LENGTH (FT) <br />< 13' <br />14' - 20' <br />21' -26' <br />TELECOMMUNICATIONS BONDING <br />CONDUCTOR (TBC) SCHEDULE <br />27' -33' <br />34' -41' <br />42' -52' <br />53' -66' <br />> 66' <br />WIRE SIZE (AWG) <br />#6 <br />#4 <br />#3 <br />#2 <br />#1 <br />#1/0 <br />#2/0 <br />#3/0 <br />1. EXISTING 1200A, 208/120V, 3-PHASE ELECTRICAL SERVICE TO BUILDING IS TO BE MAINTAINED. <br />2. EXISTING UTILITY METER FOR EXISTING ELECTRICAL SERVICE SERVING THE BUILDING -THERE IS ONE <br />UTILITY METER FOR THE ENTIRE BUILDING. <br />3. EXISTING TENANT SERVICE DISCONNECT FUSED AT 100A TO BE MAINTAINED. MODIFY AND EXTEND <br />EXISTING FEEDER FROM DISCONNECT TO NEW TENANT PANELBOARD 'A'. COORDINATE WORK WITH <br />LANDLORD. <br />4. EXISTING TENANT SERVICE DISCONNECT FUSED AT 200A TO BE MAINTAINED. MODIFY AND EXTEND <br />EXISTING FEEDER FROM DISCONNECT TO NEW TENANT PANELBOARD 'A'. COORDINATE WORK WITH <br />LANDLORD. <br />5. EXISTING FEEDER TO BE RE-ROUTED TO NEW TENANT PANEL 'B'. MODIFY EXISTING CONDUCTORS AS <br />REQUIRED. CONTRACTOR SHALL MATCH EXISTING COPPER 4#3/0 + 1#6G IN 2-1/2" CONDUIT -FIELD <br />VERIFY. ANY EXISTING OR NEW JUNCTION BOXES SHALL BE ACCESSIBLE. COORDINATE WORK WITH <br />BUILDING LANDLORD. <br />6. PROVIDE 100A MCB, 208/120V, 3PH, 4W, 48-POLE PANELBOARD 'A' FOR VERIZON TENANT FITOUT. REFER <br />TO PANEL SCHEDULES FOR MORE INFORMATION. <br />7. PROVIDE 200A MCB, 208/120V, 3PH, 4W, 48-POLE PANELBOARD 'A' FOR VERIZON TENANT FITOUT. REFER <br />TO PANEL SCHEDULES FOR MORE INFORMATION. <br />8. PROVIDE EMON DMON SUB-METER 2000 CLASS CONFIGURED FOR 3-PHASE, 4-WIRE, 100A. BASIS OF <br />DESIGN MODEL NO.: E20-480100-J-D-KIT. <br />9. PROVIDE EMON DMON SUB-METER 2000 CLASS CONFIGURED FOR 3-PHASE, 4-WIRE, 200A. BASIS OF <br />DESIGN MODEL NO.: E20-480200-J-D-KIT. <br />10. EXISTING FEEDER TO BE RE-ROUTED TO NEW TENANT PANEL 'A'. MODIFY EXISTING CONDUCTORS AS <br />REQUIRED. CONTRACTOR SHALL MATCH EXISTING COPPER 4#2 + 1#8G IN 1-1/2" CONDUIT -FIELD <br />VERIFY. ANY EXISTING OR NEW JUNCTION BOXES SHALL BE ACCESSIBLE. COORDINATE WORK WITH <br />BUILDING LANDLORD. <br />11. EXISTING EQUIPMENT SHOWN FOR REFERENCE ONLY. EXISTING EQUIPMENT IS NOT IN SCOPE AND <br />SHALL BE MAINTAINED. <br />12. EXISTING FEEDER SHOWN FOR REFERENCE ONLY EXISTING FEEDER IS NOT IN SCOPE AND SHALL BE <br />MAINTAINED. <br />KEY NOTES # <br />GENERAL NOTES <br />1. COORDINATE ELECTRICAL TIE-IN WORK SCOPE AND RESPONSIBILITIES WITH LOCAL UTILITY, BUILDING LANDLORD <br />AND THEIR CONTRACTOR. <br />2. CONFIRM AVAILABLE FAULT CURRENT WITH BUILDING LANDLORD. <br />3. EXISTING CONDITIONS ARE SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING <br />FIELD CONDITIONS. <br />4. CIRCUIT NUMBERS SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL FIELD COORDINATE WITH EXISTING <br />BRANCH CIRCUIT NUMBERS. <br />TELCO 108 <br />1 <br />PANEL 'A' <br />100A MCB <br />208/120V <br />3PH, 4W <br />VERIZON STORE <br />ELECTRICAL CLOSET1ST FLOOR <br />10 <br />6 <br />PANEL 'B' <br />200 MCB <br />208/120V <br />3PH, 4W <br />M <br />2 <br />4 <br />3 <br />7 <br />M <br />8 <br />M <br />9 <br />(E) MAIN SERVICE SWBD FUSED AT <br />1000A, 208/120V, 3PH, 4W <br />5 <br />2ND FLOOR <br />(E)PANEL <br />'CL' <br />175A MCB <br />208/120V <br />3PH, 4W <br />(E)PANEL <br />'CR' <br />100A MCB <br />208/120V <br />3PH, 4W <br />ROOF <br />AREA NOT IN <br />CONTRACT <br />(E)ELEVATOR MACHINE ROOM <br />AREA NOT IN CONTRACT <br />AREA NOT IN CONTRACT <br />AREA NOT IN CONTRACT <br />(E)60AF/50AT/3P <br />(E)15HP ELEVATOR <br />DISCONNECT <br />(E)GUTTER 'A1' FOR ROOFTOP EQUIPMENT (E)GUTTER 'A1' FOR ROOFTOP EQUIPMENT <br />11 <br />11 <br />11 11 <br />1111 <br />12 <br />1212 <br />1212 <br />Mechanical and Electrical Engineers <br />Lilker Associates <br />1001 Avenue of the Americas <br />New York, NY 10018 <br />tel 212.695.1000 <br />fax 212.695.1299 <br />www.lilker.com <br />Kenneth A. Gruskin AIA <br />No. Date Description <br />Consultant: <br />Checked By: <br />Drawn By: <br />Job Address: <br />Drawing Title: <br />Revision Issue: <br />Professional Seal: <br />Drawing Number: <br />2024 Gruskin Architecture + Design, P.C.c <br />This document and the ideas and designs incorporated <br />herein, as an instrument of professional service, is the <br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C., <br />and is not to be used in whole or in part for any other <br />project without the written authorization of GRUSKIN <br />ARCHITECTURE + DESIGN, P.C. <br />North <br />Arrow: <br />Job Name and Number: <br />Date Issued For <br />All Rights Reserved <br />Client: <br />Landlord: <br />Permit: <br />Bid: <br />Construction: <br />0006261 <br />AR91629 <br />5421 <br />9613 <br />39209 <br />10635 <br />2537 <br />11016 <br />5734 <br />ARC 2596 <br />4674 <br />2666 <br />AI 09999 <br />2796 <br />0401 011223 <br />2572 <br />17680 <br />RA-015432-B <br />025528-1 NY <br />TX <br />VA <br />VT <br />MA <br />MT <br />RI <br />PA <br />NY <br />NJ <br />NH <br />MD <br />LA <br />ME <br />KS <br />FL <br />DE <br />CT <br />AZ <br />AL <br />C-1967WY <br />RA011075GA <br />AR10400066IN <br />C-29898CA <br />NM 004168 <br />ARC-400347CO <br />HI AR 11489 <br />PR 19965 <br />OR 4899 <br />SC 6834 <br />NC 9961 <br />13761OH <br />05713IA <br />WV 3727 <br />IL 001-019152 <br />UT 5881358-0301 <br />ID AR-984459 <br />1301052379MI <br />ARC100723DC <br />WI 9900-005MN44326 <br />A-3547NE <br />3811AR <br />5967KY 101374TN <br />MS 3860 <br />1666ND <br />A-2005029740MO <br />a4895OK <br />NV 5521 <br />WA 10344 <br />13167AK <br />SD 11532 <br />C: <br />\ <br />R <br />e <br />v <br />i <br />t <br /> <br />L <br />o <br />c <br />a <br />l <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />2 <br />4 <br />0 <br />0 <br />1 <br />3 <br />0 <br />8 <br />_ <br />V <br />E <br />R <br />I <br />Z <br />O <br />N <br />_ <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />_ <br />C <br />A <br />_ <br />EL <br />E <br />C <br />T <br />R <br />I <br />C <br />A <br />L <br />_ <br />v <br />2 <br />3 <br />_ <br />M <br />H <br />o <br />a <br />n <br />g <br />E <br />P <br />E <br />A <br />V <br />. <br />r <br />v <br />t <br />2023-0069 <br />Proposed <br />Store Design <br />for: VERIZON <br />3500 South Bristol Street <br />Suite 100 <br />Santa Ana, CA 92704 <br />3/15/24 <br />3/15/24 <br />4/5/24 <br />POWER RISER DIAGRAM <br />& PANEL SCHEDULES <br />E.2.0 <br />DB <br />MH <br />54 OF 81 <br />1/8" = 1'-0"1 POWER RISER DIAGRAM <br />NOT TO SCALE <br />1 4/15/24 Addendum 1 : HQ Update <br />3 6/3/24 City Comments <br />3 <br />3 <br />3 <br />3 <br />3500 S Bristol St Unit# 100 - <br />101119098, 20182666 & <br />401390437/11/2024