M <br />BDD <br />GENERAL MECHANICAL NOTES <br />1. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED WITH THE EXISTING <br />CONDITIONS OF THE PROJECT. REVIEW THE GENERAL NOTES, SPECIFICATIONS AND OTHER DRAWINGS FOR <br />ADDITIONAL REQUIREMENTS WHICH MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE <br />CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT, ENGINEER AND/OR OWNER OF CONFLICTS OR DISCREPANCIES <br />PRIOR TO SUBMISSION OF BID. <br />2. EXISTING ROOFTOP UNITS, CONTROLS, PIPING, WIRING, DUCTWORK DISTRIBUTION, ETC SERVING THIS SPACE <br />SHALL BE REMOVED IN ACCORDANCE WITH ARCHITECTURAL DRAWINGS. EXISTING ROOF CURBS SHALL BE <br />REUSED AND MODIFIED WITH ROOF CURB ADAPTERS AS REQUIRED. ANY OTHER EXISTING OPENGS THRU ROOF <br />SHALL BE PATCHED AND SEALED AIR AND WATER TIGHT. ANY SYSTEMS PASSING THRU THIS SPACE SERVING <br />ADJACENT TENANTS SHALL REMAIN DURING DEMOLITION AND CONSTRUCTION PHASES. <br />3. EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND SITE VISITS AND MAY NOT REFLECT EXACT <br />"AS-BUILT" CONDITIONS. FIELD VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. COORDINATE <br />NEW WORK AND DEMOLITION WITH OTHER DISCIPLINES AND EXISTING CONDITIONS PRIOR TO CONSTRUCTION. <br />4. COORDINATE THE INSTALLATION OF THE MECHANICAL SYSTEMS WITH OTHER TRADES TO ENSURE A NEAT AND <br />ORDERLY INSTALLATION. INSTALL DUCTWORK AND PIPING AS TIGHT TO STRUCTURE AS POSSIBLE. COORDINATE <br />WITH OTHER TRADES TO AVOID CONFLICTS. COORDINATE INSTALLATION OF DUCTWORK AND PIPING TO AVOID <br />CONFLICTS WITH ELECTRICAL PANELS, LIGHTING FIXTURES, ETC. ANY MODIFICATIONS REQUIRED DUE TO LACK <br />OF COORDINATION WILL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO EXTRA COST TO THE OWNER. <br />5. WHERE SHUTDOWN OF EXISTING SYSTEMS IS REQUIRED DURING NEW WORK, COORDINATE SHUTDOWN TIME AND <br />DURATION WITH THE OWNER TO MINIMIZE DOWNTIME. NOTIFY OWNER SEVEN (7) DAYS PRIOR TO INTERRUPTION <br />OF SERVICE. <br />6. MAINTAIN A 15' MINIMUM CLEARANCE FROM OUTDOOR AIR INTAKES TO RESTROOM EXHAUST & SANITARY PIPING. <br />MAINTAIN A MINIMUM 2' CLEARANCE FROM ALL OTHER EQUIPMENT. <br />7. DURING INSTALLATION OF NEW WORK, AVOID DAMAGING EXISTING SURFACES AND EQUIPMENT TO REMAIN. <br />REPAIR DAMAGE CAUSED DURING CONSTRUCTION AT NO EXTRA COST TO THE OWNER. <br />8. CORROSION RESISTANT BIRD SCREENS WILL BE PROVIDED ON THE OUTDOOR AIR INTAKE OF ALL MECHANICAL <br />UNITS TO PREVENT BIRD NESTING & RESIST PENETRATION BY A 0.5" DIAMETER PROBE. <br />9. PROVIDE TEMPORARY BARRIERS TO CONTAIN DUST AND DEBRIS RESULTING FROM THE PERFORMANCE OF THE <br />WORK TO THE AREA WHERE WORK IS BEING PERFORMED. <br />10. ALL MECHANICAL EQUIPMENT SHOWN ON THE MECHANICAL PLANS SHALL BE PROVIDED BY THE MECHANICAL <br />CONTRACTOR UNLESS OTHERWISE NOTED. <br />11. NEW MECHANICAL EQUIPMENT, DUCTWORK AND PIPING ARE SHOWN AT APPROXIMATE LOCATIONS. FIELD <br />MEASURE FINAL DUCTWORK AND PIPING LOCATIONS PRIOR TO FABRICATION AND MAKE ADJUSTMENTS AS <br />REQUIRED TO FIT THE DUCTWORK AND PIPING WITHIN THE AVAILABLE SPACE. VERIFY THAT FINAL EQUIPMENT <br />LOCATIONS MEET MANUFACTURER'S RECOMMENDATIONS REGARDING SERVICE CLEARANCE AND PROPER <br />AIRFLOW CLEARANCE AROUND EQUIPMENT. <br />12. REFER TO ARCHITECTURAL DRAWINGS FOR RELATED CONSTRUCTION DETAILS AS APPLICABLE TO THE HVAC <br />SYSTEM. VERIFY CHASES AND PENETRATIONS SHOWN ON ARCHITECTURAL DRAWINGS THAT ARE INTENDED FOR <br />DUCTWORK AND PIPING MEET REQUIREMENTS. <br />13. INDOOR AIR QUALITY MEASURES: PROTECT INSIDE OF (INSTALLED AND DELIVERED) DUCTWORK AND HVAC UNITS <br />FROM EXPOSURE TO DUST, DIRT, PAINT AND MOISTURE. REPLACE INSULATION THAT HAS GOTTEN WET AT ANY <br />TIME DURING CONSTRUCTION, DRYING THE INSULATION IS NOT ACCEPTABLE. c SEAL ANY TEARS OR JOINTS OF <br />INTERNAL FIBERGLASS INSULATION. REMOVE DEBRIS FROM CEILING/RETURN AIR PLENUM INCLUDING DUST. AN <br />INDEPENDENT, PROFESSIONAL DUCT CLEANING COMPANY SHALL VACUUM CLEAN ANY DUCTWORK CONNECTED <br />TO HVAC UNITS THAT WERE OPERATED DURING THE CONSTRUCTION PERIOD AFTER NEW FILTERS ARE <br />INSTALLED AND PRIOR TO TURNING SYSTEM OVER TO THE OWNER. THE INTERNAL SURFACES AND ASSOCIATED <br />COILS OF ANY HVAC UNITS THAT WERE OPERATED SHALL ALSO BE CLEANED. <br />14. INSTALL DUCTWORK AND PIPING PARALLEL TO BUILDING COLUMN LINES UNLESS OTHERWISE SHOWN OR NOTED. <br />15. OVERHEAD HANGERS AND SUPPORTS FOR EQUIPMENT, DUCTWORK AND PIPING SHALL BE FASTENED TO <br />BUILDING JOISTS OR BEAMS. DO NOT ATTACH HANGERS AND SUPPORTS TO THE ABOVE FLOOR SLAB OR ROOF <br />EXCEPT WHERE CONCRETE INSERTS IN CONCRETE SLABS ARE ALLOWED BY THE SPECIFICATIONS. <br />16. COORDINATE LOCATION OF EQUIPMENT SUPPORTS WITH LOCATION OF EQUIPMENT ACCESS PANELS/DOORS TO <br />ENABLE SERVICE OF EQUIPMENT AND/OR FILTER REPLACEMENT. PROVIDE ARCHITECTURAL ACCESS PANELS FOR <br />ALL MECHANICAL EQUIPMENT LOCATED ABOVE INACCESSIBLE CEILINGS. ACCESS PANELS TO BE LOCATED TO <br />PROVIDE ADEQUATE ACCESS TO EQUIPMENT. COORDINATE LOCATION WITH ARCHITECTURAL RCP. <br />17. SEAL PENETRATIONS THROUGH THE BUILDING COMPONENTS IN ACCORDANCE WITH THE CONTRACT <br />SPECIFICATIONS. FIREPROOF PENETRATIONS THROUGH FIRE RATED COMPONENTS IN ACCORDANCE WITH U.L. <br />REQUIREMENTS. <br />18. COORDINATE THE EXACT MOUNTING SIZE AND FRAME TYPE OF DIFFUSERS, REGISTERS AND GRILLES WITH THE <br />SUPPLIER TO MEET THE CEILING, WALL AND DUCT INSTALLATION REQUIREMENTS. <br />19. ADJUST LOCATION OF CEILING DIFFUSERS, REGISTERS AND GRILLES AS REQUIRED TO ACCOMMODATE FINAL <br />CEILING GRID AND LIGHTING LOCATIONS AS COORDINATED WITH ARCHITECTURAL DRAWINGS. <br />20. LOCATE AND SET THERMOSTATS AT LOCATIONS SHOWN ON PLANS. VERIFY EXACT LOCATIONS WITH ARCHITECT <br />PRIOR TO INSTALLATION. INSTALL DEVICES WITH TOP OF DEVICE AT MAXIMUM 48" AFF TO MEET ADA <br />REQUIREMENTS UNLESS NOTED OTHERWISE ON PLANS. PROVIDE INSULATED BACKING FOR THERMOSTATS <br />MOUNTED ON EXTERIOR BUILDING WALLS. INSTALL WIRING IN CONDUIT PROVIDED BY DIVISION 26. AT A MINIMUM, <br />PROVIDE CONDUIT IN THE WALL FROM THE JUNCTION BOX TO 6" ABOVE THE CEILING. <br />21. COORDINATE THE LOCATION AND ELEVATION OF WALL-MOUNTED DEVICES WITH PRESENTATION BOARDS, <br />DISPLAY CABINETS, SHELVES OR OTHER COMPONENTS SHOWN ON THE ARCHITECTURAL DRAWINGS THAT ARE <br />TO BE INSTALLED UNDER OTHER DIVISIONS. CONTRACTOR WILL NOT BE REIMBURSED FOR RELOCATION OF <br />WALL-MOUNTED DEVICES CAUSED BY A LACK OF COORDINATION. <br />22. PROVIDE A MANUAL BALANCING DAMPER IN EACH BRANCH DUCT TAKEOFF FROM MAIN SUPPLY, RETURN, <br />OUTDOOR AND EXHAUST AIR DUCTS. PROVIDE CHORD OPERATED DAMPERS WHERE LOCATED ABOVE <br />INACCESSIBLE CEILINGS. <br />23. PROVIDE A PREFABRICATED 45 DEGREE, HIGH EFFICIENCY, RECTANGULAR/ROUND BRANCH DUCT TAKEOFF <br />FITTING WITH MANUAL BALANCING DAMPER AND LOCKING QUADRANT FOR BRANCH DUCT CONNECTIONS AND <br />TAKE-OFFS TO INDIVIDUAL DIFFUSERS, REGISTERS AND GRILLES. <br />24. BRANCH DUCTWORK TO AIR OUTLETS SHALL BE SAME SIZE AS OUTLET NECK SIZE UNLESS OTHERWISE NOTED. <br />25. REFER TO SPECIFICATIONS FOR DUCTWORK AND PIPING INSULATION REQUIREMENTS. DUCT SIZES ON <br />MECHANICAL PLANS INDICATE CLEAR INSIDE AIRFLOW DIMENSIONS, INCREASE SHEET METAL SIZES <br />ACCORDINGLY TO ACCOUNT FOR THICKNESS OF DUCT LINER. <br />26. FLEXIBLE DUCTWORK SHALL NOT EXCEED 5'-0" IN LENGTH AND SHALL BE INSTALLED AND SUPPORTED TO AVOID <br />SHARP BENDS AND SAGGING. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. <br />27. PROVIDE A NEW SET OF AIR FILTERS IN UNITS PRIOR TO TESTING, ADJUSTING AND BALANCING AND BEFORE <br />TURNING SYSTEM(S) OVER TO OWNER. <br />28. HVAC SYSTEMS AND CONTROLS WILL BE COMMISSIONED PER THE REQUIREMENTS OF THE COMMISSIONING <br />SECTION OF THE LEED PROTOTYPE GREEN SPECIFICATIONS. <br />29. PRIOR TO COMMENCING WORK ON THE STORE, THE GENERAL CONTRACTOR SHALL PROVIDE COPIES OF THE <br />COMMISSIONING SPECIFICATIONS IN THE LEED PROTOTYPE GREEN SPECIFICATIONS TO THE MECHANICAL, <br />ELECTRICAL, PLUMBING, AND CONTROLS SUB-CONTRACTORS. <br />30. PROVIDE 1" ACOUSTICAL LINING ON AS FOLLOWS (INCREASE DUCT DIAMATER AS REQUIRED): <br />-ALL TRANSFER DUCTWORK AND PLENUMS. <br />-EXHAUST DUCTWORK: 15'-0" UPSTREAM AND DOWNSTREAM OF EXHAUST FANS. <br />-ALL EXPOSED SUPPLY AND RETURN AIR DUCTWORK. <br /> -MINIMUM 25 FT UPSTREAM AND DOWNSTREAM OF AIR HANDLING UNITS <br />RETAIL SALES <br />101 <br />RESTROOM <br />102 <br />RESTROOM <br />103 <br />OPEN OFFICE <br />104 <br />INVENTORY <br />105 <br />MANAGER <br />106 <br />J.C. <br />107 <br />TELCO <br />108 <br />6"ø <br />CD-1 <br />(145) <br />6"ø <br />CD-1 <br />(145) <br />6"ø <br />CD-1 <br />(145) <br />6"ø <br />CD-1 <br />(145) <br />8"ø <br />CD-1 <br />(200) <br />8"ø <br />CD-1 <br />(200) <br />6"ø <br />CD-1 <br />(145) <br />6"ø <br />CD-1 <br />(145) <br />8"ø <br />CD-1 <br />(200) <br />6"ø <br />CD-1 <br />(80) <br />6"ø <br />CD-2 <br />(75) <br />8"ø <br />RG-2 <br />(100) <br />8"ø <br />RG-2 <br />(100) <br />6"ø <br />CD-2 <br />(75)8"ø <br />RG-1 <br />(100) <br />8"ø <br />CD-1 <br />(225) <br />8"ø <br />CD-1 <br />(225) <br />8"ø <br />CD-1 <br />(225) <br />6"ø <br />CD-1 <br />(100) <br />8"ø <br />RG-1 <br />6"ø <br />CD-1 <br />(100) <br />8"ø <br />RG-1 <br />6"ø <br />CD-2 <br />(100) <br />6"ø <br />CD-2 <br />(100) <br />6"ø <br />CD-2 <br />(100) <br />22"x22" <br />RG-1 <br />22"x22" <br />RG-1 <br />12"x26" <br />26"x12" <br />12"x22" <br />12"x22" <br />14 <br />" <br />x <br />1 <br />0 <br />" <br />10 <br />" <br />x <br />1 <br />0 <br />" <br />10 <br />" <br />x <br />8 <br />" <br />10 <br />" <br />x <br />6 <br />" <br />8"ø <br />8"ø 8"ø <br />8" <br />ø <br />8" <br />ø <br />8" <br />ø <br />10 <br />" <br />x <br />6 <br />" <br />10"x6" <br />6" <br />ø <br />EF-1 <br />(300) <br />10"x8"10"x6" <br />10 <br />" <br />x <br />6 <br />" <br />10"x6" <br />10 <br />" <br />x <br />6 <br />" <br />10 <br />" <br />x <br />6 <br />" <br />10 <br />" <br />x <br />6 <br />" <br />10"x8" <br />10 <br />" <br />x <br />8 <br />" <br />10 11 <br />8 <br />7 <br />5 <br />S <br />RTU-1 <br />T <br />RTU-1 <br />6 <br />6 <br />CRU-1 <br />3 <br />2 <br />3 <br />10 <br />" <br />x <br />6 <br />" <br />T <br />FCU-1 <br />FCU-1 <br />(1550) <br />(150) <br />9 <br />10 <br />" <br />x <br />8 <br />" <br />D <br />EDH-1 <br />8"ø <br />CD-1 <br />(225) <br />12"x10"12"x12" <br />6"ø <br />6"ø <br />6" <br />ø <br />10 <br />" <br />x <br />1 <br />0 <br />" <br />8"ø <br />6"ø <br />6"ø <br />6"ø <br />6" <br />ø <br />10" <br />x8" <br />12"ø <br />RG-1 <br />6"ø <br />10 <br />" <br />x <br />6 <br />" <br />10"x6" <br />10 <br />" <br />x <br />6 <br />" <br />10"x6" <br />6"ø 10"x10" <br />10 <br />" <br />x <br />1 <br />0 <br />" <br />14"x10" <br />8" <br />ø <br />10"x10" <br />14 <br />" <br />x <br />1 <br />2 <br />" <br />COD <br />6" <br />ø <br />18"x12" <br />COD 6" <br />ø <br />22"x12" <br />8"ø <br />8"ø <br />18 <br />" <br />x <br />1 <br />0 <br />" <br />CD <br />22"x14" <br />14"x8" <br />14"x8" <br />14"x8" <br />14"x12"18"x12"22"x12" <br />18"x12" <br />18 <br />" <br />x <br />1 <br />2 <br />" <br />4 <br />6 <br />CD <br />10"x6" <br />18"x18" <br />RG-1 <br />6" <br />ø <br />1 <br />1 <br />1 <br />10 <br />" <br />x <br />6 <br />" <br />3 <br />CODCOD <br />12 <br />MECHANICAL KEYNOTES <br />PROVIDE 2-WAY DIFFUSER BLANK-OFF <br />DUCT SMOKE DETECTORS SHALL BE INSTALLED IN SUPPLY DUCT MAINS <br />AFTER ELECTRIC DUCT HEATER EDH-1. <br />1" DOOR UNDERCUT FOR MAKEUP AIR TO RESTROOMS AND JANITOR'S <br />CLOSET. <br />COORDINATE ROUTING OF REFRIGERANT PIPING AND POWER/CONTROL <br />WIRING FOR CRU-1 AND FCU-1 UP TO ROOF IN FIELD. UTILIZE PATHWAYS AND <br />SHAFT FROM FORMER EQUIPMENT SERVING FORMER TENANT, IF FEASIBLE. <br />CRU-1 TO BE LOCATED ABOVE DOORWAY, BELOW HUNG CEILING. <br />COORDINATE EXACT LOCATION WITH ALL TRADES. PROVIDE CONDENSATE <br />PUMP AND PIPE CONDENSATE TO MOP SINK IN JANITOR'S CLOSET. <br />NEW VERIZON-STANDARD THERMOSTAT TO BE PROVIDED FOR NEW RTU-1 IN <br />OPEN OFFICE. PROVIDE REMOTE TEMPERATURE SENSOR IN SALES AREA <br />AND TIE IN TO THERMOSTAT. THERMOSTAT SHALL OPERATE BASED ON <br />READINGS FROM REMOTE SENSOR. SENSOR TO BE MOUNTED 72" AFF AND <br />BE PLASTIC 'BUTTON SENSOR' SIMILAR TO MODEL ACI -A/CP-PBS, 10K TYPE <br />II THERMISTOR. COORDINATE INSTALLATION WITH CONTROLS CONTRACTOR <br />AS REQUIRED. <br />CONNECT NEW SUPPLY AND RETURN DUCTWORK TO EXISTING SUPPLY AND <br />RETURN DUCT RISERS FROM RTU-1 ON ROOF. CONNECT IN CEILING OF 1ST <br />FLOOR AND PROVIDE DUCT TRANSITIONS AS REQUIRED. <br />HANG UNIT FROM STRUCTURE ABOVE WITH SUPPLEMENTAL SUPPORTS AS <br />REQUIRED. PROVIDE HANGER RODS AND SPRING ISOLATORS. PROVIDE <br />FLEXIBLE CONNECTIONS AT ALL DUCT CONNECTIONS TO UNIT. PROVIDE <br />ACCESS DOORS FOR MANUFACTURER REQUIRED CLEARANCES IF LOCATED <br />ABOVE AN INACCESSIBLE CEILING. COORDINATE EXACT LOCATION OF <br />THERMOSTAT & CONTROL BOX WITH ARCHITECT BEFORE INSTALLING. SEE <br />SCHEDULES AND DETAILS FOR ADDITIONAL REQUIREMENTS. <br />PROVIDE 2" HIGH AUXILIARY DRIP PAN BELOW UNIT & SUPPORT <br />INDEPENDENTLY. DRIP PAN SHALL EXTEND 4" BEYOND ALL AC UNIT TRIM. <br />PROVIDE CONDENSATE PUMP IN PAN & PIPE TO NEAREST DRAIN. <br />COORDINATE WITH CONTROLS CONTRACTOR FOR INTERCONNECTION OF <br />LEAK DETECTION AND CONNECTION TO BMS. <br />PROVIDE 12"Wx12"H OUTSIDE AIR INTAKE LOUVER WITH MINIMUM 0.3 SQ FT <br />OF FREE AREA. PROVIDE 12"Wx12"Hx12"D INSULATED PLENUM. PITCH <br />TOWARD LOUVER. REFER TO DETAILS AND SPECIFICATIONS FOR <br />ADDITIONAL INFORMATION. FIELD COORDINATE EXACT PENETRATION <br />LOCATION. EXHAUST DISCHARGE SHALL BE MINIMUM 10 FEET FROM <br />OUTSIDE AIR INTAKES AND PROPERTY LINES. <br />PROVIDE 18"WX12"H EXHAUST AIR OPENING WITH MINIMUM 0.4 SQ FT OF <br />FREE AREA FOR EF-1. PROVIDE 18"WX12"HX12"D INSULATED PLENUM. PITCH <br />TOWARD LOUVER. REFER TO DETAILS AND SPECIFICATIONS FOR <br />ADDITIONAL INFORMATION. FIELD COORDINATE EXACT PENETRATION <br />LOCATION. EXHAUST DISCHARGE SHALL BE MINIMUM 10 FEET FROM <br />OUTSIDE AIR INTAKES AND PROPERTY LINES. PROVIDE CORROSION <br />RESISTANT SCREEN (HAVING NOT LESS THAN ¼’NOR LARGER THAN ½” <br />OPENING) ON EXHAUST AIR DISCHARGE LOUVER. <br />PROVIDE BACKDRAFT DAMPER AT EXHAUST OUTLET. <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 <br />7 <br />8 <br />9 <br />10 <br />11 <br />12 <br />3 <br />Mechanical and Electrical Engineers <br />Lilker Associates <br />1001 Avenue of the Americas <br />New York, NY 10018 <br />tel 212.695.1000 <br />fax 212.695.1299 <br />www.lilker.com <br />Kenneth A. Gruskin AIA <br />No. Date Description <br />Consultant: <br />Checked By: <br />Drawn By: <br />Job Address: <br />Drawing Title: <br />Revision Issue: <br />Professional Seal: <br />Drawing Number: <br />2022 Gruskin Architecture + Design, P.C.c <br />This document and the ideas and designs incorporated <br />herein, as an instrument of professional service, is the <br />property of GRUSKIN ARCHITECTURE + DESIGN, P.C., <br />and is not to be used in whole or in part for any other <br />project without the written authorization of GRUSKIN <br />ARCHITECTURE + DESIGN, P.C. <br />North <br />Arrow: <br />Job Name and Number: <br />Date Issued For <br />All Rights Reserved <br />Client: <br />Landlord: <br />Permit: <br />Bid: <br />Construction: <br />0006261 <br />AR91629 <br />5421 <br />9613 <br />39209 <br />10635 <br />2537 <br />11016 <br />5734 <br />ARC 2596 <br />4674 <br />2666 <br />AI 09999 <br />2796 <br />0401 011223 <br />2572 <br />17680 <br />RA-015432-B <br />025528-1 NY <br />TX <br />VA <br />VT <br />MA <br />MT <br />RI <br />PA <br />NY <br />NJ <br />NH <br />MD <br />LA <br />ME <br />KS <br />FL <br />DE <br />CT <br />AZ <br />AL <br />C-1967WY <br />RA011075GA <br />AR10400066IN <br />C-29898CA <br />NM 004168 <br />ARC-400347CO <br />HI AR 11489 <br />PR 19965 <br />OR 4899 <br />SC 6834 <br />NC 9961 <br />13761OH <br />05713IA <br />WV 3727 <br />IL 001-019152 <br />UT 5881358-0301 <br />ID AR-984459 <br />1301052379MI <br />ARC100723DC <br />WI 9900-005MN44326 <br />A-3547NE <br />3811AR <br />5967KY 101374TN <br />MS 3860 <br />1666ND <br />A-2005029740MO <br />a4895OK <br />NV 5521 <br />WA 10344 <br />13167AK <br />SD 11532 <br />C: <br />\ <br />R <br />e <br />v <br />i <br />t <br /> <br />L <br />o <br />c <br />a <br />l <br /> <br />F <br />i <br />l <br />e <br />s <br />\ <br />2 <br />4 <br />0 <br />0 <br />1 <br />3 <br />0 <br />8 <br />_ <br />V <br />E <br />R <br />I <br />Z <br />O <br />N <br />_ <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />_ <br />C <br />A <br />_ <br />ME <br />C <br />H <br />A <br />N <br />I <br />C <br />A <br />L <br />_ <br />v <br />2 <br />3 <br />_ <br />r <br />t <br />r <br />o <br />v <br />a <br />t <br />o <br />T <br />7 <br />V <br />P <br />K <br />. <br />r <br />v <br />t <br />2023-0069 <br />Proposed <br />Store Design <br />for: VERIZON <br />3500 South Bristol Street <br />Suite 100 <br />Santa Ana, CA 92704 <br />3/15/24 <br />3/15/24 <br />4/5/24 <br />MECHANICAL <br />CONSTRUCTION PLAN <br />M.1.0 <br />MB <br />KG <br />38 OF 81 <br />1/4" = 1'-0"1 MECHANICAL CONSTRUCTION PLAN 3 6-3-2024 City Comments <br />3500 S Bristol St Unit# 100 - <br />101119098, 20182666 & <br />401390437/11/2024