Laserfiche WebLink
STRUCTURAL STEEL <br />500SN001 <br />1. FABRICATION, ERECTION AND MATERIALS SHALL CONFORM WITH THE AISC SPECIFICATION FOR <br />STRUCTURAL STEEL BUILDINGS, THE AISC SEISMIC PROVISIONS FOR STRUCTURAL STEEL <br />BUILDINGS AND THE AISC CODE OF STANDARD PRACTICE, LATEST EDITIONS ADOPTED BY THE <br />BUILDING CODE SPECIFIED IN THE DESIGN CRITERIA NOTES, UNO. <br />2. ALL HOT ROLLED STEEL SHAPES, PLATES AND BARS SHALL BE NEW STEEL CONFORMING TO ASTM <br />A6, UNO IN THE STRUCTURAL DRAWINGS. STRUCTURAL STEEL SHALL BE AS FOLLOWS: <br />A. WIDE FLANGE AND WT SHAPES: ASTM A992 <br />B. M- AND S- SHAPES: ASTM A572 GRADE 50 <br />C. C- AND MC- SHAPES: ASTM A992 <br />D. L- SHAPES: ASTM A572 GRADE 50 <br />E. ROUND HSS: ASTM A500 GRADE C (Fy = 50 KSI) <br />F. RECTANGULAR HSS: ASTM A500 GRADE C (Fy = 50 KSI) <br />G. PIPE: ASTM A53, GRADE B (Fy = 35 KSI) <br />H. BASE PLATES UP TO 4” THICK: ASTM A572 GRADE 50 <br />I. ALL OTHER PLATE MATERIAL: ASTM A572 GRADE 50, UNO <br />J. BUILT UP COLUMNS: ASTM A572 GRADE 50 <br />K. PLATE GIRDERS: ASTM A572 GRADE 50 <br />L. CONNECTION MATERIAL <br />a. COLUMN CONTINUITY PLATES AND DOUBLER PLATES: ASTM A572 GRADE 50 <br />b. BRACED FRAME GUSSET PLATES: ASTM A572 GRADE 50 <br />3. ALL STRUCTURAL STEEL SHALL RECEIVE A MINIMUM OF ONE SHOP COAT OF PRIMER PAINT. DO <br />NOT PAINT AREAS TO BE FIELD WELDED, FIREPROOFED, GALVANIZED, TO RECEIVE SLIP-CRITICAL <br />HIGH STRENGTH BOLTS, OR TO BE EMBEDDED IN CONCRETE. PROVIDE ADDITIONAL PAINTING AS <br />NOTED IN THE SPECIFICATIONS. <br />4. ALL STRUCTURAL STEEL SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING <br />SHALL BE INSTALLED AND SHALL BE LEFT IN PLACE UNTIL OTHER MEANS ARE PROVIDED TO <br />ADEQUATELY BRACE THE STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL <br />BASE PLATE AND SUPPORT CONDITIONS DURING ERECTION AND BRACING AS REQUIRED. SEE <br />AISC AND OSHA REQUIREMENTS. <br />5. GROUT BELOW BASE PLATES SHALL BE NON-METALLIC, NON-SHRINK GROUT WITH A MINIMUM <br />COMPRESSIVE STRENGTH OF 10,000 PSI AT 28 DAYS UNO. COLUMN BASE PLATES SHALL BE <br />PROMPTLY GROUTED AFTER STEEL FRAME HAS BEEN PLUMBED AND PRIOR TO INSTALLATION OF <br />METAL DECKING. <br />6. STRUCTURAL STEEL BELOW GRADE SHALL HAVE 3 INCHES MINIMUM OF CONCRETE COVER. <br />7. STRUCTURAL BOLTS AND THREADED FASTENERS <br />A. BOLTED CONNECTIONS SHALL CONSIST OF UNFINISHED BOLTS CONFORMING TO ASTM F3125 <br />GRADE A325 UNO. <br />B. WHERE HIGH-STRENGTH BOLTS ARE SPECIFIED, BOLTS CONFORMING TO ASTM F3125 GRADE <br />A325 OR GRADE A490 SHALL BE PROVIDED AS INDICATED. HIGH STRENGTH BOLTS IN SLIP- <br />CRITICAL AND PRETENSION JOINTS SHALL CONFORM TO THE REQUIREMENTS OF ASTM F1852 <br />FOR TWIST-OFF TYPE TENSION CONTROL BOLT PRETENSIONING OR BE PROVIDED WITH <br />DIRECT TENSION INDICATOR WASHERS CONFORMING TO THE REQUIREMENTS OF ASTM F959. <br />C. ANCHOR RODS CAST IN CONCRETE OR MASONRY SHALL BE HEADED BOLTS WITH CUT THREAD, <br />FULL DIAMETER BODY STYLE CONFORMING TO ASTM F1554 GRADE 36, 55 (WELDABLE PER S1 <br />SUPPLEMENTARY REQUIREMENTS), OR GRADE 105 AS INDICATED ON DRAWINGS. IN LIEU OF <br />HEADED ANCHOR RODS, THREADED ROD CONFORMING TO THE ABOVE SPECIFICATIONS MAY <br />BE USED WITH DOUBLE NUTS TIGHTENED TO PREVENT ROTATION. ANCHOR ROD PROJECTION <br />ABOVE TOP OF FOUNDATION SHALL BE AS NOTED ON THE DRAWINGS. <br />D. BOLTED CONNECTIONS SHALL HAVE WASHERS CONFORMING TO ASTM F436 UNO. WASHERS <br />MAY BE OMITTED AT SNUG-TIGHTENED AND SLIP-CRITICAL CONNECTIONS, EXCEPT WHERE <br />REQUIRED BY THE RCSC SPECIFICATION FOR STRUCTURAL JOINTS, LATEST EDITION. <br />E. BASE PLATES SHALL HAVE NUTS AND WASHERS AT TOP AND BOTTOM OF PLATE. WASHERS <br />FOR BASE PLATES SHALL BE A36 SQUARE OR CIRCULAR PLATE UNLESS ASTM F844 WASHERS <br />ARE PERMITTED. SEE BASE PLATE DETAILS FOR PLATE WASHER SIZE AND PERMISSIBLE <br />WASHER TYPE. <br />F. THREADED RODS SHALL CONFORM TO ASTM A36 UNLESS NOTED OTHERWISE ON THE <br />DRAWINGS. <br />G. PINS: ALL PINS IN PIN CONNECTED MEMBERS SHALL CONFORM TO ASTM A36 OR ASTM A108 AS <br />INDICATED ON THE DRAWINGS. <br />8. ADDITIONAL REQUIREMENTS FOR "SLIP-CRITICAL" BOLTED CONNECTIONS: <br />A. "SLIP-CRITICAL" CONNECTIONS (A325-SC DESIGN VALUES WITH SPECIAL INSPECTION) ARE <br />REQUIRED AT ALL MOMENT FRAME CONNECTIONS, BRACED FRAME CONNECTIONS, AT ALL <br />CONNECTIONS ALONG CHORD LINES AND DRAG LINES (AS NOTED ON PLANS), AND UNO, AT ALL <br />BOLTS IN OVERSIZED OR SLOTTED HOLES. <br />B. THE SPECIAL INSPECTOR MUST BE PRESENT DURING THE INSTALLATION AND TIGHTENING <br />OPERATION OF "SLIP-CRITICAL" CONNECTIONS. <br />9. PROVIDE 3/4" DIAMETER STITCH BOLTS AND RING FILLS, SPACED AT NOT MORE THAN 2'-0" ON <br />CENTER AT ALL DOUBLE ANGLE MEMBERS UNO. <br />10. AT WOOD TO STEEL PARALLEL CONTACT, BOLT WITH 1/2" DIAMETER BOLTS AT MAXIMUM 24"CC <br />UNLESS NOTED OTHERWISE IN THE DRAWINGS. <br />11. BOLT HOLES SHALL BE AISC STANDARD HOLES UNLESS SPECIFIED OTHERWISE. USE STANDARD <br />AISC GAGE AND PITCH FOR BOLTS EXCEPT AS NOTED OTHERWISE. <br />12. WELDING SHALL BE DONE BY THE ELECTRIC ARC PROCESS IN ACCORDANCE WITH AMERICAN <br />WELDING SOCIETY STANDARDS, USING ONLY CERTIFIED WELDERS. ALL GROOVE WELDS SHALL <br />HAVE COMPLETE PENETRATION UNLESS NOTED OTHERWISE. ALL ELECTRODES FOR WELDING <br />SHALL COMPLY WITH AWS D1.1 AND D1.8 AS APPLICABLE, E70 SERIES MINIMUM. <br />13. WELD LENGTHS SPECIFIED ON PLANS ARE THE NET EFFECTIVE LENGTHS REQUIRED. <br />14. MINIMUM FILLET WELDS: (T = THICKNESS OF THINNER PART JOINED) <br />3/16" @ T < 1/2" <br />1/4" @ T < 3/4" <br />5/16" @ T > 3/4" <br />15. WELDING PROCEDURE SPECIFICATIONS (WPS) FOR SHOP AND FIELD PREQUALIFIED WELD JOINTS <br />AND WELD JOINTS QUALIFIED BY TEST SHALL BE SUBMITTED FOR REVIEW BY THE STRUCTURAL <br />ENGINEER AND THE OWNER’S TESTING LABORATORY PRIOR TO FABRICATION. ALL WELDING <br />PROCEDURE ITEMS SUCH AS BASE METALS, WELDING PROCESSES, FILLER METALS AND JOINT <br />DETAILS THAT MEET THE REQUIREMENTS OF AWS D1.1 SECTION 3 SHALL BE CONSIDERED AS <br />PREQUALIFIED. ANY CHANGE OR SUBSTITUTION THAT IS BEYOND THE RANGE OR TOLERANCE OR <br />REQUIREMENTS FOR PREQUALIFICATION SHALL BE QUALIFIED BY TEST PER AWS D1.1 SECTION 4 <br />PART B. SUBMIT TEST REPORTS SHOWING SUCCESSFUL PASSAGE OF QUALIFICATION TESTS FOR <br />ALL NON-PREQUALIFIED WELDING PROCEDURE SPECIFICATIONS. <br />STATEMENT OF STRUCTURAL SPECIAL INSPECTIONS AND TESTING <br />110SN001 <br />1. SPECIAL INSPECTIONS AND TESTING SHALL BE PROVIDED BY A TESTING AND INSPECTION <br />AGENCY, EMPLOYED BY THE OWNER (OR OWNER'S AUTHORIZED AGENT), AND APPROVED BY <br />THE BUILDING OFFICIAL TO PROVIDE SPECIAL INSPECTIONS AND TESTING FOR THE <br />PARTICULAR TYPE OF CONSTRUCTION. <br />2. TABLES OF SPECIAL INSPECTIONS AND TESTING ARE DERIVED FROM THE STRUCTURAL <br />PROVISIONS OF THE CBC AND REFERENCED STANDARDS AND ARE FOR REFERENCE ONLY. <br />THE INCLUDED TABLES ARE PROVIDED FOR THE CONVENIENCE OF THE OWNER, TESTING <br />AGENCY AND CONTRACTOR IN DEVELOPING THE SCOPE OF WORK FOR REQUIRED TESTING <br />AND INSPECTION OF STRUCTURAL MATERIALS AND COMPONENTS. FINAL DEFINITION OF THIS <br />SCOPE OF WORK IS TO BE DETERMINED BY THE TESTING AGENCY AND THE OWNER (OR <br />OWNER'S AUTHORIZED AGENT). <br />3. FREQUENCY OF SPECIAL INSPECTIONS AND TESTING SHALL BE, AT A MINIMUM, AS NOTED FOR <br />THE INDIVIDUAL ELEMENTS WITHIN THE TABLES BELOW. THE CONTRACTOR SHALL <br />COORDINATE TIMING OF SPECIAL INSPECTIONS AND TESTING WITH THE SPECIAL INSPECTION <br />AND TESTING AGENCY. <br />4. PRIOR TO THE START OF CONSTRUCTION, THE TESTING AND INSPECTION AGENCY SHALL <br />PROVIDE DOCUMENTATION TO THE BUILDING OFFICIAL DEMONSTRATING COMPETENCE AND <br />RELEVANT EXPERIENCE OR TRAINING OF THE SPECIAL INSPECTORS WHO WILL PERFORM THE <br />SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION, IN ACCORDANCE WITH CBC <br />SECTION 1704.2.1. <br />5. THE TESTING AND INSPECTION AGENCY SHALL SUBMIT REPORTS OF SPECIAL INSPECTIONS <br />AND TESTS TO THE BUILDING OFFICIAL, STRUCTURAL ENGINEER OF RECORD AND THE <br />CONTRACTOR, PER CBC SECTION 1704.2.4. THE REPORTS SHALL INDICATE WHETHER WORK <br />INSPECTED OR TESTED CONFORMED TO THE APPROVED CONSTRUCTION DOCUMENTS. ANY <br />DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE CONTRACTOR <br />FOR CORRECTION. IF DISCREPANCIES ARE NOT CORRECTED, THEY SHALL BE BROUGHT TO <br />THE ATTENTION OF THE BUILDING OFFICIAL AND THE STRUCTURAL ENGINEER OF RECORD. <br />6. SPECIAL INSPECTION AND TESTING RECORDS SHALL BE RETAINED BY THE CONTRACTOR ON <br />SITE UNTIL COMPLETION OF CONSTRUCTION. <br />7. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT TO THE BUILDING OFFICIAL <br />ACKNOWLEDGING RESPONSIBILITY FOR CONSTRUCTION OF THE MAIN LATERAL-FORCE <br />RESISTING SYSTEM PRIOR TO COMMENCEMENT OF THAT WORK AS REQUIRED BY CBC <br />SECTION 1704.4. <br />8. THE OWNER OR THE OWNER'S AUTHORIZED AGENT SHALL SUBMIT TO THE BUILDING OFFICIAL, <br />A FINAL REPORT DOCUMENTING SPECIAL INSPECTIONS AND TESTS PER CBC SECTION 1704.2.4, <br />AND REPORTS AND CERTIFICATES PER CBC SECTION 1704.5. <br />9. ALL SOILS AND FOUNDATION EXCAVATION INSPECTIONS SHALL BE BY THE GEOTECHNICAL <br />ENGINEER OF RECORD, OR A GEOTECHNICAL FIRM HIRED BY THE OWNER PER CBC SECTION <br />1705.6. <br />10. SPECIAL INSPECTION IS REQUIRED FOR ALL SHOP FABRICATED MEMBERS OR ASSEMBLIES <br />UNLESS WAIVED PER THE EXCEPTIONS IN CBC SECTION 1704.2.5. <br />11. DEFINITIONS: <br />a. CONTINUOUS - SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS CONTINUOUSLY <br />PRESENT WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED. <br />b. PERIODIC - SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY <br />PRESENT WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED. <br />c. QUALITY ASSURANCE (QA) - MONITORING AND INSPECTION TASKS PERFORMED BY AN <br />AGENCY OR FIRM OTHER THAN THE FABRICATOR OR ERECTOR TO ENSURE THAT THE <br />MATERIAL PROVIDED AND WORK PERFORMED BY THE FABRICATOR AND ERECTOR MEET <br />THE REQUIREMENTS OF THE APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED <br />STANDARDS. QUALITY ASSURANCE INCLUDES THOSE TASKS DESIGNATED 'SPECIAL <br />INSPECTION' BY THE APPLICABLE CODE. <br />d. QUALITY CONTROL (QC) - CONTROLS AND INSPECTIONS IMPLEMENTED BY THE <br />FABRICATOR OR ERECTOR, AS APPLICABLE, TO ENSURE THAT THE MATERIAL PROVIDED <br />AND WORK PERFORMED MEET THE REQUIREMENTS OF THE APPROVED CONSTRUCTION <br />DOCUMENTS AND REFERENCED STANDARDS. <br />e. OBSERVE (O) - OBSERVE THESE ITEMS ON A RANDOM BASIS (DAILY FOR LFRS). <br />OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. <br />f. PERFORM (P) - PERFORM THOSE TASKS PRIOR TO FINAL ACCEPTANCE FOR EACH ITEM OR <br />ELEMENT. <br />g. DOCUMENT (D) - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THAT THE WORK <br />HAS BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORT <br />NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UP, WPS SETTINGS, <br />COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP <br />FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED. <br />FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND FLOOR <br />OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT DOCUMENTS <br />AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY REPAIRED SHALL BE <br />NOTED IN THE INSPECTION REPORT. <br />12. SPECIAL INSPECTIONS AND TESTING SHALL BE PERFORMED DURING CONSTRUCTION ON THE <br />WORK SHOWN IN THE CONSTRUCTION DOCUMENTS AS REQUIRED BY CBC CHAPTER 17, THE <br />TABLES LISTED BELOW, AND THE JURISDICTION'S SPECIAL INSPECTION AND TESTING FORM. <br />IF DISCREPANCIES ARE NOTED, CONTACT THE SEOR. ALL EXCEPTIONS INCLUDED IN CBC <br />CHAPTER 17 ARE PERMITTED TO BE USED. <br />• CONCRETE CONSTRUCTION <br />• POST-INSTALLED ANCHORS <br />TYPE <br />CONCRETE CONSTRUCTION - REQUIRED SPECIAL INSPECTIONS AND TESTS <br />CBC TABLE 1705.3 <br />110SN301 <br />CONTINUOUS REFERENCED STANDARD aPERIODIC <br />1. INSPECT REINFORCEMENT, <br />INCLUDING PRESTRESSING <br />TENDONS, AND VERIFY PLACEMENT. <br />ACI 318 CH. 20, 25.2, 25.3, <br />26.6.1-26.6.3 <br />- X <br />2. REINFORCING BAR WELDING:AWS D1.4 <br />ACI 318: 26.6.4 <br />A. VERIFY WELDABILITY OF <br />REINFORCING BARS OTHER <br />THAN ASTM A706 <br />B. INSPECT SINGLE-PASS FILLET <br />WELDS, MAXIMUM 5/16" <br />C. INSPECT ALL OTHER WELDS <br />- X <br />- X <br />X - <br />3. INSPECT ANCHORS CAST IN <br />CONCRETE. <br />ACI 318: 17.8.2 <br />4. INSPECT ANCHORS POST-INSTALLED <br />IN HARDENED CONCRETE <br />MEMBERS. b <br />ACI 318: 17.8.2.4, 17.8.2 <br />A. ADHESIVE ANCHORS INSTALLED <br />IN HORIZONTALLY OR UPWARDLY <br />INCLINED ORIENTATIONS TO <br />RESIST SUSTAINED TENSION <br />LOADS. <br />x - <br />B. MECHANICAL ANCHORS AND <br />ADHESIVE ANCHORS NOT <br />DEFINED IN 4.A. <br />- X <br />5. VERIFY USE OF REQUIRED DESIGN <br />MIX. <br />ACI 318: CH. 19, 26.4.3, <br />26.4.4 <br />- X <br />6. PRIOR TO CONCRETE PLACEMENT, <br />FABRICATE SPECIMENS FOR <br />STRENGTH TESTS, PERFORM SLUMP <br />AND AIR CONTENT TESTS, AND <br />DETERMINE THE TEMPERATURE OF <br />THE CONCRETE. <br />ASTM C172 <br />ASTM C31 <br />ACI 318: 26.5, 26.12 <br />X - <br />7. INSPECT CONCRETE AND <br />SHOTCRETE PLACEMENT FOR <br />PROPER APPLICATION TECHNIQUES. <br />ACI 318: 26.5 <br />8. VERIFY MAINTENANCE OF SPECIFIED <br />CURING TEMPERATURE AND <br />TECHNIQUES. <br />ACI 318: 26.5.3-26.5.5- X <br />9. INSPECT PRESTRESSED CONCRETE <br />FOR: <br />ACI 318: 26.10 <br />A. APPLICATION OF PRESTRESSING <br />FORCES <br />B. GROUTING OF BONDED <br />PRESTRESSING TENDONS. <br />10. INSPECT ERECTION OF PRECAST <br />CONCRETE MEMBERS. <br />ACI 318: CH. 26.9- X <br />13. VERIFY IN-SITU CONCRETE <br />STRENGTH, PRIOR TO STRESSING <br />OF TENDONS IN POST-TENSIONED <br />CONCRETE AND PRIOR TO REMOVAL <br />OF SHORES AND FORMS FROM <br />BEAMS AND STRUCTURAL SLABS. <br />ACI 318: 26.11.2- X <br />14. INSPECT FORMWORK FOR SHAPE, <br />LOCATION AND DIMENSIONS OF THE <br />CONCRETE MEMBER BEING FORMED. <br />ACI 318: 26.11.1.2(b)- X <br />A. WHERE APPLICABLE, SEE SECTION 1705.13. <br />B. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH <br />REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 <br />IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE <br />NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE <br />REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL <br />PRIOR TO COMMENCEMENT OF THE WORK. <br />- X <br />X - <br />X - <br />X - <br />11. FOR PRECAST CONCRETE <br />DIAPHRAGM CONNECTIONS OR <br />REINFORCEMENT AT JOINTS <br />CLASSIFIED AS MODERATE OR HIGH <br />DEFORMABILITY ELEMENTS (MDE OR <br />HDE) IN STRUCTURES ASSIGNED TO <br />SEISMIC DESIGN CATEGORY C, D, E <br />OR F, INSPECT SUCH CONNECTIONS <br />AND REINFORCEMENT IN THE FIELD <br />FOR: <br />ACI 318: 26.13.1.3 <br />A. INSTALLATION OF THE <br />EMBEDDED PARTS. <br />B. COMPLETION OF THE CONTINUITY <br />OF REINFORCEMENT ACROSS <br />JOINTS. <br />X - <br />X - <br />X - <br />ACI 550.5 <br />C. COMPLETION OF CONNECTIONS <br />IN THE FIELD. <br />12. INSPECT INSTALLATION <br />TOLERANCES OF PRECAST <br />CONCRETE DIAPHRAGM <br />CONNECTIONS FOR COMPLIANCE <br />WITH ACI 550.5. <br />ACI 318: 26.13.1.3- X <br />COLD-FORMED METAL FRAMING <br />540SN001 <br />1. GALVANIZED SHEET STEEL SHALL CONFORM TO ASTM A653, STRUCTURAL QUALITY, WITH A <br />MINIMUM YIELD STRENGTH OF 33 KSI FOR 43 MILS (18 GA) AND THINNER AND ASTM A653, <br />STRUCTURAL QUALITY, WITH A MINIMUM YIELD STRENGTH OF 50 KSI FOR 54 MILS (16 GA) AND <br />THICKER. HOT-ROLLED CARBON SHEET AND STRIP STEEL USED IN THE FABRICATION OF COLD- <br />FORMED MEMBERS SHALL CONFORM TO ASTM A1011 WITH A RUST INHIBITIVE COATING. ALL CFS <br />MEMBERS ARE TO BE COATED IN ACCORDANCE WITH THE OPTIONS SHOWN IN PARAGRAPH 4.3 <br />AND TABLE 1 OF ASTM C955 AND SHALL HAVE A MINIMUM COATING PROTECTION LEVEL OF CP 60. <br />2. METAL STUDS AND JOISTS SHALL BE OF SIZE AND THICKNESS SHOWN ON DRAWINGS WITH THE <br />MINIMUM EFFECTIVE SECTION PROPERTIES SHOWN IN THE TABLE(S). <br />3. MINIMUM THICKNESS SHOWN IN TABLE FOR THE THICKNESS SPECIFIED REPRESENTS 95% OF <br />DESIGN THICKNESS PER AISI S240. <br />4. METAL FRAMING SHALL BE PER ICC-ES NO. 3064P OR ICC-ES 4205. CONTRACTOR SHALL BE <br />RESPONSIBLE FOR OBTAINING AGENCY APPROVAL FOR ANY SUBSTITUTIONS. <br />5. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3 "STRUCTURAL WELDING CODE-SHEET <br />STEEL". WELDERS SHALL BE AWS CERTIFIED. WELDING RODS: E60XX MIN (43 MIL AND THINNER), <br />E70XX MIN (54 MIL AND THICKER). <br />6. SMS SHALL BE PER ONE OF THE FOLLOWING: <br />A. GRABBER CONSTRUCTION PRODUCTS INC PER ESR-1271 <br />B. PRIMESOUCE BUILDING PRODUCTS PER ESR-1408 <br />C. ITW BUILDEX PER ESR-1976 <br />D. ITW BUILDEX PER ESR-3223 <br />E. HILTI PER ESR-2196 <br />F. PORTEOUS FASTENER PER ESR-3231 <br />G. ELCO CONSTRUCTION PRODUCTS PER ESR-3294 <br />H. SIMPSON STRONG-TIE COMPANY PER ESR-3006 <br />7. SMS MUST BE INSTALLED WITH THE FOLLOWING MINIMUM DIMENSIONAL LIMITATIONS: WHERE <br />MULTIPLE FASTENERS ARE USED, SCREWS ARE TO HAVE A CENTER-TO-CENTER SPACING OF AT <br />LEAST 3 TIMES THE NOMINAL DIAMETER (D). SCREWS ARE TO HAVE A CENTER-OF-SCREW TO <br />EDGE-OF-STEEL DIMENSION OF AT LEAST 1.5 TIMES THE NOMINAL DIAMETER (D) OF THE SCREW. <br />8. ALL SCREWS ARE TO PROTRUDE A MINIMUM OF THREE FULL THREADS BEYOND THE <br />CONNECTED PARTS, UNLESS OTHERWISE NOTED. WHERE THE CONNECTED PARTS ARE <br />DIFFERENT THICKNESS, THE SCREW IS TO FIRST PENETRATE THE THINNER MEMBER, THEN <br />PENETRATE THICKER PART, MEANING, THE SCREW HEAD IS IN CONTACT WITH THE THINNER <br />MEMBER, UNLESS OTHERWISE NOTED. <br />9. TYPICAL METAL TRACK SHALL BE SAME GAUGE AS STUDS WHICH IT SUPPORTS, UNPUNCHED, <br />WITH A FLANGE WIDTH OF 1 1/4 INCHES AND A DEPTH EQUAL TO THE NOMINAL STUD PLUS 2 <br />TIMES THE TRACK THICKNESS PLUS THE RADIUS. NESTED TRACKS SHALL BE FABRICATED TO <br />FILL THE OUTSIDE OF A TYPICAL METAL TRACK. DEEP LEG TRACKS SHALL HAVE A MINIMUM <br />FLANGE WIDTH OF 2 INCHES. USE SLOTTED SLIP TRACKS WHERE SPECIFIED. SEE SECTIONS <br />AND TYPICAL METAL STUD DETAILS. <br />10. METAL STUDS AND JOISTS SHALL NOT HAVE PUNCH-OUTS CLOSER THAN 10" CLEAR FROM THE <br />END OF THE MEMBER OR AT INTERMEDIATE LATERAL BEARING POINTS OF THE MEMBER. METAL <br />STUDS WHICH ARE PART OF BUILT-UP HEADER SECTIONS SHALL BE UNPUNCHED FULL LENGTH. <br />GAUGE/MIL <br />MIN THICKNESS <br />DEPTH "D" <br />2 1/2" <br />3 5/8" <br />4" <br />6" <br />8" <br />0.235 <br />SxIx <br />0.0329 0.0428 0.0538 0.0677 <br />20/33 18/43 16/54 14/68 <br />1 5/8" <br />S STUDS & <br />JOISTS <br />0.180 0.302 0.240 0.370 0.284 0.450 0.357 <br />0.551 0.268 0.710 0.372 0.873 0.444 1.069 0.574 <br />0.6481.3460.4981.0980.4170.8920.2990.692 <br />1.1643.5250.9162.8600.7672.3160.5771.793 <br />1.6637.0701.2295.6001.0194.5000.7103.384 <br />Ix Sx Ix Sx Ix Sx <br />DESIGNATION S162-33 S162-43 S162-54 S162-68 <br />- - - - 14.298 1.914 18.390 2.645 <br />- - 7.523 1.302 9.391 1.572 11.978 2.154 <br />12" <br />10" <br />COLD-FORMED METAL FRAMING SECTION PROPERTIES - SSMA C STUDS & JOISTS - S162 SECTIONS 1,2 <br />540SN002 <br />1/ <br />2 <br />" <br /> <br />T <br />Y <br />P <br />TYP <br />"D <br />" <br />NOTES: <br />1. FOR COMPLETE SECTION DESIGNATIONS IN ACCORDANCE WITH SSMA OR SFIA STANDARDS, ADD <br />MEMBER DEPTH TO FRONT OF INDICATED DESIGNATION. EXAMPLE: FOR 3 5/8" MEMBER WITH <br />GAUGE/MIL OF 18/43, THE FULL DESIGNATION IS 362S162-43. <br />2. SECTION PROPERTIES SHOWN ARE EFFECTIVE PROPERTIES CONFORMING TO AISI A7.2 PER <br />SSMA OR SFIA STANDARDS FOR MATERIAL STRENGTH NOTED IN COLD-FORMED METAL FRAMING <br />NOTES. <br />TYPE <br />CONCRETE CONSTRUCTION - POST-INSTALLED ANCHORS <br />REQUIRED SPECIAL INSPECTIONS AND TESTS <br />CBC TABLE 1705.3 <br />110SN302 <br />CONTINUOUS REFERENCED STANDARDPERIODIC <br />1. INSPECT ANCHORS POST- <br />INSTALLED IN HARDENED <br />CONCRETE MEMBERS. a,b <br />ACI 318: 17.8.2.4, 17.8.2 <br />A. ADHESIVE ANCHORS INSTALLED <br />IN HORIZONTALLY OR UPWARDLY <br />INCLINED ORIENTATIONS TO <br />RESIST SUSTAINED TENSION <br />LOADS. <br />X - <br />B. MECHANICAL ANCHORS AND <br />ADHESIVE ANCHORS NOT <br />DEFINED IN 1.A. <br />- X <br />A. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH <br />REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN <br />ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE <br />NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE <br />REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL <br />PRIOR TO COMMENCEMENT OF THE WORK. <br />B. SEE THE POST-INSTALLED ANCHOR NOTES FOR ADDITIONAL INFO. <br />600 Q STREET, SUITE 200 <br />SACRAMENTO, CA 95811 <br />916 443 0303 <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />. <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />14 <br />0 <br />1 <br /> <br />N <br />. <br /> <br />T <br />U <br />S <br />T <br />I <br />N <br /> <br />A <br />V <br />E <br />. <br /> <br />S <br />U <br />I <br />T <br />E <br /> <br /># <br />1 <br />7 <br />0 <br />SI <br />M <br />O <br />N <br />M <br />E <br />D <br /> <br />I <br />M <br />A <br />G <br />I <br />N <br />G <br />06/19/2024 <br />24-004 <br />GKA ARCHITECTS. ALL RIGHTS RESERVED <br />COPYRIGHT © 2024 <br />WWW.GKA-ARC.COM <br />(213) 200-0030 <br />LOS ANGELES, CA 90071 <br />633 W 5TH ST, STE 2607 <br />SHEET NUMBER: <br />SHEET TITLE: <br />ISSUE DATE: <br />PROJECT NUMBER: <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br /> <br />C <br />O <br />N <br />S <br />U <br />L <br />T <br />A <br />N <br />T <br />DESCRIPTIONDATEREV <br />6/ <br />2 <br />4 <br />/ <br />2 <br />0 <br />2 <br />4 <br /> <br />1 <br />0 <br />: <br />4 <br />8 <br />: <br />1 <br />8 <br /> <br />A <br />M <br />C: <br />\ <br />U <br />s <br />e <br />r <br />s <br />\ <br />K <br />e <br />i <br />t <br />h <br />S <br />\ <br />O <br />n <br />e <br />D <br />r <br />i <br />v <br />e <br /> <br />- <br /> <br />B <br />u <br />e <br />h <br />l <br />e <br />r <br /> <br />E <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br />, <br /> <br />I <br />n <br />c <br />\D <br />o <br />c <br />u <br />m <br />e <br />n <br />t <br />s <br />\ <br />2 <br />0 <br />2 <br />4 <br />- <br />0 <br />1 <br />3 <br />7 <br />_ <br />S <br />i <br />m <br />o <br />n <br />M <br />e <br />n <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />_ <br />R <br />v <br />t <br />2 <br />3 <br />_ <br />C <br />e <br />n <br />t <br />r <br />al <br />_ <br />k <br />s <br />o <br />w <br />l <br />e <br />y <br />. <br />r <br />v <br />t <br />GENERAL NOTES / <br />STRUCTURAL <br />SPECIAL <br />INSPECTIONS & <br />TESTING <br />S1.02 <br />APPLICABLE TO ALL DRAWINGS UNLESS NOTED OR SHOWN OTHERWISE <br />GENERAL NOTES <br />APPLICABLE TO ALL DRAWINGS UNLESS NOTED OR SHOWN OTHERWISE <br />STRUCTURAL SPECIAL INSPECTIONS AND TESTING <br />SEOR STAMP IS APPLICABLE ONLY <br />TO THE STRUCTURAL CONTENT OF <br />THE FOLLOWING DETAILS ON THIS <br />PAGE: <br />1401 N Tustin Ave Unit# <br />170 - TI1/27/2025