B. FIRE-TEST-RESPONSE CHARACTERISTICS: PROVIDE FIRESTOPPING SYSTEM DESIGN <br />LISTING BY A TESTING AND INSPECTION AGENCY IN ACCORD WITH THE SPECIFIED <br />UL STANDARDS. <br />C. ACCEPTABLE INSTALLER SHALL BE: <br />1. INSTALLER QUALIFICATIONS: A FIRM THAT HAS BEEN APPROVED BY FM <br />GLOBAL ACCORDING TO FM GLOBAL 4991, "APPROVAL OF FIRESTOP <br />CONTRACTOR," OR BEEN EVALUATED BY UL AND FOUND TO COMPLY WITH <br />UL's "QUALIFIED FIRESTOP CONTRACTOR PROGRAM REQUIREMENTS." <br />2. LICENSED BY STATE OR LOCAL AUTHORITY, WHERE APPLICABLE. <br />3. SUCCESSFULLY COMPLETED NOT LESS THAN 5 COMPARABLE SCALE <br />PROJECTS. <br />D. SINGLE SOURCE RESPONSIBILITY: OBTAIN FIRESTOP SYSTEMS FOR EACH KIND OF <br />PENETRATION AND CONSTRUCTION CONDITION INDICATED FROM A SINGLE PRIMARY <br />FIRESTOP SYSTEMS MANUFACTURER. <br />1. MATERIALS FROM DIFFERENT MANUFACTURER THAN ALLOWED BY TESTED <br />AND LISTED SYSTEM SHALL NOT BE INTERMIXED IN THE SAME FIRESTOP <br />SYSTEM OR OPENING. <br />2. INSTALL TESTED AND LISTED FIRESTOP SYSTEMS BEFORE INSTALLING AN <br />ENGINEERING JUDGEMENT OR EQUIVALENT FIRE RESISTANCE RATED <br />ASSEMBLY (EFFRA). <br />1.6 DELIVERY STORAGE AND HANDLING: <br />A. DELIVER FIRESTOPPING MATERIALS IN ORIGINAL, UNOPENED CONTAINERS OR PACKAGES <br />WITH INTACT AND LEGIBLE MANUFACTURER'S LABELS IDENTIFYING PRODUCT AND <br />MANUFACTURER. <br />B. STORE AND HANDLE FIRESTOPPING MATERIALS IN ACCORD WITH MANUFACTURER'S <br />PRODUCT DATA. <br />1.7 JOB CONDITIONS: <br />A. COORDINATE FIRESTOPPING INSTALLATION WITH OTHER WORK REQUIRING <br />PENETRATIONS THROUGH FIRE-RESISTIVE CONSTRUCTION. INSTALL PENETRATING <br />ELEMENTS PRIOR TO INSTALLATION OF FIRESTOPPING SYSTEMS OR DEVICES. <br />B. SECURE INSPECTION AND APPROVAL OF FIRESTOPPING WORK BY BUILDING OFFICIALS <br />PRIOR TO CONCEALMENT. <br />C. SUPPORT PENETRATING ELEMENTS INDEPENDENTLY OF FIRESTOPPING SYSTEMS OR <br />DEVICES. <br />D. DO NOT COVER UP FIRESTOPPING INSTALLATIONS UNTIL OWNER'S INSPECTION AGENCY <br />OR AUTHORITIES HAVING JURISDICTION HAVE EXAMINED EACH INSTALLATION. <br />PART 2 - PRODUCTS <br />2.1 MATERIALS, GENERAL: <br />A. VOC CONTENT: PENETRATION FIRESTOPPING SEALANTS AND SEALANT PRIMERS SHALL <br />HAVE A VOC CONTENT LESS THAN THE CURRENT VOC CONTENT LIMITS OF SOUTH <br />COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD) RULE #1113, ARCHITECTURAL <br />COATINGS, RULES IN EFFECT JANUARY 1, 2004. <br />2.2 THROUGH-PENETRATION FIRESTOP SYSTEMS: <br />A. ACCEPTABLE MANUFACTURERS; SUBJECT TO COMPLIANCE WITH SPECIFIED <br />REQUIREMENTS: <br />1. GRACE CONSTRUCTION PRODUCT. <br />2. HILTI USA. <br />3. 3M FIRE PROTECTION PRODUCTS. <br />4. NELSON FIRESTOP PRODUCTS. <br />5. RECTOR SEAL CORP. <br />6. SPECIFIED TECHNOLOGIES, INC. (STI). <br />7. TREMCO, INC. <br />B. SYSTEM DESCRIPTION: FIELD-CONSTRUCTED FIRESTOPPING FOR PENETRATIONS <br />THROUGH WALLS AND FLOORS COMPOSED OF SPECIFIED MATERIALS AND ACCESSORIES <br />ASSEMBLED IN ACCORD WITH THROUGH-PENETRATION FIRESTOPPING SYSTEM <br />NUMBERS, LISTED IN UL BUILDING MATERIALS DIRECTORY, CURRENT EDITION, AND <br />TESTED IN ACCORD WITH ASTM E814-11A. <br />C. MATERIALS: UL CLASSIFIED FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS. <br />1. FIRESTOP SEALANT: SINGLE-COMPONENT, ELASTOMERIC SILICONE OR <br />ENDOTHERMIC LATEX SEALANT COMPOUND; SELF-ADHERING, FLEXIBLE AND <br />WATERTIGHT; NON SAG AND SELF-LEVELING TYPES AS REQUIRED. <br />2. FIRESTOP FOAM: TWO-PART, ROOM TEMPERATURE VULCANIZING, SILICONE <br />ELASTOMER, NON-COMBUSTIBLE FOAM VOID SEAL. <br />3. INTUMESCENT SEALANTS AND PUTTIES: SINGLE-COMPONENT, SYNTHETIC, <br />ORGANIC/INORGANIC INTUMESCENT ELASTOMERS. <br />4. INTUMESCENT WRAP STRIPS: ONE-PART, ORGANIC/INORGANIC, INTUMESCENT <br />ELASTOMERIC SHEET; ALUMINUM FOIL-FACED ONE SIDE. <br />5. INTUMESCENT COMPOSITE SHEETS: COMPOSITE SHEETS COMPOSED OF <br />ORGANIC/INORGANIC INTUMESCENT ELASTOMERIC CORE BONDED ON ONE SIDE <br />TO 28 GA. GALVANIZED STEEL SHEET AND OTHER SIDE REINFORCED WITH <br />STEEL WIRE MESH, COVERED WITH ALUMINUM FOIL. <br />6. MINERAL WOOL OR CERAMIC FIBER SAFING: NON-COMBUSTIBLE FIBER TESTED <br />IN ACCORD WITH ASTM E136-12, WITH MELTING POINT IN EXCESS OF 2000 <br />DEGREES F.; FLAME SPREAD OF 15 MAXIMUM AND 0 SMOKE DEVELOPMENT <br />WHEN TESTED IN ACCORD WITH ASTM E84-12C. THICKNESS AND DENSITY SHALL <br />BE AS REQUIRED BY THROUGH-PENETRATION FIRESTOP SYSTEM DESIGNS. <br />D. ACCESSORIES: <br />1. PRIMERS, ADHESIVES AND BACKER RODS: AS REQUIRED BY MANUFACTURER'S <br />PRODUCT DATA AND SYSTEM DESIGNS. <br />2. FORMING, DAMMING AND PACKING MATERIALS: TYPES AS INDICATED IN <br />THROUGH-PENETRATION FIRESTOP SYSTEMS. <br />3. RESTRICTING COLLARS: MANUFACTURER'S STANDARD DESIGN AS REQUIRED <br />FOR FIRESTOP SYSTEMS. <br />4. FASTENERS, ANCHOR CLIPS, SLEEVES, CLAMPS, SPACERS, TIES, COVER PLATES <br />AND MISCELLANEOUS ACCESSORIES: PROVIDE AS REQUIRED BY <br />MANUFACTURER'S PRODUCT DATA AND IN ACCORD WITH THROUGH- <br />PENETRATION FIRESTOP SYSTEM DESIGNS. <br />2.3 THROUGH-PENETRATION FIRESTOP DEVICES: <br />A. ACCEPTABLE MANUFACTURERS; SUBJECT TO COMPLIANCE WITH SPECIFIED <br />REQUIREMENTS: <br />1. GRACE CONSTRUCTION PRODUCTS. <br />2. HILTI USA. <br />3. ISOLATEK INTERNATIONAL, INC. <br />4. NELSON FIRESTOP PRODUCTS. <br />5. PROSET SYSTEMS, INC. <br />6. SPECIFIED TECHNOLOGIES, INC. (STI). <br />7. TREMCO, INC. <br />B. TYPES: FACTORY-ASSEMBLED, SELF-CONTAINED FIRESTOPPING DEVICES FOR <br />PENETRATIONS THROUGH WALLS AND FLOORS; UL CLASSIFIED FOR THROUGH- <br />PENETRATION FIRESTOP DEVICES AS LISTED IN UL BUILDING MATERIALS DIRECTORY, <br />CURRENT EDITION, AND TESTED IN ACCORD WITH ASTM E-814-11A. <br />C. ACCESSORIES: PROVIDE SEALANTS, ADHESIVES, FASTENERS, SLEEVES, CLAMPS, <br />SPACERS, ANCHOR CLIPS, TIES AND ACCESSORIES IN ACCORD WITH MANUFACTURER'S <br />PRODUCT DATA AND AS REQUIRED FOR COMPLETE INSTALLATION. <br />2.4 FIRESTOP SEALANTS: <br />A. ACCEPTABLE PRODUCTS; SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS: <br />1. GRACE CONSTRUCTION PRODUCTS, FLAMESAFE SILICONE SEALANT. <br />2. HILTI USA, CP 601S FIRESTOP SEALANT. <br />3. NELSON FIRESTOP PRODUCTS, CLK. <br />4. 3M FIRE PROTECTION PRODUCTS, FIRE BARRIER SILICONE SEALANT 2000 N/S <br />5. RECTOR SEAL CORP., METACAULK 835+. <br />6. SPECIFIED TECHNOLOGIES, INC. (STI), SPECSEAL PEN 300 SILICONE JOINT <br />SEALANT. <br />7. TREMCO, INC., FYRE-SIL. <br />B. CHARACTERISTICS: SINGLE-COMPONENT, SELF-ADHERING, FLEXIBLE, WATERTIGHT, <br />ELASTOMERIC SILICONE SEALANT COMPOUND; UL CLASSIFIED. PROVIDE SELF-LEVELING <br />TYPE FOR HORIZONTAL APPLICATIONS, NON-SAG TYPE FOR ALL OTHER APPLICATIONS. <br />2.5 SAFING: <br />A. ACCEPTABLE PRODUCTS; SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS: <br />1. GENERAL INSULATION COMPANY, FBX SAFING INSULATION. <br />2. THERMAL CERAMICS, CERABLANKET F.S. <br />3. THERMAFIBER INC., THERMAFIBER SAFING INSULATION. <br />B. CHARACTERISTICS: <br />1. MATERIAL: SEMI-RIGID MINERAL FIBER INSULATION, MEETING ASTM C665-12, <br />TYPE 1. <br />2. DENSITY: 4.0 PCF. <br />3. THICKNESS: AS INDICATED. <br />4. FACING: UNFACED OR REINFORCED FOIL FACING, BASED ON UL DESIGN <br />SELECTED. <br />5. FIRE RESISTANCE PROPERTIES: <br />A. MELTING POINT: MINIMUM OF 2000 DEGREES F. WHEN TESTED IN <br />ACCORD WITH ASTM C24-09. <br />B. NON-COMBUSTIBLE: AS DEFINED BY ASTM E136-12 AND NFPA. <br />C. FIRE HAZARD CHARACTERISTICS: MAXIMUM FLAME SPREAD OF 15 <br />AND SMOKE DEVELOPMENT OF 5 WHEN TESTED IN ACCORD WITH <br />ASTM E84-12C (UNFACED). <br />6. FIRE SAFING: TESTED IN ACCORD WITH ASTM E119-12A WITHOUT <br />DETERIORATION FOR MINIMUM OF FIVE HOURS IN A SLAB EDGE/SPANDREL <br />CONFIGURATION. <br />C. ACCESSORIES: <br />1. CLIPS: INSULATION MANUFACTURER'S STANDARD GALVANIZED STEEL IMPALING <br />CLIPS FOR ATTACHMENT OF SAFING. <br />2. SEALANT: MANUFACTURER'S TESTED SEALANT MATERIAL FOR FOIL-FACED <br />SMOKE SEAL. <br />PART 3 - EXECUTION <br />3.1 PRE-INSTALLATION REQUIREMENTS: <br />A. PRE-INSTALLATION MEETING: PRIOR TO BEGINNING FIRESTOPPING WORK, A <br />PRE-INSTALLATION MEETING SHALL BE HELD TO REVIEW WORK TO BE ACCOMPLISHED. <br />1. CONTRACTOR, ARCHITECT, FIRESTOPPING SYSTEM MANUFACTURER'S <br />REPRESENTATIVES, INSTALLER AND OTHER SUBCONTRACTORS WHOSE WORK <br />INVOLVES FIRESTOPPING SHALL BE PRESENT. <br />2. CONTRACTOR SHALL NOTIFY ALL PARTIES AT LEAST SEVEN DAYS PRIOR TO <br />TIME FOR MEETING. <br />3. CONTRACTOR SHALL RECORD MINUTES OF MEETING AND DISTRIBUTE TO <br />ATTENDING PARTIES. <br />3.2 EXAMINATION: <br />A. EXAMINE AREAS TO RECEIVE FIRESTOPPING MATERIALS PRIOR TO BEGINNING WORK. <br />VERIFY THAT OPENING AREAS AND DIMENSIONS FOR PENETRATIONS TO RECEIVE <br />FIRESTOPPING SYSTEMS AND DEVICES DO NOT EXCEED DESIGN REQUIREMENTS. <br />B. REMOVE PROJECTIONS INTERFERING WITH INSTALLATION. PREPARE SURFACES IN <br />ACCORD WITH MANUFACTURER'S PRODUCT DATA AND UL THROUGH-PENETRATION <br />FIRESTOP DEVICES NUMBERS. <br />3.3 PREPARATION: <br />A. PRIMING: PRIME SUBSTRATES WHERE RECOMMENDED BY FIRESTOPPING MANUFACTURER <br />USING THAT MANUFACTURER'S RECOMMENDED PRODUCTS AND METHODS. CONFINE <br />PRIMERS TO AREAS OF BOND. DO NOT ALLOW SPILLAGE AND MIGRATION ONTO EXPOSED <br />SURFACES. <br />B. MASKING TAPE: USE MASKING TAPE TO PREVENT FIRESTOPPING FROM CONTACTING <br />ADJOINING SURFACES THAT WILL REMAIN EXPOSED UPON COMPLETION OF THE WORK. <br />REMOVE TAPE AS SOON AS IT IS POSSIBLE TO DO SO WITHOUT DISTURBING THE <br />FIRESTOPPING SEAL WITH SUBSTRATES. <br />3.4 INSTALLATION: <br />A. GENERAL: <br />1. COMPLY WITH MANUFACTURER'S PRODUCT DATA AND UL CLASSIFIED FOR <br />THROUGH-PENETRATION FIRESTOP DEVICES NUMBERS. <br />2. INSTALL FIRESTOPPING MATERIALS FITTED TO ADJACENT CONSTRUCTION <br />TO FILL VOIDS. <br />3. FIRESTOP PENETRATIONS THROUGH FIRE-RATED WALLS, PARTITIONS, FLOORS <br />AND FLOOR/CEILING ASSEMBLIES WITH TESTED ASSEMBLIES IN ACCORD WITH <br />UL 1479 OR WITH A THROUGH-PENETRATION FIRESTOP SYSTEM OR DEVICE <br />WHEN TESTED IN ACCORD WITH ASTM E814-11A. <br />4. FIRESTOPPING SHALL COMPLY WITH CODE REQUIREMENTS. <br />B. FIRE AND SMOKE BARRIER IDENTIFICATION: <br />1. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE <br />PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS <br />SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR <br />STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY HAVING <br />JURISDICTION. <br />2. SUCH IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING AND IN <br />CONCEALED SPACES, AND NEAR THE TOP OF THE WALL OR BARRIER IN <br />UNFINISHED SPACES. <br />3. SUCH IDENTIFICATION SHALL BE LETTERS A MINIMUM OF 2" (51 mm) HIGH ON <br />A CONTRASTING BACKGROUND, SPACED AT 12'-0" O.C. MAXIMUM, WITH A <br />MINIMUM OF ONE PER WALL OR BARRIER. COMPLY WITH CODE REQUIREMENTS. <br />4. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "______ HOUR FIRE <br />AND SMOKE BARRIER - PROTECT ALL OPENINGS." <br />C. THROUGH-PENETRATION FIRESTOP SYSTEMS AND DEVICES: <br />1. INSTALL AT PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL <br />CONSTRUCTION, INCLUDING PARTITIONS AND FLOOR/ CEILING ASSEMBLIES, <br />IN ACCORD WITH MANUFACTURER'S PRODUCT DATA AND UL SYSTEM NUMBERS. <br />PROVIDE MATERIALS AND ACCESSORIES AS REQUIRED. <br />2. INSTALL INTUMESCENT TYPE FIRESTOP SYSTEMS WHERE PLASTIC PIPING, <br />CABLE, CONDUIT AND OTHER COMBUSTIBLE ITEMS, INCLUDING INSULATED <br />METAL PIPES, PENETRATE FIRE-RATED CONSTRUCTION. <br />3. AT CONTRACTOR'S OPTION, THROUGH-PENETRATION FIRESTOP DEVICES OF <br />SIMILAR FUNCTION MAY BE INSTALLED IN LIEU OF FIRESTOP SYSTEMS. <br />4. DO NOT REMOVE FORMING MATERIALS UNLESS SPECIFIED IN SYSTEM DESIGNS. <br />D. FIRESTOP SEALANT: SEAL PERIMETERS, VOIDS AND JOINTS OF FIRE-RATED WALLS AND <br />PARTITIONS,INCLUDING ABUTMENT OF FLOOR AND ROOF OR CEILING STRUCTURE, AND <br />FLUTES OF METAL DECKING. <br />1. IF REQUIRED BY UL DESIGN, INSTALL MINERAL WOOL OR CERAMIC FIBER IN <br />CAVITIES, PACKED FULL AND TIGHT WITH ALLOWANCE FOR SEALANT <br />INSTALLATION. <br />2. SEAL BOTH FACES OF WALLS AND PARTITIONS WITH FIRESTOP SEALANT. TOOL <br />SEALANTFLUSH WITH ADJACENT FINISH. <br />3. IN ACCORD WITH UL FIRE RESISTANCE DIRECTORY DESIGNS, PACKED CONCRETE <br />AND MASONRY JOINTS SHALL BE SEALED USING FIRESTOP SEALANT OR USING <br />SEALANT AS SPECIFIED IN JOINT SEALANTS SECTION. <br />E. MINERAL FIBER SAFING: <br />1. INSTALL SAFING IN CAVITIES OF PENETRATIONS THROUGH NON-RATED FLOOR <br />AND WALL CONSTRUCTION, INCLUDING SPACES AROUND PIPING, CONDUITS, <br />CABLES AND DUCT PENETRATIONS. <br />2. INSTALL SAFING IN VOIDS AND JOINTS OF NON-RATED WALLS AND PARTITIONS <br />ABUTTING METAL DECKING OF FLOOR AND ROOD STRUCTURES. PACK FLUTES <br />OF METAL DECKING SOLID WITH SAFING MATERIAL. <br />3. SAFING SHALL BE INSTALLED AT JOINTS AND PENETRATIONS IN NON-RATED <br />CONSTRUCTION NOT EXPOSED TO VIEW AND CONCEALED IN FINISH WORK. <br />SECURE SAFING BY COMPRESSING INTO VOIDS OR JOINTS AND USING <br />MANUFACTURER'S STANDARD CLIPS OR CLOSURE PLATES AS REQUIRED. <br />F. SEAL VOIDS AND JOINTS OF NON-RATED WALLS AND PARTITIONS ABUTTING CONCRETE <br />FLOOR AND ROOF CONSTRUCTION USING SEALANT AS SPECIFIED IN OTHER SECTIONS. <br />3.5 FIELD QUALITY CONTROL: <br />A. INSPECTION: INDEPENDENT INSPECTION AGENCY EMPLOYED AND PAID BY OWNER , WILL <br />EXAMINE PENETRATION FIRESTOPPING IN ACCORD WITH ASTM E2174-10 AND <br />ASTM E2393-10A. INSPECTION AGENCY WILL EXAMINE FIRESTOPPING AND WILL <br />DETERMINE, IN GENERAL, THAT FIRESTOPPING HAS BEEN INSTALLED IN COMPLIANCE <br />WITH TESTED AND LISTED FIRESTOP SYSTEM, AND THAT INSTALLATION PROCESS <br />CONFORMS TO FM 4991 - STANDARD FOR APPROVAL OF FIRESTOP CONTRACTORS OR <br />UL QUALIFIED FIRESTOP CONTRACTOR PROGRAM. <br />B. INSPECTOR WILL ADVISE CONTRACTOR OF DEFICIENCIES NOTED WITHIN ONE WORKING <br />DAY. <br />C. DO NOT PROCEED TO ENCLOSE FIRESTOPPING WITH OTHER CONSTRUCTION UNTIL <br />INSPECTION AGENCY HAS VERIFIED FIRESTOP INSTALLATION COMPLIES WITH <br />REQUIREMENTS OF CONTRACT DOCUMENTS. <br />D. WHERE DEFICIENCIES ARE FOUND, REPAIR OR REPLACE FIRESTOPPING SO THAT IT <br />COMPLIES WITH REQUIREMENTS OF TESTED AND LISTED SYSTEM DESIGN. <br />3.6 CLEANING: <br />A. CLEAN OFF EXCESS FILL MATERIALS AND SEALANTS ADJACENT TO OPENINGS AND <br />JOINTS AS WORK PROGRESSES. USE METHODS AND CLEANING MATERIALS APPROVED <br />BY MANUFACTURERS OF FIRESTOPPING PRODUCTS AND OR ASSEMBLIES IN WHICH <br />OPENINGS AND JOINTS OCCUR. <br />B. PROTECT FIRESTOPPING DURING AND AFTER CURING PERIOD FROM CONTACT WITH <br />CONTAMINATING SUBSTANCES. <br />END OF SECTION <br />SECTION 07 9200 - JOINT SEALANTS <br />PART 1 - GENERAL <br />1.1 SUMMARY: <br />A. DEFINITIONS: <br />1. JOINT SEALANT COMPOUND: A MATERIAL USED IN FILLING JOINTS AND SEAMS, <br />HAVING PROPERTIES OF ADHESION AND COHESION; NOT REQUIRED TO HAVE <br />EXTENSIBILITY AND RECOVERY PROPERTIES, GENERALLY FOR APPLICATION IN <br />INTERIOR JOINTS NOT SUBJECT TO MOVEMENT. <br />2. CAULK: THE PROCESS OF FILLING JOINTS, WITHOUT REGARD TO TYPE OF <br />MATERIAL. <br />3. JOINT FAILURE: A CAULKED JOINT EXHIBITING ONE OR MORE OF THE FOLLOWING <br />CHARACTERISTICS: <br />A. AIR AND/OR WATER LEAKAGE. <br />B. MIGRATION AND/OR REVERSION. <br />C. LOSS OF ADHESION. <br />D. LOSS OF COHESION. <br />E. FAILURE TO CURE. <br />F. DISCOLORATION. <br />G. STAINING OF ADJACENT WORK. <br />H. DEVELOPMENT OF BUBBLES, AIR POCKETS OR VOIDS. <br />1.2 ACTION SUBMITTALS: <br />A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DESCRIPTION, INDICATING <br />CONFORMANCE WITH SPECIFIED REQUIREMENTS AND INSTALLATION INSTRUCTIONS <br />FOR EACH TYPE OF SEALANT. INDICATE PREPARATION AND PRIMING REQUIREMENTS <br />FOR EACH SUBSTRATE CONDITION. <br />B. COLOR SAMPLES: <br />1. SAMPLES FOR INITIAL INSPECTION: SAMPLES SHALL BE ACTUAL MATERIALS <br />OR LITERATURE DEPICTING ACTUAL COLORS OF STANDARD COLOR MATERIALS <br />SHOWING FULL RANGE OF COLORS AVAILABLE FOR EACH PRODUCT EXPOSED <br />TO VIEW. <br />2. SUBMIT SAMPLES OF CUSTOM COLOR SEALANT MATERIALS MATCHING COLOR <br />SAMPLE PROVIDED BY ARCHITECT. <br />3. SAMPLES FOR VERIFICATION: FOR EACH KIND AND COLOR OF JOINT SEALANT <br />REQUIRED, PROVIDE SAMPLES WITH JOINT SEALANTS IN 1/2" WIDE JOINTS <br />FORMED BETWEEN TWO 6" LONG STRIPS OF MATERIAL MATCHING <br />APPEARANCE OF EXPOSED SURFACES ADJACENT TO JOINT SEALANTS. <br />1.3 INFORMATIONAL SUBMITTALS: <br />A. ADHESION COMPATIBILITY TEST RESULTS: SUBMIT A LETTER FROM SEALANT <br />MANUFACTURER INDICATING ADHESION AND COMPATIBILITY TESTING HAS BEEN <br />PERFORMED AND THAT MATERIALS ARE COMPATIBLE AND THAT ADHESION IS <br />ACCEPTABLE. INDICATE REQUIREMENTS FOR PRIMERS OR SPECIAL PREPARATION. <br />B. SUBSTRATE STAINING TEST RESULTS: SUBMIT A LETTER FROM SEALANT <br />MANUFACTURER INDICATING THAT SUBSTRATE STAIN TESTING HAS BEEN PERFORMED <br />ON ACTUAL SAMPLES OF SUBSTRATES INDICATED TO RECEIVE JOINT SEALANT AND <br />THAT SEALANT WAS FOUND TO BE NON-STAINING TO SUBSTRATE. INDICATE <br />REQUIREMENTS FOR PRIMERS OR SPECIAL PREPARATION TO MEET NON-STAINING <br />REQUIREMENTS. <br />C. JOINT SEALANT SCHEDULE: INCLUDE THE FOLLOWING INFORMATION: <br />1. JOINT-SEALANT APPLICATION, JOINT LOCATION, AND DESIGNATION. <br />2. JOINT-SEALANT MANUFACTURER AND PRODUCT NAME. <br />3. JOINT-SEALANT FORMULATION. <br />4. JOINT-SEALANT COLOR. <br />1.4 QUALITY ASSURANCE: <br />A. APPLICABLE STANDARDS AS REFERENCED HEREIN: <br />1. ASTM INTERNATIONAL (ASTM). <br />2. UNITED STATES DEPARTMENT OF AGRICULTURE (USDA). <br />B. ADHESION COMPATIBILITY TESTS: PERFORM TESTS ON ACTUAL SAMPLES OF <br />ALUMINUM FRAMING SYSTEM COMPONENTS, TO DETERMINE THAT MATERIALS ARE <br />COMPATIBLE AND THAT ADHESION IS ACCEPTABLE. IDENTIFY REQUIREMENTS FOR <br />PRIMERS OR SPECIAL PREPARATION. <br />C. SUBSTRATE STAINING TEST RESULTS: PERFORM TEST ON ACTUAL SAMPLES OF <br />STONE VENEER TO RECEIVE JOINT SEALANT TO DETERMINE THAT SEALANT IS <br />NON-STAINING TO SUBSTRATE. IDENTIFY REQUIREMENTS FOR PRIMERS OR SPECIAL <br />PREPARATION TO MEET NON-STAINING REQUIREMENTS. <br />1. TEST POROUS SUBSTANCES IN ACCORD WITH ASTM C1248-08(2012). <br />2. TEST NON-POROUS SUBSTRATES IN ACCORD WITH ASTM D2203-01(2011). <br />D. VOC CONTENT OF INTERIOR SEALANTS: SEALANTS AND SEALANT PRIMERS USED <br />INSIDE THE WEATHERPROOFING SYSTEM SHALL HAVE A VOC CONTENT LESS THAN <br />THE CURRENT VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY MANAGEMENT <br />DISTRICT (SCAQMD) RULE #1113, ARCHITECTURAL COATING, RULES IN EFFECT <br />JANUARY 1, 2004. <br />E. ARCHITECT RESERVES THE RIGHT TO REJECT WORK NOT IN CONFORMANCE WITH <br />SELECTED COLORS, BASED UPON SAMPLES SUBMITTED. <br />1.5 PROJECT/ SITE CONDITIONS: <br />A. PROTECTION OF ADJACENT SURFACES: <br />1. PROTECT BY APPLYING MASKING MATERIAL OR MANIPULATING APPLICATION <br />EQUIPMENT TO KEEP MATERIALS IN JOINT. IF MASKING MATERIALS ARE <br />USED, ALLOW NO TAPE TO TOUCH CLEANED SURFACES TO RECEIVE SEALANT. <br />REMOVE TAPE IMMEDIATELY AFTER CAULKING, BEFORE SURFACE SKIN <br />BEGINS TO FORM. <br />2. REMOVE MISAPPLIED MATERIALS FROM SURFACES BY USING SOLVENTS <br />AND METHODS RECOMMENDED BY MANUFACTURER. <br />3. AT SURFACES FROM WHICH MATERIALS HAVE BEEN REMOVED, RESTORE <br />TO ORIGINAL CONDITION AND APPEARANCE. <br />1.6 WARRANTIES: <br />A. INSTALLER'S WARRANTY: WARRANT WORK TO BE FREE FROM DEFECTS IN MATERIALS <br />AND WORKMANSHIP, INCLUDING JOINT FAILURE, FOR A PERIOD OF TWO YEARS. <br />B. WARRANTIES SHALL BEGIN AT DATE OF SUBSTANTIAL COMPLETION. <br />PART 2 - PRODUCTS <br />2.1 ONE-PART, NON-SAG POLYURETHANE SEALANT: <br />A. ACCEPTABLE PRODUCTS: <br />1. BASF BUILDING PRODUCTS, SONOLASTIC NP-1. <br />2. PECORA CORP., DYNATROL I-XL. <br />3. TREMCO, INC., AN RPM COMPANY, VULKEM 116 <br />4. TREMCO, INC., AN RPM COMPANY, DYMONIC. <br />B. CHARACTERISTICS: <br />1. TYPE: ONE-PART, NON-SAG POLYURETHANE-BASED SEALANT; MEETING <br />ASTM C920-11, TYPE S, GRADE NS, CLASS 25, FOR USE NT. <br />2. COLORS: COLORS AS SELECTED BY ARCHITECT. <br />2.2 SILICONE BATH SEALANT FOR WET AREAS: <br />A. ACCEPTABLE PRODUCTS: <br />1. BASF BUILDING SYSTEMS, OMNIPLUS. <br />2. DOW CORNING CORP., 786 MILDEW-RESISTANT SILICONE SEALANT. <br />3. FRANKLIN INTERNATIONAL, TITEBOND KITCHEN & BATH SEALANT. <br />4. GE ADVANCED MATERIALS, SANITARY SCS1700. <br />5. PECORA CORP., #898NST SILICONE SANITARY SEALANT. <br />B. CHARACTERISTICS: <br />1. TYPE: ONE-PART SILICON RUBBER, MILDEW- AND STAIN-RESISTANT, ACID- <br />CURING SILICONE SEALANT; MEETING ASTM C920-11, TYPE S, GRADE NS, <br />CLASS 25, FOR USE NT. <br />2. COLOR: CLEAR, WHITE OR OFF-WHITE, AS SELECTED BY ARCHITECT. <br />2.3 TWO-PART POLYURETHANE SEALANT FOR HORIZONTAL TRAFFIC-BEARING PAVEMENTS: <br />A. ACCEPTABLE PRODUCTS: <br />1. BASF BUILDING SYSTEMS, SONOLASTIC SL 2. <br />2. PECORA CORP., UREXPAN NR-200. <br />3. TREMCO, INC., AN RPM COMPANY, 45 SSL. <br />B. CHARACTERISTICS: <br />1. TYPE: TWO-COMPONENT POLYURETHANE SEALANT FOR HORIZONTAL <br />TRAFFIC-BEARING SURFACES MEETING ASTM C920-11, TYPE M, GRADE P <br />OR NS, MINIMUM CLASS 25, FOR USE T; SELF-LEVELING FOR FLAT SURFACES <br />AND NON-SAG FOR SLOPED SURFACES. <br />2. COLORS: COLORS AS SELECTED BY ARCHITECT. <br />2.4 SOLVENT-RELEASE-CURING ACRYLIC SEALANT: <br />A. ACCEPTABLE PRODUCTS: <br />1. FRANKLIN INTERNATIONAL, TITEBOND PAINTERS PLUS CAULK. <br />2. SCHNEE-MOREHEAD, INC., ACRYL-R ACRYLIC SEALANT. <br />3. TREMCO, INC., AN RPM COMPANY, MONO 555. <br />B. CHARACTERISTICS: <br />1. TYPE: ONE-PART, ACRYLIC POLYMER SEALANT, MEETING ASTM C1311-11. <br />2. COLORS: STANDARD COLORS AS SELECTED BY ARCHITECT. <br />2.5 PAINTABLE ACRYLIC-LATEX JOINT SEALANT: <br />A. ACCEPTABLE PRODUCTS: <br />1. BASF BUILDING SYSTEMS, SONOLASTIC SONOLAC. <br />2. BOSTIK, CHEM-CALK 600. <br />3. FRANKLIN INTERNATIONAL, TITEBOND PAINTERS CAULK. <br />4. GE ADVANCED MATERIALS, RCS20. <br />5. PECORA CORP., AC-20 ACRYLIC LATEX. <br />6. TREMCO, INC., AN RPM COMPANY, TREMFLEX 834. <br />B. CHARACTERISTICS: FLEXIBLE, PAINTABLE, NON-STAINING, NON-BLEEDING ACRYLIC LATEX <br />OR SILICONIZED ACRYLIC EMULSION, MEETING ASTM C834-10, TYPE OP, GRADE NF. <br />2.6 ACCESSORY MATERIALS: <br />A. JOINT CLEANER: TYPE RECOMMENDED BY MATERIAL MANUFACTURER FOR <br />SUBSTRATES INDICATED. <br />B. JOINT PRIMER/SEALER: TYPE RECOMMENDED BY MATERIAL MANUFACTURER FOR <br />SUBSTRATES, CONDITIONS AND EXPOSURES INDICATED. <br />C. BOND BREAKER TAPE: PLASTIC TAPE APPLIED TO CONTACT SURFACES WHERE BOND <br />TO SUBSTRATE OR JOINT FILLER MUST BE AVOIDED FOR MATERIAL PERFORMANCE. <br />D. SEALANT BACKER ROD: COMPRESSIBLE ROD STOCK AS RECOMMENDED BY SEALANT <br />MANUFACTURER FOR COMPATIBILITY WITH SEALANT. PROVIDE SIZE AND SHAPE OF ROD <br />TO CONTROL JOINT DEPTH. <br />E. TOOLING AGENT: AGENT RECOMMENDED BY MATERIAL MANUFACTURER TO ENSURE <br />CONTACT OF MATERIAL WITH INNER JOINT FACES. <br />PART 3 - EXECUTION <br />3.1 JOB MOCK-UP: <br />A. PREPARE, CAULK AND FINISH ONE MOCK-UP SAMPLE OF EACH JOINT CONDITION. <br />B. SAMPLE JOINTS SHALL BE APPROVED BY ARCHITECT PRIOR TO BEGINNING WORK. <br />APPROVED, UNDAMAGED MOCK-UP JOINTS SHALL SERVE AS A STANDARD OF QUALITY <br />FOR THE REMAINDER OF THE WORK. <br />3.2 JOINT SURFACE PREPARATION: <br />A. CLEAN JOINTS OF DEBRIS AND PROJECTIONS INCLUDING SHIMS. <br />B. CLEAN JOINT SURFACES IMMEDIATELY BEFORE CAULKING JOINTS. REMOVE DIRT, <br />INSECURE COATINGS, MOISTURE AND OTHER SUBSTANCES WHICH WOULD INTERFERE <br />WITH BOND. <br />C. ROUGHEN JOINT SURFACES OF NON-POROUS MATERIALS, UNLESS MATERIAL <br />MANUFACTURER'S PRODUCT DATA INDICATES EQUAL BOND STRENGTH AS POROUS <br />SURFACES. RUB WITH FINE ABRASIVE CLOTH OR WOOL TO PRODUCE DULL SHEEN. <br />3.3 APPLICATION: <br />A. COMPLY WITH JOINT SEALANT MATERIAL MANUFACTURER'S PRODUCT DATA AND ASTM <br />C1193-09 EXCEPT WHERE MORE STRINGENT REQUIREMENTS ARE SPECIFIED. <br />B. PRIME JOINT SURFCES WHERE RECOMMENDED BY MATERIAL MANUFACTURER. DO <br />NOT ALLOW PRIMER/SEALER TO SPILL OR MIGRATE ONTO ADJACENT SURFACES. <br />C. INSTALL BACKER ROD FOR JOINT SEALANT MATERIALS, EXCEPT WHERE RECOMMENDED <br />BY MATERIAL MANUFACTURER TO BE OMITTED FOR APPLICATION INDICATED. <br />1. PLACE BACKER ROD TO MAINTAIN RECOMMENDED SEALANT THICKNESS AND <br />PROFILE. <br />2. PLACE ROD AT DEPTH TO PROVIDE SEALANT MANUFACTURER'S <br />RECOMMENDED SEALANT DEPTH. <br />3. DO NOT TWIST ROD DURING INSTALLATION. <br />4. PLACE ROD TO MINIMIZE POSSIBILITY OF EXTRUSION WHEN JOINT IS <br />COMPRESSED. <br />5. INSTALL BOND BREAKER TAPE IN LIEU OF BACKER ROD FOR SHALLOW, CLOSED <br />JOINTS AND AS RECOMMENDED BY MANUFACTURER'S PRODUCT DATA. <br />D. EMPLOY INSTALLATION TECHNIQUES WHICH WILL ENSURE THAT MATERIALS ARE <br />DEPOSITED IN UNIFORM, CONTINUOUS RIBBONS WITHOUT GAPS OR AIR POCKETS, <br />WITH COMPLETE WETTING OF JOINT BOND SURFACES. WHERE HORIZONTAL JOINTS <br />ARE BETWEEN A HORIZONTAL SURFACE AND A VERTICAL SURFACE, FILL JOINT TO FORM <br />SLIGHT COVE SO THAT JOINT WILL NOT TRAP MOISTURE AND DEBRIS. <br />E. DO NOT ALLOW MATERIALS TO OVERFLOW ONTO ADJACENT SURFACES. PREVENT <br />STAINING OF ADJACENT SURFACES. <br />F. REMOVE EXCESS AND MISPLACED MATERIALS AS WORK PROGRESSES. CLEAN THE <br />ADJOINING SURFACES TO REMOVE MISPLACED MATERIALS, WITHOUT DAMAGE TO <br />ADJACENT SURFACES OR FINISHES. <br />G. INTERIOR JOINTS: AT INTERIOR JOINTS AND SEAMS AT ABUTTING AND ADJACENT <br />MATERIALS, RECESS JOINT SEALANT 3/16" IN JOINTS WIDER THAN 1/4". AT JOINTS 1/4" <br />OR LESS IN WIDTH, TOOL JOINT SEALANT FLUSH. <br />H. TOOL JOINTS OF NON-SAG SEALANT TO CONCAVE PROFILE AND SMOOTH, UNIFORM <br />SURFACE, FLUSH WITH EDGES OF SUBSTRATE. MAINTAIN SEALANT DEPTH-TO-WIDTH <br />RATIO IN ACCORD WITH MANUFACTURER'S PRODUCT DATA. <br />I. CURE JOINT SEALANTS IN ACCORD WITH MANUFACTURER'S PRODUCT DATA TO OBTAIN <br />HIGH EARLY BOND STRENGTH, INTERNAL COHESIVE STRENGTH AND SURFACE <br />DURABILITY. PROTECT UNCURED SURFACES FROM CONTAMINATION AND PHYSICAL <br />DAMAGE. <br />3.4 JOINT SEALANT SCHEDULE: <br />A. INTERIOR JOINTS AT PERIMETER OF WINDOWS AND OF HOLLOW METAL FRAMING: <br />ONE-PART, NON-SAG POLYURETHANE SEALANT. <br />B. INTERIOR CONCEALED BEDDING JOINTS AND THRESHOLDS: SOLVENT-RELEASE-CURING <br />ACRYLIC SEALANT. <br />C. INTERIOR HORIZONTAL TRAFFIC-BEARING JOINTS, EXCLUDING TILE FLOOR JOINTS: <br />TWO-PART POLYURETHANE SEALANT. <br />D. FIRESTOPPED JOINTS: FIRESTOP SEALANT AS SPECIFIED IN FIRESTOPPING SECTION. <br />E. TYPICAL INTERIOR JOINTS AND SEAMS AT ABUTTING AND ADJACENT MATERIALS <br />EXCEPT AS SPECIFIED HEREIN: PAINTABLE ACRYLIC-LATEX JOINT SEALANT. <br />F. INTERIOR JOINTS IN CONJUNCTION WITH FIXTURES AND TILE FINISHES: SILICONE <br />BATH SEALANT. <br />END OF SECTION <br />SECTION 08 1416 - FLUSH WOOD DOORS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A. SECTION INCLUDES: <br />1. WOOD DOORS. <br />B. RELATED REQUIREMENTS: <br />1. DIVISION 01 - GENERAL REQUIREMENTS. <br />2. SECTION 09 9000 - PAINTING AND COATING. <br />1.02 DESIGN REQUIREMENTS <br />A. DRAWINGS INDICATE SIZES, LOCATIONS AND GENERAL DETAILS OF WOOD DOOR <br />CONSTRUCTION AND INSTALLATION. <br />B. REGULATORY REQUIREMENTS: <br />1. FIRE RATED DOORS SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING <br />AND CERTIFICATION AGENCY IN ACCORDANCE WITH LOCAL BUILDING CODES <br />AND ACCEPTABLE TO THE AUTHORITIES HAVING JURISDICTION. THE LISTED <br />DOORS SHALL MEET OR EXCEED THE REQUIREMENTS OF UL10B, NFPA 252 AND <br />NFPA 80. ALL DOOR REQUIRING FIRE-RATING SHALL CARRY EITHER A UL OR <br />ITS (INTERTEK TESTING SERVICES-WARNOCK HERSEY) LABEL. <br />2. ASTM E2074 – STANDARD TEST METHOD FOR FIRE TESTS OF DOOR <br />ASSEMBLIES, INCLUDING POSITIVE PRESSURE ON SIDE-HINGED AND PIVOTED <br />SWINGING DOOR ASSEMBLIES. <br />1.03 SUBMITTALS <br />A. SHOP DRAWINGS: SUBMIT SCHEDULES, PLANS, ELEVATIONS AND DETAILS INDICATING <br />DOOR CONSTRUCTION DETAILS, OPENING IDENTIFICATION SYMBOLS, SIZES, DOOR <br />TYPE AND GRADE, FIRE CLASSIFICATION, SWING, LIGHT AND LOUVER CUTOUT SIZE <br />AND LOCATIONS, AND UNDERCUTS. <br />B. PRODUCT DATA: SUBMIT MANUFACTURERS TECHNICAL DATA FOR EACH SPECIFIED <br />DOOR TYPE, INCLUDING DETAILS OF WOOD SPECIES, DESIGN AND CONSTRUCTION, <br />FACTORY FINISHING SPECIFICATIONS AND INSTALLATION INSTRUCTIONS. <br />C. COLOR/FINISH SAMPLES: SUBMIT SAMPLES OF NOT LESS THAN 4-INCH BY 6-INCH ON <br />REPRESENTATIVE DOOR FINISH AND SAMPLES OF 3-INCH BY 8-INCH FOR THE EXPOSED <br />EDGES. EACH SAMPLE SHALL BEAR A LABEL IDENTIFYING THE JOB NAME, ARCHITECT, <br />CONTRACTOR AND THE WOODWORK INSITUTE FINISH SYSTEM NUMBER. <br />1.04 QUALITY ASSURANCE <br />A. WOOD DOORS CONSTRUCTION, MANUFACTURE, AND FABRICATION SHALL CONFORM TO <br />ANSI/WDMA I.S. 1-A, CUSTOM GRADE, EXTRA HEAVY DUTY GRADE INCLUDING THE <br />LATEST REVISIONS, AND SPECIAL REQUIREMENTS SPECIFIED. <br />B. DOORS SHALL BE FABRICATED, HARDWARE FACTORY FITTED AND MACHINED, AND <br />FACTORY FINISHED, UNLESS NOTED OTHERWISE. <br />C. WOOD DOOR FINISHES SHALL COMPLY WITH THE ARCHITECTURAL WOODWORK <br />INSTITUTE STANDARDS. <br />D. DOORS SHALL BE PRODUCTS OF ONE MANUFACTURER. <br />E. DOOR MODIFICATIONS ARE NOT PERMITTED, UNLESS REVIEWED BY THE ARCHITECT OF <br />RECORD. <br />1.05 DELIVERY, STORAGE AND HANDLING <br />A. DELIVER MATERIALS IN MANUFACTURERS ORIGINAL, UNOPENED, UNDAMAGED <br />CONTAINERS WITH IDENTIFICATION LABELS INTACT. <br />B. DELIVER DOORS TO THE PROJECT SITE ONLY AFTER BUILDING HAS BEEN PROVIDED <br />WITH DESIGN TEMPERATURE AND HUMIDITY. <br />C. STORE AND HANDLE IN ACCORDANCE WITH ANSI/WDMA I.S.1-A. STORE DOORS <br />PROTECTED FROM EXPOSURE TO HARMFUL CONDITIONS AND AT TEMPERATURE AND <br />HUMIDITY CONDITIONS RECOMMENDED BY THE MANUFACTURER. <br />1.06 PROJECT CONDITIONS <br />A. DO NOT INSTALL DOORS UNTIL BUILDING IS ENCLOSED AND AMBIENT CONDITIONS ARE <br />WITHIN THE TEMPERATURE AND HUMIDITY RANGE RECOMMENDED BY DOOR <br />MANUFACTURER. <br />1.07 WARRANTY <br />A. MANUFACTURER SHALL PROVIDE A LIFE TIME MATERIAL WARRANTY FOR INTERIOR <br />DOORS. <br />B. INSTALLER SHALL PROVIDE A TWO YEAR FABRICATION AND INSTALLATION WARRANTY <br />FOR ALL DOORS. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A. PROVIDE PRODUCTS MANUFACTURED BY ONE OF THE FOLLOWING: <br />1. ALGOMA HARDWOOD INC. <br />2. MARSHFIELD DOOR SYSTEMS. <br />3. EGGERS INDUSTRIES. <br />4. OR EQUAL. <br />2.02 DOOR CONSTRUCTION <br />A. LAMINATED, SHIELDED CORE, WXR&20PP, 20&MIN. <br />1. THICKNESS: 1-3/4 INCH. <br />A. CLEAR FINISH: <br />1) GRADE: PREMIUM. <br />2) FACE: PLAIN SLICED WHITE MAPLE. <br />2. CROSSBANDS: HARDWOOD VENEER OR ENGINEERED HIGH DENSITY <br />FIBERBOARD, 1/16 INCH THICK. <br />3. SIDE EDGES: 3/4 INCH, VENEER TO MATCH FACE VENEER, BONDED TO CORE. <br />FACTORY INSTALL CONCEALED INTUMESCENT SEALS PER UL 10C FOR <br />POSITIVE PRESSURE FIRE DOORS. <br />4. TOP AND BOTTOM EDGES: 1&1/8 INCH, BONDED TO CORE. FACTORY INSTALL <br />INTUMESCENT SEALS AT TOP RAIL PER UL 10C FOR POSITIVE PRESSURE FIRE <br />DOORS. <br />5. FACE ASSEMBLY ADHESIVE: TYPE I, WATERPROOF. <br />6. CORE ASSEMBLY ADHESIVE: TYPE II, WATER&RESISTANT. <br />7. CORE: BONDED LOW DENSITY STAVED WOOD. <br />8. MOISTURE STRIPPING: NOT APPLICABLE. <br />9. SHIELDING: SHEET LEAD BONDED ONE SIDE OR TWO SIDES TO CROSSBAND, <br />THICKNESS TO CONFORM TO SHIELDING REQUIREMENTS OF WALL IN WHICH <br />DOOR IS INSTALLED. <br />10. BLOCKING FOR HARDWARE: FLAME RESISTANT, 6 INCH TOP EDGE FOR <br />CLOSERS, 5.5 INCHES FOR BOTTOM HARDWARE OR AUTOMATIC CLOSERS <br />WHERE APPLICABLE, 5 X 18 INCH LOCK BLOCKS, 5.5 INCH CROSS BLOCKING <br />FOR PANIC HARDWARE, 5 X 12 INCH FOR FLOOR CLOSERS OR PIVOT HINGES <br />WHERE APPLICABLE. <br />11. ALGOMA HARDWOODS, INC.'S "ALGOMA GRADE LEAD LINED DOOR, FD 1/3 <br />HOUR"; MARSHFIELD DOOR SYSTEMS, INC.'S "X-RAY DOOR WXR-20"; EGGERS <br />INDUSTRIES, "LEAD SHIELD DOOR & 20 MINUTE FIRE DOOR. <br />2.03 FABRICATION <br />A. FABRICATE FIRE&RATED DOORS IN ACCORDANCE WITH WI QUALITY STANDARDS AND <br />WDMAI.S.1 & A & LATEST EDITION AND TO UL OR WH REQUIREMENTS. ATTACH <br />PERMANENT METAL <br />FIRE & RATING LABEL TO DOOR EDGE, EITHER ON HINGE STILE OR TOP EDGE. <br />B. PRE & MACHINE DOORS AT FACTORY FOR FINISH HARDWARE. CUTOUTS FOR <br />HARDWARE IN DOORS HAVING A FIRE RATING OF 20 MINUTES OR MORE SHALL BE <br />ACCOMPLISHED AT THE FACTORY BEFORE LABELS ARE AFFIXED. PREPARATION SHALL <br />BE PERFORMED IN ACCORDANCE WITH MANUFACTURER’S INSPECTION SERVICE <br />PROCEDURE AND UNDER LABEL SERVICE. <br />C. VENEER: FACE VENEER GRAIN SHALL RUN VERTICALLY; CROSSBAND VENEER RUN <br />HORIZONTALLY. <br />2.04 FACTORY FINISH <br />A. FACTORY FINISH: PREMIUM FINISH, MEET OR EXCEED PERFORMANCE STANDARDS OF <br />WI SYSTEM CATALYZED POLYURETHANE. FACTORY & FINISHED DOORS SHALL BE <br />INSTALLED JUST PRIOR TO SUBSTANTIAL COMPLETION. <br />1. CLEAR FINISH: WI SYSTEM 5, CATALYZED POLYURETHANE. <br />PART 3 - EXECUTION <br />3.1 EXAMINATION <br />A. VERIFY THAT OPENINGS ARE READY TO RECEIVE WORK AND FIELD MEASUREMENTS <br />ARE AS INDICATED ON SHOP DRAWINGS. <br />B. BEGINNING OF INSTALLATION MEANS ACCEPTANCE OF EXISTING CONDITIONS. <br />C. PRODUCT SCHEDULE: FOR HOLLOW-METAL DOORS AND FRAMES, PREPARED BY OR <br />UNDER THE SUPERVISION OF SUPPLIER, USING SAME REFERENCE NUMBERS FOR <br />DETAILS AND OPENINGS AS THOSE ON DRAWINGS. COORDINATE WITH FINAL DOOR <br />HARDWARE SCHEDULE. <br />1.7 INFORMATIONAL SUBMITTALS <br />A. PRODUCT TEST REPORTS: FOR EACH TYPE OF HOLLOW-METAL DOOR AND FRAME <br />ASSEMBLY, FOR TESTS PERFORMED BY A QUALIFIED TESTING AGENCY. <br />B. OVERSIZE CONSTRUCTION CERTIFICATION: FOR ASSEMBLIES REQUIRED TO BE <br />FIRE-RATED AND EXCEEDING LIMITATIONS OF LABELED ASSEMBLIES. <br />1.8 DELIVERY, STORAGE, AND HANDLING <br />A. DELIVER HOLLOW-METAL DOORS AND FRAMES PALLETIZED, PACKAGED, OR CRATED TO <br />PROVIDE PROTECTION DURING TRANSIT AND PROJECT-SITE STORAGE. DO NOT USE <br />NONVENTED PLASTIC. <br />1. PROVIDE ADDITIONAL PROTECTION TO PREVENT DAMAGE TO <br />FACTORY-FINISHED UNITS. <br />B. DELIVER WELDED FRAMES WITH TWO REMOVABLE SPREADER BARS ACROSS BOTTOM <br />OF FRAMES, TACK WELDED TO JAMBS AND MULLIONS. <br />C. STORE HOLLOW-METAL DOORS AND FRAMES VERTICALLY UNDER COVER AT PROJECT <br />SITE WITH HEAD UP. PLACE ON MINIMUM 4-INCH- HIGH WOOD BLOCKING. PROVIDE <br />MINIMUM 1/4-INCH SPACE BETWEEN EACH STACKED DOOR TO PERMIT AIR CIRCULATION. <br />PART 2 - PRODUCTS <br />2.1 MANUFACTURERS <br />A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY ONE OF THE FOLLOWING: <br />1. CECO DOOR; ASSA ABLOY. <br />2. CURRIES COMPANY; ASSA ABLOY. <br />3. REPUBLIC DOORS AND FRAMES. <br />4. OR APPROVED EQUAL <br />B. SOURCE LIMITATIONS: OBTAIN HOLLOW-METAL DOOR AND FRAMES FROM SINGLE <br />SOURCE FROM SINGLE MANUFACTURER. <br />2.2 PERFORMANCE REQUIREMENTS <br />A. FIRE-RATED ASSEMBLIES: COMPLYING WITH NFPA 80 AND LISTED AND LABELED BY A <br />QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION FOR <br />FIRE-PROTECTION RATINGS AND TEMPERATURE-RISE LIMITS INDICATED, BASED ON <br />TESTING AT POSITIVE PRESSURE ACCORDING TO NFPA 252 OR UL 10C. <br />1. SMOKE- AND DRAFT-CONTROL ASSEMBLIES: PROVIDE ASSEMBLIES WITH <br />GASKETS LISTED AND LABELED FOR SMOKE AND DRAFT CONTROL BY A <br />QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING <br />JURISDICTION, BASED ON TESTING ACCORDING TO UL 1784 AND INSTALLED <br />IN COMPLIANCE WITH NFPA 105. <br />B. FIRE-RATED, BORROWED-LITE ASSEMBLIES: COMPLYING WITH NFPA 80 AND LISTED <br />AND LABELED BY A QUALIFIED TESTING AGENCY ACCEPTABLE TO AUTHORITIES <br />HAVING JURISDICTION, FOR FIRE-PROTECTION RATINGS INDICATED, BASED ON <br />TESTING ACCORDING TO NFPA 257 OR UL 9. <br />2.3 INTERIOR STANDARD STEEL DOORS AND FRAMES <br />A. CONSTRUCT HOLLOW-METAL DOORS AND FRAMES TO COMPLY WITH STANDARDS <br />INDICATED FOR MATERIALS, FABRICATION, HARDWARE LOCATIONS, HARDWARE <br />REINFORCEMENT, TOLERANCES, AND CLEARANCES, AND AS SPECIFIED. <br />B. HEAVY-DUTY DOORS AND FRAMES: SDI A250.8, LEVEL 2; SDI A250.4, LEVEL B PROVIDE <br />AT ALL SCHEDULED INTERIOR DOOR LOCATIONS EXCEPT STAIRWELLS. <br />1. DOORS: <br />A. TYPE: AS INDICATED IN THE DOOR SCHEDULE. <br />B. THICKNESS: AS INDICATED IN THE DOOR SCHEDULE. <br />C. FACE: AS INDICATED IN THE DOOR SCHEDULE. <br />D. EDGE CONSTRUCTION: MODEL 2, SEAMLESS. <br />E. EDGE BEVEL: PROVIDE MANUFACTURER'S STANDARD BEVELED OR <br />SQUARE EDGES. <br />F. CORE: MANUFACTURER'S STANDARD. <br />G. FIRE-RATED CORE: MANUFACTURER'S STANDARD CORE FOR <br />FIRE-RATED AND TEMPERATURE-RISE-RATED DOORS. <br />2. FRAMES: <br />A. MATERIALS: UNCOATED STEEL SHEET, MINIMUM THICKNESS OF <br />0.059 INCH. <br />B. SIDELITE AND TRANSOM FRAMES: FABRICATED FROM SAME <br />THICKNESS MATERIAL AS ADJACENT DOOR FRAME. <br />C. CONSTRUCTION: FULL PROFILE WELDED. <br />3. EXPOSED FINISH: PRIME. <br />2.4 FRAME ANCHORS <br />A. JAMB ANCHORS: <br />1. TYPE: ANCHORS OF MINIMUM SIZE AND TYPE REQUIRED BY APPLICABLE <br />DOOR AND FRAME STANDARD, AND SUITABLE FOR PERFORMANCE LEVEL <br />INDICATED. <br />2. QUANTITY: MINIMUM OF THREE ANCHORS PER JAMB, WITH ONE ADDITIONAL <br />ANCHOR FOR FRAMES WITH NO FLOOR ANCHOR. PROVIDE ONE ADDITIONAL <br />ANCHOR FOR EACH 24 INCHES OF FRAME HEIGHT ABOVE 7 FEET. <br />B. FLOOR ANCHORS: PROVIDE FLOOR ANCHORS FOR EACH JAMB AND MULLION THAT <br />EXTENDS TO FLOOR. <br />C. FLOOR ANCHORS FOR CONCRETE SLABS WITH UNDERLAYMENT: ADJUSTABLE-TYPE <br />ANCHORS WITH EXTENSION CLIPS, ALLOWING NOT LESS THAN 2-INCH HEIGHT <br />ADJUSTMENT. TERMINATE BOTTOM OF FRAMES AT TOP OF UNDERLAYMENT. <br />D. MATERIAL: ASTM A 879/A 879M, COMMERCIAL STEEL (CS), 04Z COATING DESIGNATION; <br />MILL PHOSPHATIZED. <br />1. FOR ANCHORS BUILT INTO EXTERIOR WALLS, STEEL SHEET COMPLYING WITH <br />ASTM A 1008/A 1008M OR ASTM A 1011/A 1011M; HOT-DIP GALVANIZED <br />ACCORDING TO ASTM A 153/A 153M, CLASS B. <br />2.5 MATERIALS <br />A. COLD-ROLLED STEEL SHEET: ASTM A 1008/A 1008M, COMMERCIAL STEEL (CS), TYPE B; <br />SUITABLE FOR EXPOSED APPLICATIONS. <br />B. HOT-ROLLED STEEL SHEET: ASTM A 1011/A 1011M, COMMERCIAL STEEL (CS), TYPE B; <br />FREE OF SCALE, PITTING, OR SURFACE DEFECTS; PICKLED AND OILED. <br />C. METALLIC-COATED STEEL SHEET: ASTM A 653/A 653M, COMMERCIAL STEEL (CS), TYPE B. <br />D. INSERTS, BOLTS, AND FASTENERS: HOT-DIP GALVANIZED ACCORDING TO <br />ASTM A 153/A 153M. <br />E. POWER-ACTUATED FASTENERS IN CONCRETE: FASTENER SYSTEM OF TYPE <br />SUITABLE FOR APPLICATION INDICATED, FABRICATED FROM CORROSION-RESISTANT <br />MATERIALS, WITH CLIPS OR OTHER ACCESSORY DEVICES FOR ATTACHING <br />HOLLOW-METAL FRAMES OF TYPE INDICATED. <br />F. MINERAL-FIBER INSULATION: ASTM C 665, TYPE I (BLANKETS WITHOUT MEMBRANE <br />FACING); CONSISTING OF FIBERS MANUFACTURED FROM SLAG OR ROCK WOOL; <br />WITH MAXIMUM FLAME-SPREAD AND SMOKE-DEVELOPED INDEXES OF 25 AND 50, <br />RESPECTIVELY; PASSING ASTM E 136 FOR COMBUSTION CHARACTERISTICS. <br />G. GLAZING: COMPLY WITH REQUIREMENTS IN SECTION 088000 "GLAZING." <br />H. DOOR SILENCERS: 1/2 INCH DIAMETER TAMPER-PROOF GREY RUBBER CONE-SHAPED <br />PLUGS. <br />2.6 FABRICATION <br />A. HOLLOW-METAL FRAMES: FABRICATE IN ONE PIECE EXCEPT WHERE HANDLING AND <br />SHIPPING LIMITATIONS REQUIRE MULTIPLE SECTIONS. WHERE FRAMES ARE <br />FABRICATED IN SECTIONS, PROVIDE ALIGNMENT PLATES OR ANGLES AT EACH <br />JOINT, FABRICATED OF METAL OF SAME OR GREATER THICKNESS AS FRAMES. <br />1. PROVIDE COUNTERSUNK, FLAT- OR OVAL-HEAD EXPOSED SCREWS AND BOLTS <br />FOR EXPOSED FASTENERS UNLESS OTHERWISE INDICATED. <br />2. DOOR SILENCERS: EXCEPT ON WEATHER-STRIPPED FRAMES, DRILL STOPS <br />TO RECEIVE DOOR SILENCERS AS FOLLOWS. KEEP HOLES CLEAR DURING <br />CONSTRUCTION. <br />A. SINGLE-DOOR FRAMES: DRILL STOP IN STRIKE JAMB TO RECEIVE <br />THREE DOOR SILENCERS. <br />B. HARDWARE PREPARATION: FACTORY PREPARE HOLLOW-METAL DOORS AND FRAMES <br />TO RECEIVE TEMPLATED CYLINDRICAL HARDWARE, AND ELECTRICAL WIRING; INCLUDE <br />CUTOUTS, REINFORCEMENT, DRILLING, AND TAPPING ACCORDING TO <br />SDI A250.6, THE DOOR HARDWARE SCHEDULE, AND TEMPLATES. <br />1. REINFORCE DOORS AND FRAMES TO RECEIVE NONTEMPLATED, CYLINDRICAL, <br />AND SURFACE-MOUNTED DOOR HARDWARE. <br />2. COMPLY WITH BHMA A156.115 FOR PREPARING HOLLOW-METAL DOORS AND <br />FRAMES FOR HARDWARE. <br />2.7 STEEL FINISHES <br />A. PRIME FINISH: CLEAN, PRETREAT, AND APPLY MANUFACTURER'S STANDARD PRIMER. <br />1. SHOP PRIMER: MANUFACTURER'S STANDARD, FAST-CURING, LEAD- AND <br />CHROMATE-FREE PRIMER COMPLYING WITH SDI A250.10; RECOMMENDED <br />BY PRIMER MANUFACTURER FOR SUBSTRATE; COMPATIBLE WITH <br />SUBSTRATE AND FIELD-APPLIED COATINGS DESPITE PROLONGED EXPOSURE. <br />PART 3 - EXECUTION <br />3.1 PREPARATION <br />A. REMOVE WELDED-IN SHIPPING SPREADERS INSTALLED AT FACTORY. RESTORE <br />EXPOSED FINISH BY GRINDING, FILLING, AND DRESSING, AS REQUIRED TO MAKE <br />REPAIRED AREA SMOOTH, FLUSH, AND INVISIBLE ON EXPOSED FACES. TOUCH UP <br />FACTORY-APPLIED FINISHES WHERE SPREADERS ARE REMOVED. <br />B. DRILL AND TAP DOORS AND FRAMES TO RECEIVE NONTEMPLATED, CYLINDRICAL, <br />AND SURFACE-MOUNTED DOOR HARDWARE. <br />3.2 INSTALLATION <br />A. GENERAL: INSTALL HOLLOW-METAL DOORS AND FRAMES PLUMB, RIGID, PROPERLY <br />ALIGNED, AND SECURELY FASTENED IN PLACE. COMPLY WITH APPROVED SHOP <br />DRAWINGS AND WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />B. HOLLOW-METAL FRAMES: COMPLY WITH SDI A250.11OR NAAMM-HMMA 840. <br />1. SET FRAMES ACCURATELY IN POSITION; PLUMBED, ALIGNED, AND BRACED <br />SECURELY UNTIL PERMANENT ANCHORS ARE SET. AFTER WALL <br />CONSTRUCTION IS COMPLETE, REMOVE TEMPORARY BRACES WITHOUT <br />DAMAGE TO COMPLETED WORK. <br />A. WHERE FRAMES ARE FABRICATED IN SECTIONS, FIELD SPLICE AT <br />APPROVED LOCATIONS BY WELDING FACE JOINT CONTINUOUSLY; <br />GRIND, FILL, DRESS, AND MAKE SPLICE SMOOTH, FLUSH, AND <br />INVISIBLE ON EXPOSED FACES. TOUCH-UP FINISHES. <br />B. INSTALL FRAMES WITH REMOVABLE STOPS LOCATED ON <br />SECURE SIDE OF OPENING. <br />2. FLOOR ANCHORS: SECURE WITH POSTINSTALLED ANCHORS. <br />A. FLOOR ANCHORS MAY BE SET WITH POWER-ACTUATED FASTENERS <br />INSTEAD OF POSTINSTALLED EXPANSION ANCHORS IF SO <br />INDICATED AND APPROVED ON SHOP DRAWINGS. <br />3. SOLIDLY PACK MINERAL-FIBER INSULATION INSIDE FRAMES. <br />4. INSTALLATION TOLERANCES: ADJUST HOLLOW-METAL FRAMES TO THE <br />FOLLOWING TOLERANCES: <br />A. SQUARENESS: PLUS OR MINUS 1/16 INCH, MEASURED AT DOOR <br />RABBET ON A LINE 90 DEGREES FROM JAMB PERPENDICULAR <br />TO FRAME HEAD. <br />B. ALIGNMENT: PLUS OR MINUS 1/16 INCH, MEASURED AT JAMBS ON A <br />HORIZONTAL LINE PARALLEL TO PLANE OF WALL. <br />C. TWIST: PLUS OR MINUS 1/16 INCH, MEASURED AT OPPOSITE FACE <br />CORNERS OF JAMBS ON PARALLEL LINES, AND PERPENDICULAR <br />TO PLANE OF WALL. <br />D. PLUMBNESS: PLUS OR MINUS 1/16 INCH, MEASURED AT <br />JAMBS AT FLOOR. <br />C. HOLLOW-METAL DOORS: FIT AND ADJUST HOLLOW-METAL DOORS ACCURATELY IN <br />FRAMES, WITHIN CLEARANCES SPECIFIED BELOW. <br />1. NON-FIRE-RATED STEEL DOORS: COMPLY WITH SDI A250.8 OR NAAMM-HMMA <br />841 AND NAAMM-HMMA GUIDE SPECIFICATION INDICATED. <br />D. GLAZING: COMPLY WITH INSTALLATION REQUIREMENTS IN SECTION 088000 <br />"GLAZING" AND WITH HOLLOW-METAL MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />3.3 CLEANING AND TOUCHUP <br />A. PRIME-COAT TOUCHUP: IMMEDIATELY AFTER ERECTION, SAND SMOOTH RUSTED OR <br />DAMAGED AREAS OF PRIME COAT AND APPLY TOUCHUP OF COMPATIBLE AIR-DRYING, <br />RUST-INHIBITIVE PRIMER. <br />B. TOUCHUP PAINTING: CLEANING AND TOUCHUP PAINTING OF ABRADED AREAS OF <br />PAINT ARE SPECIFIED IN PAINTING SECTIONS. <br />END OF SECTION <br />DIVISION 8 - OPENINGS <br />SECTION 08 1113 - HOLLOW METAL FRAMES <br />PART 1 - GENERAL <br />1.1 RELATED DOCUMENTS <br />A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL <br />AND SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS, <br />APPLY TO THIS SECTION. <br />1.2 SUMMARY <br />A. SECTION INCLUDES: <br />1. INTERIOR STANDARD STEEL DOORS AND FRAMES. <br />1.3 DEFINITIONS <br />A. MINIMUM THICKNESS: MINIMUM THICKNESS OF BASE METAL WITHOUT COATINGS <br />ACCORDING TO NAAMM-HMMA 803 OR SDI A250.8. <br />1.4 COORDINATION <br />A. COORDINATE ANCHORAGE INSTALLATION FOR HOLLOW-METAL FRAMES. FURNISH <br />SETTING DRAWINGS, TEMPLATES, AND DIRECTIONS FOR INSTALLING ANCHORAGES, <br />INCLUDING SLEEVES, CONCRETE INSERTS, ANCHOR BOLTS, AND ITEMS WITH <br />INTEGRAL ANCHORS. DELIVER SUCH ITEMS TO PROJECT SITE IN TIME FOR <br />INSTALLATION. <br />B. COORDINATE REQUIREMENTS FOR INSTALLATION OF DOOR HARDWARE, ELECTRIFIED <br />DOOR HARDWARE, AND ACCESS CONTROL AND SECURITY SYSTEMS. <br />1.5 PREINSTALLATION MEETINGS <br />A. PREINSTALLATION CONFERENCE: CONDUCT CONFERENCE AT PROJECT SITE. <br />1.6 ACTION SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />1. INCLUDE CONSTRUCTION DETAILS, MATERIAL DESCRIPTIONS, CORE <br />DESCRIPTIONS, FIRE-RESISTANCE RATINGS, TEMPERATURE-RISE RATINGS, <br />AND FINISHES. <br />B. SHOP DRAWINGS: INCLUDE THE FOLLOWING: <br />1. ELEVATIONS OF EACH DOOR TYPE. <br />2. DETAILS OF DOORS, INCLUDING VERTICAL- AND HORIZONTAL-EDGE DETAILS <br />AND METAL THICKNESSES. <br />3. FRAME DETAILS FOR EACH FRAME TYPE, INCLUDING DIMENSIONED PROFILES <br />AND METAL THICKNESSES. <br />4. LOCATIONS OF REINFORCEMENT AND PREPARATIONS FOR HARDWARE. <br />5. DETAILS OF EACH DIFFERENT WALL OPENING CONDITION. <br />6. DETAILS OF ELECTRICAL RACEWAY AND PREPARATION FOR ELECTRIFIED <br />HARDWARE, ACCESS CONTROL SYSTEMS, AND SECURITY SYSTEMS. <br />7. DETAILS OF ANCHORAGES, JOINTS, FIELD SPLICES, AND CONNECTIONS. <br />8. DETAILS OF ACCESSORIES. <br />9. DETAILS OF MOLDINGS, REMOVABLE STOPS, AND GLAZING. <br />DIVISION 9 - FINISHES <br />SECTION 09 2900 - GYPSUM BOARD <br />PART 1 - GENERAL <br />1.1 SUMMARY: <br />A RELATED WORK: <br />1. ROUGH CARPENTRY. <br />2. FINISH CARPENTRY AND MILLWORK. <br />3. PAINTING AND COATING. <br />4. WALL COVERINGS. <br />5. ELECTRICAL. <br />1.2 ACTION SUBMITTALS: <br />A. PRODUCT DATA: INDICATE PRODUCT DESCRIPTION, INCLUDING COMPLIANCE WITH <br />SPECIFIED REQUIREMENTS AND INSTALLATION REQUIREMENTS. INCLUDE SPECIFIC <br />REQUIREMENTS FOR FIRE-RATED AND ACOUSTICALLY RATED PARTITIONS AND CEILING <br />ASSEMBLIES. MARK MANUFACTURER'S BROCHURES TO INCLUDE ONLY THOSE PRODUCTS <br />PROPOSED FOR USE. INCLUDE COMPLETE DETAILS OF SHAFTWALL SYSTEM. INCLUDE <br />DETAILS FOR SUPPLEMENTARY FIRE PROTECTION AT PENETRATIONS AND LOCATIONS OF <br />ACOUSTICAL SEALANT. <br />1.3 INFORMATIONAL SUBMITTALS: <br />A. STRUCTURAL DESIGN CALCULATIONS: SUBMIT FOR ARCHITECT'S INFORMATION ONLY. <br />INDICATE COMPLIANCE WITH SPECIFIED DESIGN CRITERIA. CALCULATIONS SHALL BEAR <br />THE SEAL OF A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF CALIFORNIA. <br />1.4 QUALITY ASSURANCE: <br />A. APPLICABLE STANDARDS; STANDARDS OF THE FOLLOWING: <br />1. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). <br />2. ASTM INTERNATIONAL (ASTM) AS REFERENCED HEREIN. <br />3. ASSOCIATION OF THE WALL AND CEILING INDUSTRIES - INTERNATIONAL (AWCI). <br />4. CEILINGS AND INTERIOR SYSTEMS CONSTRUCTION ASSOCIATION (CISCA). <br />5. GYPSUM ASSOCIATION (GA). <br />6. STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) <br />7. UNDERWRITERS LABORATORIES, INC. (UL) <br />8. INTERTEK TESTING SERVICES/WARNOCK HERSEY, INC. (WHI). <br />9. "RECOMMENDED SPECIFICATION, AWCI, CISCA AND PDCA. <br />10. PAINTING AND DECORATING CONTRACTORS OF AMERICA (PDCA). <br />B. DESIGN CRITERIA: <br />1. SOUND RATING: CONSTRUCT DESIGNATED PARTITIONS IN ACCORD WITH <br />MANUFACTURER'S PRODUCT DATA, AS SUBMITTED, FOR OBTAINING SOUND <br />TRANSMISSION CLASS (STC) RATINGS AS INDICATED ON THE DRAWINGS, IN <br />ACCORD WITH ASTM E90-09. <br />2. FIRE-RESISTANCE: COMPLY WITH FIRE-RESISTANCE DESIGNS INDICATED ON <br />THE DRAWINGS. USE ONLY MANUFACTURERS AND TYPES OF MATERIALS AS <br />REQUIRED BY INDICATED DESIGNS. DESIGNS WITH TESTS BY OTHERTHAN <br />TESTING AGENCY LISTED MAY BE SUBMITTED FOR ARCHITECT'S ACCEPTANCE, <br />SUBJECT TO PRIOR ACCEPTANCE BY GOVERNING AUTHORITIES. <br />1.5 DELIVERY, STORAGE AND HANDLING: <br />A. DELIVERY: DELIVER MATERIALS IN ORIGINAL PACKAGES, CONTAINERS OR BUNDLES <br />BEARING BRAND NAME, APPLICABLE STANDARD DESIGNATION AND NAME OF <br />MANUFACTURER OR SUPPLIER. <br />B. STORAGE: <br />1. STACK GYPSUM BOARD INSIDE BUILDING, OFF FLOOR ON PALLETS OR SIMILAR <br />PLATFORMS PROVIDING CONTINUOUS SUPPORT FOR GYPSUM BOARD AND TO <br />PREVENT SAGGING. STACK GYPSUM BOARD FLAT AND SO THAT LONG LENGTHS <br />ARE NOT OVER SHORT LENGTHS. <br />2. PROTECT GYPSUM BOARD FROM DIRECT EXPOSURE TO RAIN, SUNLIGHT OR <br />OTHER EXCESSIVE WEATHER CONDITIONS. <br />3. DO NOT OVERLOAD FLOOR SYSTEMS. <br />1.6 PROJECT/SITE CONDITIONS: <br />A. ENVIRONMENTAL CONDITIONS: <br />1. DURING MECHANICAL APPLICATION OF GYPSUM BOARD, MAINTAIN ROOM <br />TEMPERATURE AT NOT LESS THAN 40 DEGREES F. <br />2. DURING ADHESIVE APPLICATION OF GYPSUM BOARD, JOINT TREATMENT, <br />TEXTURING, AND DECORATION, MAINTAIN ROOM TEMPERATURE NOT LESS <br />THAN <br />50 DEGREES F FOR 48 HOURS PRIOR TO APPLICATION AND CONTINUOUSLY <br />THEREAFTER UNTIL COMPLETELY DRY AND UNTIL PERMANENT HEATING <br />SYSTEM IS IN OPERATION OR BUILDING IS OCCUPIED. <br />B. VENTILATION: <br />1. PROVIDE VENTILATION DURING AND FOLLOWING ADHESIVE AND JOINT <br />TREATMENT APPLICATIONS, AND DRYING AND CURING PERIODS. <br />2. USE TEMPORARY AIR CIRCULATORS IN ENCLOSED AREAS LACKING NATURAL <br />VENTILATION. <br />3. UNDER SLOW DRYING CONDITIONS, ALLOW ADDITIONAL DRYING TIME <br />BETWEEN <br />COATS OF JOINT TREATMENT. <br />4. PROTECT INSTALLED MATERIALS FROM DRAFTS DURING HOT, DRY WEATHER. <br />C. WHEN RECOMMENDATIONS OF MANUFACTURER'S PRODUCT DATA EXCEED THE <br />ABOVE, COMPLY WITH REQUIREMENTS OF MANUFACTURER'S PRODUCT DATA. <br />PART 2 - PRODUCTS <br />2.1 FRAMING MEMBERS: <br />A. GYPSUM BOARD STUDS: MEETING REQUIREMENTS OF ASTM C645-11; CHANNEL TYPE, <br />ROLL-FORMED FROM DIP GALVANIZED STEEL COMPLYING WITH ASTM A1003-09 AND <br />WITH ASTM A653-11, G40 MINIMUM. <br />1. STUD SIZE: AS INDICATED ON DRAWINGS, EXCEPT MINIMUM 3-5/8" DEPTH <br />WHERE PARTITION IS INDICATED TO RECEIVE TILE CLADDING FINISH. <br />A. WALL: METAL STUDS, GALVANIZED STEEL. <br />B. SHAFT WALLS: "C-H" STUDS, HOT-DIPPED GALVANIZED, GAUGES AS <br />REQUIRED TO SUIT VARIOUS CLEAR-SPAN CONDITIONS. <br />C. "KING STUDS": INDICATED ON DRAWINGS. <br />2. STUD GAUGE: AS INDICATED ON THE DRAWINGS AND AS REQUIRED BY <br />MANUFACTURER'S PRODUCT DATA FOR HEIGHTS AND CONDITIONS OF USE, <br />WITH MAXIMUM ALLOWABLE DEFLECTIONS AS FOLLOWS: <br />A. VERTICAL SHAFTS: L/120 AT 10 PSF. <br />B. ALL OTHER PARTITIONS: L/240 AT 5 PSF. <br />3. COMPLY WITH SUBMITTED DESIGN CALCULATIONS. <br />B. FLOOR AND CEILING RUNNERS: HOT DIP GALVANIZED STEEL, 1" DEEP, MINIMUM, <br />BY WIDTHS TO RECEIVE STUDS, SAME GAUGE AS STUDS. RUNNER TRACKS SHALL HAVE <br />SLOTTED HOLES FOR ATTACHMENT TO STRUCTURE AND STUDS, FOR SLIP JOINTS <br />WHERE REQUIRED BY MANUFACTURER'S PRODUCT DATA. <br />1. WALL: RUNNERS, GALVANIZED STEEL, SIZES AND SHAPES COMPATIBLE WITH <br />METAL STUD SYSTEM. <br />2. SHAFT WALL: STEEL "J" RUNNERS, GALVANIZED STEEL. <br />C. HEADER: BRADY CONSTRUCTION INNOVATIONS, INC., PRO-X HEADER, 54 MIL AND PRO-X <br />CLIP, 54 MIL. <br />2.2 GYPSUM BOARD: <br />A. REGULAR BOARD: MEETING ASTM C1396-11, THICKNESS INDICATED, TAPERED ROUNDED <br />EDGES. <br />B. FIRE-RETARDANT BOARD: MEETING ASTM C1396-11, TYPE X, THICKNESS INDICATED, <br />TAPERED ROUNDED EDGES. <br />C. INTERIOR CEILING BOARD: MEETING ASTM C1396-11, 5/8" THICKNESS, REGULAR GRADE, <br />TAPERED EGDES. <br />D. COREBOARD: MEETING ASTM C1396-11, 1" THICKNESS, SQUARE EDGES, <br />FIRE-RETARDANT BOARD. <br />E. MOLD AND MOISTURE RESISTANT BOARD: TREATED PAPER-FACED GYPSUM BOARD. <br />1. ACCEPTABLE PRODUCTS: <br />A. AMERICAN GYPSUM, M-BLOC. <br />B. NATIONAL GYPSUM, XP GYPSUM BOARD AND XP FIRE-SHIELD <br />GYPSUM BOARD. <br />C. UNITED STATES GYPSUM (USG), SHEETROCK MOLD TOUGH GYPSUM <br />PANELS. <br />2. THICKNESS: 5/8" THICKNESS TYPE X GRADE FIRE-RATED BOARD, TAPERED <br />EDGES. <br />3. DESCRIPTION: MOLD AND MOISTURE RESISTANT GYPSUM CORE ENCASED <br />IN MOLD AND MOISTURE RESISTANT FACERS, WITH TAPERED LONG EDGES. <br />PANELS SHALL COMPLY WITH ASTM C1396-11. <br />4. MOLD RESISTANCE: RESISTANT TO MOLD GROWTH WHEN TESTED IN ACCORD <br />WITH ASTM D3273-12, SCORE OF 10. <br />5. WATER ABSORPTION: LESS THAN 5% OF BOARD WEIGHT WHEN TESTED IN <br />ACCORD WITH ASTM C473-12. <br />6. JOINT TAPE: AS RECOMMENDED BY GYPSUM BOARD MANUFACTURER. <br />7. LIMITATIONS: DO NOT USE AS A TILE BACKER BOARD. <br />2.3 TILE BACKER BOARD: <br />A. WATER-RESISTANT, COATED GLASS MAT BACKER BOARD FOR TILE: <br />1. ACCEPTABLE PRODUCT: G-P GYPSUM PRODUCTS, DENS-SHIELD FIREGUARD <br />TILE BACKER. <br />2. CHARACTERISTICS: MEETING ASTM C1178-11, MINIMUM 1/2" THICKNESS, <br />NON-COMBUSTABLE, 5/8" THICKNESS TYPE X, WATER-RESISTANT, SILICON <br />BASED GYPSUM CORE, FIBERGLASS SURFACE MATS, FRONT AND BACK, <br />COATED WITH WATER AND VAPOR RETARDANT COATING. <br />3. JOINT TAPE: FIBERGLASS MESH JOINT TAPE AS RECOMMENDED BY GYPSUM <br />BOARD MANUFACTURER. <br />2.4 GYPSUM SHAFTWALL SYSTEM: <br />A. ACCEPTABLE PRODUCTS; SUBJECT TO COMPLIANCE WITH SPECIFIED REQUIREMENTS: <br />1. AMERICAN GYPSUM, M-BLOC SHAFT LINER. <br />2. G-P GYPSUM PRODUCTS, DENSGLASS SHAFTLINER. <br />3. NATIONAL GYPSUM CO., EXP EXTENDED EXPOSURE SHAFTLINER. <br />4. TEMPLE-INLAND, GREENGLASS LINER BOARD. <br />5. U.S. GYPSUM CO., SHEETROCK GLASS-MAT LINER PANELS. <br />B. MATERIALS: MOISTURE- AND MOLD-RESISTANT, NONCOMBUSTIBLE, TYPE X GYPSUM <br />SHAFTLINER COREBOARD COATED WITH GLASS MAT FACINGS, METAL FRAMING <br />MEMBERS, AND FIBER-REINFORCED GYPSUM BOARD WITH FIBERGLASS MAT FACE ON <br />UNEXPOSED SIDE AND PAPER FACE ON EXPOSED SIDE. <br />C. FIRE-RESISTIVE RATING: IN ACCORD WITH FIRE-RATED ASSEMBLY DESIGN INDICATED. <br />2.5 SOUND CONTROL MATERIALS: <br />A. CONTRACTOR'S OPTION: BASED ON SOUND RATINGS AND FIRE-RESISTANCE RATINGS <br />REQUIRED FOR ASSEMBLIES, CONTRACTOR MAY SELECT GLASS FIBER OR MINERAL <br />WOOL SOUND ATTENUATION MATERIALS AS FOLLOWS: <br />1. GLASS FIBER SOUND ATTENUATION BATTS: <br />A. ACCEPTABLE MANUFACTURERS: <br />1) CERTAINTEED CORP. <br />2) KNAUF INSULATION. <br />3) JOHNS MANVILLE CORP. <br />4) OWENS-CORNING CORP. <br />B. CHARACTERISTICS: <br />1) TYPE: UNFACED FIBERGLASS BATTS FOR FRICTION FIT <br />BETWEEN STUDS, COMPLYING WITH ASTM C665-12, TYPE1. <br />2) SURFACE BURNING CHARACTERISTICS: MAXIMUM 25 FLAME <br />SPREAD AND 50 SMOKE DEVELOPMENT WHEN TESTED IN <br />ACCORD WITH ASTM E84-12C. <br />3) ASSEMBLY STC: AS INDICATED ON DRAWINGS. <br />4) THICKNESS: AS INDICATED ON DRAWINGS, BUT MINIMUM <br />3-1/2" THICK TO ACHIEVE R-13. <br />2. MINERAL WOOL SOUND ATTENUATION BLANKETS: <br />A. ACCEPTABLE MANUFACTURERS: <br />1) IIG, MINWOOL, LLC, MINWOOL SOUND ATTENUATION FIRE <br />BATTS. <br />2) OWENS-CORNING CORP., SOUND ATTENUATION FIRE BATT. <br />3) U.S. GYPSUM CO., THERMAFIBER SAFB (SOUND <br />ATTENUATION FIRE BLANKETS). OWENS-CORNING CORP. <br />B. CHARACTERISTICS: <br />1) TYPE: PAPERLESS, SEMI-RIDIG MINERAL WOOL FIBER <br />BLANKET COMPLYING WITH ASTM C665-12, TYPE 1. <br />2) DENSITY: MAXIMUM 4.0 PCF FOR 1" THICKNESS, AND <br />MAXIMUM 2.5 PCF. FOR GREATER THICKNESSES. <br />3) SURFACE BURNING CHARACTERISTICS: MAXIMUM 15 FLAME <br />SPREAD AND 5 SMOKE DEVELOPMENT WHEN TESTED IN <br />ACCORD WITH ASTM E84-12C. <br />4) ASSEMBLY STC: AS INDICATED ON DRAWINGS. <br />5) THICKNESS: AS INDICATED ON DRAWINGS, BUT MINIMUM <br />REQUIRED THICKNESS TO ACHIEVE R-13 <br />B. ACOUSTICAL TAPE: CLOSED CELL POLYVINYL CHLORIDE FOAM TAPE, 1/4" THICKNESS <br />BY 1" WIDE. <br />C. ACOUSTICAL JOINT SEALANT: MANUFACTURER'S STANDARD NON-SAG, PAINTABLE, <br />NON-STAINING LATEX SEALANT COMPLYING WITH ASTM C834-10. PRODUCT EFFECTIVELY <br />REDUCES AIRBORNE SOUND TRANSMISSION THROUGH PERIMETER JOINTS AND <br />OPENINGS IN BUILDING CONSTRUCTION AS DEMOSTRATED BY TESTING <br />REPRESENTATIVEASSEMBLIES ACCORDING TO ASTM E90-09. <br />1. PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE <br />OF THE FOLLOWING: <br />A. ACCUMETRIC LLC; BOSS 824 ACOUSTICAL SOUND SEALANT. <br />B. GRABBER CONSTRUCTION PRODUCTS; ACOUSTICAL SEALANT GSC. <br />C. PECORA CORPORATION; AC-20 FTR. <br />D. SPECIFIED TECHNOLOGIES, INC.; SMOKE N SOUND ACOUSTICAL <br />SEALANT. <br />E. USG CORPORATION; SHEETROCK ACOUSTICAL SEALANT. <br />2. ACOUSTICAL JOINT SEALANT SHALL HAVE A VOC CONTENT OF LESS THAN THE <br />CURRENT VOC CONTENT LIMITS OF SOUTH COAST AIR QUALITY MANAGEMENT <br />DISTRICT (SCAQMD) RULE #1168, ADHESIVES AND SEALANTS, AMENDED <br />JANUARY 7, 2005. <br />2.6 FASTENERS: <br />A. FASTENERS FOR METAL FRAMING, CORROSION-RESISTANT: <br />1. FOR FASTENING FRAMING MEMBERS TO CONCRETE SURFACES: FASTENERS <br />SHALL BE BEADED DRIVE PINS OR THREADED STUDS DRIVEN BY POWER <br />ACTUATED TOOLS. FASTENERS SHALL RESIST DESIGN LOADS IN ACCORD <br />WITH REQUIREMENTS OF ASTM E1190-11. <br />2. FOR FASTENING TO METAL DECKING AND FOR FASTENING FRAMING MEMBERS <br />TOGETHER: TYPE S, PAN HEAD SCREWS, IN SIZES RECOMMENDED BY GYPSUM <br />BOARD MANUFACTURER FOR APPLICATIONS INDICATED. <br />3. PROVIDE SLOTTED, STAND-OFF WASHERS FOR SLIP JOINT ATTACHMENTS. <br />4. REFER TO DETAILS INDICATED IN DRAWINGS. <br />B. SCREWS FOR GYPSUM BOARD AND ACCESSORY APPLICATION: MEETING ASTM C1002-07, <br />CORROSION-RESISTANT. <br />1. FOR APPLICATION OF SINGLE LAYER OR BASE LAYER OF GYPSUM BOARD TO <br />METAL FRAMING: 1", TYPE S, BUGLE HEAD. <br />2. FOR APPLICATION OF FACE LAYER OF GYPSUM BOARD TO METAL FRAMING IN <br />DOUBLE LAYER CONSTRUCTION: 1-5/8", TYPE S, BUGLE HEAD. <br />3. FOR GYPSUM BOARD TO GYPSUM BOARD APPLICATION: 1-1/2", TYPE G, BUGLE <br />HEAD. <br />C. SCREWS FOR GLASS MAT FACED BOARD APPLICATION: CORROSSION RESISTANT SHEET <br />METAL SCREWS WITH HEAD DIAMETER PROVIDING 125 LB. FASTENER PULL-THROUGH <br />AND PULL-OUT RESISTANCE. SCREW LENGTH SHALL PROVIDE 1/4" MINIMUM THREAD <br />ENGAGEMENT. <br />R <br />No. <br />F <br />LICENSE <br />STATE <br />D <br />O <br />A RCHITECT <br />C AL IFORNIA <br />STEPHE WHITE <br />RENEWAL <br />DATE <br />C-34829 <br />N <br />08/31/25 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />MATTERPORT LINK: https://my.matterport.com/show/?m=FW21iEbmuii <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br />50 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br />1/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />C:\Users\jpark\Documents\R314412.44 - KP SAN 1st Flr Gen Rad_A22_Central_jhaLWMQW.rvt <br />5/20/2024 10:23:25 AM <br />SOCC 2023 R RAD SAN 1ST FLOOR <br />GEN RAD REPLACEMENT (5284) <br />G0-03 <br />SPECIFICATIONS <br />CA361 1 <br />CAP028060R314412.44 <br />SANTA ANA MEDICAL OFFICES <br />1900 E. 4TH ST. <br />SANTA ANA, CA 92701 <br />CITY SUBMITTAL 04/19/2024 <br />BID SET 05/20/2024 <br />1900 E 4th St - <br />1011190678/9/2024