UP FINISHES.
<br />B. INSTALL FRAMES WITH REMOVABLE STOPS LOCATED ON
<br />SECURE SIDE OF OPENING.
<br />2. FLOOR ANCHORS: SECURE WITH POSTINSTALLED ANCHORS.
<br />A. FLOOR ANCHORS MAY BE SET WITH POWER-ACTUATED FASTENERS
<br />INSTEAD OF POSTINSTALLED EXPANSION ANCHORS IF SO
<br />INDICATED AND APPROVED ON SHOP DRAWINGS.
<br />3. SOLIDLY PACK MINERAL-FIBER INSULATION INSIDE FRAMES.
<br />4. INSTALLATION TOLERANCES: ADJUST HOLLOW-METAL FRAMES TO THE
<br />FOLLOWING TOLERANCES:
<br />A. SQUARENESS: PLUS OR MINUS 1/16 INCH, MEASURED AT DOOR
<br />RABBET ON A LINE 90 DEGREES FROM JAMB PERPENDICULAR
<br />TO FRAME HEAD.
<br />B. ALIGNMENT: PLUS OR MINUS 1/16 INCH, MEASURED AT JAMBS ON A
<br />HORIZONTAL LINE PARALLEL TO PLANE OF WALL.
<br />C. TWIST: PLUS OR MINUS 1/16 INCH, MEASURED AT OPPOSITE FACE
<br />CORNERS OF JAMBS ON PARALLEL LINES, AND PERPENDICULAR
<br />TO PLANE OF WALL.
<br />D. PLUMBNESS: PLUS OR MINUS 1/16 INCH, MEASURED AT
<br />JAMBS AT FLOOR.
<br />C. HOLLOW-METAL DOORS: FIT AND ADJUST HOLLOW-METAL DOORS ACCURATELY IN
<br />FRAMES, WITHIN CLEARANCES SPECIFIED BELOW.
<br />1. NON-FIRE-RATED STEEL DOORS: COMPLY WITH SDI A250.8 OR NAAMM-HMMA
<br />841 AND NAAMM-HMMA GUIDE SPECIFICATION INDICATED.
<br />D. GLAZING: COMPLY WITH INSTALLATION REQUIREMENTS IN SECTION 088000
<br />"GLAZING" AND WITH HOLLOW-METAL MANUFACTURER'S WRITTEN INSTRUCTIONS.
<br />3.3 CLEANING AND TOUCHUP
<br />A. PRIME-COAT TOUCHUP: IMMEDIATELY AFTER ERECTION, SAND SMOOTH RUSTED OR
<br />DAMAGED AREAS OF PRIME COAT AND APPLY TOUCHUP OF COMPATIBLE AIR-DRYING,
<br />RUST-INHIBITIVE PRIMER.
<br />B. TOUCHUP PAINTING: CLEANING AND TOUCHUP PAINTING OF ABRADED AREAS OF
<br />PAINT ARE SPECIFIED IN PAINTING SECTIONS.
<br />END OF SECTION
<br />DIVISION 8 - OPENINGS
<br />SECTION 08 1113 - HOLLOW METAL FRAMES
<br />PART 1 - GENERAL
<br />1.1 RELATED DOCUMENTS
<br />A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL
<br />AND SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS,
<br />APPLY TO THIS SECTION.
<br />1.2 SUMMARY
<br />A. SECTION INCLUDES:
<br />1. INTERIOR STANDARD STEEL DOORS AND FRAMES.
<br />1.3 DEFINITIONS
<br />A. MINIMUM THICKNESS: MINIMUM THICKNESS OF BASE METAL WITHOUT COATINGS
<br />ACCORDING TO NAAMM-HMMA 803 OR SDI A250.8.
<br />1.4 COORDINATION
<br />A. COORDINATE ANCHORAGE INSTALLATION FOR HOLLOW-METAL FRAMES. FURNISH
<br />SETTING DRAWINGS, TEMPLATES, AND DIRECTIONS FOR INSTALLING ANCHORAGES,
<br />INCLUDING SLEEVES, CONCRETE INSERTS, ANCHOR BOLTS, AND ITEMS WITH
<br />INTEGRAL ANCHORS. DELIVER SUCH ITEMS TO PROJECT SITE IN TIME FOR
<br />INSTALLATION.
<br />B. COORDINATE REQUIREMENTS FOR INSTALLATION OF DOOR HARDWARE, ELECTRIFIED
<br />DOOR HARDWARE, AND ACCESS CONTROL AND SECURITY SYSTEMS.
<br />1.5 PREINSTALLATION MEETINGS
<br />A. PREINSTALLATION CONFERENCE: CONDUCT CONFERENCE AT PROJECT SITE.
<br />1.6 ACTION SUBMITTALS
<br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT.
<br />1. INCLUDE CONSTRUCTION DETAILS, MATERIAL DESCRIPTIONS, CORE
<br />DESCRIPTIONS, FIRE-RESISTANCE RATINGS, TEMPERATURE-RISE RATINGS,
<br />AND FINISHES.
<br />B. SHOP DRAWINGS: INCLUDE THE FOLLOWING:
<br />1. ELEVATIONS OF EACH DOOR TYPE.
<br />2. DETAILS OF DOORS, INCLUDING VERTICAL- AND HORIZONTAL-EDGE DETAILS
<br />AND METAL THICKNESSES.
<br />3. FRAME DETAILS FOR EACH FRAME TYPE, INCLUDING DIMENSIONED PROFILES
<br />AND METAL THICKNESSES.
<br />4. LOCATIONS OF REINFORCEMENT AND PREPARATIONS FOR HARDWARE.
<br />5. DETAILS OF EACH DIFFERENT WALL OPENING CONDITION.
<br />6. DETAILS OF ELECTRICAL RACEWAY AND PREPARATION FOR ELECTRIFIED
<br />HARDWARE, ACCESS CONTROL SYSTEMS, AND SECURITY SYSTEMS.
<br />7. DETAILS OF ANCHORAGES, JOINTS, FIELD SPLICES, AND CONNECTIONS.
<br />8. DETAILS OF ACCESSORIES.
<br />9. DETAILS OF MOLDINGS, REMOVABLE STOPS, AND GLAZING.
<br />DIVISION 9 - FINISHES
<br />SECTION 09 2900 - GYPSUM BOARD
<br />PART 1 - GENERAL
<br />1.1 SUMMARY:
<br />A RELATED WORK:
<br />1. ROUGH CARPENTRY.
<br />2. FINISH CARPENTRY AND MILLWORK.
<br />3. PAINTING AND COATING.
<br />4. WALL COVERINGS.
<br />5. ELECTRICAL.
<br />1.2 ACTION SUBMITTALS:
<br />A. PRODUCT DATA: INDICATE PRODUCT DESCRIPTION, INCLUDING COMPLIANCE WITH
<br />SPECIFIED REQUIREMENTS AND INSTALLATION REQUIREMENTS. INCLUDE SPECIFIC
<br />REQUIREMENTS FOR FIRE-RATED AND ACOUSTICALLY RATED PARTITIONS AND CEILING
<br />ASSEMBLIES. MARK MANUFACTURER'S BROCHURES TO INCLUDE ONLY THOSE PRODUCTS
<br />PROPOSED FOR USE. INCLUDE COMPLETE DETAILS OF SHAFTWALL SYSTEM. INCLUDE
<br />DETAILS FOR SUPPLEMENTARY FIRE PROTECTION AT PENETRATIONS AND LOCATIONS OF
<br />ACOUSTICAL SEALANT.
<br />1.3 INFORMATIONAL SUBMITTALS:
<br />A. STRUCTURAL DESIGN CALCULATIONS: SUBMIT FOR ARCHITECT'S INFORMATION ONLY.
<br />INDICATE COMPLIANCE WITH SPECIFIED DESIGN CRITERIA. CALCULATIONS SHALL BEAR
<br />THE SEAL OF A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF CALIFORNIA.
<br />1.4 QUALITY ASSURANCE:
<br />A. APPLICABLE STANDARDS; STANDARDS OF THE FOLLOWING:
<br />1. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).
<br />2. ASTM INTERNATIONAL (ASTM) AS REFERENCED HEREIN.
<br />3. ASSOCIATION OF THE WALL AND CEILING INDUSTRIES - INTERNATIONAL (AWCI).
<br />4. CEILINGS AND INTERIOR SYSTEMS CONSTRUCTION ASSOCIATION (CISCA).
<br />5. GYPSUM ASSOCIATION (GA).
<br />6. STEEL STUD MANUFACTURERS ASSOCIATION (SSMA)
<br />7. UNDERWRITERS LABORATORIES, INC. (UL)
<br />8. INTERTEK TESTING SERVICES/WARNOCK HERSEY, INC. (WHI).
<br />9. "RECOMMENDED SPECIFICATION, AWCI, CISCA AND PDCA.
<br />10. PAINTING AND DECORATING CONTRACTORS OF AMERICA (PDCA).
<br />B. DESIGN CRITERIA:
<br />1. SOUND RATING: CONSTRUCT DESIGNATED PARTITIONS IN ACCORD WITH
<br />MANUFACTURER'S PRODUCT DATA, AS SUBMITTED, FOR OBTAINING SOUND
<br />TRANSMISSION CLASS (STC) RATINGS AS INDICATED ON THE DRAWINGS, IN
<br />ACCORD WITH ASTM E90-09.
<br />2. FIRE-RESISTANCE: COMPLY WITH FIRE-RESISTANCE DESIGNS INDICATED ON
<br />THE DRAWINGS. USE ONLY MANUFACTURERS AND TYPES OF MATERIALS AS
<br />REQUIRED BY INDICATED DESIGNS. DESIGNS WITH TESTS BY OTHERTHAN
<br />TESTING AGENCY LISTED MAY BE SUBMITTED FOR ARCHITECT'S ACCEPTANCE,
<br />SUBJECT TO PRIOR ACCEPTANCE BY GOVERNING AUTHORITIES.
<br />1.5 DELIVERY, STORAGE AND HANDLING:
<br />A. DELIVERY: DELIVER MATERIALS IN ORIGINAL PACKAGES, CONTAINERS OR BUNDLES
<br />BEARING BRAND NAME, APPLICABLE STANDARD DESIGNATION AND NAME OF
<br />MANUFACTURER OR SUPPLIER.
<br />B. STORAGE:
<br />1. STACK GYPSUM BOARD INSIDE BUILDING, OFF FLOOR ON PALLETS OR SIMILAR
<br />PLATFORMS PROVIDING CONTINUOUS SUPPORT FOR GYPSUM BOARD AND TO
<br />PREVENT SAGGING. STACK GYPSUM BOARD FLAT AND SO THAT LONG LENGTHS
<br />ARE NOT OVER SHORT LENGTHS.
<br />2. PROTECT GYPSUM BOARD FROM DIRECT EXPOSURE TO RAIN, SUNLIGHT OR
<br />OTHER EXCESSIVE WEATHER CONDITIONS.
<br />3. DO NOT OVERLOAD FLOOR SYSTEMS.
<br />1.6 PROJECT/SITE CONDITIONS:
<br />A. ENVIRONMENTAL CONDITIONS:
<br />1. DURING MECHANICAL APPLICATION OF GYPSUM BOARD, MAINTAIN ROOM
<br />TEMPERATURE AT NOT LESS THAN 40 DEGREES F.
<br />2. DURING ADHESIVE APPLICATION OF GYPSUM BOARD, JOINT TREATMENT,
<br />TEXTURING, AND DECORATION, MAINTAIN ROOM TEMPERATURE NOT LESS
<br />THAN
<br />50 DEGREES F FOR 48 HOURS PRIOR TO APPLICATION AND CONTINUOUSLY
<br />THEREAFTER UNTIL COMPLETELY DRY AND UNTIL PERMANENT HEATING
<br />SYSTEM IS IN OPERATION OR BUILDING IS OCCUPIED.
<br />B. VENTILATION:
<br />1. PROVIDE VENTILATION DURING AND FOLLOWING ADHESIVE AND JOINT
<br />TREATMENT APPLICATIONS, AND DRYING AND CURING PERIODS.
<br />2. USE TEMPORARY AIR CIRCULATORS IN ENCLOSED AREAS LACKING NATURAL
<br />VENTILATION.
<br />3. UNDER SLOW DRYING CONDITIONS, ALLOW ADDITIONAL DRYING TIME
<br />BETWEEN
<br />COATS OF JOINT TREATMENT.
<br />4. PROTECT INSTALLED MATERIALS FROM DRAFTS DURING HOT, DRY WEATHER.
<br />C. WHEN RECOMMENDATIONS OF MANUFACTURER'S PRODUCT DATA EXCEED THE
<br />ABOVE, COMPLY WITH REQUIREMENTS OF MANUFACTURER'S PRODUCT DATA.
<br />PART 2 - PRODUCTS
<br />2.1 FRAMING MEMBERS:
<br />A. GYPSUM BOARD STUDS: MEETING REQUIREMENTS OF ASTM C645-11; CHANNEL TYPE,
<br />ROLL-FORMED FROM DIP GALVANIZED STEEL COMPLYING WITH ASTM A1003-09 AND
<br />WITH ASTM A653-11, G40 MINIMUM.
<br />1. STUD SIZE: AS INDICATED ON DRAWINGS, EXCEPT MINIMUM 3-5/8" DEPTH
<br />WHERE PARTITION IS INDICATED TO RECEIVE TILE CLADDING FINISH.
<br />A. WALL: METAL STUDS, GALVANIZED STEEL.
<br />B. SHAFT WALLS: "C-H" STUDS, HOT-DIPPED GALVANIZED, GAUGES AS
<br />REQUIRED TO SUIT VARIOUS CLEAR-SPAN CONDITIONS.
<br />C. "KING STUDS": INDICATED ON DRAWINGS.
<br />2. STUD GAUGE: AS INDICATED ON THE DRAWINGS AND AS REQUIRED BY
<br />MANUFACTURER'S PRODUCT DATA FOR HEIGHTS AND CONDITIONS OF USE,
<br />WITH MAXIMUM ALLOWABLE DEFLECTIONS AS FOLLOWS:
<br />A. VERTICAL SHAFTS: L/120 AT 10 PSF.
<br />B. ALL OTHER PARTITIONS: L/240 AT 5 PSF.
<br />3. COMPLY WITH SUBMITTED DESIGN CALCULATIONS.
<br />B. FLOOR AND CEILING RUNNERS: HOT DIP GALVANIZED STEEL, 1" DEEP, MINIMUM,
<br />BY WIDTHS TO RECEIVE STUDS, SAME GAUGE AS STUDS. RUNNER TRACKS SHALL HAVE
<br />SLOTTED HOLES FOR ATTACHMENT TO STRUCTURE AND STUDS, FOR SLIP JOINTS
<br />WHERE REQUIRED BY MANUFACTURER'S PRODUCT DATA.
<br />1. WALL: RUNNERS, GALVANIZED STEEL, SIZES AND SHAPES COMPATIBLE WITH
<br />METAL STUD SYSTEM.
<br />2. SHAFT WALL: STEEL "J" RUNNERS, GALVANIZED STEEL.
<br />C. HEADER: BRADY CONSTRUCTION INNOVATIONS, INC., PRO-X HEADER, 54 MIL AND PRO-X
<br />CLIP, 54 MIL.
<br />2.2 GYPSUM BOARD:
<br />A. REGULAR BOARD: MEETING ASTM C1396-11, THICKNESS INDICATED, TAPERED ROUNDED
<br />EDGES.
<br />B. FIRE-RETARDANT BOARD: MEETING ASTM C1396-11, TYPE X, THICKNESS INDICATED,
<br />TAPERED ROUNDED EDGES.
<br />C. INTERIOR CEILING BOARD: MEETING ASTM C1396-11, 5/8" THICKNESS, REGULAR GRADE,
<br />TAPERED EGDES.
<br />D. COREBOARD: MEETING ASTM C1396-11, 1" THICKNESS, SQUARE EDGES,
<br />FIRE-RETARDANT BOARD.
<br />E. MOLD AND MOISTURE RESISTANT BOARD: TREATED PAPER-FACED GYPSUM BOARD.
<br />1. ACCEPTABLE PRODUCTS:
<br />A. AMERICAN GYPSUM, M-BLOC.
<br />B. NATIONAL GYPSUM, XP GYPSUM BOARD AND XP FIRE-SHIELD
<br />GYPSUM BOARD.
<br />C. UNITED STATES GYPSUM (USG), SHEETROCK MOLD TOUGH GYPSUM
<br />PANELS.
<br />2. THICKNESS: 5/8" THICKNESS TYPE X GRADE FIRE-RATED BOARD, TAPERED
<br />EDGES.
<br />3. DESCRIPTION: MOLD AND MOISTURE RESISTANT GYPSUM CORE ENCASED
<br />IN MOLD AND MOISTURE RESISTANT FACERS, WITH TAPERED LONG EDGES.
<br />PANELS SHALL COMPLY WITH ASTM C1396-11.
<br />4. MOLD RESISTANCE: RESISTANT TO MOLD GROWTH WHEN TESTED IN ACCORD
<br />WITH ASTM D3273-12, SCORE OF 10.
<br />5. WATER ABSORPTION: LESS THAN 5% OF BOARD WEIGHT WHEN TESTED IN
<br />ACCORD WITH ASTM C473-12.
<br />6. JOINT TAPE: AS RECOMMENDED BY GYPSUM BOARD MANUFACTURER.
<br />7. LIMITATIONS: DO NOT USE AS A TILE BACKER BOARD.
<br />2.3 TILE BACKER BOARD:
<br />A. WATER-RESISTANT, COATED GLASS MAT BACKER BOARD FOR TILE:
<br />1. ACCEPTABLE PRODUCT: G-P GYPSUM PRODUCTS, DENS-SHIELD FIREGUARD
<br />TILE BACKER.
<br />2. CHARACTERISTICS: MEETING ASTM C1178-11, MINIMUM 1/2" THICKNESS,
<br />NON-COMBUSTABLE, 5/8" THICKNESS TYPE X, WATER-RESISTANT, SILICON
<br />BASED GYPSUM CORE, FIBERGLASS SURFACE MATS, FRONT AND BACK,
<br />COATED WITH WATER AND VAPOR RETARDANT COATING.
<br />3. JOINT TAPE: FIBERGLASS MESH JOINT TAPE AS RECOMMENDED BY GYPSUM
<br />BOARD MANUFACTURER.
<br />2.4 GYPSUM SHAFTWALL SYSTEM:
<br />A. ACCEPTABLE PRODUCTS; SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS:
<br />1. AMERICAN GYPSUM, M-BLOC SHAFT LINER.
<br />2. G-P GYPSUM PRODUCTS, DENSGLASS SHAFTLINER.
<br />3. NATIONAL GYPSUM CO., EXP EXTENDED EXPOSURE SHAFTLINER.
<br />4. TEMPLE-INLAND, GREENGLASS LINER BOARD.
<br />5. U.S. GYPSUM CO., SHEETROCK GLASS-MAT LINER PANELS.
<br />B. MATERIALS: MOISTURE- AND MOLD-RESISTANT, NONCOMBUSTIBLE, TYPE X GYPSUM
<br />SHAFTLINER COREBOARD COATED WITH GLASS MAT FACINGS, METAL FRAMING
<br />MEMBERS, AND FIBER-REINFORCED GYPSUM BOARD WITH FIBERGLASS MAT FACE ON
<br />UNEXPOSED SIDE AND PAPER FACE ON EXPOSED SIDE.
<br />C. FIRE-RESISTIVE RATING: IN ACCORD WITH FIRE-RATED ASSEMBLY DESIGN INDICATED.
<br />2.5 SOUND CONTROL MATERIALS:
<br />A. CONTRACTOR'S OPTION: BASED ON SOUND RATINGS AND FIRE-RESISTANCE RATINGS
<br />REQUIRED FOR ASSEMBLIES, CONTRACTOR MAY SELECT GLASS FIBER OR MINERAL
<br />WOOL SOUND ATTENUATION MATERIALS AS FOLLOWS:
<br />1. GLASS FIBER SOUND ATTENUATION BATTS:
<br />A. ACCEPTABLE MANUFACTURERS:
<br />1) CERTAINTEED CORP.
<br />2) KNAUF INSULATION.
<br />3) JOHNS MANVILLE CORP.
<br />4) OWENS-CORNING CORP.
<br />B. CHARACTERISTICS:
<br />1) TYPE: UNFACED FIBERGLASS BATTS FOR FRICTION FIT
<br />BETWEEN STUDS, COMPLYING WITH ASTM C665-12, TYPE1.
<br />2) SURFACE BURNING CHARACTERISTICS: MAXIMUM 25 FLAME
<br />SPREAD AND 50 SMOKE DEVELOPMENT WHEN TESTED IN
<br />ACCORD WITH ASTM E84-12C.
<br />3) ASSEMBLY STC: AS INDICATED ON DRAWINGS.
<br />4) THICKNESS: AS INDICATED ON DRAWINGS, BUT MINIMUM
<br />3-1/2" THICK TO ACHIEVE R-13.
<br />2. MINERAL WOOL SOUND ATTENUATION BLANKETS:
<br />A. ACCEPTABLE MANUFACTURERS:
<br />1) IIG, MINWOOL, LLC, MINWOOL SOUND ATTENUATION FIRE
<br />BATTS.
<br />2) OWENS-CORNING CORP., SOUND ATTENUATION FIRE BATT.
<br />3) U.S. GYPSUM CO., THERMAFIBER SAFB (SOUND
<br />ATTENUATION FIRE BLANKETS). OWENS-CORNING CORP.
<br />B. CHARACTERISTICS:
<br />1) TYPE: PAPERLESS, SEMI-RIDIG MINERAL WOOL FIBER
<br />BLANKET COMPLYING WITH ASTM C665-12, TYPE 1.
<br />2) DENSITY: MAXIMUM 4.0 PCF FOR 1" THICKNESS, AND
<br />MAXIMUM 2.5 PCF. FOR GREATER THICKNESSES.
<br />3) SURFACE BURNING CHARACTERISTICS: MAXIMUM 15 FLAME
<br />SPREAD AND 5 SMOKE DEVELOPMENT WHEN TESTED IN
<br />ACCORD WITH ASTM E84-12C.
<br />4) ASSEMBLY STC: AS INDICATED ON DRAWINGS.
<br />5) THICKNESS: AS INDICATED ON DRAWINGS, BUT MINIMUM
<br />REQUIRED THICKNESS TO ACHIEVE R-13
<br />B. ACOUSTICAL TAPE: CLOSED CELL POLYVINYL CHLORIDE FOAM TAPE, 1/4" THICKNESS
<br />BY 1" WIDE.
<br />C. ACOUSTICAL JOINT SEALANT: MANUFACTURER'S STANDARD NON-SAG, PAINTABLE,
<br />NON-STAINING LATEX SEALANT COMPLYING WITH ASTM C834-10. PRODUCT EFFECTIVELY
<br />REDUCES AIRBORNE SOUND TRANSMISSION THROUGH PERIMETER JOINTS AND
<br />OPENINGS IN BUILDING CONSTRUCTION AS DEMOSTRATED BY TESTING
<br />REPRESENTATIVEASSEMBLIES ACCORDING TO ASTM E90-09.
<br />1. PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE
<br />OF THE FOLLOWING:
<br />A. ACCUMETRIC LLC; BOSS 824 ACOUSTICAL SOUND SEALANT.
<br />B. GRABBER CONSTRUCTION PRODUCTS; ACOUSTICAL SEALANT GSC.
<br />C. PECORA CORPORATION; AC-20 FTR.
<br />D. SPECIFIED TECHNOLOGIES, INC.; SMOKE N SOUND ACOUSTICAL
<br />SEALANT.
<br />E. USG CORPORATION; SHEETROCK ACOUSTICAL SEALANT.
<br />2. ACOUSTICAL JOINT SEALANT SHALL HAVE A VOC CONTENT OF LESS THAN THE
<br />CURRENT VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY MANAGEMENT
<br />DISTRICT (SCAQMD) RULE #1168, ADHESIVES AND SEALANTS, AMENDED
<br />JANUARY 7, 2005.
<br />2.6 FASTENERS:
<br />A. FASTENERS FOR METAL FRAMING, CORROSION-RESISTANT:
<br />1. FOR FASTENING FRAMING MEMBERS TO CONCRETE SURFACES: FASTENERS
<br />SHALL BE BEADED DRIVE PINS OR THREADED STUDS DRIVEN BY POWER
<br />ACTUATED TOOLS. FASTENERS SHALL RESIST DESIGN LOADS IN ACCORD
<br />WITH REQUIREMENTS OF ASTM E1190-11.
<br />2. FOR FASTENING TO METAL DECKING AND FOR FASTENING FRAMING MEMBERS
<br />TOGETHER: TYPE S, PAN HEAD SCREWS, IN SIZES RECOMMENDED BY GYPSUM
<br />BOARD MANUFACTURER FOR APPLICATIONS INDICATED.
<br />3. PROVIDE SLOTTED, STAND-OFF WASHERS FOR SLIP JOINT ATTACHMENTS.
<br />4. REFER TO DETAILS INDICATED IN DRAWINGS.
<br />B. SCREWS FOR GYPSUM BOARD AND ACCESSORY APPLICATION: MEETING ASTM C1002-07,
<br />CORROSION-RESISTANT.
<br />1. FOR APPLICATION OF SINGLE LAYER OR BASE LAYER OF GYPSUM BOARD TO
<br />METAL FRAMING: 1", TYPE S, BUGLE HEAD.
<br />2. FOR APPLICATION OF FACE LAYER OF GYPSUM BOARD TO METAL FRAMING IN
<br />DOUBLE LAYER CONSTRUCTION: 1-5/8", TYPE S, BUGLE HEAD.
<br />3. FOR GYPSUM BOARD TO GYPSUM BOARD APPLICATION: 1-1/2", TYPE G, BUGLE
<br />HEAD.
<br />C. SCREWS FOR GLASS MAT FACED BOARD APPLICATION: CORROSSION RESISTANT SHEET
<br />METAL SCREWS WITH HEAD DIAMETER PROVIDING 125 LB. FASTENER PULL-THROUGH
<br />AND PULL-OUT RESISTANCE. SCREW LENGTH SHALL PROVIDE 1/4" MINIMUM THREAD
<br />ENGAGEMENT.
<br />R
<br />No.
<br />F
<br />LICENSE
<br />STATE
<br />D
<br />O
<br />A RCHITECT
<br />C AL IFORNIA
<br />STEPHE WHITE
<br />RENEWAL
<br />DATE
<br />C-34829
<br />N
<br />08/31/25
<br />SHEET TITLE
<br />PROJECT
<br />FACILITY
<br />FAC NO: BLDG NO:FLOOR LEV:SECTION:
<br />KP PROJ. NO.
<br />MATTERPORT LINK: https://my.matterport.com/show/?m=FW21iEbmuii
<br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA
<br />ARCHITECT
<br />CONSULTANT
<br />ARCHITECT SEAL CONSULTANT SEAL
<br />KAISER FOUNDATION HOSPITALS
<br />NATIONAL FACILITIES SERVICES
<br />1800 HARRISON STREET OAKLAND,
<br />CALIFORNIA 94612
<br />ISSUE / REVISION LOG
<br />NO. ISSUED DATE
<br />0
<br />5'
<br />50
<br />'
<br />GR
<br />A
<br />P
<br />H
<br />I
<br />C
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />S
<br />:
<br />1/
<br />1
<br />6
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />25
<br />'
<br />1/
<br />8
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />5'
<br />0
<br />12
<br />'
<br />1/
<br />4
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />6'
<br />1/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />1'
<br />0
<br />2'
<br />1-
<br />1
<br />/
<br />2
<br />"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />0
<br />1'
<br />3"
<br />
<br />=
<br />
<br />1
<br />'
<br />-
<br />0
<br />"
<br />IF
<br />
<br />T
<br />H
<br />I
<br />S
<br />
<br />S
<br />H
<br />E
<br />E
<br />T
<br />
<br />I
<br />S
<br />
<br />N
<br />O
<br />T
<br />
<br />30
<br />"
<br />x
<br />4
<br />2
<br />"
<br />,
<br />
<br />I
<br />T
<br />
<br />I
<br />S
<br />
<br />A
<br />
<br />R
<br />E
<br />D
<br />U
<br />C
<br />E
<br />D
<br />
<br />PR
<br />I
<br />N
<br />T
<br />
<br />-
<br />
<br />S
<br />C
<br />A
<br />L
<br />E
<br />
<br />AC
<br />C
<br />O
<br />R
<br />D
<br />I
<br />N
<br />G
<br />L
<br />Y
<br />AGENCY APPLICATION NUMBER
<br />AGENCY APPROVAL STAMP
<br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS
<br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION.
<br />HZ PROJ. NO.
<br />Phone 310.820.4600 | Fax 310.207.4215
<br />www.huitt-zollars.com
<br />C:\Users\jpark\Documents\R314412.44 - KP SAN 1st Flr Gen Rad_A22_Central_jhaLWMQW.rvt
<br />5/20/2024 10:23:25 AM
<br />SOCC 2023 R RAD SAN 1ST FLOOR
<br />GEN RAD REPLACEMENT (5284)
<br />G0-03
<br />SPECIFICATIONS
<br />CA361 1
<br />CAP028060R314412.44
<br />SANTA ANA MEDICAL OFFICES
<br />1900 E. 4TH ST.
<br />SANTA ANA, CA 92701
<br />CITY SUBMITTAL 04/19/2024
<br />BID SET 05/20/2024
<br />1900 E 4th St -
<br />1011190678/9/2024
|