16B PART 2 ELECTRICAL SERVICE AND GROUNDING <br />16B 2 -1 ELECTRICAL SERVICE <br />SEE DRAWINGS FOR TYPE, SIZE, VOLTAGE, PHASE, AND OTHER REQUIREMENTS. <br />16B 2 -2 CONNECTION TO SERVING UTILITIES <br />LANDLORD SHALL PROVIDE RACEWAYS, TERMINATIONS, METERING PROVISIONS, AND MISCELLANEOUS EQUIPMENT <br />REQUIRED FOR ELECTRICAL AND TELEPHONE SERVICES FOR CONNECTION BY THE SERVING UTILITY, IN STRICT <br />COMPLIANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND OF THE SERVING UTILITY INVOLVED. <br />LANDLORD SHALL PROVIDE ALL MATERIALS AND EQUIPMENT REQUIRED FOR COMPLETE UTILITY CONNECTION BUT <br />NOT FURNISHED BY THE SERVING UTILITY. LANDLORD SHALL PAY ALL CHARGES OF THE SERVING UTILITY FOR THE <br />ELECTRICAL SERVICE(S). <br />16B 2 -3 GROUNDING <br />PERMANENTLY AND EFFECTIVELY GROUND AND BOND THE ELECTRICAL INSTALLATION IN A THOROUGH AND <br />EFFICIENT MANNER, AND IN CONFORMANCE, AT A MINIMUM, WITH NFPA 70, OR THESE DOCUMENTS, WHERE THEY <br />EXCEED CODE REQUIREMENTS. USE BARE OR INSULATED CONDUCTORS, AS SPECIFIED HEREIN, AND OTHER <br />MATERIALS INDICATED ON THE DRAWINGS. <br />16B PART 3 DISTRIBUTION AND CONTROL EQUIPMENT <br />16B 3 -1 LIGHT AND APPLIANCE PANELBOARDS <br />PANELBOARDS: SQUARE D TYPE NQOD (FOR 240/208V SERVICE) OR NF (FOR 480V SERVICE) OR APPROVED EQUAL BY <br />SIEMENS, CUTLER HAMMER, OR GENERAL ELECTRIC, AS SCHEDULED ON THE DRAWINGS; COMPLETE WITH BOLT-ON <br />THERMAL MAGNETIC, MOLDED CASE CIRCUIT BREAKERS ASSEMBLED IN A DEAD-FRONT FINISHED CABINET <br />CONTAINING A TYPEWRITTEN CARD DIRECTORY INDICATION EXACTLY WHAT EACH CIRCUIT BREAKER CONTROLS; <br />FULLY-RATED AND WITH THE INTEGRATED SHORT CIRCUIT CURRENT RATINGS INDICATED ON THE DRAWINGS. PLUG- <br />IN TYPE BREAKERS WILL NOT BE ACCEPTABLE. ALL TWO AND THREE POLE BREAKER: COMMON TRIP TYPE. <br />BREAKERS USED AS SWITCHES FOR 120V OR 277V LIGHTING CIRCUITS: APPROVED FOR THE PURPOSE AND MARKED <br />"SWD". BREAKERS USED FOR THE PROTECTION OF HVAC AND REFRIGERATION EQUIPMENT: HACR TYPE. <br />16B 3 -2 CIRCUIT BREAKERS IN EXISTING PANELBOARDS <br />PROVIDE NEW CIRCUIT BREAKERS, FOR INSTALLATION IN EXISTING PANELBOARDS, OF THE SAME MANUFACTURER, <br />TYPE AND SHORT CIRCUIT CURRENT INTERRUPTING RATINGS AS THE EXISTING PANELBOARD CIRCUIT BREAKERS. <br />16B 3 -3 DISCONNECT (SAFETY) SWITCHES <br />DISCONNECT (SAFETY) SWITCHES: SQUARE D, SIEMENS, CUTLER HAMMER, OR GENERAL ELECTRIC FUSED OR NON- <br />FUSED (AS INDICATED ON DRAWINGS OR REQUIRED) NEMA KS1, HEAVY DUTY, EXTERNALLY OPERATED, VISIBLE- <br />BLADE SAFETY SWITCHES; NEMA ENCLOSURE TYPE INDICATED ON THE DRAWINGS OR SUITABLE FOR THE <br />ENVIRONMENT IN WHICH INSTALLED. BASED ON FUSIBLE SWITCH AND FUSE SIZES INDICATED, INCLUDE CLASS R, J, <br />OR L FUSE PROVISIONS AS APPLICABLE. <br />PROVIDE SWITCHES WHERE NOT FURNISHED WITH THE STARTING EQUIPMENT, AT ALL OTHER POINTS REQUIRED BY <br />NFPA 70, AND WHERE INDICATED ON THE DRAWINGS. <br />16B 3 -4 FUSES <br />PROVIDE EACH CIRCUIT AND SET OF FUSE CLIPS THROUGHOUT THE WORK WITH BUSSMANN, FERRAZ SHAWMUT, OR <br />LITTLEFUSE FUSES, SIZES AND TYPES AS REQUIRED OR INDICATED. ALL FUSES LARGER THAN 600A: UL CLASS L, <br />SIMILAR TO TYPE KRP-C BUSSMANN LOW PEAK OR EQUAL. FUSES USED TO PROTECT MOTORS: UL CLASS RK5, <br />BUSSMANN FUSETRON OR EQUAL, FUSES USED TO PROTECT ALL OTHER ELECTRICAL EQUIPMENT: UL CLASS RK1, <br />DUAL ELEMENT, BUSSMANN LPS/LPN OR EQUAL. ALL FUSED DEVICES SHALL BE LABELED AS TO TYPE AND SIZE OF <br />FUSE REQUIRED. <br />FURNISH THREE SPARE FUSES OF EACH SIZE AND TYPE USED ON THE PROJECT (EXCEPT FOR MAIN SWITCH FUSES, <br />FURNISH ON SPARE), NEATLY CONTAINED IN A PROPERLY LABELED CABINET. <br />16B 3 -5 DRY -TYPE TRANSFORMERS <br />TRANSFORMERS: GENERAL PURPOSE, UL-LISTED/LABELED 150 DEGREES C TEMPERATURE RISE ABOVE 40 DEGREES <br />C AMBIENT. INSULATING MATERIALS: EXCEED NEMA ST-020 STANDARDS, RATED FOR 220 DEGREES C, UL- <br />COMPONENT RECOGNIZED INSULATION SYSTEM. PHASES, VOLTAGES, AND SIZES: AS INDICATED ON THE DRAWINGS. <br />SOUND LEVEL: NOT EXCEEDING NEMA STANDARDS FOR THE SIZES INDICATED. FULL-CAPACITY PRIMARY TAPS: <br />BELOW 25 KVA -MINIMUM OF TWO 5 PERCENT (2-); 25 KVA TO 300 KVA -MINIMUM OF SIX 2.5 PERCENT (2+, 4 -); ABOVE <br />300 KVA -FOUR 2.5 PERCENT (2+, 2-). TRANSFORMER CORE AND COIL ASSEMBLIES: MOUNTED ON INTEGRAL <br />VIBRATION -ABSORBING PADS. MAKE FINAL CONDUIT CONNECTIONS TO TRANSFORMERS WITH FLEXIBLE CONDUIT, <br />WITH AT LEAST 6 INCHES OF SLACK IN ALL DIRECTIONS. TRANSFORMER ENCLOSURES: FULLY ENCLOSED (EXCEPT <br />FOR VENTILATION OPENINGS), NEMA 2, DRIP-PROOF, FABRICATED OF HEAVY GAUGE SHEET STEEL CONSTRUCTION. <br />PROVIDE ENERGY-EFFICIENT TRANSFORMERS COMPLYING WITH NEMA TP-1, WHEN TESTED IN ACCORDANCE WITH <br />NEMA TP-2. <br />MANUFACTURERS: SQUARE D, GENERAL ELECTRIC, ACME, SIEMENS <br />16B PART 4 LIGHT FIXTURES, LAMPS AND BALLASTS <br />16B 4 -1 LIGHT FIXTURE LOCATIONS <br />LIGHT FIXTURES SHOWN ON THE ELECTRICAL DRAWINGS REPRESENT GENERAL ARRANGEMENTS ONLY. REFER TO <br />ARCHITECTURAL DRAWINGS FOR MORE EXACT LOCATIONS. COORDINATE LOCATION WITH ALL OTHER TRADES <br />BEFORE INSTALLATION TO AVOID CONFLICTS. COORDINATE LIGHT FIXTURE LOCATIONS IN MECHANICAL ROOMS WITH <br />FINAL INSTALLED PIPING AND DUCTWORK LAYOUTS. <br />16B 4 -2 LIGHT FIXTURES <br />VERIZON SHALL PROVIDE LIGHT FIXTURES, INCLUDING ALL LAMPS AND ANY SPECIFIED ACCESSORIES. ELECTRICAL <br />CONTRACTOR SHALL PROVIDE ALL MATERIAL AND LABOR TO SECURELY HANG, CLEAN, AND MAKE LIGHT FIXTURES <br />COMPLETELY READY FOR USE, AND TO PROVIDE: ALL HANGERS, SUPPORTS, AND MISCELLANEOUS HARDWARE <br />REQUIRED TO INSTALL LIGHT FIXTURES; PROPER TRIM TO FIT EACH CEILING CONDITION ACTUALLY ENCOUNTERED; <br />ADDITIONAL TIE WIRES CONNECTED TO STRUCTURE TO CONFORM TO SEISMIC REQUIREMENTS WHERE REQUIRED BY <br />THE APPLICABLE BUILDING CODE. <br />THROUGH WIRING OF RECESSED LIGHT FIXTURES, IN SUSPENDED CEILINGS, IS NOT PERMITTED. CONNECT EACH <br />LIGHT FIXTURE BY A WHIP TO A JUNCTION BOX. THE WHIP SHALL BE OF SUFFICIENT LENGTH TO ALLOW THE LIGHT <br />FIXTURE TO BE RELOCATED WITHIN A 6-FOOT RADIUS. <br />16B 4 -3 LAMPS <br />VERIZON SHALL PROVIDE LAMPS PER LIGHT FIXTURE SCHEDULE. <br />16B 4 -4 BALLASTS <br />VERIZON SHALL PROVIDE BALLASTS PER LIGHT FIXTURE SCHEDULE. <br />16B PART 5 MISCELLANEOUS ELECTRICAL <br />16B 5 -1 WIRING OF MECHANICAL EQUIPMENT <br />PROVIDE ALL RACEWAYS AND POWER WIRING FOR ALL DIVISION 15 EQUIPMENT REQUIRING ELECTRICAL <br />CONNECTIONS, INCLUDING, BUT NOT LIMITED TO, PUMPS, WATER HEATERS, AND HVAC EQUIPMENT, AND ALL LINE- <br />VOLTAGE CONTROL AND INTERLOCK WIRING NOT PROVIDED UNDER DIVISION 15. CONNECT PER MANUFACTURERS' <br />WIRING DIAGRAMS. COORDINATE WITH DIVISION 15 FOR DISCONNECTS FURNISHED WITH EQUIPMENT, AND PROVIDE <br />ALL DISCONNECT SWITCHES AS REQUIRED. AFTER INSTALLING WIRING, VERIFY THAT EACH MOTOR LOAD HAS THE <br />CORRECT PHASE ROTATION. <br />VERIFY THE ACTUAL "MAXIMUM OVERCURRENT PROTECTION" (MDCP) DEVICE RATINGS AND "MINIMUM CIRCUIT <br />AMPACITY" (MCA) CONDUCTOR SIZING FOR MECHANICAL EQUIPMENT FROM THE EQUIPMENT NAMEPLATE. BASE <br />ELECTRICAL INSTALLATIONS ON ACTUAL REQUIRED AMPERAGES, WHICH MAY VARY SOMEWHAT FROM THE <br />CONDUCTOR AND EQUIPMENT SIZES SHOWN ON THE DRAWINGS; HOWEVER, IN IN CASE, REDUCE THE SIZE OF <br />CONDUCTORS INDICATED ON THE DRAWINGS WITHOUT AUTHORIZATION FROM THE ENGINEER. PROVIDE PROPERLY <br />SIZED ELECTRICAL WIRING AND EQUIPMENT WITHOUT EXTRA COST TO THE OWNER. NOTIFY THE ENGINEER OF ALL <br />CHANGES REQUIRED IN THE ELECTRICAL INSTALLATION DUE TO EQUIPMENT VARIANCES SO THAT THE EFFECTS ON <br />FEEDERS, BRANCH CIRCUITS, PANELBOADS, FUSES AND CIRCUIT BREAKERS CAN BY CHECKED PRIOR TO <br />PURCHASING AND INSTALLATION. BE RESPONSIBLE FOR COORDINATING WITH DIVISION 15 TO VERIFY THE ACTUAL <br />AMPACITIES AND CORRECT SIZES OF ALL CONDUCTORS AND OVERCURRENT PROTECTIVE DEVICES FOR ALL <br />EQUIPMENT, AND CORRECT OVERLOAD HEATERS FOR ALL MOTORS, WHEN STARTERS ARE PROVIDED UNDER <br />DIVISION 16. <br />16B 5 -2 WIRING OF THERMOSTATS, TIME AND TEMPERATURE CONTROLS <br />PROVIDE ALL RACEWAYS, DEVICE BOXES, POWER WIRING, AND LINE-VOLTAGE CONTROL AND INTERLOCK WIRING NOT <br />PROVIDED UNDER DIVISION 15, FOR ALL THERMOSTATS, TEMPERATURE CONTROL DEVICES, AND CONTROLS, <br />INCLUDING, BUT NOT LIMITED TO, NIGHT-STATS, WATER HEATER INTERLOCKS, TIME SWITCHES AND OVERRIDE <br />TIMERS. SEE MECHANICAL DRAWINGS FOR LOCATIONS AND TEMPERATURE CONTROL DIAGRAMS. LOW-VOLTAGE <br />CONDUCTORS FOR THERMOSTATS AND TEMPERATURE CONTROL SYSTEM MA BE RUN EXPOSED ABOVE FINISHED <br />ACCESSIBLE CEILINGS, IF APPROVED AND LISTED FOR THIS PURPOSE, BUT SHALL BE INSTALLED CONDUIT WITHIN <br />WALLS AND WHERE EXPOSED IN THE WORK AREAS. <br />16B 5 -3 TELEPHONE SYSTEM PROVISIONS <br />PROVIDE INCOMING TELEPHONE SERVICE RACEWAYS AS INDICATED O DRAWINGS OR AS REQUIRED BY THE SERVING <br />TELEPHONE COMPANY. PROVIDE 3/4-INCH THICK PLYWOOD BOARD, FIRE-RETARDANT-TREATED AND STAMPED FRT, <br />SECURELY ANCHORED TO THE WALL, AT THE LOCATION AND OF THE SIZE AS INDICATED ON THE DRAWINGS. <br />PROVIDE FLUSH MOUNTED TELEPHONE OUTLET BOXES WITH 3/4-INCH EMT STUB-UP CONCEALED TO ACCESSIBLE <br />CEILING SPACE AT LOCATIONS AS INDICATED ON THE DRAWINGS. <br />16B 5 -4 DATA SYSTEM PROVISIONS <br />PROVIDE FLUSH MOUNTED DATA OUTLET BOXES WITH 3/4-INCH CONDUIT STUB-UP CONCEALED TO ACCESSIBLE <br />CEILING SPACE AT LOCATIONS AS INDICATED ON THE DRAWINGS. <br />16B 5 -5 PHOTOCELLS <br />PHOTOCELLS AND REQUIRED CABLING TO BE INSTALLED BY ELECTRICIAN. EMS PHOTOCELL TO BE PROVIDED BY EMS <br />CONTRACTOR. <br />TYPE: <br />1. ELECTRONIC DIGITAL. <br />16B 5 -6 LIGHTING CONTACTORS <br />1. LIGHTING CONTACTORS: ELECTRICAL CONTRACTOR SHALL CONFIGURE CONTACTORS TO BE NORMALLY CLOSED: <br />INDUSTRIAL DUTY TYPE: SILVER ALLOY, DOUBLE BREAK CONTACTS, CAPABLE OF ADDING POLES IN THE FIELD; <br />NUMBER AND RATING OF POLES AS INDICATED ON THE DRAWINGS OR REQUIRED BY THE LOAD CONTROLLED; <br />TYPED DIRECTORY AFFIXED TO THE INSIDE OF THE ENCLOSURE DOOR LISTING ALL BRANCH CIRCUITS SWITCHED <br />AND THE CONTROL POWER BRANCH CIRCUIT. <br />2. SHORT CIRCUIT CURRENT RATING: 22,000A AT 240V MAXIMUM <br />3. ENCLOSURES: NEMA 1, OR AS INDICATED ON THE DRAWINGS <br />4. COIL VOLTAGE: 120V AC <br />5. CONTACTORS PROVIDED BY EMS CONTRACTOR AND INSTALLED BY ELECTRICIAN. <br />ELECTRICALLY-HELD TYPE: <br />CONTROL INTERFACE -ELECTRICAL CONTRACTOR SHALL CONFIGURE CONTACTORS TO BE NORMALLY CLOSED: TWO- <br />WIRE <br />MANUFACTURERS: <br />A. SQUARE D CLASS 8903 L <br />B. CUTLER HAMMER EQUIVALENT <br />C. GENERAL ELECTRIC EQUIVALENT <br />D. SIEMENS EQUIVALENT <br />E. ASCO EQUIVALENT <br />16B 5 -7 SIGNALING SYSTEM <br />THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY WITH THE LANDLORD AND THE LOCAL MUNICIPALITY <br />WHETHER OR NOT A FIRE ALARM SIGNALING SYSTEM IS REQUIRED FOR THE TENANT LEASE SPACE. IF REQUIRED, <br />THE GC SHALL RETAIN THE SERVICES OF A LICENSED FIRE ALARM SYSTEM CONTRACTOR TO DESIGN AND INSTALL <br />THE SIGNALING SYSTEM. THE FIRE ALARM SYSTEM CONTRACTOR SHALL PRODUCE ALL REQUIRED DRAWINGS, <br />SUBMIT TO THE LOCAL AUTHORITY TO OBTAIN PERMITS, AND PERFORM THE WORK. <br />PROVIDE A COMPLETE AND FUNCTIONING 24V SIGNALING SYSTEM FOR LOADING DOOR SIGNALS, AND OTHERS AS <br />INDICATED ON THE DRAWINGS. LOW-VOLTAGE CONDUCTORS FOR SIGNALING SYSTEM MAY BE RUN EXPOSED ABOVE <br />FINISHED CEILINGS, BUT SHALL BE INSTALLED IN CONDUIT WITHIN WALLS AND WHERE EXPOSED IN THE WORK <br />AREAS. <br />SIGNAL BELL UNITS SHALL BE ATW SECURITY PC-300 FOR 24V OPERATION , INSTALLED ON A STANDARD SWITCH BOX <br />WITH BLANK PLATE. TRANSFORMER SHALL BE EDWARDS NO. 872, HAVING CAPACITY OF 25W AT 24V. EXTERIOR <br />PUSH BUTTON SHALL BE EDWARDS NO. 1786-C WITH SOLID BRASS CAP. <br />16B 5 -8 MISCELLANEOUS EQUIPMENT AND CONNECTIONS <br />ALL WIRING AND CONNECTIONS TO ILLUMINATED CASES. <br />ALL WIRING AND CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS, INCLUDING, BUT NOT LIMITED TO P.O.S. <br />STATIONS., ETC. <br />ALL RACEWAYS, DEVICE BOXES, AND ALL WIRING AND CONNECTIONS OF DEVICES TO ENERGY MANAGEMENT SYSTEM <br />THAT ARE NOT THE RESPONSIBILITY OF DIVISION 15. <br />ALL WIRING AND CONNECTIONS OF EXIT DOOR ALARMS. <br />16B 5 -9 EXISTING FIRE ALARM SYSTEM MODIFICATIONS <br />PROVIDE THE FOLLOWING NEW EQUIPMENT, COMPATIBLE WITH, OR OF THE SAME MANUFACTURER AS, THE EXISTING <br />FIRE ALARM CONTROL PANEL AND SYSTEM, AS REQUIRED BY BUILDING CODES, THE LANDLORD, OR BOTH, AND <br />CONNECT TO THE EXISTING FIRE ALARM CONTROL PANEL: <br />1. ADDITIONAL INITIATING DEVICES, INDICATING APPLIANCES, AND INTERCONNECTING CIRCUITS. <br />2. ADDITIONAL ZONE MODULES REQUIRED BY NEW ZONING. <br />3. NEW AMPLIFIERS AND OTHER EQUIPMENT THAT MAY BE REQUIRED TO INCORPORATE THE NEW INITIATING <br />DEVICES AND INDICATING APPLIANCES INTO THE EXISTING SYSTEM. <br />4. A NEW ZONE MAP, INCLUDING ALL EXISTING ZONES AND ALL NEW ZONES, FRAMED, MOUNTED UNDER GLASS, AND <br />INSTALLED ADJACENT TO THE FIRE ALARM CONTROL PANEL. HORN/STROBES SHALL MEET ALL REQUIREMENTS <br />OF THE AMERICANS WITH DISABILITIES ACT. <br />16B 5 -10 DUCT SMOKE DETECTION <br />ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL SMOKE DETECTORS. REFER TO MECHANICAL DRAWINGS <br />AND COORDINATE WITH MECHANICAL CONTRACTOR. <br />17 COMMISSIONING <br />GENERAL CONTRACTOR TO COORDINATE WITH VERIZON FOR MEP COMMISSIONING AND FORWARD ALL <br />FUNCTIONALITY AND COMMISSIONING FORMS TO REQUIRED SUB-CONTRACTORS.COMMISSIONING WILL BE <br />COMPLETED ON ALL PROJECTS NOT JUST LEED PROJECTS.CONTRACTORS TO REFER TO VZW BID PACKAGE FOR <br />FORMS AND TESTING REQUIREMENTS.ALL CONTRACTORS TO REFER TO THE DOCUMENT TITLED COMMISSIONING <br />TESTING SCHEDULE WITHIN THE BID PACKAGE.THIS FILE WILL OUTLINE THE REQUIRED SCHEDULE AND THE <br />MATERIALS/EQUIPMENT THE SUB-CONTRACTOR WILL BE RESPONSIBLE TO BRING TO COMPLETE THE TESTING.VZW <br />WILL ESTABLISH A DATE FOR THIS TESTING.THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS MUST <br />CONFIRM THAT THEY WILL BE AVAILABLE ON SITE FOR THE COMMISSIONING. <br />TYPE MC CABLE MAY ONLY BE USED: <br />1. IN LIEU OF FLEXIBLE CONDUIT AND WIRING FROM LIGHT FIXTURES IN ACCESSIBLE CEILINGS TO JUNCTION BOXES <br />(ATTACHED TO BUILDING STRUCTURE) ABOVE THE CEILING. PROVIDE CABLE WHIPS OF SUFFICIENT LENGTHS TO <br />ALLOW FOR RELOCATION EACH LIGHT FIXTURE WITHIN A 5-FOOT RADIUS OF ITS INSTALLED LOCATION, BUT NOT <br />EXCEEDING 6 FEET IN UNSUPPORTED LENGTHS. <br />PROPERLY IDENTIFY ALL TERMINAL BLOCKS & WIRE TERMINALS FOR CONTROL WIRING W/ VINYL STICK-ON MARKERS <br />OR EQUIVALENT. PROVIDE ARCHITECT W/ A LIST OF PROPOSED IDENTIFYING NUMBERS FOR REVIEW PRIOR TO <br />INSTALLATION. <br />PROVIDE AN EQUIPMENT-GROUNDING CONDUCTOR, OR BONDING JUMPER, AS APPLICABLE, IN ALL BRANCH CIRCUITS <br />& FEEDER, SIZED IN ACCORDANCE W/ NFPA 70 TABLES 250.66 OR 250.122, AS APPLICABLE, UNLESS INDICATED AS <br />LARGER ON DRAWINGS. <br />VOLTAGE DROP IN BRANCH CIRCUITS SHALL NOT EXCEED 3 PERCENT. <br />VOLTAGE DROP AT FEEDER CONDUCTOR SHALL NOT EXCEED 2 PERCENT. <br />16B 1 -6 JUNCTION BOXES, PULL BOXES, CABINETS AND WIREWAYS <br />PROVIDE JUNCTION BOXES, PULL BOXES, CABINETS AND WIREWAYS WHEREVER NECESSARY FOR PROPER <br />INSTALLATION OF VARIOUS ELECTRICAL SYSTEMS ACCORDING TO NFPA 70 AND WHERE INDICATED ON THE <br />DRAWINGS. SIZE AS REQUIRED FOR THE SPECIFIC FUNCTION OR AS REQUIRED BY NFPA 70, WHICHEVER IS LARGER. <br />CONSTRUCTION SHALL BE OF A NEMA DESIGN SUITABLE FOR THE ENVIRONMENT INSTALLED. <br />JUNCTION BOXES INSTALLED BEHIND WALL CASES, AND IN OR ON OTHER STORE FIXTURES, EXCEPT WHERE <br />OTHERWISE SPECIFIED, SHALL BE 4-INCH SQUARE OR LARGER, WITH GALVANIZED COVERS. <br />16B 1 -7 OUTLET BOXES <br />ALL OUTLETS INCLUDING LIGHT FIXTURE, SWITCH, RECEPTACLE, AND SIMILAR OUTLETS: NATIONAL ELECTRICAL, <br />APPLETON, STEEL CITY, RACO, OR APPROVED EQUAL, GALVANIZED STEEL KNOCKOUT BOXES, SUITABLE IN DESIGN <br />TO THE PURPOSE THEY SERVE AND THEY SPACE THEY OCCUPY. SIZE AS REQUIRED FOR THE SPECIFIC FUNCTION <br />OR AS REQUIRED BY NRPA 70, WHICHEVER IS LARGER. SEE ALL OUTLET BOXES IN WALLS, COLUMNS, FLOORS, OR <br />CEILINGS SO THEY ARE FLUSH WITH THE FINISHED SURFACE, ACCURATELY SET, AND RIGIDLY SECURED IN POSITION. <br />PROVIDE PLASTER RINGS, EXTENSION RINGS AND/OR MASONRY RINGS AS REQUIRED FOR FLUSH MOUNTING. <br />PROVIDE APPROVED CAST OUTLET BOXES, WITH HUBS AND WEATHERPROOF COVERS, IN ALL AREAS SUBJECT TO <br />CAMP, WET, OR HARSH CONDITIONS. <br />16B 1 -8 OUTLET LOCATIONS <br />COORDINATE LOCATIONS OF OUTLET BOXES. OUTLETS ARE ONLY APPROXIMATELY LOCATED ON THE SMALL SCALE <br />DRAWINGS. USE GREAT CARE IN THE ACTUAL LOCATION BY CONSULTING THE VARIOUS LARGE SCALE DETAILED <br />DRAWINGS USED BY OTHER DIVISION TRADES, AND BY SECURING DEFINITE LOCATIONS FROM THE ARCHITECT. <br />16B 1 -9 MOUNTING HEIGHTS <br />UNLESS NOTED OTHERWISE, INSTALL WIRING DEVICES AS INDICATED BELOW (NOTE: ALL DIMENSIONS ARE TO THE <br />CENTER OF THE OUTLET BOX UNLESS NOTED OTHERWISE): <br />RECEPTACLES <br />GENERAL: (ALL RECEPTACLES ARE TO BE MOUNTED VERTICALLY U.N.O. -WHEN MOUNTED ADJACENT TO ANOTHER <br />DEVICE THE ORIENTATION SHALL MATCH) <br />A. VERTICALLY WITH THE E GROUND SLOT MOUNTED AT THE TOP: 16 INCHES ABOVE FINISHED FLOOR. <br />B. HORIZONTALLY WITH NEUTRAL SLOT MOUNTED AT THE TOP: 16 INCHES ABOVE FINISHED FLOOR. <br />ABOVE COUNTERS: <br />A. FOR 36-INCH HIGH COUNTER TOPS: 44 INCHES ABOVE FINISHED FLOOR, VERTICALLY. <br />B. FOR 34-INCH HIGH COUNTER TOPS: 44 INCHES ABOVE FINISHED FLOOR, VERTICALLY. <br />MECHANICAL & ELECTRICAL EQUIPMENT ROOMS & JANITORS CLOSETS: <br />A. 44 INCHES ABOVE FINISHED FLOOR, VERTICALLY <br />GFCI RECEPTACLES: <br />A. SAME AS GENERAL RECEPTACLES. <br />ISOLATED GROUND RECEPTACLES: <br />A. SAME AS GENERAL RECEPTACLES. <br />CONCRETE BLOCK WALLS: <br />A. DIMENSIONS ABOVE MAY BE ADJUSTED SLIGHTLY, AS REQUIRED TO COMPENSATE FOR VARIABLE JOINT <br />DIMENSIONS, SUCH THAT BOTTOM OR TOP OF BOXES, AS APPLICABLE, ARE AT BLOCK JOINTS. <br />SWITCHES: <br />GENERAL: <br />A. 44 INCHES ABOVE FINISHED FLOOR. <br />ABOVE COUNTERS: <br />A. SAME AS FOR RECEPTACLES <br />CONCRETE BLOCK WALLS: <br />A. 42 INCHES ABOVE FINISHED FLOOR (DIMENSIONS MAY BE ADJUSTED SLIGHTLY, AS REQUIRED TO <br />COMPENSATE FOR VARIABLE JOINT DIMENSIONS, SUCH THAT BOTTOM OR TOPE OF BOXES ARE AT BLOCK <br />JOINTS. <br />WALLS WITH WAINSCOTING: <br />A. 44 INCHES ABOVE FINISHED FLOOR. <br />TELEPHONE/DATA OUTLET BOXES: <br />GENERAL: <br />A. MATCH MOUNTING HEIGHT OF ADJACENT WIRING DEVICE LISTED ABOVE. <br />WALL-MOUNTED TELEPHONE: <br />A. 52 INCHES ABOVE FINISHED FLOOR. <br />16B 1 -10 WIRING DEVICES <br />PROVIDE THE FOLLOWING WIRING DEVICES WHERE SHOWN ON DRAWINGS OR REQ'D. MINOR CHANGES RELATIVE TO <br />THE LOCATION OF ELECTRICAL EQUIPMENT MAY BE MADE TO COMPLY W/ STRUCTURAL/BUILDING CONDITIONS AS <br />DETERMINED IN THE COURSE OF CONSTRUCTION. PROVIDE ALL WIRING DEVICES OF THE SAME MANUFACTURER DO <br />NOT MIX ON THE PROJECT, TO THE MAXIMUM EXTENT POSSIBLE. COORDINATE COLOR OF TOGGLES AND <br />RECEPTACLES WITH ARCHITECT. <br />Type of Device Hubbell Pass&Seymour Leviton Cooper Wiring Devices <br />Simplex Receptacle HBL5361 5361 5891 5351 <br />Duplex Receptacle CR5352 5352 5352 5352 <br />GFCI Receptacle GF5352 2091 6898/6598 XGF20 <br />Safety Receptacle HBL8300SG TR63 8300-SC TR 8300 <br />(20A / 125V) <br />Isolated Ground (IG)IG5362 IG6300 8300-IG IG5362 <br />Receptacle <br />Quad/4-Plex HBL420 420 21254 N/A <br />Single Pole Switch CS1221 PS 20 AC1 1221-2 2221 <br />Double Pole Switch CS1222 PS 20AC2 1222-2 2222 <br />Three-way Switch CS1223 PS 20AC3 1223-2 2223 <br />Four-way Switch CS1224 PS 20AC4 1224-2 2224 <br />SP3W, Incandescent <br />Momentary SPDT,HBL1557 1251 1257 1995 <br />Center-Off Switch <br />16B 1 -11 SWITCH AND OUTLET COVER PLATES <br />SWITCH AND OUTLET PLATES: COLORED, SMOOTH NYLON; BY THE SAME MANUFACTURER AS THE WIRING DEVICES, <br />WHEREVER POSSIBLE. VERIFY DESIRED MATERIALS AND COLORS WITH ENGINEER BEFORE INSTALLATION. SWITCH <br />PLATES IN UNFINISHED ROOMS AND SPACES: STAMPED STEEL, CADMIUM PLATED. INSTALL GROUPS OF SWITCHES <br />UNDER ONE GANGED-PLATE, USUALLY VERTICALLY; OR, WHERE REQUIRED BY DETAILS, HORIZONTALLY. SET ALL <br />COVER PLATES PLUMB, PARALLEL, AND FINISHED FLUSH WITH THE WALL. <br />16B 1 -12 WEATHERPROOF COVER PLATES <br />PROVIDE GFCI RECEPTACLES FOR DESIGNATED WEATHERPROOF RECEPTACLES, UNLESS INDICATED OTHERWISE ON <br />THE DRAWINGS. <br />FOR WET LOCATIONS: IN-USE NEMA 3R, UL-LABELED PLATES MOLDED FROM A CLEAR HIGH IMPACT ULTRAVIOLET <br />STABILIZED POLYCARBONATE MATERIAL FOR EASY VERIFICATION THAT CORDS ARE PLUGGED IN AND THAT THE GFCI <br />IS FUNCTIONING. <br />COVER PLATES: BY THE SAME MANUFACTURER AS THE WIRING DEVICES; COMPLYING WITH NFPA 70 406.8 (B) <br />REQUIREMENTS FOR UNATTENDED USE. <br />DIVISION 16 (CONTINUED) <br />Mechanical and Electrical Engineers <br />Lilker Associates <br />1001 Avenue of the Americas <br />New York, NY 10018 <br />tel 212.695.1000 <br />fax 212.695.1299 <br />www.lilker.com <br />Kenneth A. Gruskin AIA <br />No. Date Description <br />Consultant: <br />Checked By: <br />Drawn By: <br />Job Address: <br />Drawing Title: <br />Revision Issue: <br />Professional Seal: <br />Drawing Number: <br />2024 Gruskin Architecture + Design, P.C.c <br />This document and the ideas and designs incorporated <br />herein, as an instrument of professional service, is the <br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C., <br />and is not to be used in whole or in part for any other <br />project without the written authorization of GRUSKIN <br />ARCHITECTURE + DESIGN, P.C. <br />North <br />Arrow: <br />Job Name and Number: <br />Date Issued For <br />All Rights Reserved <br />Client: <br />Landlord: <br />Permit: <br />Bid: <br />Construction: <br />0006261 <br />AR91629 <br />5421 <br />9613 <br />39209 <br />10635 <br />2537 <br />11016 <br />5734 <br />ARC 2596 <br />4674 <br />2666 <br />AI 09999 <br />2796 <br />0401 011223 <br />2572 <br />17680 <br />RA-015432-B <br />025528-1 NY <br />TX <br />VA <br />VT <br />MA <br />MT <br />RI <br />PA <br />NY <br />NJ <br />NH <br />MD <br />LA <br />ME <br />KS <br />FL <br />DE <br />CT <br />AZ <br />AL <br />C-1967WY <br />RA011075GA <br />AR10400066IN <br />C-29898CA <br />NM 004168 <br />ARC-400347CO <br />HI AR 11489 <br />PR 19965 <br />OR 4899 <br />SC 6834 <br />NC 9961 <br />13761OH <br />05713IA <br />WV 3727 <br />IL 001-019152 <br />UT 5881358-0301 <br />ID AR-984459 <br />1301052379MI <br />ARC100723DC <br />WI 9900-005MN44326 <br />A-3547NE <br />3811AR <br />5967KY 101374TN <br />MS 3860 <br />1666ND <br />A-2005029740MO <br />a4895OK <br />NV 5521 <br />WA 10344 <br />13167AK <br />SD 11532 <br />C: <br />\ <br />R <br />e <br />v <br />i <br />t <br /> <br />L <br />o <br />c <br />a <br />l <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />2 <br />4 <br />0 <br />0 <br />1 <br />3 <br />0 <br />8 <br />_ <br />V <br />E <br />R <br />I <br />Z <br />O <br />N <br />_ <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />_ <br />C <br />A <br />_ <br />EL <br />E <br />C <br />T <br />R <br />I <br />C <br />A <br />L <br />_ <br />v <br />2 <br />3 <br />_ <br />D <br />B <br />e <br />l <br />l <br />B <br />R <br />N <br />E <br />Z <br />. <br />r <br />v <br />t <br />2023-0069 <br />Proposed <br />Store Design <br />for: VERIZON <br />Metro Pointe <br />3500 South Bristol Street <br />Suite 100 <br />Santa Ana, CA 92704 <br />3/15/24 <br />3/15/24 <br />ELECTRICAL <br />SPECIFICATIONS (2 OF 2) <br />E.0.3 <br />DB <br />MH <br />48 OF 81 <br />3500 S Bristol St Unit# 100 - <br />101119098, 20182666 & <br />401390437/11/2024