16B PART 2 ELECTRICAL SERVICE AND GROUNDING
<br />16B 2 -1 ELECTRICAL SERVICE
<br />SEE DRAWINGS FOR TYPE, SIZE, VOLTAGE, PHASE, AND OTHER REQUIREMENTS.
<br />16B 2 -2 CONNECTION TO SERVING UTILITIES
<br />LANDLORD SHALL PROVIDE RACEWAYS, TERMINATIONS, METERING PROVISIONS, AND MISCELLANEOUS EQUIPMENT
<br />REQUIRED FOR ELECTRICAL AND TELEPHONE SERVICES FOR CONNECTION BY THE SERVING UTILITY, IN STRICT
<br />COMPLIANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND OF THE SERVING UTILITY INVOLVED.
<br />LANDLORD SHALL PROVIDE ALL MATERIALS AND EQUIPMENT REQUIRED FOR COMPLETE UTILITY CONNECTION BUT
<br />NOT FURNISHED BY THE SERVING UTILITY. LANDLORD SHALL PAY ALL CHARGES OF THE SERVING UTILITY FOR THE
<br />ELECTRICAL SERVICE(S).
<br />16B 2 -3 GROUNDING
<br />PERMANENTLY AND EFFECTIVELY GROUND AND BOND THE ELECTRICAL INSTALLATION IN A THOROUGH AND
<br />EFFICIENT MANNER, AND IN CONFORMANCE, AT A MINIMUM, WITH NFPA 70, OR THESE DOCUMENTS, WHERE THEY
<br />EXCEED CODE REQUIREMENTS. USE BARE OR INSULATED CONDUCTORS, AS SPECIFIED HEREIN, AND OTHER
<br />MATERIALS INDICATED ON THE DRAWINGS.
<br />16B PART 3 DISTRIBUTION AND CONTROL EQUIPMENT
<br />16B 3 -1 LIGHT AND APPLIANCE PANELBOARDS
<br />PANELBOARDS: SQUARE D TYPE NQOD (FOR 240/208V SERVICE) OR NF (FOR 480V SERVICE) OR APPROVED EQUAL BY
<br />SIEMENS, CUTLER HAMMER, OR GENERAL ELECTRIC, AS SCHEDULED ON THE DRAWINGS; COMPLETE WITH BOLT-ON
<br />THERMAL MAGNETIC, MOLDED CASE CIRCUIT BREAKERS ASSEMBLED IN A DEAD-FRONT FINISHED CABINET
<br />CONTAINING A TYPEWRITTEN CARD DIRECTORY INDICATION EXACTLY WHAT EACH CIRCUIT BREAKER CONTROLS;
<br />FULLY-RATED AND WITH THE INTEGRATED SHORT CIRCUIT CURRENT RATINGS INDICATED ON THE DRAWINGS. PLUG-
<br />IN TYPE BREAKERS WILL NOT BE ACCEPTABLE. ALL TWO AND THREE POLE BREAKER: COMMON TRIP TYPE.
<br />BREAKERS USED AS SWITCHES FOR 120V OR 277V LIGHTING CIRCUITS: APPROVED FOR THE PURPOSE AND MARKED
<br />"SWD". BREAKERS USED FOR THE PROTECTION OF HVAC AND REFRIGERATION EQUIPMENT: HACR TYPE.
<br />16B 3 -2 CIRCUIT BREAKERS IN EXISTING PANELBOARDS
<br />PROVIDE NEW CIRCUIT BREAKERS, FOR INSTALLATION IN EXISTING PANELBOARDS, OF THE SAME MANUFACTURER,
<br />TYPE AND SHORT CIRCUIT CURRENT INTERRUPTING RATINGS AS THE EXISTING PANELBOARD CIRCUIT BREAKERS.
<br />16B 3 -3 DISCONNECT (SAFETY) SWITCHES
<br />DISCONNECT (SAFETY) SWITCHES: SQUARE D, SIEMENS, CUTLER HAMMER, OR GENERAL ELECTRIC FUSED OR NON-
<br />FUSED (AS INDICATED ON DRAWINGS OR REQUIRED) NEMA KS1, HEAVY DUTY, EXTERNALLY OPERATED, VISIBLE-
<br />BLADE SAFETY SWITCHES; NEMA ENCLOSURE TYPE INDICATED ON THE DRAWINGS OR SUITABLE FOR THE
<br />ENVIRONMENT IN WHICH INSTALLED. BASED ON FUSIBLE SWITCH AND FUSE SIZES INDICATED, INCLUDE CLASS R, J,
<br />OR L FUSE PROVISIONS AS APPLICABLE.
<br />PROVIDE SWITCHES WHERE NOT FURNISHED WITH THE STARTING EQUIPMENT, AT ALL OTHER POINTS REQUIRED BY
<br />NFPA 70, AND WHERE INDICATED ON THE DRAWINGS.
<br />16B 3 -4 FUSES
<br />PROVIDE EACH CIRCUIT AND SET OF FUSE CLIPS THROUGHOUT THE WORK WITH BUSSMANN, FERRAZ SHAWMUT, OR
<br />LITTLEFUSE FUSES, SIZES AND TYPES AS REQUIRED OR INDICATED. ALL FUSES LARGER THAN 600A: UL CLASS L,
<br />SIMILAR TO TYPE KRP-C BUSSMANN LOW PEAK OR EQUAL. FUSES USED TO PROTECT MOTORS: UL CLASS RK5,
<br />BUSSMANN FUSETRON OR EQUAL, FUSES USED TO PROTECT ALL OTHER ELECTRICAL EQUIPMENT: UL CLASS RK1,
<br />DUAL ELEMENT, BUSSMANN LPS/LPN OR EQUAL. ALL FUSED DEVICES SHALL BE LABELED AS TO TYPE AND SIZE OF
<br />FUSE REQUIRED.
<br />FURNISH THREE SPARE FUSES OF EACH SIZE AND TYPE USED ON THE PROJECT (EXCEPT FOR MAIN SWITCH FUSES,
<br />FURNISH ON SPARE), NEATLY CONTAINED IN A PROPERLY LABELED CABINET.
<br />16B 3 -5 DRY -TYPE TRANSFORMERS
<br />TRANSFORMERS: GENERAL PURPOSE, UL-LISTED/LABELED 150 DEGREES C TEMPERATURE RISE ABOVE 40 DEGREES
<br />C AMBIENT. INSULATING MATERIALS: EXCEED NEMA ST-020 STANDARDS, RATED FOR 220 DEGREES C, UL-
<br />COMPONENT RECOGNIZED INSULATION SYSTEM. PHASES, VOLTAGES, AND SIZES: AS INDICATED ON THE DRAWINGS.
<br />SOUND LEVEL: NOT EXCEEDING NEMA STANDARDS FOR THE SIZES INDICATED. FULL-CAPACITY PRIMARY TAPS:
<br />BELOW 25 KVA -MINIMUM OF TWO 5 PERCENT (2-); 25 KVA TO 300 KVA -MINIMUM OF SIX 2.5 PERCENT (2+, 4 -); ABOVE
<br />300 KVA -FOUR 2.5 PERCENT (2+, 2-). TRANSFORMER CORE AND COIL ASSEMBLIES: MOUNTED ON INTEGRAL
<br />VIBRATION -ABSORBING PADS. MAKE FINAL CONDUIT CONNECTIONS TO TRANSFORMERS WITH FLEXIBLE CONDUIT,
<br />WITH AT LEAST 6 INCHES OF SLACK IN ALL DIRECTIONS. TRANSFORMER ENCLOSURES: FULLY ENCLOSED (EXCEPT
<br />FOR VENTILATION OPENINGS), NEMA 2, DRIP-PROOF, FABRICATED OF HEAVY GAUGE SHEET STEEL CONSTRUCTION.
<br />PROVIDE ENERGY-EFFICIENT TRANSFORMERS COMPLYING WITH NEMA TP-1, WHEN TESTED IN ACCORDANCE WITH
<br />NEMA TP-2.
<br />MANUFACTURERS: SQUARE D, GENERAL ELECTRIC, ACME, SIEMENS
<br />16B PART 4 LIGHT FIXTURES, LAMPS AND BALLASTS
<br />16B 4 -1 LIGHT FIXTURE LOCATIONS
<br />LIGHT FIXTURES SHOWN ON THE ELECTRICAL DRAWINGS REPRESENT GENERAL ARRANGEMENTS ONLY. REFER TO
<br />ARCHITECTURAL DRAWINGS FOR MORE EXACT LOCATIONS. COORDINATE LOCATION WITH ALL OTHER TRADES
<br />BEFORE INSTALLATION TO AVOID CONFLICTS. COORDINATE LIGHT FIXTURE LOCATIONS IN MECHANICAL ROOMS WITH
<br />FINAL INSTALLED PIPING AND DUCTWORK LAYOUTS.
<br />16B 4 -2 LIGHT FIXTURES
<br />VERIZON SHALL PROVIDE LIGHT FIXTURES, INCLUDING ALL LAMPS AND ANY SPECIFIED ACCESSORIES. ELECTRICAL
<br />CONTRACTOR SHALL PROVIDE ALL MATERIAL AND LABOR TO SECURELY HANG, CLEAN, AND MAKE LIGHT FIXTURES
<br />COMPLETELY READY FOR USE, AND TO PROVIDE: ALL HANGERS, SUPPORTS, AND MISCELLANEOUS HARDWARE
<br />REQUIRED TO INSTALL LIGHT FIXTURES; PROPER TRIM TO FIT EACH CEILING CONDITION ACTUALLY ENCOUNTERED;
<br />ADDITIONAL TIE WIRES CONNECTED TO STRUCTURE TO CONFORM TO SEISMIC REQUIREMENTS WHERE REQUIRED BY
<br />THE APPLICABLE BUILDING CODE.
<br />THROUGH WIRING OF RECESSED LIGHT FIXTURES, IN SUSPENDED CEILINGS, IS NOT PERMITTED. CONNECT EACH
<br />LIGHT FIXTURE BY A WHIP TO A JUNCTION BOX. THE WHIP SHALL BE OF SUFFICIENT LENGTH TO ALLOW THE LIGHT
<br />FIXTURE TO BE RELOCATED WITHIN A 6-FOOT RADIUS.
<br />16B 4 -3 LAMPS
<br />VERIZON SHALL PROVIDE LAMPS PER LIGHT FIXTURE SCHEDULE.
<br />16B 4 -4 BALLASTS
<br />VERIZON SHALL PROVIDE BALLASTS PER LIGHT FIXTURE SCHEDULE.
<br />16B PART 5 MISCELLANEOUS ELECTRICAL
<br />16B 5 -1 WIRING OF MECHANICAL EQUIPMENT
<br />PROVIDE ALL RACEWAYS AND POWER WIRING FOR ALL DIVISION 15 EQUIPMENT REQUIRING ELECTRICAL
<br />CONNECTIONS, INCLUDING, BUT NOT LIMITED TO, PUMPS, WATER HEATERS, AND HVAC EQUIPMENT, AND ALL LINE-
<br />VOLTAGE CONTROL AND INTERLOCK WIRING NOT PROVIDED UNDER DIVISION 15. CONNECT PER MANUFACTURERS'
<br />WIRING DIAGRAMS. COORDINATE WITH DIVISION 15 FOR DISCONNECTS FURNISHED WITH EQUIPMENT, AND PROVIDE
<br />ALL DISCONNECT SWITCHES AS REQUIRED. AFTER INSTALLING WIRING, VERIFY THAT EACH MOTOR LOAD HAS THE
<br />CORRECT PHASE ROTATION.
<br />VERIFY THE ACTUAL "MAXIMUM OVERCURRENT PROTECTION" (MDCP) DEVICE RATINGS AND "MINIMUM CIRCUIT
<br />AMPACITY" (MCA) CONDUCTOR SIZING FOR MECHANICAL EQUIPMENT FROM THE EQUIPMENT NAMEPLATE. BASE
<br />ELECTRICAL INSTALLATIONS ON ACTUAL REQUIRED AMPERAGES, WHICH MAY VARY SOMEWHAT FROM THE
<br />CONDUCTOR AND EQUIPMENT SIZES SHOWN ON THE DRAWINGS; HOWEVER, IN IN CASE, REDUCE THE SIZE OF
<br />CONDUCTORS INDICATED ON THE DRAWINGS WITHOUT AUTHORIZATION FROM THE ENGINEER. PROVIDE PROPERLY
<br />SIZED ELECTRICAL WIRING AND EQUIPMENT WITHOUT EXTRA COST TO THE OWNER. NOTIFY THE ENGINEER OF ALL
<br />CHANGES REQUIRED IN THE ELECTRICAL INSTALLATION DUE TO EQUIPMENT VARIANCES SO THAT THE EFFECTS ON
<br />FEEDERS, BRANCH CIRCUITS, PANELBOADS, FUSES AND CIRCUIT BREAKERS CAN BY CHECKED PRIOR TO
<br />PURCHASING AND INSTALLATION. BE RESPONSIBLE FOR COORDINATING WITH DIVISION 15 TO VERIFY THE ACTUAL
<br />AMPACITIES AND CORRECT SIZES OF ALL CONDUCTORS AND OVERCURRENT PROTECTIVE DEVICES FOR ALL
<br />EQUIPMENT, AND CORRECT OVERLOAD HEATERS FOR ALL MOTORS, WHEN STARTERS ARE PROVIDED UNDER
<br />DIVISION 16.
<br />16B 5 -2 WIRING OF THERMOSTATS, TIME AND TEMPERATURE CONTROLS
<br />PROVIDE ALL RACEWAYS, DEVICE BOXES, POWER WIRING, AND LINE-VOLTAGE CONTROL AND INTERLOCK WIRING NOT
<br />PROVIDED UNDER DIVISION 15, FOR ALL THERMOSTATS, TEMPERATURE CONTROL DEVICES, AND CONTROLS,
<br />INCLUDING, BUT NOT LIMITED TO, NIGHT-STATS, WATER HEATER INTERLOCKS, TIME SWITCHES AND OVERRIDE
<br />TIMERS. SEE MECHANICAL DRAWINGS FOR LOCATIONS AND TEMPERATURE CONTROL DIAGRAMS. LOW-VOLTAGE
<br />CONDUCTORS FOR THERMOSTATS AND TEMPERATURE CONTROL SYSTEM MA BE RUN EXPOSED ABOVE FINISHED
<br />ACCESSIBLE CEILINGS, IF APPROVED AND LISTED FOR THIS PURPOSE, BUT SHALL BE INSTALLED CONDUIT WITHIN
<br />WALLS AND WHERE EXPOSED IN THE WORK AREAS.
<br />16B 5 -3 TELEPHONE SYSTEM PROVISIONS
<br />PROVIDE INCOMING TELEPHONE SERVICE RACEWAYS AS INDICATED O DRAWINGS OR AS REQUIRED BY THE SERVING
<br />TELEPHONE COMPANY. PROVIDE 3/4-INCH THICK PLYWOOD BOARD, FIRE-RETARDANT-TREATED AND STAMPED FRT,
<br />SECURELY ANCHORED TO THE WALL, AT THE LOCATION AND OF THE SIZE AS INDICATED ON THE DRAWINGS.
<br />PROVIDE FLUSH MOUNTED TELEPHONE OUTLET BOXES WITH 3/4-INCH EMT STUB-UP CONCEALED TO ACCESSIBLE
<br />CEILING SPACE AT LOCATIONS AS INDICATED ON THE DRAWINGS.
<br />16B 5 -4 DATA SYSTEM PROVISIONS
<br />PROVIDE FLUSH MOUNTED DATA OUTLET BOXES WITH 3/4-INCH CONDUIT STUB-UP CONCEALED TO ACCESSIBLE
<br />CEILING SPACE AT LOCATIONS AS INDICATED ON THE DRAWINGS.
<br />16B 5 -5 PHOTOCELLS
<br />PHOTOCELLS AND REQUIRED CABLING TO BE INSTALLED BY ELECTRICIAN. EMS PHOTOCELL TO BE PROVIDED BY EMS
<br />CONTRACTOR.
<br />TYPE:
<br />1. ELECTRONIC DIGITAL.
<br />16B 5 -6 LIGHTING CONTACTORS
<br />1. LIGHTING CONTACTORS: ELECTRICAL CONTRACTOR SHALL CONFIGURE CONTACTORS TO BE NORMALLY CLOSED:
<br />INDUSTRIAL DUTY TYPE: SILVER ALLOY, DOUBLE BREAK CONTACTS, CAPABLE OF ADDING POLES IN THE FIELD;
<br />NUMBER AND RATING OF POLES AS INDICATED ON THE DRAWINGS OR REQUIRED BY THE LOAD CONTROLLED;
<br />TYPED DIRECTORY AFFIXED TO THE INSIDE OF THE ENCLOSURE DOOR LISTING ALL BRANCH CIRCUITS SWITCHED
<br />AND THE CONTROL POWER BRANCH CIRCUIT.
<br />2. SHORT CIRCUIT CURRENT RATING: 22,000A AT 240V MAXIMUM
<br />3. ENCLOSURES: NEMA 1, OR AS INDICATED ON THE DRAWINGS
<br />4. COIL VOLTAGE: 120V AC
<br />5. CONTACTORS PROVIDED BY EMS CONTRACTOR AND INSTALLED BY ELECTRICIAN.
<br />ELECTRICALLY-HELD TYPE:
<br />CONTROL INTERFACE -ELECTRICAL CONTRACTOR SHALL CONFIGURE CONTACTORS TO BE NORMALLY CLOSED: TWO-
<br />WIRE
<br />MANUFACTURERS:
<br />A. SQUARE D CLASS 8903 L
<br />B. CUTLER HAMMER EQUIVALENT
<br />C. GENERAL ELECTRIC EQUIVALENT
<br />D. SIEMENS EQUIVALENT
<br />E. ASCO EQUIVALENT
<br />16B 5 -7 SIGNALING SYSTEM
<br />THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY WITH THE LANDLORD AND THE LOCAL MUNICIPALITY
<br />WHETHER OR NOT A FIRE ALARM SIGNALING SYSTEM IS REQUIRED FOR THE TENANT LEASE SPACE. IF REQUIRED,
<br />THE GC SHALL RETAIN THE SERVICES OF A LICENSED FIRE ALARM SYSTEM CONTRACTOR TO DESIGN AND INSTALL
<br />THE SIGNALING SYSTEM. THE FIRE ALARM SYSTEM CONTRACTOR SHALL PRODUCE ALL REQUIRED DRAWINGS,
<br />SUBMIT TO THE LOCAL AUTHORITY TO OBTAIN PERMITS, AND PERFORM THE WORK.
<br />PROVIDE A COMPLETE AND FUNCTIONING 24V SIGNALING SYSTEM FOR LOADING DOOR SIGNALS, AND OTHERS AS
<br />INDICATED ON THE DRAWINGS. LOW-VOLTAGE CONDUCTORS FOR SIGNALING SYSTEM MAY BE RUN EXPOSED ABOVE
<br />FINISHED CEILINGS, BUT SHALL BE INSTALLED IN CONDUIT WITHIN WALLS AND WHERE EXPOSED IN THE WORK
<br />AREAS.
<br />SIGNAL BELL UNITS SHALL BE ATW SECURITY PC-300 FOR 24V OPERATION , INSTALLED ON A STANDARD SWITCH BOX
<br />WITH BLANK PLATE. TRANSFORMER SHALL BE EDWARDS NO. 872, HAVING CAPACITY OF 25W AT 24V. EXTERIOR
<br />PUSH BUTTON SHALL BE EDWARDS NO. 1786-C WITH SOLID BRASS CAP.
<br />16B 5 -8 MISCELLANEOUS EQUIPMENT AND CONNECTIONS
<br />ALL WIRING AND CONNECTIONS TO ILLUMINATED CASES.
<br />ALL WIRING AND CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS, INCLUDING, BUT NOT LIMITED TO P.O.S.
<br />STATIONS., ETC.
<br />ALL RACEWAYS, DEVICE BOXES, AND ALL WIRING AND CONNECTIONS OF DEVICES TO ENERGY MANAGEMENT SYSTEM
<br />THAT ARE NOT THE RESPONSIBILITY OF DIVISION 15.
<br />ALL WIRING AND CONNECTIONS OF EXIT DOOR ALARMS.
<br />16B 5 -9 EXISTING FIRE ALARM SYSTEM MODIFICATIONS
<br />PROVIDE THE FOLLOWING NEW EQUIPMENT, COMPATIBLE WITH, OR OF THE SAME MANUFACTURER AS, THE EXISTING
<br />FIRE ALARM CONTROL PANEL AND SYSTEM, AS REQUIRED BY BUILDING CODES, THE LANDLORD, OR BOTH, AND
<br />CONNECT TO THE EXISTING FIRE ALARM CONTROL PANEL:
<br />1. ADDITIONAL INITIATING DEVICES, INDICATING APPLIANCES, AND INTERCONNECTING CIRCUITS.
<br />2. ADDITIONAL ZONE MODULES REQUIRED BY NEW ZONING.
<br />3. NEW AMPLIFIERS AND OTHER EQUIPMENT THAT MAY BE REQUIRED TO INCORPORATE THE NEW INITIATING
<br />DEVICES AND INDICATING APPLIANCES INTO THE EXISTING SYSTEM.
<br />4. A NEW ZONE MAP, INCLUDING ALL EXISTING ZONES AND ALL NEW ZONES, FRAMED, MOUNTED UNDER GLASS, AND
<br />INSTALLED ADJACENT TO THE FIRE ALARM CONTROL PANEL. HORN/STROBES SHALL MEET ALL REQUIREMENTS
<br />OF THE AMERICANS WITH DISABILITIES ACT.
<br />16B 5 -10 DUCT SMOKE DETECTION
<br />ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL SMOKE DETECTORS. REFER TO MECHANICAL DRAWINGS
<br />AND COORDINATE WITH MECHANICAL CONTRACTOR.
<br />17 COMMISSIONING
<br />GENERAL CONTRACTOR TO COORDINATE WITH VERIZON FOR MEP COMMISSIONING AND FORWARD ALL
<br />FUNCTIONALITY AND COMMISSIONING FORMS TO REQUIRED SUB-CONTRACTORS.COMMISSIONING WILL BE
<br />COMPLETED ON ALL PROJECTS NOT JUST LEED PROJECTS.CONTRACTORS TO REFER TO VZW BID PACKAGE FOR
<br />FORMS AND TESTING REQUIREMENTS.ALL CONTRACTORS TO REFER TO THE DOCUMENT TITLED COMMISSIONING
<br />TESTING SCHEDULE WITHIN THE BID PACKAGE.THIS FILE WILL OUTLINE THE REQUIRED SCHEDULE AND THE
<br />MATERIALS/EQUIPMENT THE SUB-CONTRACTOR WILL BE RESPONSIBLE TO BRING TO COMPLETE THE TESTING.VZW
<br />WILL ESTABLISH A DATE FOR THIS TESTING.THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS MUST
<br />CONFIRM THAT THEY WILL BE AVAILABLE ON SITE FOR THE COMMISSIONING.
<br />TYPE MC CABLE MAY ONLY BE USED:
<br />1. IN LIEU OF FLEXIBLE CONDUIT AND WIRING FROM LIGHT FIXTURES IN ACCESSIBLE CEILINGS TO JUNCTION BOXES
<br />(ATTACHED TO BUILDING STRUCTURE) ABOVE THE CEILING. PROVIDE CABLE WHIPS OF SUFFICIENT LENGTHS TO
<br />ALLOW FOR RELOCATION EACH LIGHT FIXTURE WITHIN A 5-FOOT RADIUS OF ITS INSTALLED LOCATION, BUT NOT
<br />EXCEEDING 6 FEET IN UNSUPPORTED LENGTHS.
<br />PROPERLY IDENTIFY ALL TERMINAL BLOCKS & WIRE TERMINALS FOR CONTROL WIRING W/ VINYL STICK-ON MARKERS
<br />OR EQUIVALENT. PROVIDE ARCHITECT W/ A LIST OF PROPOSED IDENTIFYING NUMBERS FOR REVIEW PRIOR TO
<br />INSTALLATION.
<br />PROVIDE AN EQUIPMENT-GROUNDING CONDUCTOR, OR BONDING JUMPER, AS APPLICABLE, IN ALL BRANCH CIRCUITS
<br />& FEEDER, SIZED IN ACCORDANCE W/ NFPA 70 TABLES 250.66 OR 250.122, AS APPLICABLE, UNLESS INDICATED AS
<br />LARGER ON DRAWINGS.
<br />VOLTAGE DROP IN BRANCH CIRCUITS SHALL NOT EXCEED 3 PERCENT.
<br />VOLTAGE DROP AT FEEDER CONDUCTOR SHALL NOT EXCEED 2 PERCENT.
<br />16B 1 -6 JUNCTION BOXES, PULL BOXES, CABINETS AND WIREWAYS
<br />PROVIDE JUNCTION BOXES, PULL BOXES, CABINETS AND WIREWAYS WHEREVER NECESSARY FOR PROPER
<br />INSTALLATION OF VARIOUS ELECTRICAL SYSTEMS ACCORDING TO NFPA 70 AND WHERE INDICATED ON THE
<br />DRAWINGS. SIZE AS REQUIRED FOR THE SPECIFIC FUNCTION OR AS REQUIRED BY NFPA 70, WHICHEVER IS LARGER.
<br />CONSTRUCTION SHALL BE OF A NEMA DESIGN SUITABLE FOR THE ENVIRONMENT INSTALLED.
<br />JUNCTION BOXES INSTALLED BEHIND WALL CASES, AND IN OR ON OTHER STORE FIXTURES, EXCEPT WHERE
<br />OTHERWISE SPECIFIED, SHALL BE 4-INCH SQUARE OR LARGER, WITH GALVANIZED COVERS.
<br />16B 1 -7 OUTLET BOXES
<br />ALL OUTLETS INCLUDING LIGHT FIXTURE, SWITCH, RECEPTACLE, AND SIMILAR OUTLETS: NATIONAL ELECTRICAL,
<br />APPLETON, STEEL CITY, RACO, OR APPROVED EQUAL, GALVANIZED STEEL KNOCKOUT BOXES, SUITABLE IN DESIGN
<br />TO THE PURPOSE THEY SERVE AND THEY SPACE THEY OCCUPY. SIZE AS REQUIRED FOR THE SPECIFIC FUNCTION
<br />OR AS REQUIRED BY NRPA 70, WHICHEVER IS LARGER. SEE ALL OUTLET BOXES IN WALLS, COLUMNS, FLOORS, OR
<br />CEILINGS SO THEY ARE FLUSH WITH THE FINISHED SURFACE, ACCURATELY SET, AND RIGIDLY SECURED IN POSITION.
<br />PROVIDE PLASTER RINGS, EXTENSION RINGS AND/OR MASONRY RINGS AS REQUIRED FOR FLUSH MOUNTING.
<br />PROVIDE APPROVED CAST OUTLET BOXES, WITH HUBS AND WEATHERPROOF COVERS, IN ALL AREAS SUBJECT TO
<br />CAMP, WET, OR HARSH CONDITIONS.
<br />16B 1 -8 OUTLET LOCATIONS
<br />COORDINATE LOCATIONS OF OUTLET BOXES. OUTLETS ARE ONLY APPROXIMATELY LOCATED ON THE SMALL SCALE
<br />DRAWINGS. USE GREAT CARE IN THE ACTUAL LOCATION BY CONSULTING THE VARIOUS LARGE SCALE DETAILED
<br />DRAWINGS USED BY OTHER DIVISION TRADES, AND BY SECURING DEFINITE LOCATIONS FROM THE ARCHITECT.
<br />16B 1 -9 MOUNTING HEIGHTS
<br />UNLESS NOTED OTHERWISE, INSTALL WIRING DEVICES AS INDICATED BELOW (NOTE: ALL DIMENSIONS ARE TO THE
<br />CENTER OF THE OUTLET BOX UNLESS NOTED OTHERWISE):
<br />RECEPTACLES
<br />GENERAL: (ALL RECEPTACLES ARE TO BE MOUNTED VERTICALLY U.N.O. -WHEN MOUNTED ADJACENT TO ANOTHER
<br />DEVICE THE ORIENTATION SHALL MATCH)
<br />A. VERTICALLY WITH THE E GROUND SLOT MOUNTED AT THE TOP: 16 INCHES ABOVE FINISHED FLOOR.
<br />B. HORIZONTALLY WITH NEUTRAL SLOT MOUNTED AT THE TOP: 16 INCHES ABOVE FINISHED FLOOR.
<br />ABOVE COUNTERS:
<br />A. FOR 36-INCH HIGH COUNTER TOPS: 44 INCHES ABOVE FINISHED FLOOR, VERTICALLY.
<br />B. FOR 34-INCH HIGH COUNTER TOPS: 44 INCHES ABOVE FINISHED FLOOR, VERTICALLY.
<br />MECHANICAL & ELECTRICAL EQUIPMENT ROOMS & JANITORS CLOSETS:
<br />A. 44 INCHES ABOVE FINISHED FLOOR, VERTICALLY
<br />GFCI RECEPTACLES:
<br />A. SAME AS GENERAL RECEPTACLES.
<br />ISOLATED GROUND RECEPTACLES:
<br />A. SAME AS GENERAL RECEPTACLES.
<br />CONCRETE BLOCK WALLS:
<br />A. DIMENSIONS ABOVE MAY BE ADJUSTED SLIGHTLY, AS REQUIRED TO COMPENSATE FOR VARIABLE JOINT
<br />DIMENSIONS, SUCH THAT BOTTOM OR TOP OF BOXES, AS APPLICABLE, ARE AT BLOCK JOINTS.
<br />SWITCHES:
<br />GENERAL:
<br />A. 44 INCHES ABOVE FINISHED FLOOR.
<br />ABOVE COUNTERS:
<br />A. SAME AS FOR RECEPTACLES
<br />CONCRETE BLOCK WALLS:
<br />A. 42 INCHES ABOVE FINISHED FLOOR (DIMENSIONS MAY BE ADJUSTED SLIGHTLY, AS REQUIRED TO
<br />COMPENSATE FOR VARIABLE JOINT DIMENSIONS, SUCH THAT BOTTOM OR TOPE OF BOXES ARE AT BLOCK
<br />JOINTS.
<br />WALLS WITH WAINSCOTING:
<br />A. 44 INCHES ABOVE FINISHED FLOOR.
<br />TELEPHONE/DATA OUTLET BOXES:
<br />GENERAL:
<br />A. MATCH MOUNTING HEIGHT OF ADJACENT WIRING DEVICE LISTED ABOVE.
<br />WALL-MOUNTED TELEPHONE:
<br />A. 52 INCHES ABOVE FINISHED FLOOR.
<br />16B 1 -10 WIRING DEVICES
<br />PROVIDE THE FOLLOWING WIRING DEVICES WHERE SHOWN ON DRAWINGS OR REQ'D. MINOR CHANGES RELATIVE TO
<br />THE LOCATION OF ELECTRICAL EQUIPMENT MAY BE MADE TO COMPLY W/ STRUCTURAL/BUILDING CONDITIONS AS
<br />DETERMINED IN THE COURSE OF CONSTRUCTION. PROVIDE ALL WIRING DEVICES OF THE SAME MANUFACTURER DO
<br />NOT MIX ON THE PROJECT, TO THE MAXIMUM EXTENT POSSIBLE. COORDINATE COLOR OF TOGGLES AND
<br />RECEPTACLES WITH ARCHITECT.
<br />Type of Device Hubbell Pass&Seymour Leviton Cooper Wiring Devices
<br />Simplex Receptacle HBL5361 5361 5891 5351
<br />Duplex Receptacle CR5352 5352 5352 5352
<br />GFCI Receptacle GF5352 2091 6898/6598 XGF20
<br />Safety Receptacle HBL8300SG TR63 8300-SC TR 8300
<br />(20A / 125V)
<br />Isolated Ground (IG)IG5362 IG6300 8300-IG IG5362
<br />Receptacle
<br />Quad/4-Plex HBL420 420 21254 N/A
<br />Single Pole Switch CS1221 PS 20 AC1 1221-2 2221
<br />Double Pole Switch CS1222 PS 20AC2 1222-2 2222
<br />Three-way Switch CS1223 PS 20AC3 1223-2 2223
<br />Four-way Switch CS1224 PS 20AC4 1224-2 2224
<br />SP3W, Incandescent
<br />Momentary SPDT,HBL1557 1251 1257 1995
<br />Center-Off Switch
<br />16B 1 -11 SWITCH AND OUTLET COVER PLATES
<br />SWITCH AND OUTLET PLATES: COLORED, SMOOTH NYLON; BY THE SAME MANUFACTURER AS THE WIRING DEVICES,
<br />WHEREVER POSSIBLE. VERIFY DESIRED MATERIALS AND COLORS WITH ENGINEER BEFORE INSTALLATION. SWITCH
<br />PLATES IN UNFINISHED ROOMS AND SPACES: STAMPED STEEL, CADMIUM PLATED. INSTALL GROUPS OF SWITCHES
<br />UNDER ONE GANGED-PLATE, USUALLY VERTICALLY; OR, WHERE REQUIRED BY DETAILS, HORIZONTALLY. SET ALL
<br />COVER PLATES PLUMB, PARALLEL, AND FINISHED FLUSH WITH THE WALL.
<br />16B 1 -12 WEATHERPROOF COVER PLATES
<br />PROVIDE GFCI RECEPTACLES FOR DESIGNATED WEATHERPROOF RECEPTACLES, UNLESS INDICATED OTHERWISE ON
<br />THE DRAWINGS.
<br />FOR WET LOCATIONS: IN-USE NEMA 3R, UL-LABELED PLATES MOLDED FROM A CLEAR HIGH IMPACT ULTRAVIOLET
<br />STABILIZED POLYCARBONATE MATERIAL FOR EASY VERIFICATION THAT CORDS ARE PLUGGED IN AND THAT THE GFCI
<br />IS FUNCTIONING.
<br />COVER PLATES: BY THE SAME MANUFACTURER AS THE WIRING DEVICES; COMPLYING WITH NFPA 70 406.8 (B)
<br />REQUIREMENTS FOR UNATTENDED USE.
<br />DIVISION 16 (CONTINUED)
<br />Mechanical and Electrical Engineers
<br />Lilker Associates
<br />1001 Avenue of the Americas
<br />New York, NY 10018
<br />tel 212.695.1000
<br />fax 212.695.1299
<br />www.lilker.com
<br />Kenneth A. Gruskin AIA
<br />No. Date Description
<br />Consultant:
<br />Checked By:
<br />Drawn By:
<br />Job Address:
<br />Drawing Title:
<br />Revision Issue:
<br />Professional Seal:
<br />Drawing Number:
<br />2024 Gruskin Architecture + Design, P.C.c
<br />This document and the ideas and designs incorporated
<br />herein, as an instrument of professional service, is the
<br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C.,
<br />and is not to be used in whole or in part for any other
<br />project without the written authorization of GRUSKIN
<br />ARCHITECTURE + DESIGN, P.C.
<br />North
<br />Arrow:
<br />Job Name and Number:
<br />Date Issued For
<br />All Rights Reserved
<br />Client:
<br />Landlord:
<br />Permit:
<br />Bid:
<br />Construction:
<br />0006261
<br />AR91629
<br />5421
<br />9613
<br />39209
<br />10635
<br />2537
<br />11016
<br />5734
<br />ARC 2596
<br />4674
<br />2666
<br />AI 09999
<br />2796
<br />0401 011223
<br />2572
<br />17680
<br />RA-015432-B
<br />025528-1 NY
<br />TX
<br />VA
<br />VT
<br />MA
<br />MT
<br />RI
<br />PA
<br />NY
<br />NJ
<br />NH
<br />MD
<br />LA
<br />ME
<br />KS
<br />FL
<br />DE
<br />CT
<br />AZ
<br />AL
<br />C-1967WY
<br />RA011075GA
<br />AR10400066IN
<br />C-29898CA
<br />NM 004168
<br />ARC-400347CO
<br />HI AR 11489
<br />PR 19965
<br />OR 4899
<br />SC 6834
<br />NC 9961
<br />13761OH
<br />05713IA
<br />WV 3727
<br />IL 001-019152
<br />UT 5881358-0301
<br />ID AR-984459
<br />1301052379MI
<br />ARC100723DC
<br />WI 9900-005MN44326
<br />A-3547NE
<br />3811AR
<br />5967KY 101374TN
<br />MS 3860
<br />1666ND
<br />A-2005029740MO
<br />a4895OK
<br />NV 5521
<br />WA 10344
<br />13167AK
<br />SD 11532
<br />C:
<br />\
<br />R
<br />e
<br />v
<br />i
<br />t
<br />
<br />L
<br />o
<br />c
<br />a
<br />l
<br />
<br />F
<br />i
<br />l
<br />e
<br />s
<br />\
<br />2
<br />4
<br />0
<br />0
<br />1
<br />3
<br />0
<br />8
<br />_
<br />V
<br />E
<br />R
<br />I
<br />Z
<br />O
<br />N
<br />_
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />_
<br />C
<br />A
<br />_
<br />EL
<br />E
<br />C
<br />T
<br />R
<br />I
<br />C
<br />A
<br />L
<br />_
<br />v
<br />2
<br />3
<br />_
<br />D
<br />B
<br />e
<br />l
<br />l
<br />B
<br />R
<br />N
<br />E
<br />Z
<br />.
<br />r
<br />v
<br />t
<br />2023-0069
<br />Proposed
<br />Store Design
<br />for: VERIZON
<br />Metro Pointe
<br />3500 South Bristol Street
<br />Suite 100
<br />Santa Ana, CA 92704
<br />3/15/24
<br />3/15/24
<br />ELECTRICAL
<br />SPECIFICATIONS (2 OF 2)
<br />E.0.3
<br />DB
<br />MH
<br />48 OF 81
<br />3500 S Bristol St Unit# 100 -
<br />101119098, 20182666 &
<br />401390437/11/2024
|