SECTION 16A GENERAL ELECTRICAL REQUIREMENTS <br />16A 1 GENERAL INSTRUCTIONS <br />16A 1 -1 GENERAL REQUIREMENTS <br />ALL REQUIREMENTS UNDER DIVISION 1 AND THE GENERAL AND SUPPLEMENTARY CONDITIONS OF <br />THESE SPECIFICATIONS APPLY TO THIS SECTION AND DIVISION. WHERE THE REQUIREMENTS OF THIS <br />SECTION AND DIVISION EXCEED THOSE OF DIVISION 1, THIS SECTION AND DIVISION TAKE <br />PRECEDENCE. BECOME THOROUGHLY FAMILIAR WITH ALL THEIR CONTENTS AS TO REQUIREMENTS <br />THAT AFFECT THIS DIVISION, SECTION OR BOTH. WORK REQUIRED UNDER THIS DIVISION INCLUDES <br />ALL MATERIAL, EQUIPMENT, APPLIANCES, AND LABOR REQUIRED TO COMPLETE THE ENTIRE <br />ELECTRICAL SYSTEM AS REQUIRED BY THE DRAWINGS AND SPECIFICATIONS, OR REASONABLY <br />INFERRED TO BE NECESSARY TO FACILITATE EACH SYSTEM'S FUNCTIONING AS IMPLIED BY THE <br />DESIGN AND THE EQUIPMENT SPECIFIED. <br />THE SPECIFICATIONS AND DRAWINGS FOR THE PROJECT ARE COMPLEMENTARY, AND PORTIONS OF <br />THE WORK DESCRIBED IN ONE, SHALL BE PROVIDED AS IF DESCRIBED IN BOTH. IN THE EVEN OF <br />DISCREPANCIES, NOTIFY THE ARCHITECT / ENGINEER AND REQUEST CLARIFICATION PRIOR TO <br />PROCEEDING WITH THE WORK INVOLVED. <br />DRAWINGS ARE GRAPHIC REPRESENTATIONS OF THE WORK UPON WHICH THE CONTRACT IS BASED. <br />THEY SHOW THE MATERIALS AND THEIR RELATIONSHIP TO ONE ANOTHER, INCLUDING SIZES, SHAPES, <br />LOCATIONS, AND CONNECTIONS. THEY ALSO CONVEY THE SCOPE OF WORK, INDICATING THE <br />INTENDED GENERAL ARRANGEMENT OF THE EQUIPMENT, FIXTURES, OUTLETS AND CIRCUITS WITHOUT <br />SHOWING ALL OF THE EXACT DETAILS AS TO ELEVATIONS, OFFSETS, CONTROL LINES, AND OTHER <br />INSTALLATION REQUIREMENTS. USE THE DRAWINGS AS A GUIDE WHEN LAYING OUT THE WORK AND <br />TO VERIFY THAT MATERIALS AND EQUIPMENT WILL FIT INTO THE DESIGNATED SPACES, AND WHICH, <br />WHEN INSTALLED PER MANUFACTURER' REQUIREMENTS WILL ENSURE A COMPLETE, COORDINATED, <br />SATISFACTORY AND PROPERLY OPERATING SYSTEM. <br />DRAWINGS ARE SCHEMATIC IN NATURE. SHOW THE VARIOUS COMPONENTS OF THE SYSTEMS <br />APPROXIMATELY TO SCALE AND ATTEMPT TO INDICATE HOW THEY SHALL BE INTEGRATED WITH <br />OTHER PARTS OF THE WORK. FIGURED DIMENSIONS TAKE PRECEDENCE TO SCALED DIMENSIONS. <br />DETERMINE EXACT LOCATIONS BY JOB MEASUREMENTS, BY CHECKING THE REQUIREMENTS OF <br />OTHER TRADES, AND BY REVIEWING ALL CONTRACT DOCUMENTS. CORRECT ERRORS THAT COULD <br />HAVE BEEN AVOIDED BY PROPER CHECKING AND INSPECTION, AT NO ADDITIONAL COST TO THE <br />OWNER. <br />SPECIFICATIONS DEFINE THE QUALITATIVE REQUIREMENTS FOR PRODUCTS, MATERIAL, AND <br />WORKMANSHIP UPON WHICH THE CONTRACT IS BASED. <br />16A 1 -2 DEFINITIONS <br />WHENEVER USED IN THESE SPECIFICATIONS OR DRAWINGS, THE FOLLOWING TERMS SHALL HAVE THE <br />INDICATED MEANINGS: <br />1. FURNISH: "TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, <br />ASSEMBLING, INSTALLING, AND SIMILAR OPERATIONS." <br />2. INSTALL: "TO PERFORM ALL OPERATIONS AT THE PROJECT SITE, INCLUDING, BUT NOT LIMITED TO, <br />AND AS REQUIRED: UNLOADING, UNPACKING, ASSEMBLING, ERECTING, PLACING, ANCHORING, <br />APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, TESTING, <br />COMMISSIONING, STARTING UP AND SIMILAR OPERATIONS, COMPLETE, AND READY FOR THE <br />INTENDED USE." <br />3. PROVIDE: "TO FURNISH AND INSTALL COMPLETE, AND READY FOR THE INTENDED USE." <br />4. FURNISHED BY OWNER (OR OWNER-FURNISHED) OR FURNISHED BY OTHERS: "AN ITEM FURNISHED <br />BY THE OWNER OR UNDER OTHER DIVISIONS OR CONTRACTS, AND INSTALLED UNDER THE <br />REQUIREMENTS OF THIS DIVISION, COMPLETE, AND READY FOR THE INTENDED USE, INCLUDING ALL <br />ITEMS AND SERVICES INCIDENTAL TO THE WORK NECESSARY FOR PROPER INSTALLATION AND <br />OPERATION. INCLUDE THE INSTALLATION UNDER THE WARRANTY REQ'D BY THIS DIVISION. <br />5. ENGINEER: WHERE REFERENCED IN THIS DIVISION, "ENGINEER" IS THE ENGINEER OF RECORD & <br />THE DESIGN PROFESSIONAL FOR THE WORK UNDER THIS DIVISION, & IS A CONSULTANT TO, & AN <br />AUTHORIZED REPRESENTATIVE OF, THE ARCHITECT, AS DEFINED IN THE GENERAL AND/OR <br />SUPPLEMENTARY CONDITIONS. WHEN USING IN THIS DIVISION, IT MEANS INCREASED <br />INVOLVEMENT BY, & OBLIGATIONS TO, THE ENGINEER, IN ADDITION TO INVOLVEMENT BY, AND <br />OBLIGATIONS TO, THE "ARCHITECT". <br />6. AHJ: THE LOCAL CODE AND/OR INSPECTION AGENCY (AUTHORITY) HAVING JURISDICTION OVER <br />THE WORK. <br />7. NRTL: NATIONALLY RECOGNIZED TESTING LABORATORY, AS DEFINED AND LISTED BY OSHA IN 29 <br />CFR 1910.7 (E.G., UL, ETL, CSA), AND ACCEPTABLE TO THE AHJ OVER THIS PROJECT. <br />THE TERMS "APPROVED EQUAL", "EQUIVALENT", OR "EQUAL" ARE USED SYNONYMOUSLY AND SHALL <br />MEAN "ACCEPTED BY OR ACCEPTABLE TO THE ENGINEER AS EQUIVALENT TO THE ITEM OR <br />MANUFACTURER SPECIFIED". THE TERM "APPROVED" SHALL MEAN LABELED, LISTED, CERTIFIED, OR <br />ALL THREE, BY AN NRTL, AND ACCEPTABLE TO THE AHJ OVER THIS PROJECT. <br />16A 1 -3 PRE-BID SITE VISIT <br />PERSONALLY INSPECT THE SITE OF THE PROPOSED WORK AND BECOME FULLY INFORMED OF <br />CONDITIONS UNDER WHICH THE WORK IS TO BE DONE. FAILURE TO DO SO WILL NOT BE CONSIDERED <br />SUFFICIENT JUSTIFICATION TO REQUEST OR OBTAIN EXTRA COMPENSATION OVER AND ABOVE THE <br />CONTRACT PRICE. <br />16A 1 -4 MATERIAL AND WORKMANSHIP <br />PROVIDE ALL MATERIAL AND EQUIPMENT NEW AND IN FIRST CLASS CONDITION. PROVIDE MARKINGS <br />OR A NAMEPLATE FOR ALL MATERIAL AND EQUIPMENT IDENTIFYING THE MANUFACTURER AND <br />PROVIDING SUFFICIENT REFERENCE TO ESTABLISH QUALITY, SIZE AND CAPACITY. ALL WORKMANSHIP <br />SHALL BE OF THE FINEST POSSIBLE BY EXPERIENCED MECHANICS OF THE PROPER TRADE. IN <br />GENERAL, PROVIDE THE FOLLOWING QUALITY GRADE(S) FOR ALL MATERIALS AND EQUIPMENT LIGHT <br />DUTY AND RESIDENTIAL TYPE EQUIPMENT WILL NOT BE ACCEPTABLE: <br />1. COMMERCIAL SPECIFICATION GRADE <br />PROVIDE ALL HOISTS, SCAFFOLDS, STAGING, RUNWAYS, TOOLS, MACHINERY AND EQUIPMENT <br />REQUIRED FOR THE PERFORMANCE OF THE ELECTRICAL WORK. STORE AND MAINTAIN MATERIAL AND <br />EQUIPMENT IN CLEAN CONDITION, AND PROTECTED FROM WEATHER, MOISTURE, AND PHYSICAL <br />DAMAGE. <br />FURNISH ONLY MATERIAL & EQUIPMENT THAT ARE LISTED, LABELED, CERTIFIED, OR ALL THREE, BY A <br />NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), WHENEVER ANY LISTING OR LABELING <br />EXISTS FOR THE TYPES OF MATERIAL AND EQUIPMENT SPECIFIED. AT A MINIMUM, GENERAL WORK <br />PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BE IN ACCORDANCE WITH NECA 1 (LATEST <br />EDITION). "STANDARD PRACTICES FOR GOOD WORKMANSHIP IN ELECTRICAL CONSTRUCTION". <br />16A 1 -5 MANUFACTURERS <br />IN OTHER ARTICLES WHERE LISTS OF MANUFACTURERS ARE INTRODUCED, SUBJECT TO COMPLIANCE <br />WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE MANUFACTURERS SPECIFIED. <br />WHERE A LIST IS PROVIDED, MANUFACTURERS ARE LISTED ALPHABETICALLY AND NOT IN ANY <br />ACCORDANCE WITH RANKING OR PREFERENCE. <br />WHERE MANUFACTURERS ARE NOT LISTED, PROVIDE PRODUCTS SUBJECT TO COMPLIANCE WHERE <br />REQUIREMENTS FROM MANUFACTURERS THAT HAVE BEEN ACTIVELY INVOLVED IN MANUFACTURING <br />THE SPECIFIED PRODUCT FOR NO LESS THAN 5 YEARS <br />16A 1 -6 COORDINATION <br />COORDINATE ALL WORK WITH OTHER DIVISIONS AND TRADES SO THAT VARIOUS COMPONENTS OF THE <br />ELECTRICAL SYSTEMS ARE INSTALLED AT THE PROPER TIME, FIT THE AVAILABLE SPACE, AND ALLOW <br />PROPER SERVICE ACCESS TO ALL EQUIPMENT. REFER TO ALL DRAWINGS, INCLUDING, BUT NOT <br />LIMITED TO, CIVIL, ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND PLUMBING, AND TO RELEVANT <br />EQUIPMENT SUBMITTALS AND SHOP DRAWINGS TO DETERMINE THE EXTENT OF CLEAR SPACES. MAKE <br />ALL OFFSETS REQUIRED TO CLEAR EQUIPMENT, BEAMS AND OTHER STRUCTURAL MEMBERS, AND TO <br />FACILITATE CONCEALING RACEWAYS IN THE MANNER ANTICIPATED IN THE DESIGN. PROVIDE <br />MATERIALS WITH TRIM THAT WILL FIT PROPERLY THE TYPES OF CEILING, WALL, OR FLOOR FINISHES <br />ACTUALLY INSTALLED. <br />16A 1 -7 ORDINANCES, CODES, AND STANDARDS <br />COMPLY, AT A MINIMUM, WITH NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARDS, STATE <br />AND LOCAL BUILDING CODES, AND ALL OTHER APPLICABLE CODES AND ORDINANCES FOR <br />PERFORMANCE, WORKMANSHIP, EQUIPMENT, AND MATERIALS. ADDITIONALLY, COMPLY WITH RULES <br />AND REGULATIONS OF PUBLIC UTILITIES AND MUNICIPAL DEPARTMENTS AFFECTED BY CONNECTION <br />OF SERVICES. <br />WHERE CONFLICTS BETWEEN VARIOUS CODES, ORDINANCES, RULES, AND REGULATIONS EXIST, <br />COMPLY WITH THE MOST STRINGENT. WHEREVER REQUIREMENTS OF THESE SPECIFICATIONS, <br />DRAWINGS, OR BOTH, EXCEED THOSE OF THE ABOVE ITEMS, THE REQUIREMENTS OF THESE <br />SPECIFICATIONS, DRAWINGS, OR BOTH SHALL GOVERN. CODE COMPLIANCE, ATA MINIMUM, IS <br />MANDATORY. CONSTRUE NOTHING IN THESE CONSTRUCTION DOCUMENTS AS PERMITTING WORK NOT <br />IN COMPLIANCE, AT A MINIMUM, WITH THESE CODES. <br />BRING ALL CONFLICTS OBSERVED BETWEEN CODES, ORDINANCES, RULES, REGULATIONS, <br />REFERENCED STANDARDS, AND THESE DOCUMENTS TO THE ENGINEER'S ATTENTION FOR FINAL <br />RESOLUTION. CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY VIOLATION OF THE LAW. <br />PROVIDE AND MAINTAIN ALL NECESSARY SIGNAL LIGHTS AND GUARDS FOR THE SAFETY OF THE <br />PUBLIC. OBTAIN AND PAY FOR ALL PERMITS FOR WORK IN THIS DIVISION. <br />16A 1 -7 ORDINANCES, CODES, AND STANDARDS <br />COMPLY, AT A MINIMUM, WITH NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARDS, STATE <br />AND LOCAL BUILDING CODES, AND ALL OTHER APPLICABLE CODES AND ORDINANCES FOR <br />PERFORMANCE, WORKMANSHIP, EQUIPMENT, AND MATERIALS. ADDITIONALLY, COMPLY WITH RULES <br />AND REGULATIONS OF PUBLIC UTILITIES AND MUNICIPAL DEPARTMENTS AFFECTED BY CONNECTION <br />OF SERVICES. <br />WHERE CONFLICTS BETWEEN VARIOUS CODES, ORDINANCES, RULES, AND REGULATIONS EXIST, <br />COMPLY WITH THE MOST STRINGENT. WHEREVER REQUIREMENTS OF THESE SPECIFICATIONS, <br />DRAWINGS, OR BOTH, EXCEED THOSE OF THE ABOVE ITEMS, THE REQUIREMENTS OF THESE <br />SPECIFICATIONS, DRAWINGS, OR BOTH SHALL GOVERN. CODE COMPLIANCE, ATA MINIMUM, IS <br />MANDATORY. CONSTRUE NOTHING IN THESE CONSTRUCTION DOCUMENTS AS PERMITTING WORK NOT <br />IN COMPLIANCE, AT A MINIMUM, WITH THESE CODES. <br />BRING ALL CONFLICTS OBSERVED BETWEEN CODES, ORDINANCES, RULES, REGULATIONS, <br />REFERENCED STANDARDS, AND THESE DOCUMENTS TO THE ENGINEER'S ATTENTION FOR FINAL <br />RESOLUTION. CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY VIOLATION OF THE LAW. <br />PROVIDE AND MAINTAIN ALL NECESSARY SIGNAL LIGHTS AND GUARDS FOR THE SAFETY OF THE <br />PUBLIC. OBTAIN AND PAY FOR ALL PERMITS FOR WORK IN THIS DIVISION. <br />16A 1 -8 PROTECTION OF EQUIPMENT AND MATERIALS <br />STORE AND PROTECT FROM DAMAGE EQUIPMENT AND MATERIALS DELIVERED TO JOB SITE, IN <br />ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. FOR MATERIALS AND EQUIPMENT <br />SUSCEPTIBLE TO CHANGING WEATHER CONDITIONS, DAMPNESS, OR TEMPERATURE VARIATIONS, <br />STORE INSIDE IN CONDITION SPACES. FOR MATERIALS AND EQUIPMENT NOT SUSCEPTIBLE TO THESE <br />CONDITIONS, COVER WITH WATERPROOF, TEAR-RESISTANT, HEAVY TARP OR POLYETHYLENE PLASTIC <br />AS REQUIRED TO PROTECT FROM PLASTER, DIRT, PAINT, WATER, OR PHYSICAL DAMAGE. EQUIPMENT <br />AND MATERIAL THAT HAS BEEN DAMAGED BY CONSTRUCTION ACTIVITIES WILL BE REJECTED, AND <br />CONTRACTOR SHALL FURNISH NEW EQUIPMENT AND MATERIAL OF A LIKE KIND. <br />PLUG OR CAP OPEN ENDS OF CONDUITS WHILE STORED AND INSTALLED DURING CONSTRUCTION <br />WHEN NOT IN USE TO PREVENT THE ENTRANCE OF DEBRIS INTO THE SYSTEMS. <br />16A 1 -9 SUBSTITUTIONS <br />INCLUDE IN THE BASIC BID THE PRODUCTS SPECIFICALLY NAMED IN THESE SPECIFICATIONS OR ON <br />THE DRAWINGS. SUBMIT, IN THE FORM OF ALTERNATES, WITH BID, PRODUCTS OF ANY OTHER <br />MANUFACTURERS FOR SIMILAR USE, PROVIDED THE DIFFERENCES IN COST, F ANY, ARE INCLUDED <br />FOR EACH PROPOSED ALTERNATE. <br />PRIOR TO THE BID DATE, SUBSTITUTIONS WILL NOT BE CONSIDERED UNLESS SUBMITTED TO THE <br />ARCHITECT, FOR REVIEW, AT LEAST TEN CALENDAR DAYS PRIOR TO THE DATE FOR RECEIPT OF BIDS. <br />INCLUDE THE NAME OF THE MATERIAL OR EQUIPMENT FOR WHICH IT IS TO BE SUBSTITUTED AND A <br />COMPLETE DESCRIPTION OF THE PROPOSED SUBSTITUTE INCLUDING CUT SHEETS, PHOTO METRIC <br />DATA, AND ALL OTHER INFORMATION NECESSARY FOR AN EVALUATION FOR EACH SUCH REQUEST. <br />PROVIDE FACTORY GENERATED POINT-BY-POINT CALCULATIONS). PROVIDE INTERIOR POINT-BY- <br />POINT CALCULATIONS AT THE DISCRETION OF THE ENGINEER. SUBMIT A $100.00 REVIEW FEE TO THE <br />ENGINEER WITH EACH SUCH POINT-BY-POINT CALCULATION FOR USE OF ELECTRONIC BASE FILES. <br />AFTER THE BID DATE, PROPOSALS TO SUBSTITUTE LIGHT FIXTURES FOR THOSE SHOWN ON THE <br />DRAWINGS OR SPECIFIED HEREIN, WILL ONLY BE CONSIDERED AS A DEDUCT. SUBMIT PROPOSED <br />SUBSTITUTIONS SEPARATELY, IN SUBMITTAL FORM, WITH A LIST OF PROPOSED SUBSTITUTIONS <br />TOGETHER WITH A DEDUCT PRICE FOR EACH SUBSTITUTION. THE ARCHITECT, ENGINEER, OR BOTH, <br />WILL THEN REVIEW PROPOSED SUBSTITUTIONS. <br />THE ENGINEER WILL HAVE THE FINAL AUTHORITY AS TO WHETHER THE LIGHT FIXTURE IS AN <br />ACCEPTABLE REPLACEMENT TO THE SPECIFIED ITEM. THE PROPOSED SUBSTITUTION MAY ALSO BE <br />REJECTED BY THE ARCHITECT FOR AESTHETIC REASONS IF FELT NECESSARY OR DESIRABLE. IN THE <br />EVENT THE PROPOSED SUBSTITUTIONS HEREIN DESCRIBED ARE REJECTED, FURNISH THE SPECIFIED <br />ITEM. <br />16A 1 -10 ELECTRONIC DRAWING FILES <br />IN PREPARATION OF SHOP DRAWINGS, CONTRACTOR MAY, AT HIS OPTION, OBTAIN ELECTRONIC <br />DRAWING FILES IN AUTOCAD OR DXF FORMAT FROM THE ENGINEER. CONTRACTOR SHALL CONTACT <br />THE ARCHITECT FOR WRITTEN AUTHORIZATION. ARCHITECT'S WRITTEN AUTHORIZATION AND <br />ENGINEER'S RELEASE AGREEMENT FORM MAY BE REQUIRED BEFORE ELECTRONIC DRAWING FILES <br />WILL BE SENT. <br />16A 1 -11 OPERATION AND MAINTENANCE INSTRUCTIONS <br />SUBMIT TO THE ARCHITECT, COPIES EACH OF OPERATIONS AND MAINTENANCE INSTRUCTION <br />MANUALS, APPROPRIATELY BOUND INTO MANUAL FORM INCLUDING APPROVED COPIES OF THE <br />FOLLOWING, REVISED IF NECESSARY TO SHOW SYSTEM AND EQUIPMENT AS ACTUALLY INSTALLED. <br />PROVIDE THE NUMBER OF SUBMITTALS REQUIRED BY DIVISION 1; HOWEVER, AT A MINIMUM, SUBMIT (3) <br />SETS, AND INCLUDE, AT A MINIMUM, THE FOLLOWING INFORMATION: <br />1. MANUFACTURERS' CATALOGS AND PRODUCT DATA SHEETS <br />2. WIRING DIAGRAMS <br />3. MAINTENANCE INSTRUCTIONS <br />4. OPERATING INSTRUCTIONS <br />5. PARTS LISTS <br />6. TEST REPORTS AS DEFINED IN NETA ATS FOR THE SYSTEMS AND EQUIPMENT PROVIDED OR <br />FURNISHED OR INSTALLED UNDER THIS CONTRACT. <br />7. NAMES, ADDRESSES, TELEPHONE NUMBERS, AND E-MAIL ADDRESSES OF LOCAL CONTACTS FOR <br />WARRANTEE SERVICES AND SPARE PARTS. <br />SUBMIT MANUALS PRIOR TO REQUESTING THE FINAL PUNCH LIST AND BEFORE ANY REQUESTS FOR <br />SUBSTANTIAL COMPLETION. ALSO PROVIDE ADEQUATE VERBAL INSTRUCTIONS OF SYSTEM <br />OPERATIONS TO OWNER'S REPRESENTATIVE AT THE COMPLETION OF, AND BEFORE FINAL <br />ACCEPTANCE OF, THE WORK. <br />16A 1 -12 TRAINING <br />AT A TIME MUTUALLY AGREED UPON BETWEEN THE OWNER AND CONTRACTOR, PROVIDE THE <br />SERVICES OF A FACTORY TRAINED AND AUTHORIZED REPRESENTATIVE TO TRAIN OWNER'S <br />DESIGNATED PERSONNEL ON THE OPERATION AND MAINTENANCE OF THE EQUIPMENT PROVIDED FOR <br />THIS PROJECT. <br />PROVIDE TRAINING TO INCLUDE BUT NOT BE LIMITED TO AN OVERVIEW OF THE SYSTEM AND/OR <br />EQUIPMENT AS IT RELATES TO THE FACILITY AS A WHOLE; OPERATION AND MAINTENANCE <br />PROCEDURES AND SCHEDULES RELATED TO STARTUP AND SHUTDOWN, TROUBLESHOOTING, <br />SERVICING, PREVENTIVE MAINTENANCE AND APPROPRIATE OPERATOR INTERVENTION; AND REVIEW <br />OF DATA INCLUDED IN THE OPERATION AND MAINTENANCE INSTRUCTIONS. <br />SUBMIT A CERTIFICATION LETTER TO THE ARCHITECT STATING THAT THE OWNER'S DESIGNATED <br />REPRESENTATIVE HAS BEEN TRAINED AS SPECIFIED HEREIN. LETTER SHALL INCLUDE DATE, TIME, <br />ATTENDEES AND SUBJECT OF TRAINING. THE CONTRACTOR AND THE OWNER'S REPRESENTATIVE <br />SHALL SIGN THE CERTIFICATION LETTER INDICATING AGREEMENT THAT THE TRAINING HAS BEEN <br />PROVIDED. <br />SCHEDULE TRAINING WITH OWNER WITH AT LEAST 7 DAYS' ADVANCE NOTICE. <br />16A 1 -13 WARRANTIES <br />WARRANT EACH SYSTEM AND EACH ELEMENT THEREOF AGAINST ALL DEFECTS DUE TO FAULTY <br />WORKMANSHIP, DESIGN OR MATERIAL FOR A PERIOD OF 12 MONTHS FROM DATE OF SUBSTANTIAL <br />COMPLETION, UNLESS SPECIFIC ITEMS ARE NOTED TO CARRY A LONGER WARRANTY IN THE <br />CONSTRUCTION DOCUMENTS OR MANUFACTURER'S STANDARD WARRANTY EXCEEDS 12 MONTHS. <br />REMEDY ALL DEFECTS, OCCURRING WITHIN THE WARRANTY PERIOD(S), AS STATED IN THE GENERAL <br />CONDITIONS AND DIVISION 1. <br />ALSO WARRANT THE FOLLOWING ADDITIONAL ITEMS: <br />1. ALL RACEWAYS ARE FREE FROM OBSTRUCTIONS, HOLES, CRUSHING, OR BREAKS OF ANY NATURE. <br />2. ALL RACEWAY SEALS ARE EFFECTIVE. <br />3. THE ENTIRE ELECTRICAL SYSTEM IS FREE FROM ALL SHORT CIRCUITS AND UNWANTED OPEN <br />CIRCUITS AND GROUNDS. <br />THE ABOVE WARRANTIES SHALL INCLUDE LABOR AND MATERIAL. MAKE REPAIRS OR REPLACEMENTS <br />WITHOUT ANY ADDITIONAL COSTS TO THE OWNER. <br />PERFORM THE REMEDIAL WORK PROMPTLY, UPON WRITTEN NOTICE FROM THE ENGINEER OR OWNER. <br />AT THE TIME OF SUBSTANTIAL COMPLETION, DELIVER TO THE OWNER ALL WARRANTIES, IN WRITING <br />AND PROPERLY EXECUTED, INCLUDING TERM LIMITS FOR WARRANTIES EXTENDING BEYOND THE ONE <br />YEAR PERIOD, EACH WARRANTY INSTRUMENT BEING ADDRESSED TO THE OWNER AND STATING THE <br />COMMENCEMENT DATE AND TERM. <br />16A 1 -14 MISCELLANEOUS REMODELING WORK <br />PROVIDE ALL DEMOLITION OF EXISTING ELECTRICAL SYSTEMS AND NEW ELECTRICAL SYSTEM <br />MODIFICATIONS REQUIRED BECAUSE OF BUILDING REMODELING, AS NOTED ON THE DRAWINGS, OR <br />NECESSARY FOR PROPER OPERATION AND NEW CONSTRUCTION. REMOVE ALL ABANDONED CABLES <br />AND WIRING ABOVE ACCESSIBLE CEILINGS AND VENTILATION SHAFTS. <br />16A PART 2 ELECTRICAL WORK <br />16A 2 -1 EXCAVATION AND BACK FILLING <br />PERFORM EXCAVATION AND BACKFILL REQUIRED FOR INSTALLATION OF UNDERGROUND WORK <br />UNDER THIS CONTRACT. TRENCHES SHALL BE OF SUFFICIENT WIDTH. CRIB OR BRACE <br />TRENCHES WO PREVENT CAVE-IN OR SETTLEMENT. DO NOT EXCAVATE TRENCHES CLOSE TO <br />COLUMNS AND WALLS OF NEW BUILDING WITHOUT PRIOR CONSULTATION WITH THE ENGINEER. <br />USE PUMPING EQUIPMENT IF REQUIRED TO KEEP TRENCHES FREE OF WATER. BACKFILL <br />TRENCHES IN MAXIMUM 6-INCH LAYERS OF WELL TAMPED DRY EARTH IN A MANNER TO PREVENT <br />FUTURE SETTLEMENT. <br />EXCAVATION AS HEREIN SPECIFIED SHALL BE CLASSIFIED AS COMMON EXCAVATION. COMMON <br />EXCAVATION SHALL COMPRISE THE SATISFACTORY REMOVAL AND DISPOSITION OF MATERIAL OF <br />WHATEVER SUBSTANCES AND OF EVERY DESCRIPTION ENCOUNTERED, INCLUDING ROCK, IF ANY, <br />WITHIN THE LIMITS OF THE WORK AS SPECIFIED AND SHOWN ON THE DRAWINGS. DISPOSE OF <br />EXCAVATED MATERIALS THAT ARE CONSIDERED UNSUITABLE FOR BACKFILL AND SURPLUS OF <br />EXCAVATED MATERIAL WHICH IS NOT REQUIRED FOR BACKFILL, ALL TO THE SATISFACTION OF <br />THE ENGINEER. <br />16A 2 -2 COINCIDENTAL DAMAGE <br />REPAIR ALL STREETS, SIDEWALKS, DRIVES, PAVING, WALLS, FINISHES, AND OTHER FACILITIES <br />DAMAGED IN THE COURSE OF THIS WORK. REPAIR MATERIALS SHALL MATCH EXISTING <br />CONSTRUCTION. REPAIR MATERIALS SHALL GENERALLY MATCH EXISTING CONSTRUCTION. ALL <br />BACKFILLING AND REPAIRING SHALL MEET ALL REQUIREMENTS OF THE OWNER, CITY AND <br />OTHERS HAVING JURISDICTION. REPAIR WORK SHALL BE THOROUGHLY FIRST CLASS. CONFORM <br />TO ALL REQUIREMENTS OF DIVISION 2 OF THESE SPECIFICATIONS. <br />16A 2 -3 CUTTING AND PATCHING <br />FOLLOWING THE REQUIREMENTS IN DIVISION 1, CUT WALLS, FLOORS, CEILINGS, AND OTHER <br />PORTIONS OF THE FACILITY AS REQUIRED TO PERFORM WORK UNDER THIS DIVISION. OBTAIN <br />PERMISSION OF THE ENGINEER, OWNER, OR BOTH, BEFORE DOING ANY CUTTING. CUT ALL <br />HOLES AS SMALL AS POSSIBLE. PATCH WALLS, FLOORS, AND OTHER PORTIONS OF THE FACILITY <br />AS REQUIRED BY WORK UNDER THIS DIVISION. ALL PATCHING SHALL BE THOROUGHLY FIRST <br />CLASS AND SHALL MATCH THE ORIGINAL MATERIAL AND CONSTRUCTION, INCLUDING FIRE <br />RATINGS IF APPLICABLE. <br />16A 2 -4 ROUGH-IN <br />COORDINATE WITHOUT DELAY ALL ROUGHING-IN WITH OTHER DIVISIONS. CONCEAL ALL <br />RACEWAYS EXCEPT IN UNFINISHED AREAS AND WHERE OTHERWISE INDICATED ON THE <br />DRAWINGS. <br />16A 2 -5 SUPPORT SYSTEMS <br />STEEL SLOTTED SUPPORT SYSTEMS (SLOTTED CHANNEL): COMPLY WITH MFMA-3, FACTORY- <br />FABRICATED COMPONENTS FOR FIELD ASSEMBLY; 12-GAUGE, 1-5/8 INCH BY 1-5/8 INCH; COOPER <br />B-LINE, ERICO INTERNATIONAL CORPORATION, HILTI INC., POWER-STRUT, THOMAS & BETTS <br />CORPORATION, UNISTRUT. <br />FINISHES <br />1. METALLIC COATINGS: HOT-DIP GALVANIZED AFTER FABRICATION AND APPLIED ACCORDING TO <br />MFMA-3. <br />FIELD FABRICATION: <br />1. WHERE FIELD CUTTING OF STANDARD LENGTHS OF CHANNEL ARE REQUIRED, MAKE CUTS <br />STRAIT AND PERPENDICULAR TO MANUFACTURED SURFACES. <br />2. FOR FIELD-CUT OR DAMAGED SURFACES OF COATED CHANNELS, DRESS CUT ENDS, DAMAGED <br />SURFACES, OR BOTH, WITH AN ABRASIVE MATERIAL (E.G., FILE, GRINDING STONE, OR SIMILAR) <br />AND CLEANSER TO REMOVE OILS, RUST, SHARP EDGES AND SHARDS). <br />3. FOR CHANNEL WITH A FACTORY-APPLIED COATING, RE-FINISH CUT EDGES WITH A COATING <br />COMPATIBLE WITH THE FACTORY FINISH AND AS RECOMMENDED BY THE MANUFACTURER <br />(E.G. MANUFACTURER'S TOUCH-UP PAINT OR ZINC-RICH COLD-GALVANIZING COMPOUND, AS <br />APPLICABLE). <br />16A 2 -6 PENETRATIONS <br />COORDINATE SLEEVE SELECTION AND APPLICATION WITH SELECTION AND APPLICATION OF FIRE- <br />STOPPING SPECIFIED IN DIVISION 7 SECTION "THROUGH -PENETRATION FIRESTOP SYSTEMS." <br />ROOFS: <br />1. COORDINATE ALL ROOF PENETRATIONS WITH ENGINEER, OWNER, AND AS APPLICABLE, THE <br />ROOFING CONTRACTOR PROVIDING A ROOF WARRANTY. <br />2. KEEP ALL RACEWAY PENETRATIONS WITHIN MECHANICAL EQUIPMENT CURBS WHEREVER <br />POSSIBLE. COORDINATE WITH DIVISION 15 WORK <br />3. FLASH AND COUNTERFLASH ALL OPENINGS THROUGH ROOF, AND/OR PROVIDE PRE- <br />FABRICATED MOLDED SEALS COMPATIBLE WITH THE ROOF CONSTRUCTION INSTALLED, OR AS <br />REQUIRED BY THE ENGINEER, OWNER, OR ROOFING CONTRACTOR. ALL ROOF PENETRATIONS <br />SHALL BE LEAKTIGHT AT THE TERMINATION OF THE WORK AND SHALL NOT VOID ANY NEW OR <br />EXISTING ROOF WARRANTIES. <br />WALLS AND FLOORS: <br />SLEEVES FOR RACEWAYS AND CABLES <br />1. STEEL PIPE SLEEVES: ASTM A 53/A 53M, TYPE E, GRADE B, SCHEDULE 40, GALVANIZED STEEL, <br />PLAIN ENDS AND DRIP RINGS. <br />2. CAST-IRON PIPE SLEEVES: CAST OR FABRICATED "WALL PIPE," EQUIVALENT TO DUCTILE - <br />IRON PRESSURE PIPE, WITH PLAIN ENDS AND INTEGRAL WATERSTOP, UNLESS OTHERWISE <br />INDICATED. <br />SLEEVES FOR RECTANGULAR OPENINGS: GALVANIZED SHEET STEEL WITH MINIMUM 0.052-INCH <br />THICKNESS AS INDICATED AND OF LENGTH SO SUIT APPLICATION. <br />16A 2 -7 FIRE -STOPPING FLOOR AND WALL PENETRATIONS <br />FIRE -RESISTANT THROUGH PENETRATION SEALANTS: TWO -PART, FOAMED-IN-PLACE, <br />SILICONE SEALANT FORMULATED FOR USE IN THROUGH-PENETRATION FIRE-STOPPING AROUND <br />CABLES, RACEWAYS, AND CABLE TRAY PENETRATIONS THROUGH FIRE-RATED WALLS AND <br />FLOORS. SEALANTS AND ACCESSORIES SHALL HAVE FIRE-RESISTANCE RATINGS INDICATED, AS <br />ESTABLISHED BY TESTING IDENTICAL ASSEMBLIES IN ACCORDANCE WITH AST E 814, BY <br />UNDERWRITERS' LABORATORIES, INC., OR OTHER NRTL ACCEPTABLE TO AHJ. <br />ACCEPTABLE MANUFACTURERS: <br />A. HILTI, INC. <br />B. 3M CORP. <br />C. RECTORSEAL <br />D. SPECIFY TECHNOLOGY INC. <br />E. UNITED STATES GYPSUM COMPANY <br />16A 2 -8 ACCESS DOORS <br />PROVIDE ACCESS DOORS IN CEILINGS AND WALLS, WHERE INDICATED OR REQUIRED FOR <br />ACCESS OR MAINTENANCE TO CONCEALED EQUIPMENT INSTALLED UNDER THIS SECTION. <br />PROVIDE CONCEALED HINGES, SCREWDRIVER-TYPE LOCK, AND ANCHOR STRAPS. <br />MANUFACTURED BY MILCOR, ZURN, TITUS, OR EQUAL. OBTAIN ARCHITECT'S APPROVAL OF TYPE, <br />SIZE, LOCATION AND COLOR BEFORE ORDERING. <br />16A 2-9 EQUIPMENT FURNISHED BY OTHERS <br />PROVIDE NECESSARY EQUIPMENT AND ACCESSORIES THAT ARE NOT PROVIDED BY THE <br />EQUIPMENT SUPPLIER OR OWNER TO COMPLETE INSTALLATION OF EQUIPMENT FURNISHED BY <br />OTHERS, IN LOCATIONS AS INDICATED ON THE DRAWINGS, SPECIFIED HEREIN, OR BOTH <br />EQUIPMENT AND ACCESSORIES NOT PROVIDED BY THE EQUIPMENT SUPPLIER MAY INCLUDE <br />SUCH ITEMS AS FLEXIBLE CORDS AND PLUGS, AS REQUIRE FOR PROPER OPERATION OF THE <br />COMPLETE SYSTEM, IN ACCORDANCE WITH THE MANUFACTURERS' INSTRUCTIONS. <br />BE RESPONSIBLE FOR CORRECT ROUGH-IN DIMENSIONS, AN VERIFY THEM WITH ENGINEER, <br />OWNER'S REPRESENTATIVE, EQUIPMENT SUPPLIER, OR ALL THREE, PRIOR TO ROUGH-IN AND <br />SERVICE INSTALLATIONS. <br />16A 2 -10 CLEANING <br />IN ADDITION TO THE REQUIREMENTS OF DIVISION 1, REMOVE FROM THE PREMISES DIRT AND <br />REFUSE RESULTING FROM THE PERFORMANCE OF THE ELECTRICAL WORK, AS REQUIRED, TO <br />PREVENT ACCUMULATION. COOPERATE IN MAINTAINING REASONABLY CLEAN PREMISES AT ALL <br />TIMES. IMMEDIATELY PROPER TO FINAL INSPECTION, MAKE A FINAL CLEANUP OF DIRT AND <br />REFUSE RESULTING FORM THE WORK. CLEAN ALL MATERIAL AND EQUIPMENT INSTALLED UNDER <br />THIS DIVISION. REMOVE DIRT, DUST, PLASTER, STAINS AND FOREIGN MATTER FROM ALL <br />SURFACES. TOUCH UP AND RESTORE ALL DAMAGED FINISHES TO THEIR ORIGINAL CONDITION. <br />16A 2 -11 ADJUSTING, ALIGNING AND TESTING <br />ADJUST, ALIGN, AND TEST ALL ELECTRICAL EQUIPMENT ON THIS PROJECT PROVIDED UNDER THIS <br />DIVISION AND ALL ELECTRICAL EQUIPMENT FURNISHED BY OTHERS FOR INSTALLATION OR <br />WIRING UNDER THIS DIVISION, FOR PROPER OPERATION. <br />DIVISION 16 <br />TEST ALL SYSTEMS AND EQUIPMENT ACCORDING TO THE REQUIREMENTS IN NETA ATS (LATEST <br />EDITION) AND ALL ADDITIONAL REQUIREMENTS SPECIFIED IN FOLLOWING SECTIONS. <br />MAINTAIN THE FOLLOWING ON THE PROJECT PREMISES AT ALL TIMES: A TRUE RMS READING <br />VOLTMETER , A TRUE RMS READING AMMETER, AND A MEGOHMMETER INSULATION RESISTANCE <br />TESTER. PROVIDE TEST DATA READINGS AS REQUESTED OR AS REQUIRED BY THE ENGINEER. <br />16A 2 -12 EQUIPMENT IDENTIFICATION <br />PROVIDE EQUIPMENT IDENTIFICATION NAMEPLATES: <br />1. ON ALL PANELBOARDS, SWITCHES, STARTERS, DIMMERS, SWITCHES IN DISTRIBUTION <br />PANELBOARDS AND SWITCHBOARDS. <br />NAMEPLATES: <br />1. ENGRAVED, CONTRASTING COLOR, THREE-LAYER, LAMINATED PLASTIC INDICATION THE NAME OF <br />THE EQUIPMENT, LOAD, OR CIRCUIT AS DESIGNATED ON THE DRAWINGS AND IN THE <br />SPECIFICATIONS: <br />2. SELF-ADHERING, WITH A PERMANENT, WEATHERPROOF ADHESIVE <br />3. ATTACHMENT METHOD SHALL BE ACCEPTABLE TO THE MANUFACTURERS OF THE EQUIPMENT TO <br />WHICH THE NAMEPLATES ARE BEING APPLIED. <br />4. COLOR: BLACK BACKGROUND WITH WHITE LETTERS: LETTER HEIGHT: 1/4-INCH MINIMUM [AS <br />INDICATED ON THE DRAWINGS]. <br />16A 2 -13 SYSTEM START UP <br />1. PRIOR TO STARTING UP THE ELECTRICAL SYSTEMS: <br />2. CHECK ALL COMPONENTS AND DEVICES. <br />3. LUBRICATE ITEMS ACCORDINGLY. <br />4. TIGHTEN SCREWS AND BOLTS FOR CONNECTORS AND TERMINALS ACCORDING T0 <br />MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE <br />VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A AND UL 486B. <br />5. ADJUST TAPS ON EACH TRANSFORMER FOR RATED SECONDARY VOLTAGE. <br />6. CHECK AND RECORD BUILDING'S SERVICE ENTRANCE VOLTAGE, GROUNDING, CONDITIONS, <br />GROUND RESISTANCE, AND PROPER PHASING. <br />7. BALANCE ALL SINGLE-PHASE LOADS AT EACH PANELBOARD, REDISTRIBUTING BRANCH CIRCUIT <br />CONNECTIONS UNTIL BALANCE IS ACHIEVED. DO NOT TYPE UP FINAL PANELBOARD DIRECTORIES <br />UNTIL ALL RE-BALANCING AND REDISTRIBUTION OF CIRCUITS ARE COMPLETE. <br />8. REPLACE ALL BURNED-OUT LAMPS & LAMPS USED FOR TEMPORARY CONSTRUCTION LIGHTING IN <br />PERMANENT LIGHT FIXTURES. <br />9. AFTER ALL SYSTEMS HAVE BEEN INSPECTED AND ADJUSTED, CONFIRM ALL OPERATING <br />FEATURES REQUIRED BY THE DRAWINGS AND SPECIFICATION AND MAKE FINAL ADJUSTMENT AS <br />NECESSARY. <br />16A PART 3 EXISTING EQUIPMENT REUSE AND REMOVAL <br />16A 3 -1 GENERAL: <br />REMOVE ALL EXISTING WIRING, LIGHT FIXTURES, EXPOSED CONDUITS AND OTHER ELECTRICAL <br />INSTALLATIONS NOT REUSED PRIOR TO SUBSTANTIAL COMPLETION OF THE WORK. <br />EXISTING RACEWAYS MAY BE REUSED IF THEIR POINTS OF TERMINATIONS ARE SUITABLE: IF THEY <br />ARE CLEAN INSIDE WITH NO EVIDENCE OF RUST OR BURRS; IF FREE FROM CRACKS, FLATTENED <br />SECTIONS OR SHARP BENDS: AND IF SUITABLY LOCATED TO AVOID CONFLICTS WITH OTHER TRADES <br />OR INSTALLATIONS. CAREFULLY "FISH" ALL EXISTING CONDUITS REUSED UNDER THIS CONTRACT TO <br />REMOVE ALL DEBRIS AND OBSTRUCTIONS, AND SWAB UNTIL ALL MOISTURE IS REMOVED. <br />CUT, PATCH, AND REPAIR WHERE REQUIRED FOR NEW ELECTRICAL INSTALLATIONS, AND PATCH AND <br />REPAIR ALL SURFACE DAMAGE RESULTING FROM THIS WORK. CUT FLUSH WITH THE FLOOR AND <br />PLUG AT BOTH ENDS. RACEWAYS STUBBED ABOVE THE FLOOR AND NOT USED AT SUBSTANTIAL <br />COMPLETION OF THE WORK <br />RELOCATE ALL EXISTING ELECTRICAL SYSTEMS REQUIRED TO BE IN OPERATION A SUBSTANTIAL <br />COMPLETION OF THE CONTRACT, IF REQUIRED, AS A RESULT OF WORK INCLUDED UNDER THIS <br />CONTRACT, EVEN IF NOT SPECIFICALLY INDICATED IN THE DRAWINGS OR SPECIFICATIONS. <br />SECTION 16B BASIC ELECTRICAL MATERIALS AND METHODS <br />16B 1 METHODS <br />16B 1 -1 RACEWAYS <br />METALLIC CONDUIT AND TUBING: <br />1. ELECTRICAL METALLIC TUBING AND FITTINGS (EMT): ANSI C80.3 UL 797. <br />2. FLEXIBLE METAL CONDUIT (FMC): ZINC-COATED STEEL OR ALUMINUM, UL 1. <br />3. INTERMEDIATE METAL CONDUIT (IMC): HOT-DIP GALVANIZED RIGID STEEL CONDUIT:ANSI C80.6, <br />UL 1242. <br />4. LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC): FLEXIBLE STEEL CONDUIT WITH PVC JACKET: UL <br />360 <br />5. RIGID METAL CONDUIT (FMC): HOT-DIP GALVANIZED RIGID STEEL CONDUIT (GRS): ANSI C80.1, UL 6. <br />6. RIGID ALUMINUM CONDUIT (RAC): ANSI C80.5 UL 6A. <br />7. PLASTIC-COATED IMC, RMC, AND FITTINGS: NEMA RN 1, UL LISTED. <br />8. IMC AND RMC FITTINGS: NEMA FB 1; COMPATIBLE WITH CONDUIT TYPE AND MATERIAL, UL LISTED <br />NON -METALLIC CONDUIT AND TUBING: <br />RIGID NONMETALLIC CONDUIT (RNC): SCHEDULE 40 PVC, 90 DEG C RATED, NEMA TC-2, UL 651; <br />FITTINGS: NEMA TC 3, TC 6; UL 514, COMPATIBLE WITH CONDUIT/TUBING TYPE AND MATERIAL, UL <br />LISTED <br />16B 1 -2 RACEWAY INSTALLATION <br />INSTALL ALL CIRCULAR RACEWAYS CONCEALED ABOVE SUSPENDED CEILINGS OR CONCEALED IN <br />WALLS OR FLOORS WHEREVER POSSIBLE EXCEPT WHERE OTHERWISE INDICATED. <br />PROVIDE GRS FOR ALL CONDUITS RUN UNDERGROUND, EXPOSED TO WEATHER, OR EXPOSED TO <br />OTHER HAZARDOUS CONDITIONS. PROVIDE GRS INSTALLED BELOW GRADE WITH A CORROSION <br />RESISTANT BONDED-PLASTIC OR APPROVED MASTIC COATING. THIS SHALL INCLUDE THE 90-DEGREE <br />ELBOW BELOW GRADE AND THE ENTIRE VERTICAL TRANSITION TO ABOVE GRADE. <br />ALL OTHER RACEWAY MAY BE EMT WHERE APPROVED BY LOCAL CODE. USE SET-SCREW TYPE <br />FITTINGS FOR EMT, WITH ALL FITTING UL LISTED FOR THE ENVIRONMENT IN WHICH THEY ARE USED. <br />AT CONTRACTOR'S OPTION, PVC CONDUIT MAY BE USED UNDERGROUND WHERE PERMITTED BY <br />LOCAL CODE AND WHERE NOT SPECIFICALLY RESTRICTED BY THE DOCUMENTS. WHEN USED, <br />PROVIDE COATED GRS, AS SPECIFIED ABOVE, FOR ALL BENDS GREATER THAT 30 DEGREES, <br />INCLUDING THE 90-DEGREE ELBOW BELOW GRADE AND THE ENTIRE VERTICAL TRANSITIONS TO <br />ABOVE GRADE. <br />USE FMC FOR FINAL CONNECTION TO EACH MOTOR AND TRANSFORMER, AND TO ANY DEVICE THAT <br />WOULD OTHERWISE TRANSMIT MOTION, VIBRATION, OR NOISED. WHERE EXPOSED TO LIQUIDS, <br />VAPORS OR SUNLIGHT, USE LFMC. PROVIDE ALL FMC AND LFMC WITH AN INSULATED BONDING <br />CONDUCTOR. <br />USE ONLY METAL RACEWAYS FOR ALL POWER WIRING FROM THE OUTPUT OF VARIABLE FREQUENCY <br />DRIVES TO THEIR RESPECTIVE MOTORS. <br />INSTALL RACEWAYS PARALLEL AND PERPENDICULAR TO BUILDING LINES. <br />INSTALL RACEWAYS TO REQUIREMENTS OF STRUCTURE AND TO REQUIREMENTS OF ALL OTHER <br />WORK ON THE PROJECT. INSTALL RACEWAY TO CLEAR ALL OPENINGS, DEPRESSIONS, PIPES, DUCTS, <br />REINFORCING STEEL, AND OTHER IMMOVABLE OBSTACLES. INSTALL RACEWAYS SET IN FORMS FOR <br />CONCRETE STRUCTURE IN SUCH A MANNER THAT INSTALLATION WILL NOT AFFECT THE STRENGTH OF <br />THE STRUCTURE. EXCEPT WHERE APPROVED IN WRITING BY THE ENGINEER, INSTALL NO RACEWAY <br />IN A SLAB-ON-GRADE. LOCATE RACEWAY IN GRANULAR FILL BELOW SLABS-ON-GRADE. <br />INSTALL RACEWAYS CONTINUOUS BETWEEN CONNECTIONS TO OUTLETS, BOXES AND CABINETS WITH <br />A MINIMUM POSSIBLE NUMBER OF BENDS AND NOT MORE THAN THE EQUIVALENT OF FOUR 90- <br />DEGREE BENDS BETWEEN CONNECTIONS. USE MANUFACTURED ELBOWS FOR ALL 45-AND 90- <br />DEGREE BENDS, UNLESS APPROVED BY THE ENGINEER IN ADVANCE, MAKE OTHER BENDS SMOOTH <br />AND EVEN AND WITHOUT FLATTENING RACEWAY OR FLAKING GALVANIZING OR ENAMEL. RADII OF <br />BENDS SHALL BE AS LONG AS POSSIBLE AND NEVER SHORTER THAN THE CORRESPONDING TRADE <br />ELBOW. USE LONG RADIUS ELBOWS WHERE NECESSARY, INDICATED, OR BOTH. <br />SECURELY FASTEN RACEWAYS IN PLACE WITH APPROVED STRAPS, HANGERS AND STEEL SUPPORTS <br />AS REQUIRED. ATTACH RACEWAY SUPPORTS TO THE BUILDING STRUCTURE. HANG SINGLE <br />RACEWAYS FOR FEEDERS WITH MALLEABLE SPLIT RING HANGERS WITH ROD AND TURNBUCKLE <br />SUSPENSION FROM INSERTS SPACED NOR OVER 10 FEET APART IN CONSTRUCTION ABOVE. CLAMP <br />GROUPS OF HORIZONTAL FEEDER RACEWAYS TO STEEL CHANNELS THAT ARE SUSPENDED FRO <br />INSERTS SPACED NOT OVER 10 FEET APART IN CONSTRUCTION ABOVE. SECURELY CLAMP VERTICAL <br />FEEDER RACEWAYS TO STRUCTURAL VERTICAL FEEDERS WHERE REQUIRED. ADD RACEWAY <br />SUPPORTS WITHIN 12 INCHES OF ALL BENDS, ON BOTH SIDES OF THE BENDS. DO NOT SUPPORT <br />RACEWAYS FROM SUSPENDED CEILING COMPONENTS. <br />REAM RACEWAY ENDS, THOROUGHLY CLEAN RACEWAYS BEFORE INSTALLATION, AND KEEP CLEAN <br />AFTER INSTALLATIONS. PLUG OR COVER OPENINGS AND BOXES AS REQUIRED TO KEEP RACEWAYS <br />CLEAN DURING CONSTRUCTION AND FISH ALL RACEWAYS CLEAR OF OBSTRUCTIONS BEFORE <br />PULLING CONDUCTORS WIRES. PROVIDE RACEWAYS OF AMPLE SIZE FOR PULLING OF WIRE AND NOT <br />SMALLER THAN CODE REQUIREMENTS AND NOT LESS THAN 1/2-INCH IN SIZE, UNLESS INDICATED <br />OTHERWISE ON DRAWINGS. <br />PROTECT ALL RACEWAY INSTALLATIONS AGAINST DAMAGE DURING CONSTRUCTION. REPAIR ALL <br />RACEWAYS DAMAGED OR MOVED OUT OF LINE AFTER ROUGHING-IN TO MEET ENGINEER'S APPROVAL <br />WITHOUT ADDITIONAL COST TO THE OWNER. <br />ALIGN AND INSTALL TRUE AND PLUMB ALL RACEWAY TERMINATIONS AT PANELBOARDS, SWITCHBOARDS, <br />MOTOR CONTROL EQUIPMENT AND JUNCTION BOXES. <br />INSTALL APPROVED EXPANSION/DEFLECTION FITTINGS WHERE RACEWAYS PASS THROUGH )IF EMBEDDED) <br />OR ACROSS (IF EXPOSED) EXPANSION JOINTS. <br />INSTALL A PULL WIRE IN EACH EMPTY RACEWAY THAT IS LEFT FOR INSTALLATION OF CONDUCTORS OR <br />CABLES UNDER OTHER DIVISIONS OR CONTRACTS. USE POLYPROPYLENE OR MONOFILAMENT PLASTIC <br />LINE WITH NOT LESS THAT 200-LB TENSILE STRENGTH. LEAVE AT LEAST 24 INCHES OF SLACK AT EACH END <br />OF PULL WIRE. <br />MAKE ALL JOINTS AND CONNECTIONS IN A MANNER THAT WILL ENSURE MECHANICAL STRENGTH AND <br />ELECTRICAL CONTINUITY. <br />EFFECTIVELY SEAL RACEWAYS, BY INSTALLING A CONDUIT FITTING AT THE BOUNDARY OF THE TWO <br />SPACES, AND FILLING IT WITH AN APPROVED PLIABLE MATERIAL, AFTER CONDUCTORS OR CABLES HAVE <br />BEEN INSTALLED AND TESTED, WHEN EVER: <br />1. RACEWAYS PASS FROM NON-COOLED TO COOLED SPACES. <br />2. RACEWAYS TRANSITION FROM OUTSIDE A FACILITY OR ENCLOSURE TO INSIDE, WHETHER BURIED OR <br />EXPOSED. <br />16B 1 -3 BUSHINGS AND LOCKNUTS <br />RIGIDLY TERMINATE CONDUITS ENTERING SHEET METAL ENCLOSURES TO THE ENCLOSURE WITH A <br />BUSHING AND LOCKNUT ON THE INSIDE AND A LOCKNUT OR AN APPROVED HUB ON THE OUTSIDE. CONDUIT <br />SHALL ENTER THE ENCLOSURE SQUARELY. <br />PROVIDE BUSHINGS AND LOCKNUTS MADE OF GALVANIZED MALLEABLE IRON WITH SHARP, CLEAN-CUT <br />THREADS. <br />WHERE EMT ENTERS A BOX, PROVIDE APPROVED EMT COMPRESSION CONNECTORS. <br />USE INSULATED, GROUNDING, OR COMBINATION, BUSHINGS WHEREVER CONNECTION IS SUBJECT TO <br />VIBRATION OR MOISTURE, WHEN REQUIRED BY NFPA 70, OR BOTH. <br />16B 1 -4 CONDUCTORS AND CABLES <br />CONDUCTOR MATERIAL: <br />1. ANNEALED (SOFT) COPPER COMPLYING WITH ICEA S-95-658/NEMA WC70: <br />2. CONDUCTOR INSULATION TYPES: 90-DEGREE C-RATED, TYPE THHN/THWN-2 OR XHHW-2 COMPLYING <br />WITH ICEA S-95-658/NEMA WC70. <br />3. SIZES OF CONDUCTORS & CABLES INDICATED OR SPECIFIED ARE IN AMERICAN WIRE GAGE (AWG - <br />BROWN & SHARPE). <br />4. UNLESS INDICATED OTHERWISE, SPECIAL PURPOSE CONDUCTORS AND CABLES, SUCH AS LOW <br />VOLTAGE CONTROL AND SHIELDED INSTRUMENT WIRING, SHALL BE AS RECOMMENDED BY THE SYSTEM <br />EQUIPMENT MANUFACTURER. <br />ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS NO. 8 AWG AND LARGER: STRANDED, TYPE THWN-2 OR <br />XHHW-2 INSULATION. <br />ALL CONDUCTORS, NO. 10 AWG AND SMALLER, USED FOR POWER AND LIGHTING CIRCUITS: SOLID COPPER, <br />TYPE THWN-2 (WET OR CAMP LOCATIONS, OR IN CONDUIT BELOW GRADE OR SLAB), TYPE THHN (DRY <br />LOCATIONS ONLY AND ABOVE GRADE) INSULATION, OR DUAL-RATED TYPE THHN/THWN-2. <br />HOMERUNS TO PANELBOARDS 75 FEET TO 125 FEET SHALL NOT BE LESS THAN NO. 10 AWG, AND <br />HOMERUNS 126 FEET TO 190 FEET SHALL BE NO LESS THAN NO 8 AWG. <br />ALL BRANCH CIRCUIT WIRING: NOT SMALLER THAN NO. 12 AWG. IF NO CONDUCTOR SIZE IS INDICATED ON <br />THE DRAWINGS FOR A BRANCH CIRCUIT, PROVIDE CONDUCTORS AND CONDUIT SIZED PER NFPA 70 AND <br />BASED ON THE INDICATED BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE (OCPD) RATING AND <br />NUMBER OF POLES. WHERE NO CIRCUIT SIZE (I.E. CONDUCTORS AND OCPD) IS INDICATED ON THE <br />DRAWINGS FOR A BRANCH CIRCUIT, PROVIDE THREE NO. 12 AWG CONDUCTORS, IN 3/4-INCH RACEWAY, AND <br />A 20A CIRCUIT BREAKER. <br />CONDUCTORS FIELD-INSTALLED WITHIN FLUORESCENT LIGHT FIXTURE CHANNELS: TYPE THHN. <br />CONTROL WIRING: STRANDED COPPER CONDUCTORS. 600V INSULATION, OF THE PROPER TYPE, SIZE AND <br />NUMBER AS REQUIRED TO ACCOMPLISH SPECIFIED FUNCTION. MINIMUM SIZE: NO. 14 AWG, UNLESS NOTED <br />OTHERWISE. <br />TYPE MC CABLE: 600V, UNJACKETED; ANSI E 119 AND E814, UL STANDARDS 44 OR 83 (AS APPLICABLE), AND <br />1569, NFPA 70 ARTICLE 330; ALUMINUM OR GALVANIZED STEEL INTERLOCKED ARMOR; THHN-OR XHHW- <br />INSULATED CONDUCTORS: COLOR CODE: ICEA METHOD 1, WITH GREEN INSULATED GROUNDING <br />CONDUCTOR. <br />16B 1 -5 INSTALLATION OF CONDUCTORS AND CABLES <br />INSTALL ALL WIRING IN APPROVED RACEWAY AND ENCLOSURE. <br />SUPPORT ALL CONDUCTORS AND CABLES IN VERTICAL INSTALLATIONS, AS REQUIRED BY NFPA 70, BY <br />INSTALLING CABLE SUPPORTS OR PLUG-TYPE CONDUIT RISER SUPPORTS, OR WIRE-MESH SAFETY GRIPS. <br />INSTALL ALL CONDUCTORS & CABLE IN RACEWAY CONTINUOUS WITHOUT TAPS OR SPLICES. SPLICE OR <br />TAP ONLY IN APPROVED BOXES AND ENCLOSURES WITH APPROVED SOLDERLESS CONNECTORS, OR CRIMP <br />CONNECTORS AND TERMINAL BLOCKS FOR CONTROL WIRING, AND KEEP TO THE MINIMUM REQUIRED. <br />INSULATE ALL SPLICES, TAPS, AND JOINTS AS REQUIRED BY CODES. <br />ALL MATERIALS USED TO TERMINATE, SPLICE OR TAP CONDUCTORS: DESIGNED FOR, PROPERLY SIZED <br />FOR, AND UL LISTED FOR THE SPECIFIC APPLICATION AND CONDUCTORS INVOLVED, AND INSTALLED IN <br />STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, USING THE MANUFACTURER'S <br />RECOMMENDED TOOLS. <br />WHERE WIRING IS INDICATED AS INSTALLED, BUT THE CONNECTION IS INDICATED "FUTURE" OR "BY OTHER <br />DIVISION, TRADES, OR CONTRACTS", LEAVE A MINIMUM 3-FOOT "PIGTAIL" AT THE BOX, TAPE THE ENDS OF <br />THE CONDUCTORS, AND COVER THE BOX. <br />THE NUMBER OF CONDUCTORS IN A SPECIFIC RACEWAY "HOME RUN" IS INDICATED WITH CROSS LINES <br />(TICK MARKS) ON EACH "CIRCUIT RUN" ON THE DRAWINGS. IN GENERAL, THE DIRECTION OF BRANCH <br />CIRCUIT "HOME RUN" ROUTING IS INDICATED ON THE DRAWINGS, COMPLETE WITH CIRCUIT NUMBERS AND <br />PANELBOARD DESIGNATION. CONTINUE ALL SUCH "HOME RUN" WIRING TO THE DESIGNATED PANELBOARD, <br />AS THOUGH "CIRCUIT RUNS' WERE INDICATED IN THEIR ENTIRETY. <br />WHEN MULTIPLE HOME RUNS ARE COMBINED INTO A SINGLE RACEWAY SUCH THAT THE NUMBER OF <br />CONDUCTORS EXCEEDS FOUR (CONDUCTOR COUNT IS MADE UP OF ANY COMBINATION OF PHASE AND <br />NEUTRAL CONDUCTORS), THE FOLLOWING RESTRICTIONS APPLY, WHICH ARE IN ADDITION TO THOSE IN <br />NFPA 70: <br />NORMAL CIRCUITS <br />A. MAXIMUM OF 16 CONDUCTORS IN A SINGLE RACEWAY. FOR UP TO EIGHT CONDUCTORS IN A <br />RACEWAY, MINIMUM RACEWAY SIZE: 3/4-INCH. FOR GREATER THAN EIGHT CONDUCTORS, MINIMUM <br />RACEWAY SIZE: 1-INCH. DO NOT INSTALL ANY OTHER TYPE OF CIRCUIT IN THIS RACEWAY. <br />B. THE MINIMUM WIRE SIZE FOR ALL CONDUCTORS IN THIS RACEWAY: NO. 10 AWG. <br />C. ONLY 15A AND 20A BRANCH CIRCUIT HOME RUNS MAY BE COMBINED NOT ONE RACEWAY. <br />GFCI CIRCUITS. <br />A. DO NOT USE MULTI-CONDUCTOR CIRCUITS, W/ A SHARED NEUTRAL, FOR ANY GFCI CIRCUIT BREAKER <br />OR RECEPTACLE CIRCUIT. <br />FOR BRANCH CIRCUITS FED FROM GFCI CIRCUIT BREAKERS, LIMIT THE ONE-WAY CONDUCTOR LENGTH TO <br />100 FEET BETWEEN THE PANELBOARD AND THE MOST REMOTE RECEPTACLE OR LOAD ON THE GFCI <br />CIRCUIT. <br />WIRING SHALL HAVE INSULATION OF THE PROPER COLOR TO MATCH COLOR CODE SYSTEM IN THE TABLE <br />BELOW. IN LARGER SIZES, WHERE PROPERLY COLORED INSULATION IS NOT AVAILABLE, USE VINYL <br />PLASTIC ELECTRICAL TAPE OF THE APPROPRIATE COLOR AROUND EACH CONDUCTOR AT ALL TERMINATION <br />POINTS, JUNCTION AND PULL BOXES. <br />System Voltage Conductor Type Color <br />208Y/120 PHASE A BLACK <br />PHASE B RED <br />PHASE C BLUE <br />NEUTRAL WHITE <br />EQUIPMENT GROUND GREEN <br />ISOLATED GROUND GREEN WITH YELLOW STRIPES <br />480Y/277 PHASE A BROWN <br />PHASE B ORANGE <br />PHASE C YELLOW <br />NEUTRAL GRAY <br />EQUIPMENT GROUND GREEN <br />ISOLATED GROUND GREEN WITH YELLOW STRIPES <br />Mechanical and Electrical Engineers <br />Lilker Associates <br />1001 Avenue of the Americas <br />New York, NY 10018 <br />tel 212.695.1000 <br />fax 212.695.1299 <br />www.lilker.com <br />Kenneth A. Gruskin AIA <br />No. Date Description <br />Consultant: <br />Checked By: <br />Drawn By: <br />Job Address: <br />Drawing Title: <br />Revision Issue: <br />Professional Seal: <br />Drawing Number: <br />2024 Gruskin Architecture + Design, P.C.c <br />This document and the ideas and designs incorporated <br />herein, as an instrument of professional service, is the <br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C., <br />and is not to be used in whole or in part for any other <br />project without the written authorization of GRUSKIN <br />ARCHITECTURE + DESIGN, P.C. <br />North <br />Arrow: <br />Job Name and Number: <br />Date Issued For <br />All Rights Reserved <br />Client: <br />Landlord: <br />Permit: <br />Bid: <br />Construction: <br />0006261 <br />AR91629 <br />5421 <br />9613 <br />39209 <br />10635 <br />2537 <br />11016 <br />5734 <br />ARC 2596 <br />4674 <br />2666 <br />AI 09999 <br />2796 <br />0401 011223 <br />2572 <br />17680 <br />RA-015432-B <br />025528-1 NY <br />TX <br />VA <br />VT <br />MA <br />MT <br />RI <br />PA <br />NY <br />NJ <br />NH <br />MD <br />LA <br />ME <br />KS <br />FL <br />DE <br />CT <br />AZ <br />AL <br />C-1967WY <br />RA011075GA <br />AR10400066IN <br />C-29898CA <br />NM 004168 <br />ARC-400347CO <br />HI AR 11489 <br />PR 19965 <br />OR 4899 <br />SC 6834 <br />NC 9961 <br />13761OH <br />05713IA <br />WV 3727 <br />IL 001-019152 <br />UT 5881358-0301 <br />ID AR-984459 <br />1301052379MI <br />ARC100723DC <br />WI 9900-005MN44326 <br />A-3547NE <br />3811AR <br />5967KY 101374TN <br />MS 3860 <br />1666ND <br />A-2005029740MO <br />a4895OK <br />NV 5521 <br />WA 10344 <br />13167AK <br />SD 11532 <br />C: <br />\ <br />R <br />e <br />v <br />i <br />t <br /> <br />L <br />o <br />c <br />a <br />l <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />2 <br />4 <br />0 <br />0 <br />1 <br />3 <br />0 <br />8 <br />_ <br />V <br />E <br />R <br />I <br />Z <br />O <br />N <br />_ <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />_ <br />C <br />A <br />_ <br />EL <br />E <br />C <br />T <br />R <br />I <br />C <br />A <br />L <br />_ <br />v <br />2 <br />3 <br />_ <br />D <br />B <br />e <br />l <br />l <br />B <br />R <br />N <br />E <br />Z <br />. <br />r <br />v <br />t <br />2023-0069 <br />Proposed <br />Store Design <br />for: VERIZON <br />Metro Pointe <br />3500 South Bristol Street <br />Suite 100 <br />Santa Ana, CA 92704 <br />3/15/24 <br />3/15/24 <br />ELECTRICAL <br />SPECIFICATIONS (1 OF 2) <br />E.0.2 <br />DB <br />MH <br />47 OF 81 <br />3500 S Bristol St Unit# 100 - <br />101119098, 20182666 & <br />401390437/11/2024