23XX <br />26575 Ruether Ave 2nd floor <br />CH <br />A <br />R <br />C <br />Santa Clarita, CA 91350 <br />661.383.2352 - 818.919.2248 <br />AIR-COOLED CONDENSING UNIT SCHEDULE <br />YORK <br />PD240 <br />SYMBOL REMARKSMANUFACTURER <br />& MODEL NO <br />NOTES: <br />NOMINAL <br />TONNAGE <br />20 238.0 <br />GROSS SENSIBLE <br />- <br />COOLING CAPACITY <br />(MBH) <br />34.0 <br />ELECTRICAL <br />EER <br />10.6 <br />VOLT PH HZ <br />OPER <br />WT <br />(LBS) <br />208 3 60 1,126 <br />SERVES AHU-1 <br />AHR-1 AND ASME CERTIFIED. <br />2 REFRIGERANT CIRCUITS <br />SINGLE POINT POWER CONNECTION.1. <br />2. <br />3. <br />4. <br />MCA <br />89.8 110 <br />ELECTRICAL TO PROVIDE SERVICE DISCONNECT5. <br />PROVIDED BY YORK, FIELD INSTALLED PADDLE FLOW SWITCH . <br />FACTORY CERTIFIED START-UP. <br />1 YEAR PARTS AND LABOR WARRANTY FOR THE WHOLE UNIT. <br />6. <br />7. <br />8. <br />9. <br />1, 2, 3, 4, 5, 6, 7, 8, 9 <br />CALIFORNIA CODE CONFORMANCE ASHRAE 90.1 AND UL LISTED. <br />QTY. <br />2 <br />HEATING CAPACITY <br />(MBH) <br />GROSS SENSIBLE <br />220.0 - <br />COMPRESSORS <br />RLA <br />(EACH) <br />30.1 <br />MCC <br />(EACH) <br />47 <br />LRA <br />(EACH) <br />225 <br />HP <br />3/4 <br />OUTDOOR FAN MOTOR <br />QTY. <br />4 <br />FLA <br />(EACH) <br />3.0 <br />MAX FUSE <br />SIZE (A) <br />AIR HANDLING UNIT <br />SYMBOL MANUFACTURER <br />& MODEL NO <br />ELECTRICAL <br />FAN HP VOLTS PHASE HERTZ <br />OPER <br />WT <br />(LBS) <br />REMARKS <br />AIR FLOW <br />(CFM) <br />COOLING CAPACITY <br />(BTU/HR) <br />AIR2O <br />CUSTOM AIR HANDLING UNIT 16,000 <br />@ 1.55" ESP <br />6,42920208360459,360 <br />NOTES: <br />1, 2, 3, 4, 5, 6, 7, 8, 9,10, 11459,360 <br />COOLING COIL <br />6/10 <br />TOTAL <br />AREA SERVED <br />SALES FLOOR <br />MCA MOP <br />(A) <br />154 175 <br />NOMINAL <br />TONNAGE <br />40 - <br />HEATING CAPACITY <br />(BTU/HR) <br />SENSIBLE INPUT OUTPUT <br />ACCU <br />1A <br />AHU <br />1 <br />-DIRECT COIL <br />5DX-06-60.0-10-78.0-40 <br />ROWS/FPIMODEL NUMBER <br />OUTSIDE <br />AIR <br />(CFM) <br />3,600 <br />REFRIG CHARGE <br />LBS(R-410A) <br />SYSTEM #1 SYSTEM #2 <br />34.0 <br />SYSTEM DATA <br />NO. REFRIG <br />CIRCUITS <br />SUCTION <br />LINE OD <br />2 <br />LIQUID <br />LINE OD <br />5/8" Ø <br />ACCU <br />1B <br />1-3/8" Ø <br />IEER <br />13.5 <br />YORK <br />PD240 20 238.0 -34.010.6 220.0 -34.0 1, 2, 3, 4, 5, 6, 7, 8, 92083601,12689.8 110230.1 47 225 3/4 4 3.0 2 5/8" Ø1-3/8" Ø <br />1.SERVED BY ACCU-1A AND ACCU-1B. <br />2.2" FOAM BOARD R13 INSULATION WITH THERMAL BREAK. <br />3.DOUBLE WALL AHU WITH MERV-13 AIR FILTER. <br />4.WITH ROOF CURB. <br />5.SUPPLY DUCT SMOKE DETECTOR. <br />6.ACCESSIBLE MAGNEHELIC PRESSURE DIFFERENTIAL MONITORS <br />ACROSS MERV-13 AIR FILTERS <br />7.WITH 25.5 KW ELECTRIC HEATER FOR REHEAT TO CONTROL <br />TEMPERATURE AND RH. SHALL MAINTAIN 72°F AND 50% RH. <br />8.TXV'S SHALL BE PROVIDED AN INSTALLED BY AHU MANUFACTURER. <br />9.WITH 208V SINGLE POINT POWER CONNECTION AND SEPARATE 120V <br />POWER FEED FOR LIGHTING AND CONTROLS. <br />10.CONTROLS CONTRACTOR SHALL SUPPLY AHU MANUFACTURER WITH <br />ALL END DEVICES, CONTROLLERS, AND WIRING DIAGRAMS FOR <br />INSTALLATION AT AHU FACTORY. <br />11.EQUIPMENT SHALL BE PROVIDED BY US AIR. CONTACT MARGARET <br />LEMOS @ (626) 664-1922. <br />(CFM) <br />O.A.UNIT <br />NO.TONNAGE <br />NOMINAL % EFF. <br />INPUT OUTPUT <br />C.F.M. <br />(IN.) <br />E.S.P. <br />SERVED <br />AREA <br />ELECTRICAL <br />VOLTAGE <br />SENSIBLETOTAL <br />MANUFACTURER <br />& MODEL NO. <br />V / PH / HZ <br />REMARKS <br />ROOFTOP GAS/ELECTRIC UNIT SCHEDULE <br />REMARKS: <br />HP <br />FAN MAX FUSE <br />BREAKER SIZE <br />(AMPS) <br />IEER <br />COOLING <br />CAPACITY (MBH) <br />HEATING <br />CAPACITY (MBH) <br />7.5 81.086.9 94.5116.7 208 / 3 / 60 35.5 1,3692,000 0.75 102.02,400 1, 2, 3, 4, 5, 7, 8, 9, 10, 112.0 40RTU <br />1 <br />CAPTIVEAIRE <br />CAS-HVAC1-I.125-18-7.5T TORTILLERIA 18.6 <br />MCA <br />(AMPS) <br />UNIT <br />WT. <br />(LBS.) <br />93 <br />CURB <br />WT. <br />(LBS.)DESIRED MAX <br />REHEAT <br />CAPACITY (MBH) <br />42.4 60.0 <br />1.PROVIDE UNIT WITH PRE-ENGINEERED ROOF CURB. <br />2.PROVIDE UNIT WITH SUPPLY SMOKE DETECTOR AND WIRED FOR UNIT <br />SHUTDOWN. <br />3.UNIT WITH BOTTOM SUPPLY AND BOTTOM RETURN. <br />4.PROVIDE 2" MERV 13 FILTER. <br />6.PROVIDE 0-100% MODULATING ECONOMIZER WITH DRY BULB SENSOR <br />CONTROL, BAROMETRIC RELIEF, AND FAULT DETECTION DIAGNOSTICS. <br />7.PROVIDE MANUFACTURER'S CERTIFIED START-UP <br />8.PROVIDE T24 COMPLIANT PROGRAMMABLE THERMOSTAT. <br />10.WITH MODULATING HOT GAS REHEAT. <br />11.COORDINATE WITH MANUFACTURER FOR FINAL SELECTION. <br />HOOD <br />NO. <br />MODEL <br />HOOD <br />1 <br />CAPTIVEAIRE <br />6024 ND-2 <br />FILTERS <br />TYPE <br />CAPRATE <br />SOLO FILTER <br />TYPE <br />I <br />LENGTH <br />12'-0" <br />QTY. <br />9 1 <br />REMARKS <br />REMARKS: <br />SHOWN FOR REFERENCE ONLY. SEE CAPTIVEAIRE DRAWINGS.1 <br />HEIGHT <br />16" <br />LENGTH <br />20" <br />HANGING <br />WEIGHT <br />(LBS.) <br />564 <br />HOOD <br />2 <br />EXHAUST <br />CFM <br />2,700 <br />HOOD <br />3 <br />HOOD SCHEDULE <br />CAPTIVEAIRE <br />6024 ND-2 <br />CAPRATE <br />SOLO FILTERI10'-0"7 116"20"9851,500 <br />CAPTIVEAIRE <br />6024 ND-2 I8'-0"5 116"20"5401,080 <br />HOOD <br />4 <br />I15-4"2,913 <br />DIFFUSER SCHEDULES <br />TYPESYMBOL& MODEL NO. <br />MANUFACTURER DESCRIPTION REMARKS <br />PERFORATED, STEEL, RETURN <br />PANEL <br />SUPPLY <br />RETURN/EXHAUST <br />(FLUSH FACE) <br />PERFORATED, STEEL, SQUARE <br />CEILING DIFFUSER WITH 4-WAY <br />ADJUSTABLE DISCHARGE PATTERN <br />TITUS <br />MODEL PAS, OR EQUAL <br />TITUS <br />MODEL PXP, OR EQUAL <br /> (MODULAR CORE) <br />1. REFER TO SPECIFICATIONS <br />FOR COMPLETE DESCRIPTION <br />OF AIR TERMINALS. <br />A <br />1. REFER TO SPECIFICATIONS <br />FOR COMPLETE DESCRIPTION <br />OF AIR TERMINALS. <br />B <br />INSULATION SCHEDULE <br />PIPE <br />SIZE <br />NOTES: <br />1. <br />2. <br />MANUFACTURE <br />OWENS CORNING <br />OR APPROVED <br />DUCTS (LINED) <br />HVAC SUPPLY <br />HVAC SUPPLY <br />DUCTS (WRAPPED) <br />HVAC RETURN <br />DUCTS (LINED) <br />HVAC RETURN <br />DUCTS (WRAPPED) <br />A.C. <br />CONDENSATE <br />SERVICE <br />EQUAL <br />3 PCF <br />DENSITY <br />1 PCF <br />3 PCF <br />1 PCF <br />ED-100 <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />DUCT LINER <br />ED-100 <br />BOARD <br />MATERIAL <br />FIBERGLASS <br />DUCT LINER <br />BOARD <br />TYPE <br />- <br />YES <br />NO <br />YES <br />FOIL - <br />- <br />FOIL <br />- <br />- <br />JACKET <br />SERVICE <br />NO <br />YES <br />VAPOR <br />BARRIER <br />ALL <br />-- <br />ALL <br />2" <br />1" <br />2" <br />K=.27 <br />K=.27 <br />K=.23 <br />1" UNLESS <br />OTHERWISE <br />THICKNESS <br />NOTED <br />1/2" <br />K=.23 <br />K=.21 <br />REMARKS <br />3. <br />OWENS CORNING <br />OR APPROVED <br />EQUAL <br />ASJSSII <br />FIBERGLASS <br />ALSO INSULATE SUCTION REFRIGERANT LINES. <br />4.INSULATION SHALL NOT BE LESS THAN REQUIRED TO MEET MOST CURRENT TITLE 24 REQUIREMENTS. <br />SUPPLY DUCTS RUNNING EXTERIOR TO THE BUILDING, THROUGH UNCONDITIONED SPACES AND IN ATTICS <br />WHERE THE DUCTS RUN ABOVE THE ROOF/CEILING INSULATION SHALL BE INSULATED TO A VALUE OF R-8. <br />SUPPLY AND RETURN DUCTS RUNNING IN WALLS TO BE WRAPPED WITH REFLECTIX DUCT WRAP. <br />FLAME SPREAD/SMOKE DEVELOPED RATING SHALL BE 25/50 PER NFPA. <br />RECTANGULAR, STEEL, CEILING <br />OR SIDEWALL, ADJUSTABLE <br />RETURN/EXHAUST <br />(LOUVERED) <br />TITUS <br />MODEL 250, OR EQUAL <br />1. REFER TO SPECIFICATIONS <br />FOR COMPLETE DESCRIPTION <br />OF AIR TERMINALS. <br />C <br />LOUVERED, STEEL, RETURN <br />GRILLE, 35° DEFLECTION, 3/4" <br />BLADE SPACING <br />SUPPLY <br />(ADJUSTABLE) <br />TITUS <br />MODEL 350RL, OR EQUAL <br />1. REFER TO SPECIFICATIONS <br />FOR COMPLETE DESCRIPTION <br />OF AIR TERMINALS. <br />D <br />SEE NOTES <br />1 TO 4 <br />SPLIT SYSTEM HEAT PUMP SCHEDULE <br />REMARKSREFRIG <br />TYPE <br />INDOOR <br />UNIT <br />CFM <br />OPER <br />WEIGHT <br />LBS <br />INDOOR <br />(LBS.) <br />OUTDOOR <br />UNIT <br />EER2 <br />OPER <br />WEIGHT <br />LBS <br />OUTDOOR <br />(LBS.) <br />AREA SERVED <br />SUPPLY FAN <br />VOLTS / PH / HZ <br />ELECTRICAL <br />INDOOR UNIT <br />MCA MOCPESP <br />(IN. WC) <br />INDOOR UNIT <br />MANUFACTURER <br />& MODEL NO. <br />NOMINAL <br />COOLING <br />CAPACITY <br />(BTUH) <br />NOMINAL <br />HEATING <br />CAPACITY <br />(BTUH) <br />NOMINAL <br />CAPACITY <br />(TONS) <br />AMBIENT <br />TEMP. <br />(°F) <br />SEER2 <br />REFRIGERANT <br />PIPING <br />LIQUID GAS <br />OUTDOOR <br />UNIT MANUFACTURER <br />& MODEL NO.BHP <br />HSPF2 <br />MCA <br />MAX. <br />BREAKER <br />(AMPS) <br />ELECTRICAL <br />OUTDOOR UNIT <br />VOLTS/PH/HZ <br />REMARKS: <br />1.PROVIDE TITLE 24 COMPLIANT WIRED PROGRAMMABLE THERMOSTAT. <br />2.MOUNT CONDENSING UNIT ON SPRING ISOLATORS. <br />3.THE INDOOR UNIT SHALL HAVE A BUILT-IN CONDENSATE PUMP. <br />4.CONTRACTOR TO DETERMINE THE BEST POSSIBLE ROUTING OF ALL REFRIGERANT PIPING AS <br />MEANS & METHODS. <br />5.INSTALL SPLIT SYSTEM PER MANUFACTURER'S INSTALLATION MANUAL. PROVIDE MANUFACTURER'S <br />REQUIRED CLEARANCES. <br />6.PROVIDE 2" MERV-13 AIR FILTER. <br />7.THE OUTDOOR UNIT SHALL SUPPLY POWER TO INDOOR UNIT VIA 14 AWG X 3 POWER WIRE. <br />FC <br />1 <br />CU <br />1 <br />1.51.5 <br />BREAK ROOM, <br />SAFE ROOM, <br />CHECK CASHING <br />535 SEE <br />REMARK# 7--SAMSUNG <br />AC018BNHDCH/AA 0.8208 / 1 / 60 Ø1/4"Ø1/2"0.1820.1 25 77410A12.0SAMSUNG <br />AC018BXADCH/AA 20,00018,00095 18.0 1198.1 1, 2, 3, 4, 5, 6, 7 <br />OSA <br />CFM <br />115 <br />1, 2, 3, 4, 5, 7, 8, 9, 10, 11RTU <br />2 KITCHEN <br />7.5 81.081.7 78.897.2 208 / 3 / 60 35.5 1,3702,000 0.75 101.82,000 1, 2, 3, 4, 5, 7, 8, 9, 10, 112.0 40RTU <br />3 <br />CAPTIVEAIRE <br />CAS-HVAC1-I.125-18-7.5T BAKERY 18.6 9339.3 60.0 <br />1, 2, 3, 4, 5, 7, 8, 9, 10, 11RTU <br />4 MEAT SERVICE <br />13.5 <br />COP <br />3.3 <br />3.3 <br />7.5 81.086.9 94.5116.7 208 / 3 / 60 35.5 1,3692,000 0.75 102.02,400 2.0 40 <br />CAPTIVEAIRE <br />CAS-HVAC1-I.125-18-7.5T <br />18.6 9342.4 60.0 <br />7.5 81.081.7 78.897.2 208 / 3 / 60 35.5 1,3702,000 0.75 101.82,000 2.0 40 <br />CAPTIVEAIRE <br />CAS-HVAC1-I.125-18-7.5T <br />18.6 9339.3 60.0 <br />1 <br />CAPRATE <br />SOLO FILTER <br />CAPTIVEAIRE <br />6024 ND-2 11 16"20"1,097CAPRATE <br />SOLO FILTER <br />HOLD- 420 W 17th <br />St3/7/2025