|
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
<br />DIVISION 5.2 ENERGY EFFICIENCY
<br />SECTION 5.201 GENERAL
<br />5.201.1 Scope [BSC-CG].California Energy Code [DSA-SS].For the purposes of mandatory energy efficiency
<br />standards in this code, the California Energy Commission will continue to adopt mandatory building standards.
<br />DIVISION 5.4 MATERIAL CONSERVATION AND RESOURCE
<br />EFFICIENCY
<br />SECTION 5.401 GENERAL
<br />5.401.1 SCOPE.The provisions of this chapter shall outline means of achieving material conservation and resource
<br />efficiency through protection of buildings from exterior moisture, construction waste diversion, employment of
<br />techniques to reduce pollution through recycling of materials, and building commissioning or testing and adjusting.
<br />SECTION 5.410 BUILDING MAINTENANCE AND OPERATIONS
<br />5.410.1 RECYCLING BY OCCUPANTS. Provide readily accessible areas that serve the entire building and are
<br />identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum)
<br />paper, corrugated cardboard, glass, plastics, organic waste, and metals or meet a lawfully enacted local recycling
<br />ordinance, if more restrictive.
<br />Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources
<br />Code 42649.82 (a)(2)(A) et seq. shall also be exempt from the organic waste portion of this
<br />section.
<br />5.410.1.1 Additions. All additions conducted within a 12-month period under single or multiple permits,
<br />resulting in an increase of 30% or more in floor area, shall provide recycling areas on site.
<br />Exception: Additions within a tenant space resulting in less than a 30% increase in the tenant space
<br />5.410.1.2 Sample ordinance. Space allocation for recycling areas shall comply with Chapter 18, Part 3,
<br />Division 30 of the Public Resources Code. Chapter 18 is known as the California Solid Waste Reuse and
<br />Recycling Access Act of 1991 (Act).
<br />Note: A samcople ordinance for use by local agencies may be found in Appendix A of the document at the
<br />5.410.2 COMMISSIONING. [N]New buildings 10,000 square feet and over.For new buildings 10,000 square feet
<br />and over, building commissioning shall be included in the design and construction processes of the building project to
<br />verify that the building systems and components meet the owner’s or owner representative’s project requirements.
<br />Commissioning shall be performed in accordance with this section by trained personnel with experience on projects of
<br />comparable size and complexity. For I-occupancies that are not regulated by OSHPD or for I-occupancies and
<br />L-occupancies that are not regulated by the California Energy Code Section 100.0 Scope, all requirements in
<br />Sections 5.410.2 through 5.410.2.6 shall apply.
<br />Note:For energy-related systems under the scope (Section 100) of the California Energy Code, including heating,
<br />ventilation, air conditioning (HVAC) systems and controls, indoor lighting systems and controls, as well as water
<br />heating systems and controls, refer to California Energy Code Section 120.8 for commissioning requirements
<br />Commissioning requirements shall include:
<br />1. Owner’s or Owner representative’s project requirements.
<br />2. Basis of design.
<br />3. Commissioning measures shown in the construction documents.
<br />4. Commissioning plan.
<br />5. Functional performance testing.
<br />6. Documentation and training.
<br />7. Commissioning report.
<br />Exceptions:
<br />1. Unconditioned warehouses of any size.
<br />2. Areas less than 10,000 square feet used for offices or other conditioned accessory spaces within
<br />unconditioned warehouses.
<br />3. Tenant improvements less than 10,000 square feet as described in Section 303.1.1.
<br />4. Open parking garages of any size, or open parking garage areas, of any size, within a structure.
<br />Note:For the purposes of this section, unconditioned shall mean a building, area, or room which does not
<br />provide heating and or air conditioning.
<br />Informational Notes:
<br />1. IAS AC 476 is an accreditation criteria for organizations providing training and/or certification of
<br />commissioning personnel. AC 476 is available to the Authority Having Jurisdiction as a reference for
<br />qualifications of commissioning personnel. AC 476 des not certify individuals to conduct functional
<br />performance tests or to adjust and balance systems.
<br />2. Functional performance testing for heating, ventilation, air conditioning systems and lighting controls
<br />must be performed in compliance with theCalifornia Energy Code.
<br />floor area.
<br />CalRecycle’s web site.
<br />TABLE 5.504.4.1 - ADHESIVE VOC LIMIT 1,2
<br />Less Water and Less Exempt Compounds in Grams per Liter
<br />ARCHITECTURAL APPLICATIONS CURRENT VOC LIMIT
<br />INDOOR CARPET ADHESIVES 50
<br />CARPET PAD ADHESIVES 50
<br />OUTDOOR CARPET ADHESIVES 150
<br />WOOD FLOORING ADHESIVES 100
<br />RUBBER FLOOR ADHESIVES 60
<br />SUBFLOOR ADHESIVES 50
<br />CERAMIC TILE ADHESIVES 65
<br />VCT & ASPHALT TILE ADHESIVES 50
<br />DRYWALL & PANEL ADHESIVES 50
<br />COVE BASE ADHESIVES 50
<br />MULTIPURPOSE CONSTRUCTION ADHESIVES 70
<br />STRUCTURAL GLAZING ADHESIVES 100
<br />SINGLE-PLY ROOF MEMBRANE ADHESIVES 250
<br />OTHER ADHESIVES NOT SPECIFICALLY LISTED 50
<br />SPECIALTY APPLICATIONS
<br />PVC WELDING 510
<br />CPVC WELDING 490
<br />ABS WELDING 325
<br />PLASTIC CEMENT WELDING 250
<br />ADHESIVE PRIMER FOR PLASTIC 550
<br />CONTACT ADHESIVE 80
<br />SPECIAL PURPOSE CONTACT ADHESIVE 250
<br />STRUCTURAL WOOD MEMBER ADHESIVE 140
<br />TOP & TRIM ADHESIVE 250
<br />SUBSTRATE SPECIFIC APPLICATIONS
<br />METAL TO METAL 30
<br />PLASTIC FOAMS 50
<br />POROUS MATERIAL (EXCEPT WOOD)50
<br />WOOD 30
<br />FIBERGLASS 80
<br />1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER, THE
<br />ADHESIVE
<br />WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED.
<br />2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE THE VOC
<br />CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR QUALITY
<br />MANAGEMENT
<br />DISTRICT RULE 1168, www.arb.ca.gov/DRDB/SC/CURHTML/R1168.PDF
<br />TABLE 5.504.4.2 - SEALANT VOC LIMIT
<br />Less Water and Less Exempt Compounds in Grams per Liter
<br />SEALANTS CURRENT VOC LIMIT
<br />ARCHITECTURAL 250
<br />MARINE DECK 760
<br />NONMEMBRANE ROOF 300
<br />ROADWAY 250
<br />SINGLE-PLY ROOF MEMBRANE 450
<br />OTHER 420
<br />SEALANT PRIMERS
<br />ARCHITECTURAL
<br /> NONPOROUS 250
<br /> POROUS 775
<br />MODIFIED BITUMINOUS 500
<br />MARINE DECK 760
<br />OTHER 750
<br />NOTE: FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE THE VOC
<br />CONTENT SPECIFIED IN THESE TABLES, SEE SOUTH COAST AIR QUALITY MANAGEMENT
<br />DISTRICT RULE 1168.
<br />TABLE 5.504.4.3 - CONT.
<br />GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT COMPOUNDS
<br />COATING CATEGORY CURRENT VOC LIMIT
<br />SPECIALTY COATINGS
<br />ALUMINUM ROOF COATINGS 400
<br />BASEMENT SPECIALTY COATINGS 400
<br />BITUMINOUS ROOF COATINGS 50
<br />BITUMINOUS ROOF PRIMERS 350
<br />BOND BREAKERS 350
<br />CONCRETE CURING COMPOUNDS 350
<br />CONCRETE/MASONRY SEALERS 100
<br />DRIVEWAY SEALERS 50
<br />DRY FOG COATINGS 150
<br />FAUX FINISHING COATINGS 350
<br />FIRE RESISTIVE COATINGS 350
<br />FLOOR COATINGS 100
<br />FORM-RELEASE COMPOUNDS 250
<br />GRAPHIC ARTS COATINGS (SIGN PAINTS)500
<br />HIGH-TEMPERATURE COATINGS 420
<br />INDUSTRIAL MAINTENANCE COATINGS 250
<br />LOW SOLIDS COATINGS1 120
<br />MAGNESITE CEMENT COATINGS 450
<br />MASTIC TEXTURE COATINGS 100
<br />METALLIC PIGMENTED COATINGS 500
<br />MULTICOLOR COATINGS 250
<br />PRETREATMENT WASH PRIMERS 420
<br />PRIMERS, SEALERS, & UNDERCOATERS 100
<br />REACTIVE PENETRATING SEALERS 350
<br />RECYCLED COATINGS 250
<br />ROOF COATINGS 50
<br />RUST PREVENTATIVE COATINGS 250
<br />SHELLACS:
<br />CLEAR 730
<br />OPAQUE 550
<br />SPECIALTY PRIMERS, SEALERS & UNDERCOATERS 100
<br />STAINS 250
<br />STONE CONSOLIDANTS 450
<br />SWIMMING POOL COATINGS 340
<br />TRAFFIC MARKING COATINGS 100
<br />TUB & TILE REFINISH COATINGS 420
<br />WATERPROOFING MEMBRANES 250
<br />WOOD COATINGS 275
<br />WOOD PRESERVATIVES 350
<br />ZINC-RICH PRIMERS 340
<br />1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER & EXEMPT COMPOUNDS
<br />2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS ARE LISTED IN SUBSEQUENT COLUMNS
<br />IN THE TABLE.
<br />3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIFORNIA AIR RESOURCES BOARD,
<br />ARCHITECTURAL COATINGS SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS AVAILABLE
<br />FROM THE AIR RESOURCES BOARD.
<br />TABLE 5.504.4.3 - VOC CONTENT LIMITS FOR ARCHITECTURAL
<br />COATINGS2,3
<br />GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT COMPOUNDS
<br />COATING CATEGORY CURRENT VOC LIMIT
<br />FLAT COATINGS 50
<br />NONFLAT COATINGS 100
<br />NONFLAT HIGH GLOSS COATINGS 150
<br />DIVISION 5.5 ENVIRONMENTAL QUALITY
<br />SECTION 5.501 GENERAL
<br />5.501.1 SCOPE.The provisions of this chapter shall outline means of reducing the quantity of air contaminants that
<br />are odorous, irritating, and/or harmful to the comfort and well-being of a building's installers, occupants and neighbors.
<br />SECTION 5.502 DEFINITIONS
<br />5.502.1 DEFINITIONS.The following terms are defined in Chapter 2 (and are included here for reference)
<br />ARTERIAL HIGHWAY.A general term denoting a highway primarily for through traffic usually on a continuous route.
<br />A-WEIGHTED SOUND LEVEL (dBA).The sound pressure level in decibels as measured on a sound level meter
<br />using the internationally standardized A-weighting filter or as computed from sound spectral data to which A-weighting
<br />adjustments have been made.
<br />1 BTU/HOUR.British thermal units per hour, also referred to as Btu. The amount of heat required to raise one pound
<br />of water one degree Fahrenheit per hour, a common measure of heat transfer rate. A ton of refrigeration is 12,000
<br />Btu, the amount of heat required to melt a ton (2,000 pounds) of ice at 320Fahrenheit.
<br />COMMUNITY NOISE EQUIVALENT LEVEL (CNEL). A metric similar to the day-night average sound level (Ldn),
<br />except that a 5 decibel adjustment is added to the equivalent continuous sound exposure level for evening hours
<br />(7pm to 10pm) in addition to the 10 dB nighttime adjustment used in the Ldn.
<br />COMPOSITE WOOD PRODUCTS.Composite wood products include hardwood plywood, particleboard and medium
<br />density fiberboard. “Composite wood products” does not include hardboard, structural plywood, structural panels,
<br />structural composite lumber, oriented strand board, glued laminated timber, timber, prefabricated wood I–joists or
<br />finger–jointed lumber, all as specified in California Code of Regulations (CCR), Title 17, Section 93120.1(a).
<br />Note: See CCR, Title 17, Section 93120.1.
<br />DAY-NIGHT AVERAGE SOUND LEVEL (Ldn).The A-weighted equivalent continuous sound exposure level for a
<br />24-hour period with a 10 dB adjustment added to sound levels occurring during nighttime hours (10p.m. to 7 a.m.).
<br />DECIBEL (db).A measure on a logarithmic scale of the magnitude of a particular quantity (such as sound pressure,
<br />sound power, sound intensity) with respect to a reference quantity.
<br />ELECTRIC VEHICLE (EV).An automotive-type vehicle for on-road use, such as passenger automobiles, buses,
<br />trucks, vans, neighborhood electric vehicles, electric motorcycles, and the like, primarily powered by an electric motor
<br />that draws current from a rechargeable storage battery, fuel cell, photovoltaic array, or other source of electric current.
<br />Plug-in hybrid electric vehicles (PHEV) are considered electric vehicles. For purposes of theCalifornia Electrical Code
<br />, off-road, self-propoelled electric vehicles, such as industrial trucks, hoists, lifts, transports, golf carts, airline
<br />ground support equipment, tractors, boats, and the like, are not included.
<br />ELECTRIC VEHICLE CHARGING STATION(S) (EVCSj).One or more spaces intended for charging electric
<br />vehicles.
<br />ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE).The conductors, including the ungrounded, grounded, and
<br />equipment grounding conductors and the electric vehicle connectors, attachment plugs, and all other fittings, devices,
<br />power outlets, or apparatus installed specifically for the purpose of transferring energy between the premises wiring
<br />and the electric vehicle.
<br />ENERGY EQUIVALENT (NOISE) LEVEL (Leq).The level of a steady noise which would have the same energy as
<br />the fluctuating noise level integrated over the time of period of interest.
<br />EXPRESSWAY.An arterial highway for through traffic which may have partial control of access, but which may or
<br />may not be divided or have grade separations at intersections.
<br />FREEWAY.A divided arterial highway with full control of access and with grade separations at intersections.
<br />GLOBAL WARMING POTENTIAL (GWP).The radiative forcing impact of one mass-based unit of a given
<br />greenhouse gas relative to an equivalent unit of carbon dioxide over a given period of time. Carbon dioxide is the
<br />reference compound with a GWP of one.
<br />GLOBAL WARMING POTENTIAL VALUE (GWP VALUE).A 100-year GWP value published by the
<br />Intergovernmental Panel on Climate Change (IPCC) in either its Second Assessment Report (SAR) (IPCC, 1995); or
<br />its Fourth Assessment A-3 Report (AR4) (IPCC, 2007). The SAR GWP values are found in column "SAR (100-yr)" of
<br />Table 2.14.; the AR4 GWP values are found in column "100 yr" of Table 2.14.
<br />HIGH-GWP REFRIGERANT.A compound used as a heat transfer fluid or gas that is: (a) a chlorofluorocarbon, a
<br />hdrochlorofluorocarbon, a hydrofluorocarbon, a perfluorocarbon, or any compound or blend of compounds, with a
<br />GWP value equal to or greater than 150, or (B) any ozone depleting substance as defined in Title 40 of the Code of
<br />Federal Regulations, Part 82, sec.82.3 (as amended March 10, 2009).
<br />LONG RADIUS ELBOW.Pipe fitting installed between two lengths of pipe or tubing to allow a change of direction,
<br />with a radius 1.5 times the pipe diameter.
<br />LOW-GWP REFRIGERANT.A compound used as a heat transfer fluid or gas that: (A) has a GWP value less than
<br />150, and (B) is not an ozone depleting substance as defined in Title 40 of the Code of Federal Regulations, Part 82,
<br />sec.82.3 (as amended March 10, 2009).
<br />MERV. Filter minimum efficiency reporting value, based on ASHRAE 52.2–1999.
<br />MAXIMUM INCREMENTAL REACTIVITY (MIR).The maximum change in weight of ozone formed by adding a
<br />compound to the "Base REactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to
<br />hundreths of a gram (g O3/g ROC).
<br />PRODUCT-WEIGHTED MIR (PWMIR).The sum of all weighted-MIR for all ingredients in a product subject to this
<br />article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of
<br />product (excluding container and packaging).
<br />PSIG.Pounds per square inch, guage.
<br />REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to
<br />ozone formation in the troposphere.
<br />SCHRADER ACCESS VALVES.Access fittings with a valve core installed.
<br />SHORT RADIUS ELBOW.Pipe fitting installed between two lengths of pipe or tubing to allow a change of direction,
<br />with a radius 1.0 times the pipe diameter.
<br />SUPERMARKET.For the purposes of Section 5.508.2, a supermarket is any retail food facility with 8,000 square feet
<br />or more conditioned area, and that utilizes either refrigerated display cases, or walk-in coolers or freezers connected
<br />to remote compressor units or condensing units.
<br />VOC.A volatile organic compound broadly defined as a chemical compound based on carbon chains or rings with
<br />vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain
<br />hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a)
<br />.
<br />Note: Where specific regulations are cited from different agencies such as SCAQMD, ARB, etc., the VOC definition
<br />included in that specific regulation is the one that prevails for the specific measure in question.
<br />SECTION 5.504 POLLUTANT CONTROL
<br />5.504.1 TEMPORARY VENTILATION. The permanent HVAC system shall only be used during construction if
<br />necessary to condition the building or areas of addition or alteration within the required temperature range for
<br />material and equipment installation. If the HVAC system is used during construction, use return air filters with a
<br />Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2-1999, or an average efficiency of 30%
<br />based on ASHRAE 52.1-1992 Replace all filters immediately prior to occupancy, or, if the building is occupied
<br />during alteration, at the conclusion of construction.
<br />5.504.3 Covering of duct openings and protection of mechanical equipment during construction.At the time
<br />of rough installation and during storage on the construction site until final startup of the heating, cooling and
<br />ventilation equipment, all duct and other related air distribution component openings shall be covered with tape,
<br />plastic, sheetmetal or other methods acceptable to the enforcing agency to reduce the amount of dust, water and
<br />debris which may enter the system.
<br />5.504.4.3 Paints and coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of
<br />the ARB Architectural Coatings Suggested Control Measure, as shown in Table 5.504.4.3, unless more
<br />stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty
<br />coatings categories listed in Table 5.504.4.3 shall be determined by classifying the coating as a Flat, Nonflat
<br />or Nonflat-High Gloss coating, based on its gloss, as defined in Subsections 4.21, 4.36 and 4.37 of the 2007
<br />California Air Resources Board Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-
<br />High Gloss VOC limit in Table 5.504.4.3 shall apply.
<br />5.504.4.3.1 Aerosol Paints and coatings. Aerosol paints and coatings shall meet the PWMIR Limits for
<br />ROC in Section 94522(a)(3) and other requirements, including prohibitions on use of certain toxic
<br />compounds and ozone depleting substances, in Sections 94522(c)(2) and (d)(2) of California Code of
<br />Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the
<br />Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product
<br />limits of Regulation 8 Rule 49.
<br />5.410.2.1 Owner's or Owner Representative's Project Requirements (OPR). [N]The expectations and
<br />requirements of the building appropriate to its phase shall be documented before the design phase of the
<br />project begins. This documentation shall include the following:
<br />5.410.2.2 Basis of Design (BOD). [N]A written explanation of how the design of the building systems meets
<br />the OPR shall be completed at thedesign phase of the building project. The Basis of Design document shall
<br />cover the following systems:
<br />1. Renewable energy systems.
<br />2. Landscape irrigation systems.
<br />3. Water reuse system.
<br />5.410.2.3 Commissioning plan. [N]
<br /> Functional performance tests shall demonstrate the correct
<br />document how the project will be commissioned. The commissioning plan shall include the following:
<br />1. General project information.
<br />2. Commissioning goals.
<br />3. Systems to be commissioned. Plans to test systems and components shall include:
<br />a. An explanation of the original design intent.
<br />b. Equipment and systems to be tested, including the extent of tests.
<br />c. Functions to be tested.
<br />d. Conditions under which the test shall be performed.
<br />e. Measurable criteria for acceptable performance.
<br />4. Commissioning team information.
<br />5. Commissioning process activities, schedules and responsibilities. Plans for the completion of
<br /> commissioning shall be included.
<br />5.508.2 Supermarket refrigerant leak reduction.New commercial refrigeration systems shall comply with the
<br />provisions of this section when installed in retail food stores 8,000 square feet or more conditioned area, and that
<br />utilize either refrigerated display cases, or walk-in coolers or freezers connected to remote compressor units or
<br />condensing units. The leak reduction measures apply to refrigeration systems containing high-global-warming
<br />potential (high-GWP) refrigerants with a GWP of 150 or greater. New refrigeration systems include both new facilities
<br />and the replacement of existing refrigeration systems in existing facilities.
<br />Exception:Refrigeration systems containing low-global warming potential (low-GWP) refrigerant with a GWP
<br />value less than 150 are not subject to this section. Low-GWP refrigerants are nonozone-depleting refrigerants
<br />that include ammonia, carbon dioxide (CO2), and potentially other refrigerants.
<br />5.508.2.1 Refrigerant piping.Piping compliant with the California Mechanical Code shall be installed to be
<br />accessible for leak protection and repairs. Piping runs using threaded pipe, copper tubing with an outside
<br />diameter (OD) less than 1/4 inch, flared tubing connections and short radius elbows shall not be used in
<br />refrigerant systems except as noted below.
<br />5.508.2.1.1 Threaded pipe.Threaded connections are permitted at the compressor rack.
<br />5.508.2.1.2 Copper pipe.Copper tubing with an OD less than 1/4 inch may be used in systems with a
<br />refrigerant charge of 5 pounds or less.
<br />5.508.2.1.2.1 Anchorage.One-fouth-inch OD tubing shall be securely clamped to a rigid base to
<br />keep vibration levels below 8 mils.
<br />5.508.2.1.3 Flared tubing connections.Double-flared tubing connections may be used for pressure
<br />controls, valve pilot lines and oil.
<br />Exception:Single-flared tubing connections may be used with a multiring seal coated with
<br />industrial sealant suitable for use with refrigerants and tightened in accordance with manufacturer's
<br />recommendations.
<br />5.508.2.1.4 Elbows.Short radius elbows are only permitted where space limitations prohibit use of
<br />long radius elbows.
<br />5.508.2.2 Valves.Valves Valves and fittings shall comply with the California Mechanical Code and as follows.
<br />5.508.2.2.1 Pressure relief valves.For vessels containing high-GWP refrigerant, a rupture disc shall
<br />be installed between the outlet of the vessel and the inlet of the pressure relief valve.
<br />5.508.2.2.1.1 Pressure detection.A pressure gauge, pressure transducer or other device shall
<br />be installed in the space between the rupture disc and the relief valve inlet to indicate a disc
<br />rupture or discharge of the relief valve.
<br />5.508.2.2.2 Access valves.Only Schrader access valves with a brass or steel body are permitted for use.
<br />5.508.2.2.2.1 Valve caps.For systems with a refrigerant charge of 5 pounds or more, valve caps
<br />shall be brass or steel and not plastic.
<br />5.508.2.2.2.2 Seal caps.If designed for it, the cap shall have a neoprene O-ring in place.
<br />5.508.2.2.2.2.1 Chain tethers.Chain tethers to fit ovr the stem are required for valves
<br />designed to have seal caps.
<br />Exception:Valves with seal caps that are not removed from the valve during stem operation.
<br />5.508.2.3 Refrigerated service cases.Refrigerated service cases holding food products containing vinegar and
<br />salt shall have evaporator coils of corrosion-resistant material, such as stainless steel; or be coated to prevent
<br />corrosion from these substances.
<br />5.508.2.3.1 Coil coating.Consideration shall be given to the heat transfer efficiency of coil coating to
<br />maximize energy efficiency.
<br />5.508.2.4 Refrigerant receivers.Refrigerant receivers with capacities greater than 200 pounds shall be fitted
<br />with a device tha indicates the level of refrigerant in the receiver.
<br />5.508.2.5 Pressure testing.The system shall be pressure tested during installation prior to evacuation and charging.
<br />5.508.2.5.1 Minimum pressure.The system shall be charged with regulated dry nitrogen and
<br />appropriate tracer gas to bring system pressure up to 300 psig minimum.
<br />5.508.2.5.2 Leaks.Check the system for leaks, repair any leaks, and retest for pressure using the same gauge.
<br />5.508.2.5.3 Allowable pressure change.The system shall stand, unaltered, for 24 hours with no more than a
<br />+/- one pound pressure change from 300 psig, measured with the same gauge.
<br />5.508.2.6 Evacuation.The system shall be evacuated after pressure testing and prior to charging.
<br />5.508.2.6.1 First vacuum.Pull a system vacuum down to at least 1000 microns (+/- 50 microns), and hold for
<br />30 minutes.
<br />5.508.2.6.2 Second vacuum.Pull a second system vacuum to a minimum of 500 microns and hold for 30
<br />minutes.
<br />5.508.2.6.3 Third vacuum.Pull a third vacuum down to a minimum of 300 microns, and hold for 24 hours with a
<br />maximum drift of 100 microns over a 24-hour period.
<br />5.410.2.6 Commissioning report.[N]A report of commissioning process activities undertaken through the
<br />design and construction phases of the building project shall be completed and provided to the owner or
<br />representative.
<br />5.410.4 TESTING AND ADJUSTING. New buildings less than 10,000 square feet.Testing and adjusting of
<br />systems shall be required for new buildings less than 10,000 square feet or new systems to serve an addition or
<br />alteration subject to Section 303.1.
<br />5.410.4.2 (Reserved)
<br />Note:For energy-related systems under the scope (Section 100) of the California Energy Code, including
<br />heating, ventilation, air conditioning (HVAC) systems and controls, indoor lighting system and controls, as well
<br />as water heating systems and controls, refer to California Energy Code Section 120.8 for commissioning
<br />requirements and Sections 120.5, 120.6, 130.4, and 140.9(b)3 for additional testing requirements of specific systems.
<br />5.410.4.2 Systems. Develop a written plan of procedures for testing and adjusting systems. Systems to be
<br />included for testing and adjusting shall include at a minimum, as applicable to the project:
<br />1. Renewable energy systems.
<br />2. Landscape irrigation systems.
<br />3. Water reuse systems.
<br />5.410.4.3 Procedures. Perform testing and adjusting procedures in accordance with manufacturer's
<br />specifications and applicable standards on each system.
<br />5.410.4.3.1 HVAC balancing. In addition to testing and adjusting, before a new space-conditioning
<br />system serving a building or space is operated for normal use, the system shall be balanced in
<br />accordance with the procedures defined by the Testing Adjusting and Balancing Bureau National
<br />Standards; the National Environmental Balancing Bureau Procedural Standards; Associated Air Balance
<br />Council National Standards or as approved by the enforcing agency.
<br />CHAPTER 7
<br />INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS
<br />702 QUALIFICATIONS
<br />702.1 INSTALLER TRAINING.HVAC system installers shall be trained and certified in the proper
<br />installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or
<br />certification program. Uncertified persons may perform HVAC installations when under the direct supervision and
<br />responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems.
<br />Examples of acceptable HVAC training and certification programs include but are not limited to the following:
<br />1. State certified apprenticeship programs.
<br />2. Public utility training programs.
<br />3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations.
<br />4. Programs sponsored by manufacturing organizations.
<br />5. Other programs acceptable to the enforcing agency.
<br />702.2 SPECIAL INSPECTION [HCD].When required by the enforcing agency, the owner or the
<br />responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or
<br />other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence
<br />to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to
<br />other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may
<br />be considered by the enforcing agency when evaluating the qualifications of a special inspector:
<br />1. Certification by a national or regional green building program or standard publisher.
<br />2. Certification by astatewide energy consulting or verification organization, such as HERS raters, building
<br />performance contractors, and home energy auditors.
<br />3. Successful completion of a third party apprentice training program inthe appropriate trade.
<br />4. Other programs acceptable to the enforcing agency.
<br />Notes:
<br />1. Special inspectors shall be independent entities with no financial interest in the materials or the
<br />project they are inspecting for compliance with this code.
<br />2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate
<br />homes in California according to the Home Energy Rating System (HERS).
<br />[BSC-CG] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent
<br />shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance
<br />with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the
<br />particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a
<br />recognized state, national or international association, as determined by the local agency. The area of certification
<br />shall be closely related to the primary job function, as determined by the local agency.
<br />Note: Special inspectors shall be independent entities with no financial interest in the materials or the
<br />project they are inspecting forcompliance with this code.
<br />703 VERIFICATIONS
<br />703.1 DOCUMENTATION.Documentation used to show compliance with this code shall include but is not limited
<br />to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other methods
<br />acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or
<br />special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate
<br />section or identified applicable checklist.
<br />SECTION 5.505 INDOOR MOISTURE CONTROL
<br />5.505.1 INDOOR MOISTURE CONTROL. Buildings shall meet or exceed the provisions of California Building Code,
<br />CCR, Title 24, Part 2, Sections 1202 (Ventilation) and Chapter 14 (Exterior Walls). For additional measures, see
<br />Section 5.407.2 of this code.
<br />SECTION 5.506 INDOOR AIR QUALITY
<br />5.506.1 OUTSIDE AIR DELIVERY. For mechanically or naturally ventilated spaces in buildings, meet the minimum
<br />requirements of Section 120.1 (Requirements For Ventilation) of theCalifornia Energy Code, or the applicable local
<br />code, whichever is more stringent, and Division 1, Chapter 4 of CCR, Title 8.
<br />5.506.2 CARBON DIOXIDE (CO2) MONITORING. For buildings or additions equipped with demand control
<br />ventilation, CO2 sensors and ventilation controls shall be specified and installed in accordance with the requirements
<br />of the California Energy Code, Section 120(c)(4).
<br />5.506.3 Carbon dioxide (CO2) monitoring in classrooms.
<br />(DSA-SS)Each public K-12 school classroom, as listed in Table 120.1-A of theCalifornia Energy Code,shall be
<br />equipped with a carbon dioxide monitor or sensor that meets the following requirements:
<br />1.The monitor or sensor shall be permanently affixed in a tamper-proof manner in each classroom between 3
<br />and 6 feet (914 mm and 1829 mm) above the floor and at least 5 feet (1524 mm) away from door and operable
<br />windows.
<br />2.When the monitor or sensor is not integral to an Energy Management Control System (EMCS), the monitor or
<br />sensor shall display the carbon dioxide readings on the device. When the sensor is integral to an EMCS, the
<br />carbon dioxide readings shall be available to and regularly monitored by facility personnel.
<br />3. A monitor shall provide notification though a visual indicator on the monitor when the carbon dioxide levels in
<br />the classroom have exceeded 1,100ppm. A sensor integral to an EMCS shall provide notification to facility
<br />personnel through a visual and/or audible indicator when the carbon dioxide levels in the classroom have
<br />exceeded 1,100ppm.
<br />4. The monitor or sensor shall measure carbon dioxide levels at minimum 15- minute intervals and shall maintain
<br />a record of previous carbon dioxide measurements of not less than 30 days duration.
<br />5.The monitor or sensor used to measure carbon dioxide levels shall have the capacity to measure carbon
<br />dioxide levels with a range of 400ppm to 2000ppm or greater.
<br />6.The monitor or sensor shall be certified by the manufacturer to be accurate within 75ppm at 1,000ppm carbon
<br />dioxide concentration and shall be certified by the manufacturer to require calibration no more frequently than
<br />once every 5 years.
<br />SECTION 5.507 ENVIRONMENTAL COMFORT
<br />5.507.4 ACOUSTICAL CONTROL. Employ building assemblies and components with Sound Transmission Class
<br />(STC) values determined in accordance with ASTM E 90 and ASTM E 413, or Outdoor-Indoor Sound Transmission
<br />Class (OITC) determined in accordance with ASTM E 1332, using either the prescriptive or performance method in
<br />Section 5.507.4.1 or 5.507.4.2.
<br />Exception: Buildings with few or no occupants or where occupants are not likely to be affected by exterior
<br />noise, as determined by the enforcement authority, such as factories, stadiums, storage, enclosed parking
<br />structures and utility buildings.
<br />Exception: [DSA-SS] For public schools and community colleges, the requirements of this section and all
<br />subsections apply only to new construction.
<br />5.507.4.1 Exterior noise transmission, prescriptive method. Wall and roof-ceiling assemblies exposed to
<br />the noise source making up the building or addition envelope or altered envelope shall meet a composite STC
<br />rating of at least 50 or a composite OITC rating of no less than 40,with exterior windows of a minimum STC of
<br />40 or OITC of 30 in the following locations:
<br />1. Within the 65 CNEL noise contour of an airport.
<br />Exceptions:
<br />1. Ldn or CNEL for military airports shall be determined by the facility Air Installation Compatible
<br />Land Use Zone (AICUZ) plan.
<br />2. Ldn or CNEL for other airports and heliports for which a land use plan has notbeen developed
<br /> shall be determined by the local general plan noise element.
<br />2. Within the 65 CNEL or Ldn noise contour of a freeway or expressway, railroad, industrial source or
<br /> fixed-guideway source as determined by the Noise Element of the General Plan.
<br />5.507.4.1.1. Noise exposure where noise contours are not readily available.Buildings exposed to a
<br />noise level of 65 dB L eq - 1-hr during any hour of operation shall have building, addition or alteration
<br />exterior wall and roof-ceiling assemblies exposed to the noise source meeting a composite STC rating of
<br />at least 45 (or OITC 35), with exterior windows of a minimum STC of 40 (or OITC 30).
<br />5.507.4.2 Performance Method. For buildings located as defined in Section 5.507.4.1 or 5.507.4.1.1, wall and
<br />roof-ceiling assemblies exposed to the noise source making up the building or addition envelope or altered
<br />envelope shall be constructed to provide an interiornoise environment attributable to exterior sources that does
<br />not exceed an hourly equivalent noise level (Leq-1Hr) of 50 dBA in occupied areas during any hour of operation.
<br />5.507.4.2.1 Site Features.Exterior features such as sound walls or earth berms may be utilized as
<br />appropriate to the building, addition or alteration project to mitigate sound migration to the interior.
<br />5.507.4.2.2 Documentation of Compliance.An acoustical analysis documenting complying interior
<br />levels shall be prepared by personnel approved by the architect or engineer of record.
<br />5.507.4.3 Interior sound transmission.Wall and floor-ceiling assemblies separating tenant spaces and tenant
<br />spaces and public places shall have an STC of at least 40.
<br />Note: Examples of assemblies and their various STC ratings may be found at the California Office of
<br />Noise Control: www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf.
<br />SECTION 5.508 OUTDOOR AIR QUALITY
<br />5.508.1 Ozone depletion and greenhouse gas reductions. Installations of HVAC, refrigeration and fire
<br />suppression equipment shall comply with Sections 5.508.1.1 and 5.508.1.2.
<br />5.508.1.1 Chlorofluorocarbons (CFCs).Install HVAC, refrigeration and fire suppression equipment that do not
<br />contain CFCs.
<br />5.508.1.2 Halons.Install HVAC, refrigeration and fire suppression equipment that do not contain Halons.
<br />5.504.5.3 Filters. In mechanically ventilated buildings, provide regularly occupied areas of the building with air
<br />filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV)
<br />of 13. MERV 13 filters shall be installed prior to occupancy, and recommendations for maintenance with filters
<br />of the same value shall be included in the operation and maintenance manual.
<br />Exceptions:Existing mechanical equipment.
<br />5.504.5.3.1 Labeling.Installed filters shall be clearly labeled by the manufacturer indicating the MERV
<br />rating.
<br />5.504.4.3.2 Verification.Verification of compliance with this section shall be provided at the request of
<br />the enforcing agency. Documentation may include, but is not limited to, the following:
<br />1. Manufacturer's product specification
<br />2. Field verification of on-site product containers
<br />5.410.2.5 Documentation and training. [N] A Systems Manual and Systems Operations Training are required,
<br />including Occupational Safety and Health Act (OSHA) requirements in California Code of Regulations (CCR),
<br />Title 8, Section 5142, and other related regulations.
<br />5.410.2.5.1 Systems manual. [N]Documentation of the operational aspects of the building shall be
<br />completed within thesystems manual and delivered to the building owner or representative. The
<br />systems manual shall include the following:
<br />1. Site information, including facility description, history and current requirements.
<br />2. Site contact information.
<br />3. Basic operations and maintenance, including general site operating procedures, basic
<br /> troubleshooting, recommended maintenance requirements, site events log.
<br />4. Major systems.
<br />5. Site equipment inventory and maintenance notes.
<br />6. A copy of verifications required by the enforcing agency or this code.
<br />7. Other resources and documentation, if applicable.
<br />5.410.2.5.2 Systems operations training. [N]A program for training of the appropriate maintenance
<br />staff for each equipment type and/or system shall be developed and documented in the commissioning
<br />report and shall include the following:
<br />1. System/equipment overview (what it is, what it does and with what other systems and/or
<br /> equipment it interfaces).
<br />2. Review and demonstration of servicing/preventive maintenance.
<br />3. Review of the information in the Systems Manual.
<br />4. Review of the record drawings on the system/equipment.
<br />5.504.4 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with Sections 5.504.4.1
<br />through 5.504.4.6.
<br />5.504.4.1 Adhesives, sealants and caulks. Adhesives, sealants, and caulks used on the project shall meet
<br />the requirements of the following standards:
<br />1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall
<br />comply with local or regional air pollution control or air quality management district rules where
<br />applicable, or SCAQMD Rule 1168 VOClimits, as shown in Tables 5.504.4.1 and 5.504.4.2. Such
<br />products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds
<br />(chloroform, ethylene dichloride, methylene chloride, perchloroethylene and trichloroethylene), except
<br />for aerosol products as specified in subsection 2, below.
<br />2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of
<br />product, less packaging, which do not weigh more than one pound and do not consist of more than 16 fluid
<br />ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of
<br />certain toxic compounds, of California Code of Regulations, Title 17, commencing with Section 94507.
<br />5.410.4.4 Reporting. After completion of testing, adjusting and balancing, provide a final report of testing
<br />signed by the individual responsible for performing these services.
<br />5.410.4.5 Operation and maintenance (O & M) manual. Provide the building owner or representative with
<br />detailed operating and maintenance instructions andcopies of guaranties/warranties for each system. O & M
<br />instructions shall be consistent with OSHA requirements in CCR, Title 8, Section 5142, and other related regulations.
<br />5.410.4.5.1 Inspections and reports.Include a copy of all inspection verifications and reports required
<br />by the enforcing agency.
<br />1. Environmental and sustainability goals.
<br />2. Building sustainable goals.
<br />3. Indoor environmental quality requirements.
<br />4. Project program, including facility functions and hours of operation, and need for after hours
<br />operation.
<br />5. Equipment and systems expectations.
<br />6. Building occupant and operation and maintenance (O&M) personnel expectations.
<br />5.410.2.4 Functional performance testing. [N]
<br />installation and operation of each component, system and system-to-system interface in accordance with the
<br />approved plans and specifications. Functional performance testing reports shall contain information addressing
<br />each of the building components tested, the testing methods utilized, and include reading adjustments made.
<br />NTS 1CAL GREEN NOTES 2022
<br />HE
<br />R
<br />M
<br />A
<br />L
<br />A
<br />I
<br />R
<br />
<br />I
<br />N
<br />C
<br />.
<br />T
<br />pr
<br />o
<br />p
<br />o
<br />s
<br />e
<br />d
<br />
<br />c
<br />o
<br />n
<br />t
<br />r
<br />a
<br />c
<br />t
<br />,
<br />
<br />a
<br />n
<br />d
<br />
<br />i
<br />n
<br />
<br />t
<br />h
<br />e
<br />
<br />a
<br />b
<br />s
<br />e
<br />n
<br />c
<br />e
<br />
<br />o
<br />f
<br />
<br />w
<br />r
<br />i
<br />t
<br />t
<br />e
<br />n
<br />
<br />c
<br />o
<br />nt
<br />r
<br />a
<br />c
<br />t
<br />Th
<br />e
<br />
<br />w
<br />i
<br />t
<br />h
<br />i
<br />n
<br />
<br />d
<br />e
<br />s
<br />i
<br />g
<br />n
<br />s
<br />
<br />a
<br />r
<br />e
<br />
<br />a
<br />
<br />p
<br />a
<br />r
<br />t
<br />
<br />o
<br />f
<br />
<br />a
<br />
<br />p
<br />r
<br />e
<br />s
<br />e
<br />n
<br />t
<br />a
<br />t
<br />i
<br />o
<br />n
<br />
<br />f
<br />o
<br />r
<br /> a
<br />in
<br />c
<br />o
<br />r
<br />p
<br />o
<br />r
<br />a
<br />t
<br />i
<br />n
<br />g
<br />
<br />t
<br />h
<br />e
<br />m
<br />,
<br />
<br />s
<br />h
<br />a
<br />l
<br />l
<br />
<br />r
<br />e
<br />m
<br />a
<br />i
<br />n
<br />
<br />t
<br />h
<br />e
<br />
<br />e
<br />x
<br />c
<br />l
<br />u
<br />s
<br />i
<br />v
<br />e
<br />
<br />p
<br />r
<br />o
<br />p
<br />er
<br />t
<br />y
<br />of
<br />
<br />T
<br />H
<br />E
<br />R
<br />M
<br />A
<br />L
<br />A
<br />I
<br />R
<br />
<br />I
<br />N
<br />C
<br />.
<br />,
<br />
<br />a
<br />n
<br />d
<br />
<br />m
<br />a
<br />y
<br />
<br />n
<br />o
<br />t
<br />
<br />b
<br />e
<br />
<br />c
<br />o
<br />p
<br />i
<br />e
<br />d
<br />,
<br />
<br />e
<br />x
<br />h
<br />i
<br />b
<br />i
<br />t
<br />e
<br />d
<br />t
<br />o
<br />AS
<br />
<br />N
<br />O
<br />T
<br />E
<br />D
<br />TH
<br />E
<br />R
<br />M
<br />A
<br />L
<br />A
<br />I
<br />R
<br />
<br />J
<br />O
<br />B
<br />
<br />#
<br />CH
<br />E
<br />C
<br />K
<br />E
<br />D
<br />
<br />B
<br />Y
<br />:
<br />DR
<br />A
<br />W
<br />N
<br />
<br />B
<br />Y
<br />:
<br />ot
<br />h
<br />e
<br />r
<br />s
<br />
<br />o
<br />r
<br />
<br />o
<br />t
<br />h
<br />e
<br />r
<br />w
<br />i
<br />s
<br />e
<br />
<br />u
<br />s
<br />e
<br />d
<br />
<br />i
<br />n
<br />
<br />w
<br />h
<br />o
<br />l
<br />e
<br />
<br />o
<br />r
<br />
<br />i
<br />n
<br />
<br />p
<br />a
<br />r
<br />t
<br />.
<br />SC
<br />A
<br />L
<br />E
<br />
<br />:
<br />DA
<br />T
<br />E
<br />:
<br />CO
<br />N
<br />S
<br />T
<br />R
<br />U
<br />C
<br />T
<br />I
<br />O
<br />N
<br />IS
<br />S
<br />U
<br />E
<br />RE
<br />V
<br />I
<br />S
<br />I
<br />O
<br />N
<br />S
<br />SHEET:
<br />SHEET OF
<br />JO
<br />B
<br />
<br />N
<br />A
<br />M
<br />E
<br />:
<br />SH
<br />E
<br />E
<br />T
<br />
<br />T
<br />I
<br />T
<br />L
<br />E
<br />:
<br />11
<br />4
<br />0
<br />
<br />R
<br />E
<br />D
<br />
<br />G
<br />U
<br />M
<br />
<br />S
<br />T
<br />R
<br />E
<br />E
<br />T
<br />,
<br />
<br />A
<br />N
<br />A
<br />H
<br />E
<br />I
<br />M
<br />,
<br />
<br />C
<br />A
<br />L
<br />I
<br />F
<br />O
<br />R
<br />N
<br />I
<br />A
<br />
<br />9
<br />2
<br />8
<br />0
<br />6
<br />CA
<br />L
<br />I
<br />F
<br />O
<br />R
<br />N
<br />I
<br />A
<br />
<br />S
<br />T
<br />A
<br />T
<br />E
<br />
<br />L
<br />I
<br />C
<br />E
<br />N
<br />S
<br />E
<br />
<br />N
<br />U
<br />M
<br />B
<br />E
<br />R
<br />,
<br />
<br />1
<br />0
<br />2
<br />2
<br />1
<br />6
<br />PH
<br />O
<br />N
<br />E
<br />:
<br />
<br />(
<br />7
<br />1
<br />4
<br />)
<br />
<br />6
<br />3
<br />0
<br />-
<br />3
<br />2
<br />0
<br />0
<br />AI
<br />R
<br />
<br />C
<br />O
<br />N
<br />D
<br />I
<br />T
<br />I
<br />O
<br />N
<br />I
<br />N
<br />G
<br />
<br />I
<br />N
<br />D
<br />U
<br />S
<br />T
<br />R
<br />I
<br />A
<br />L
<br />
<br />R
<br />E
<br />F
<br />R
<br />I
<br />G
<br />E
<br />R
<br />A
<br />T
<br />I
<br />O
<br />N
<br />FA
<br />X
<br />:
<br />
<br />(
<br />7
<br />1
<br />4
<br />)
<br />
<br />6
<br />3
<br />0
<br />-
<br />1
<br />4
<br />2
<br />7
<br />CA
<br />L
<br />-
<br />G
<br />R
<br />E
<br />E
<br />N
<br />
<br />N
<br />O
<br />T
<br />E
<br />S
<br />M-2
<br />2
<br />09
<br />/
<br />0
<br />3
<br />/
<br />2
<br />4
<br />
<br />P
<br />L
<br />A
<br />N
<br />
<br />C
<br />H
<br />E
<br />C
<br />K
<br />
<br />R
<br />E
<br />S
<br />U
<br />B
<br />M
<br />I
<br />T
<br />T
<br />A
<br />L
<br />Ol
<br />i
<br />v
<br />e
<br />
<br />C
<br />r
<br />e
<br />s
<br />t
<br />21
<br />3
<br />0
<br />
<br />E
<br />.
<br />
<br />4
<br />
<br />T
<br />H
<br />
<br />S
<br />T
<br />.
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />5
<br />Pr
<br />o
<br />j
<br />e
<br />c
<br />t
<br />
<br />N
<br />u
<br />m
<br />b
<br />e
<br />r
<br />GW RP
<br />09
<br />/
<br />0
<br />3
<br />/
<br />2
<br />0
<br />2
<br />4
<br />7
<br />A
<br />DIGITAL
<br />SIGNATURE
<br />9-9-2024
<br />2130 E 4th St
<br />2/11/2025
|