1.01 GENERAL REQUIREMENTS <br />PART 1 GENERAL <br />A.ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE CALIFORNIA ELECTRICAL CODE, THE CALIFORNIA BUILDING CODE, CITY AMENDMENTS, BUILDING <br />MANAGEMENT AND ALL AUTHORITIES HAVING JURISDICTION (AHJ). APPLICABLE NATIONAL, STATE AND LOCAL CODES, LAWS AND REGULATIONS GOVERNING OR <br />RELATING TO ANY PORTION OF THIS WORK SHALL BE INCORPORATED INTO AND MADE A PART OF THESE SPECIFICATIONS. <br />B.IF A CONFLICT OCCURS IN THE SPECIFICATIONS AND/OR ON THE DRAWINGS, THE MORE STRINGENT SITUATION SHALL APPLY. <br />C.ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF THIS WORK. FINAL ACCEPTANCE <br />SHALL BE DEFINED AS THE TIME AT WHICH THE ELECTRICAL WORK IS TAKEN OVER AND ACCEPTED BY THE OWNER. ENGAGE THE SERVICES OF VARIOUS <br />MANUFACTURERS SUPPLYING THE EQUIPMENT FOR THE PROPER STARTUP, TRAINING AND OPERATION OF ALL SYSTEMS INSTALLED. INSTRUCT THE OWNERS <br />PERSONNEL IN THE PROPER OPERATION AND SERVICING OF THE EQUIPMENT. <br />D.ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE CAREFULLY THE EXISTING AREAS AFFECTED BY THIS WORK TO BECOME FAMILIAR WITH EXISTING <br />CONDITIONS AND WITH DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT <br />SUCH AN EXAMINATION HAS BEEN MADE AND LATER CLAIMS WILL NOT BE RECOGNIZED FOR EXTRA LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF <br />DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH AN EXAMINATION BEEN UNDERTAKEN. <br />E.DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF ALL DEVICES <br />INCLUDING DIMENSIONS AND ELEVATIONS. WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID CONFLICTS. <br />F.ALTHOUGH NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN ON THE DRAWINGS, ANY EQUIPMENT, MATERIALS, ACCESSORIES, OR LABOR REQUIRED FOR <br />PROPER AND COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHALL BE FURNISHED AND INSTALLED AS PART OF THE ORIGINAL BID. <br />G.THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING THE LATEST COPY OF THE BUILDING RULES AND REGULATIONS. BASE BUILDING SYSTEM <br />INTERRUPTIONS ARE TO BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS. COORDINATE WITH BUILDING OWNER FOR ANY SERVICE INTERRUPTION OF <br />EXISTING SYSTEMS AND GIVE NOTICE AS REQUIRED BY BUILDING RULES AND REGULATIONS. <br />H.ANY DAMAGE TO EXISTING PARTITIONS, FLOORS, CEILINGS OR ANY PART OF THE BUILDING OR EQUIPMENT HOUSED THEREIN CAUSED BY THE WORK OF THE <br />CONTRACTOR SHALL BE REPAIRED AT NO ADDITIONAL EXPENSE TO THE OWNER. <br />I.ALL NEW MATERIALS REQUIRED SHALL CONFORM WITH THE STANDARDS OF THE UNDERWRITERS LABORATORIES, INC. (UL) IN EVERY CASE WHERE SUCH A <br />STANDARD EXISTS. <br />J.DURING THE PROJECT DURATION, THE BUILDING MANAGEMENT OFFICE AND ITS DESIGNATED REPRESENTATIVE SHALL BE ABLE TO INSPECT THE WORK IN <br />PROGRESS. ANY WORK WHICH THE BUILDING MANAGEMENT DEEMS UNACCEPTABLE SHALL BE REMOVED AND REPLACED AT THE EXPENSE OF <br />CONTRACTOR/TENANT. <br />K.ALL EQUIPMENT INSTALLED OR CONNECTED INTO THE BUILDING RISERS, SYSTEMS AND INFRASTRUCTURE SHALL BE APPROVED IN ADVANCE BY THE BUILDING <br />PRIOR TO INSTALLATION. <br />1.02 SCOPE OF WORK <br />A.PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR COMPLETE, SAFE INSTALLATION OF ALL ELECTRICAL WORK. THE SCOPE OF WORK SHALL <br />INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: <br />1.INSTALLATION OF LIGHTING FIXTURES AND LAMPS INCLUDING EXIT AND EMERGENCY LIGHTING. <br />2.INSTALLATION OF RECEPTACLES, VOICE/DATA, OUTLETS, ETC. <br />3.INSTALLATION OF NEW RACEWAY AND CONDUCTORS FOR LIGHTING AND POWER. <br />4.INSTALLATION OF LIGHTING CONTROL SYSTEM COMPLETE WITH DEVICES, CONTROLLERS, SENSORS, WIRING AND CODE MANDATED ACCEPTANCE TESTING. <br />5.ADDITION OR MODIFICATION OF EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT. <br />6.INSTALLATION OF MECHANICAL EQUIPMENT FEEDERS AND FINAL CONNECTIONS TO MECHANICAL EQUIPMENT. <br />7.GROUNDING OF ALL EQUIPMENT AS REQUIRED BY CODE AND AS SPECIFIED. <br />8.MODIFICATION OF EXISTING FIRE ALARM SYSTEM. <br />9.TEMPORARY LIGHTING AND POWER DURING CONSTRUCTION. <br />10.CUTTING, CHANNELING, CORING, AND CHASING REQUIRED TO ACCOMMODATE ELECTRIC INSTALLATION AND ROUGH PATCHING. <br />11.DEMOLITION AND REMOVAL OF ELECTRICAL EQUIPMENT AS REQUIRED INCLUDING ALL CONDUCTORS AND CONDUIT BACK TO THEIR SOURCE. <br />12.MAINTENANCE AND PROPER OPERATION OF EXISTING BASE BUILDING SYSTEMS WITHIN THE CONTRACT AREA IN ACCORDANCE WITH THE REQUIREMENTS <br />OF BUILDING MANAGEMENT. <br />13.PROVISION OF SECURITY SYSTEM INFRASTRUCTURE AS DETAILED. <br />14.PROVISION OF AUDIO VISUAL SYSTEM INFRASTRUCTURE AS DETAILED. <br />15.RECEIPT AND INSTALLATION OF DEVICES, EQUIPMENT, SYSTEMS, SUPPLIED BY OTHERS AS DETAILED. <br />16.COORDINATION WITH OTHER TRADES. <br />1.03 SUBSTITUTIONS <br />1.04 SHOP DRAWINGS <br />A.SHOP DRAWINGS SUBMISSION SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: <br />1.DISTRIBUTION EQUIPMENT (PANELS, SWITCHES, ETC.) <br />2.OVERCURRENT PROTECTIVE DEVICES (FUSES AND BREAKERS) <br />3.LIGHTING FIXTURES <br />4.WIRING DEVICES <br />5.FIRE ALARM EQUIPMENT, WIRING SCHEMATIC AND SEQUENCE OF OPERATION <br />6.FLOOR BOXES/ POKE THRU DEVICES <br />7.GROUNDING EQUIPMENT/DEVICES <br />8.CONDUIT, RACEWAYS, WIREWAYS <br />9.WIRING <br />10.LIGHTING CONTROL SYSTEMS AND DEVICES <br />11.TESTING AND COMMISSIONING SCHEDULE <br />12.TRANSFORMERS <br />13.UNINTERRUPTIBLE POWER SUPPLIES (UPS) <br />14.EMERGENCY LIGHTING INVERTERS <br />1.05 QUALITY ASSURANCE <br />A.NO SUBSTITUTE MATERIAL OR MANUFACTURER OF EQUIPMENT SHALL BE PERMITTED WITHOUT A FORMAL WRITTEN SUBMITTAL TO THE ENGINEER WHICH <br />INCLUDES ALL DIMENSIONAL, PERFORMANCE AND MATERIAL SPECIFICATIONS. <br />B.ANY CHANGES IN LAYOUT, MECHANICAL CHARACTERISTICS, STRUCTURAL REQUIREMENTS, OR DESIGN DUE TO THE USE OF A SUBSTITUTION SHALL BE SUBMITTED <br />TO THE ENGINEER AS PART OF THIS PROPOSAL. THE CONTRACTOR TAKES FULL RESPONSIBILITY FOR THE SUBSTITUTION AND ALL CHANGES RESULTING FROM <br />SUBSTITUTION. <br />C.ALL ITEMS SHALL BE SUBMITTED FOR REVIEW IN CONJUNCTION WITH THE SUBMITTAL OF THE ALTERNATE. ANY SUBSTITUTION MUST BE SUBMITTED WITH AN <br />EXPLANATION WHY SUBSTITUTION IS BEING UTILIZED. IF THE SUBSTITUTED ITEM DEVIATES FROM THE SPECIFIED ITEM, THOSE DEVIATIONS ARE TO BE IDENTIFIED <br />ON A LINE BY LINE BASIS. IF THE SUBSTITUTION IS BEING UTILIZED FOR FINANCIAL REASONS, THE ASSOCIATED CREDIT MUST BE SIMULTANEOUSLY SUBMITTED. <br />D.ALL SUBSTITUTED EQUIPMENT SHALL CONFORM TO SPACE REQUIREMENTS AND PERFORMANCE REQUIREMENTS SHOWN ON CONTRACT DOCUMENTS. <br />E.CONTRACTOR SHALL SUBMIT BID BASED ON SPECIFIED ITEMS AND SHALL SUPPLY, AS AN ALTERNATE PRICE, ANY SUBSTITUTIONS. <br />A.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY <br />ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, AND MARKED FOR INTENDED USE. <br />B.COMPLY WITH NFPA 70. <br />A.COORDINATE CHASES, SLOTS, INSERTS, SLEEVES, AND OPENINGS WITH GENERAL CONSTRUCTION WORK AND ARRANGE IN BUILDING STRUCTURE DURING <br />PROGRESS OF CONSTRUCTION TO FACILITATE THE ELECTRICAL INSTALLATIONS THAT FOLLOW. <br />B.SET INSERTS AND SLEEVES IN POURED-IN-PLACE CONCRETE, MASONRY WORK, AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED. <br />C.SEQUENCE, COORDINATE, AND INTEGRATE INSTALLING ELECTRICAL MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. COORDINATE INSTALLING <br />LARGE EQUIPMENT REQUIRING POSITIONING BEFORE CLOSING IN THE BUILDING. <br />D.COORDINATE LOCATION OF ACCESS PANELS AND DOORS FOR ELECTRICAL ITEMS THAT ARE CONCEALED BY FINISHED SURFACES. ACCESS DOORS AND PANELS <br />ARE SPECIFIED BY THE ARCHITECT. <br />E.WHERE ELECTRICAL IDENTIFICATION DEVICES ARE APPLIED TO FIELD-FINISHED SURFACES, COORDINATE INSTALLATION OF IDENTIFICATION DEVICES WITH <br />COMPLETION OF FINISHED SURFACE. <br />F.WHERE ELECTRICAL IDENTIFICATION MARKINGS AND DEVICES WILL BE CONCEALED BY ACOUSTICAL CEILINGS AND SIMILAR FINISHES, COORDINATE INSTALLATION <br />OF THESE ITEMS BEFORE CEILING INSTALLATION. <br />1.07 AS-BUILT DRAWINGS <br />A.CONTRACTOR SHALL MAINTAIN RECORD DRAWING PRINTS ON JOB SITE AND RECORD, AT TIME OF OCCURRENCE, DEVIATIONS FROM CONTRACT DOCUMENTS. <br />B.AT THE COMPLETION OF WORK AND BEFORE FINAL ACCEPTANCE, PROVIDE AS-BUILT DRAWINGS OF THE INSTALLATION, IN AUTO-CAD. AN ELECTRONIC COPY <br />(AUTOCAD FORMAT) OF ALL DRAWINGS WILL BE PROVIDED TO THE ELECTRICAL CONTRACTOR BY THE CONSULTANT AT NO COST. THE DRAWINGS WILL REFLECT <br />THE BID AND/OR CONSTRUCTION SET OF DRAWINGS. <br />C.INCORPORATE ALL CHANGES AND DEVIATIONS FROM BID DRAWINGS, UTILIZING NORMAL RECOGNIZED DRAFTING PROCEDURES THAT MATCH THE ORIGINAL <br />DRAFTING METHODOLOGY. <br />D.ALL MAIN BRANCH CONDUIT RUNS, JUNCTION BOX LOCATIONS, CONDUIT RUNS FOR ALL FLOOR OUTLETS, ETC., MUST BE REFLECTED ON THE DRAWINGS. <br />E.REMOVE ALL ELECTRICAL ENGINEER'S DRAWING DIRECTIVE NOTES TO CONTRACTOR. <br />F.CLEARLY INDICATE THE WORDS “AS-BUILT” IN THE TITLE BLOCK COLUMN OF THE DRAWINGS AS WELL AS THE ELECTRICAL CONTRACTOR'S NAME AND ADDRESS. <br />G.WHEN FOUND ACCEPTABLE BY THE CONSULTANT, SUBMIT THREE (3) SETS OF PRINTS TOGETHER WITH THE CAD DISK FOR PRESENTATION TO THE LANDLORD AND <br />TENANT. <br />1.06 COORDINATION <br />1.12 LOCATIONS OF OUTLETS <br />A.REFER TO DESIGN CONSULTANT'S/ARCHITECT'S DRAWINGS FOR EXACT LOCATIONS OF ALL LIGHTING FIXTURES AND WIRING DEVICES. <br />B.CHANGE LOCATION OF OUTLETS AT NO COST OR CREDIT, PROVIDING DISTANCE DOES NOT EXCEED (10'-0") AND INFORMATION IS GIVEN PRIOR TO INSTALLATION. <br />C.ALL OUTLETS TO BE MARKED ON JOB SITE FOR APPROVAL BY DESIGN CONSULTANT/ARCHITECT PRIOR TO INSTALLATION. <br />1.13 PLYWOOD <br />A.PLYWOOD BACKBOARDS SHALL BE 3/4” THICK, OF HIGHEST QUALITY FIRE RETARDANT FIR. <br />B.PRIME AND PAINT BACKBOARDS WITH FIRE RETARDANT PAINT COLOR AS SELECTED BY THE DESIGN CONSULTANT/ARCHITECT. <br />1.15 NOISE AND VIBRATION <br />A.ELECTRICAL EQUIPMENT IS TO OPERATE WITHOUT OBJECTIONABLE NOISE OR VIBRATION. IF, IN THE OPINION OF THE LANDLORD, ARCHITECT OR CONSULTANT, <br />THE EQUIPMENT OPERATES WITH EXCESSIVE NOISE OR VIBRATION, THEN THE EQUIPMENT MUST BE REPLACED OR NOISE OR VIBRATION ELIMINATED. <br />B.CONNECTIONS TO NOISE-PRODUCING AND VIBRATING EQUIPMENT MUST BE MADE WITH LIQUID-TIGHT FLEXIBLE CONDUIT AND ASSOCIATED CONNECTORS. THIS <br />INCLUDES TRANSFORMERS, DIMMING EQUIPMENT RACKS, AND MOTORS. USE A MINIMUM OF 3 FT OF FLEXIBLE CABLE WITH SLACK AT EACH DEVICE. <br />C.VIBRATION ISOLATORS ARE TO BE PROVIDED WHERE INDICATED OR REQUIRED. TRANSFORMERS TO BE ISOLATED FROM THE STRUCTURE, WITH SPRING AND <br />RUBBER ISOLATORS WHEN WALL MOUNTED OR SUSPENDED AND 1/2" HIGH DENSITY NEOPRENE SANDWICH PADS (TYPE MWP) WHEN FLOOR MOUNTED. <br />1.16 TENANT'S EQUIPMENT <br />A.WHERE SPECIFIED, INSTALL ALL EQUIPMENT PROVIDED BY THE TENANT. RECEIVE, STORE AND INSTALL EQUIPMENT AND ACCEPT FULL RESPONSIBILITY FOR ITS <br />CORRECT OPERATION. PROVIDE CONDUIT, WIRE, BOXES, SWITCHES, OUTLETS, DEVICES, FLEX CONNECTIONS, ETC., AS REQUIRED. <br />1.17 INTERRUPTION OF SERVICES <br />A.INTERRUPTION OF ELECTRICAL SERVICE TO ANY PART OF THE BUILDING SHALL OCCUR ONLY BY PRE-ARRANGEMENT WITH AND AT TIMES SUITABLE TO THE <br />LANDLORD. <br />B.INTERRUPTIONS SHALL ONLY OCCUR DURING PREMIUM TIME PERIODS; ALL ALLOWANCES FOR THIS SHALL BE INCLUDED IN THE PRICE SUBMITTED. <br />1.18 ENGINEERS FINAL INSPECTION <br />A.FINAL INSPECTION IS IMPERATIVE. PRIOR TO CLOSING OF CEILINGS, THIS CONTRACTOR SHALL CONTACT AMA CONSULTING ENGINEERS. (310-846-4666) AND THE <br />LANDLORD'S REPRESENTATIVE TO PERFORM A FINAL INSPECTION. WHEN CEILING TILES HAVE BEEN INSTALLED IT WILL BE NECESSARY FOR THE CONTRACTOR TO <br />REMOVE PORTIONS FOR INSPECTION. <br />1.19 COMPLETION OF CONTRACT <br />A.ALL EQUIPMENT MUST BE CLEANED AND TESTED BEFORE FINAL ACCEPTANCE BY THE CONSULTANT. <br />B.DEFECTS AND DEFICIENCIES WHICH ORIGINATE OR BECOME EVIDENT DURING THE WARRANTY PERIOD MUST BE REPAIRED OR REPLACED, AT NO COST. <br />C.IF, DURING THE WARRANTY PERIOD, TRANSFORMERS, BALLASTS, DRIVERS OR OTHER NOISE AND VIBRATION PRODUCING EQUIPMENT ARE CONSIDERED BY THE <br />CONSULTANT TO EXCEED ACCEPTABLE STANDARDS, THEN THEY MUST BE REPLACED WITHOUT DELAY OR ADDITIONAL COST TO THE TENANT. ALL WORK RELATING <br />TO THE REPLACEMENT OF DEFECTIVE ITEMS, MUST BE CARRIED OUT AFTER NORMAL WORKING HOURS AND AT A TIME WHICH IS ACCEPTABLE TO THE TENANT. <br />1.09 MATERIALS AND EQUIPMENT <br />A.ALL MATERIALS AND EQUIPMENT SHALL BE NEW, CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY AND MANUFACTURED TO THE STANDARDS <br />SPECIFIED. <br />PART 2 PRODUCT/APPLICATION <br />2.02 WIRE AND CABLE <br />A.CONDUCTORS, NO. 10 AWG AND SMALLER: SOLID COPPER. <br />B.CONDUCTORS, LARGER THAN NO. 10 AWG: STRANDED COPPER. <br />C.INSULATION: THERMOPLASTIC, RATED AT 75 DEG C MINIMUM. <br />D.MULTICONDUCTOR CABLE: COMPLY WITH NEMA WC 70 FOR METAL-CLAD CABLE, TYPE MC WITH GROUND WIRE. <br />E.FACTORY-FABRICATED CONNECTORS AND SPLICES OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE INDICATED. <br />F.FEEDERS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG AND LARGER. <br />G.BRANCH CIRCUITS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG AND LARGER. <br />H.METAL-CLAD CABLE (TYPE MC) MAY BE USED FOR COMPLETELY CONCEALED BRANCH CIRCUITRY FROM J-BOX TO OUTLETS OR LIGHTS AND WHERE PERMITTED BY <br />CODE AND ONLY IN TENANT SPACE. HOMERUNS FROM J-BOX TO PANELBOARD SHALL BE EMT. <br />I.METAL-CLAD CABLE MAY NOT BE USED FOR UPS-SUPPORTED WIRING OR FOR EMERGENCY WIRING. <br />2.03 SUPPORTING DEVICES <br />A.MATERIAL: COLD-FORMED STEEL, WITH CORROSION-RESISTANT COATING ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. <br />B.METAL ITEMS FOR USE OUTDOORS OR IN DAMP LOCATIONS: HOT-DIP GALVANIZED STEEL. <br />C.SLOTTED-STEEL CHANNEL SUPPORTS: FLANGE EDGES TURNED TOWARD WEB, AND 9/16-INCH DIAMETER SLOTTED HOLES AT A MAXIMUM OF 2 INCHES O.C., IN <br />WEBS. CHANNEL THICKNESS: SELECTED TO SUIT STRUCTURAL LOADING. <br />D.FITTINGS AND ACCESSORIES: PRODUCTS OF THE SAME MANUFACTURER AS CHANNEL SUPPORTS. <br />E.RACEWAY AND CABLE SUPPORTS: MANUFACTURED CLEVIS HANGERS, RISER CLAMPS, STRAPS, THREADED C-CLAMPS WITH RETAINERS, CEILING TRAPEZE <br />HANGERS, WALL BRACKETS, AND SPRING-STEEL CLAMPS OR CLICK-TYPE HANGERS. <br />F.PIPE SLEEVES: ASTM A 53, TYPE E, GRADE A, SCHEDULE 40, GALVANIZED STEEL, PLAIN ENDS. <br />G.CABLE SUPPORTS FOR VERTICAL CONDUIT: FACTORY-FABRICATED ASSEMBLY CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG FOR <br />NON-ARMORED ELECTRICAL CABLES IN RISER CONDUITS. PLUGS HAVE NUMBER AND SIZE OF CONDUCTOR GRIPPING HOLES AS REQUIRED TO SUIT INDIVIDUAL <br />RISERS. BODY CONSTRUCTED OF MALLEABLE-IRON CASTING WITH HOT-DIP GALVANIZED FINISH. <br />H.EXPANSION ANCHORS: CARBON-STEEL WEDGE OR SLEEVE TYPE. <br />I.TOGGLE BOLTS: ALL-STEEL SPRINGHEAD TYPE. <br />J.POWDER-DRIVEN THREADED STUDS: HEAT-TREATED STEEL. <br />K.EXCEPT FOR BRANCH CIRCUITRY INSTALL ALL CONDUIT IN HUNG CEILING SPACE ON ACCEPTABLE HANGERS AND INSERTS. CONDUIT OR MC CABLE FOR BRANCH <br />CIRCUITRY SHALL BE SUPPORTED BY CLAMPS OR PIPE STRAPS SECURED TO THE CEILING SUPPORT SYSTEM, FROM STRUCTURAL MEMBERS OR FROM THE DECK. <br />SUPPORT FROM CEILING TEES, CROSS TEES OR SUPPORT WIRES IS PROHIBITED. <br />L.SPACING OF SUPPORTS SHALL BE PER THE NEC/CEC. <br />M.INSERTS ARE TO BE OF A LEAD SHIELD TYPE. <br />N.HANGERS MUST NOT BE WELDED TO STRUCTURAL STEEL MEMBERS AND BURNING OF HOLES IN STRUCTURAL STEEL IS PROHIBITED. <br />O.SLEEVES ARE TO BE OF A TYPE SUITABLE FOR THE APPLICATION AND BE SEALED AND MADE WATERTIGHT. SLEEVES THROUGH CONCRETE SHALL BE SCHEDULE 40 <br />STEEL PIPE, SIZED FOR FREE PASSAGE OF CONDUIT AND INSTALLED FLUSH WITH UNDERSIZE OF CONCRETE SLAB AND EXTEND 4" ABOVE FINISHED FLOOR UNLESS <br />OTHERWISE NOTED. <br />2.04 PULLBOXES, JUNCTION BOXES AND OUTLET BOXES <br />A.PULLBOXES, JUNCTION BOXES AND OUTLET BOXES SHALL BE MANUFACTURED FROM GALVANIZED INDUSTRY STANDARD GAUGE SHEET STEEL. <br />B.PROVIDE PULL BOXES AND JUNCTION BOXES IN LONG STRAIGHT RUNS OF RACEWAY TO ASSURE THAT CABLES ARE NOT DAMAGED WHEN THEY ARE PULLED, TO <br />FULFILL REQUIREMENTS AS TO THE NUMBER OF BENDS PERMITTED IN RACEWAY BETWEEN CABLE ACCESS POINTS, THE ACCESSIBILITY OF CABLE JOINTS AND <br />SPLICES, AND THE APPLICATION OF CABLE SUPPORTS. <br />C.PULLBOXES AND JUNCTION BOXES SHALL BE SIZED SO THAT THE MINIMUM BENDING RADIUS CRITERIA SPECIFIED FOR THE WIRES AND CABLE ARE MAINTAINED. <br />D.SWITCH RECEPTACLE AND WALL OUTLET BOXES SHALL BE A NOMINAL 4" SQUARE, 1-1/2" OR 2-1/8" DEEP AS REQUIRED BY CODE WITH A RAISED COVER, UNLESS <br />OTHERWISE INDICATED ON THE DRAWING. <br />E.PROVIDE BLANK COVERPLATES FOR BOXES WITHOUT WIRING DEVICES. <br />F.DO NOT INSTALL OUTLET BOXES BACK TO BACK IN PARTITIONS. STAGGER TO PREVENT SOUND TRANSFER. <br />G.TWO OR MORE OUTLET BOXES THAT OCCUR AT THE SAME LOCATION SHALL BE GANGED TOGETHER IN THE SAME COVERPLATE UNLESS OTHERWISE NOTED. <br />H.LIGHTING FIXTURE BOXES SHALL BE 4" OCTAGON TYPE, DEPTH AS REQUIRED WITH 3/8" FIXTURE STUD. FOR SUSPENDED CEILING WORK, PROVIDE A 4" OCTAGON <br />BOX WITH REMOVABLE BACKPLATE WHERE REQUIRED. <br />I.PULL/JUNCTION BOX BARRIERS SHALL BE PROVIDED WHERE REQUIRED BY CODE. <br />J.INSTALL JUNCTION AND PULLBOXES IN INCONSPICUOUS LOCATIONS. <br />K.A MINIMUM OF ONE PULLBOX SHALL BE INSTALLED FOR EVERY 100 FT OF CONDUITS. (NOTE: EACH 90 DEGREE BEND SHALL EQUATE TO 30' LENGTH OF CONDUIT). <br />L.NO MORE THAN TWO (2) 90 DEGREE BENDS SHALL BE INSTALLED BETWEEN AND TWO ADJACENT PULLBOXES. <br />M.ALL EQUIPMENT, DEVICE BOXES, JUNCTION BOXES, PULLBOXES AND OUTLET BOXES SHALL BE INSTALLED TO ALLOW ACCESS TO THE BOX. <br />N.OUTLET BOXES SHALL BE PROVIDED FOR ALL LOW VOLTAGE DEVICES (I.E. TELEPHONE/DATA, SECURITY, FIRE ALARM, ETC.). COORDINATE BOX SIZE AND DEPTH <br />WITH RESPECTIVE VENDOR. <br />2.05 WIRING DEVICES <br />A.WIRING DEVICES SHALL BE SPECIFICATION GRADE, DECORATIVE STYLE, UNLESS OTHERWISE NOTED. <br />B.DEVICES GANGED TOGETHER IN MULTI-GANG BOX SHALL BE MOUNTED UNDER A SINGLE COVERPLATE. <br />C.DEVICE COLORS SHALL BE AS APPROVED BY ARCHITECT. DEVICE AND FACEPLATE SHALL MATCH. <br />D.LINE VOLTAGE SWITCHES SHALL BE 120/277 VOLTS, RATED AT 20 AMPERES, QUIET OPERATION ROCKER TYPE, DECORA STYLE. <br />E.RECEPTACLES <br />1.PROVIDE SPECIFICATION GRADE 20A. 120 VOLT, "U" GROUND RECEPTACLES, WITH MATCHING COVERPLATES. RECEPTACLES SHALL BE OF THE “DECORATOR <br />STYLE”. <br />2.REFER TO NOTES AND DETAILS FOR SPECIALITY RECEPTACLE COLORS AND MARKINGS. <br />3.RECEPTACLES TO HAVE CIRCUIT NUMBER IDENTIFIED ON THE WALL PLATE AND FURTHER IDENTIFIED WITH THE EXACT LOCATION LISTED IN THE PANEL <br />DIRECTORY. <br />4.RECEPTACLES CONTROLLED FOR COMPLIANCE WITH TITLE 24 SHALL BE LABELED WITH NEMA APPROVED MARKINGS. <br />2.06 DISCONNECT SWITCHES <br />A.INDOOR DISCONNECT SWITCHES SHALL BE "QUICK-MAKE, QUICK-BREAK," HEAVY DUTY TYPE IN NEMA 1 ENCLOSURES. PROVIDE ALL FUSES WHERE NOTED. <br />B.OUTDOOR DISCONNECT SWITCHES SHALL BE SIMILAR TO INDOOR, EXCEPT LISTED FOR OUTDOOR APPLICATIONS (NEMA 3R OR 4, AS REQUIRED). <br />C.FUSED DISCONNECT SWITCHES SHALL BE PROVIDED WITH FUSE CLIPS TO ACCEPT SPECIFIED FUSES. <br />2.07 FUSES <br />A.FUSES SHALL BE CURRENT LIMITING TYPE WITH A UL LISTED INTERRUPTING CAPACITY OF 200,000 RMS. <br />B.FUSES RATED 601 AMPS AND LARGER SHALL BE CURRENT-LIMITING, TIME-DELAY, UL CLASS L FUSES. <br />C.FUSES RATED 600 AMPS AND BELOW SHALL BE CUREENT-LIMITING, DUAL-ELEMENT, TTIME-DELAY UL CLASS RK-1 FOR NON-MOTOR CIRCUITS AND UL CLASS RK-5 <br />FOR MOTOR CIRCUITS. <br />D.ALL FUSES SHALL BE OF THE SAME MANUFACTURER. <br />2.09 PANELBOARDS <br />A.PANELBOARD BOXES SHALL BE MADE OF SHEET STEEL "BENT-UP" OR RIVETED OR BOLTED TOGETHER WITH EXTERIOR ANGLE IRON FRAME. BOX SHALL BE OF <br />SUFFICIENT SIZE TO ALLOW A GUTTER AT LEAST 6" IN WIDTH ENTIRELY SURROUNDING EACH SECTION OF BOARD. PANELBOARDS SHALL BE SURFACE OR FLUSH <br />TYPE AS NOTED ON THE DRAWINGS. PANEL BOX AND COVER SHALL BE GIVEN TWO COATS OF GRAY ENAMEL PAINT. <br />B.PROVIDE CODE GAUGE STEEL DOORS FOR ALL PANELBOARD BOXES. FRONT COVER SHALL BE A "DOOR WITHIN A DOOR" TYPE. THE OUTER DOOR (TRIM) SHALL <br />ALLOW ACCESS TO ENTIRE PANELBOARD BOX INCLUDING GUTTER SPACES. OUTER DOOR (TRIM) SHALL BE ATTACHED DIRECTLY TO BOX BY A FULL-LENGTH <br />PIANO-HINGE. THE INNER DOOR SHALL ALLOW ACCESS TO CIRCUIT BREAKERS ONLY. PROVIDE LOCK AND SET OF KEYS FOR INNER DOOR PER PANELBOARD. <br />C.PROVIDE A COPPER EQUIPMENT GROUND BAR IN EACH PANEL, AND A COPPER ISOLATED GROUND BAR AS NOTED. <br />D.PANELS SHALL BE PROVIDED WITH NEUTRAL BARS SIZED AT 200% OF THE PHASE BUS BARS. <br />E.ALL MAIN BREAKERS SHALL BE SEPARATELY MOUNTED ON TOP OR BOTTOM OF PANEL TO SUIT CABLE ENTRY. <br />F.ALL FLOOR MOUNTED DISTRIBUTION EQUIPMENT, INCLUDING PANELBOARDS AND/OR DISTRIBUTION PANELBOARDS SHALL BE INSTALLED ON A 4” HIGH CONCRETE <br />BASE TO EXTEND 2” ON ALL SIDES WITH CHAMFERED CORNERS. ALL CONCRETE WORK TO BE INCLUDED, IN THIS DIVISION. <br />G.A TYPEWRITTEN LIST OF CIRCUITS SHOWING CLEARLY THE LOADS SUPPLIED BY EACH CIRCUIT SHALL BE INSTALLED ON THE INSIDE OF EACH PANEL BOARD DOOR. <br />THIS LIST SHALL BE MOUNTED IN A STEEL FRAME UNDER A PLASTIC WINDOW. EACH PANEL SHALL BE EXTERNALLY TAGGED WITH PERMANENT LAMACOID PLATE <br />INDICATING PANEL DESIGNATION AND VOLTAGE. PANEL DIRECTORY SHALL BE SUBMITTED TO ENGINEER FOR REVIEW AND APPROVAL PRIOR TO INSTALLING IN <br />PANELBOARD. LOAD DESCRIPTION SHALL INCLUDE COLUMN GRID LINES, ROOM NUMBERS, OR OTHER INFORMATION TO CLEARLY DISTINGUISH LOAD LOCATION. <br />H.PHASE LEGS OF ALL PANELS SHALL BE BALANCED AT SUPPLY POINT TO WITHIN 10% AFTER ALL CIRCUITS ARE WIRED AND LOADS CONNECTED. <br />2.12 LIGHT FIXTURES <br />A.LIGHT FIXTURE MOUNTING HARDWARE SHALL MATCH AND BE COORDINATED WITH THE NEW CEILING SYSTEM TYPE. ALL FIXTURES SHALL BE EQUIPPED WITH <br />"EARTHQUAKE" CLIPS. <br />B.LIGHT FIXTURES SHALL BE INSTALLED WITH SEISMIC BRACING WHERE REQUIRED. <br />C.FIXTURES SHALL BE FREE OF LIGHT LEAKS BELOW CEILING. <br />D.REFER TO ARCHITECTURAL DRAWINGS FOR ALL LIGHTING FIXTURE SPECIFICATIONS. <br />E.FIXTURES SHALL BE COMPLETE WITH NEW LAMPS, BALLASTS, DRIVERS, ACCESSORIES AND MOUNTING APPURTENANCES. <br />F.ALL LIGHT FIXTURES SHALL BE U.L. APPROVED. <br />G.CONTRACTOR SHALL AIM AND ADJUST ALL LIGHT FIXTURES IN PRESENCE OF LIGHTING CONSULTANT. <br />2.13 GROUNDING <br />A.PROVIDE SUPPLEMENTARY GROUND BONDING WHERE METALLIC CONDUITS TERMINATE AT METAL CLAD EQUIPMENT (OR AT THE METAL PULL BOX OF EQUIPMENT) <br />FOR WHICH A GROUND BUS IS SPECIFIED WITH A BUSHING OF THE GROUNDING TYPE CONNECTED INDIVIDUALLY TO GROUND BUS. <br />B.GROUND ALL EQUIPMENT IN ACCORDANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. PROVIDE SEPARATE GREEN INSULATED GROUND <br />CONDUCTOR IN EVERY CONDUIT TO ALL DEVICES, LIGHTING FIXTURES AND FEEDERS (PANELBOARDS, DISCONNECT SWITCHES, ETC.). <br />C.ALL GROUND WIRES SHALL BE SUITABLY PROTECTED FROM MECHANICAL INJURY. <br />D.SPECIALTY GROUNDING AS DETAILED ON THE DESIGN DRAWINGS OR REQUESTED AS ELECTRICAL CONTRACTOR SCOPE BY OTHER CONSULTANTS DOCUMENTS. <br />2.14 MOTORS AND APPARATUS FURNISHED BY OTHERS <br />A.INSTALL ALL WIRING IN CONDUITS. CONNECT CONDUIT TO MOTOR CONDUIT TERMINAL BOXES WITH 18" TO 24" OF FLEXIBLE CONDUIT FROM END OF CONDUIT TO <br />MOTOR TERMINAL BOX. <br />B.PROVIDE CONNECTIONS TO ALL "EXISTING TO BE RELOCATED" AS WELL AS NEW MOTORS, CONTROLLERS, DISCONNECTS, ACTUATING AND CONTROL DEVICES. <br />CONDUCTORS TO MOTORS TO BE THE SAME AS TO CONTROLLERS EXCEPT AS NOTED. <br />C.ASCERTAIN EXACT LOCATIONS OF CONTROLLERS AND CONTROL SERVICES PRIOR TO INSTALLATION AND PULLING WIRING. <br />D.COORDINATE WITH ALL OTHER TRADES AND PROVIDE ALL WIRING, CONDUIT, JUNCTION BOXES, DISCONNECTS, CONNECTIONS AND TERMINATIONS. CONTRACTOR <br />SHALL BE RESPONSIBLE FOR PROPER WIRING AND NECESSARY ELECTRICAL ADJUSTMENTS AS REQUIRED BY THE EQUIPMENT SPECIFICATION. <br />E.CONFIRM ELECTRICAL REQUIREMENTS AND EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT PRIOR TO INSTALLATION. <br />2.15 LIGHTING CONTROL SYSTEMS <br />A.MANUFACTURER OF CONTROL SYSTEM MUST VERIFY TYPE, QUANTITIES, PLACEMENT OF DEVICES TO MEET DESIGN INTENT AND TITLE 24 CODE COMPLIANCE, AND <br />PROVIDE SHOP DRAWINGS FOR APPROVAL. THIRD PARTY TAKE-OFFS OR LAYOUTS WILL NOT BE ACCEPTED. <br />B.OCCUPANCY AND DAYLIGHT SENSORS QUANTITY AND LOCATIONS SHOWN ON DRAWINGS ARE FOR INTENT ONLY. PROVIDE APPROPRIATE QUANTITY AND LOCATION <br />OF DEVICES FOR ADEQUATE COVERAGE. <br />C.CONTRACTOR SHALL COORDINATE APPROPRIATE INTERFACE DEVICES REQUIRED TO MATCH THE LIGHT FIXTURE LAMP AND CONTROL TECHNOLOGY PER LIGHT <br />MANUFACTURER'S RECOMMENDATIONS. <br />D.LIGHTING CONTROL SWITCHES SHALL CONTAIN THE EXACT QUANTITY OF PUSH BUTTONS TO CONTROL THE QUANTITY OF ZONES IN THE ROOM OR AREA BEING <br />CONTROLLED. CONTROL SWITCHES WITH BUTTONS THAT DO NOT PERFORM ANY ACTION WILL NOT BE ACCEPTED. <br />E.LOCATE COMBINATION OCCUPANCY SENSOR AND SWITCH DEVICES SO OCCUPANCY SENSOR CAN OPERATE CORRECTLY. IF THE ROUGHED-IN SWITCH LOCATION <br />DOES NOT PROVIDE FOR PROPER OPERATION, THEN A STANDALONE OCCUPANCY SENSORS SHALL BE PROVIDED INSTEAD. <br />F.ALL OCCUPANCY SENSORS ON THIS PROJECT SHALL BE SET WITH THE SIMILAR DELAY SET TIME. <br />G.ALL WIRING FOR LIGHTING CONTROL DEVICES SHALL BE INSTALLED IN CONDUIT. <br />H.LIGHTING CONTROL DEVICES SHALL BE PROGRAMMED TO MATCH SEQUENCE OF OPERATIONS DESCRIBED ON THE DRAWINGS PRIOR TO ELECTRICAL ENGINEER'S <br />VISIT TO PERFORM FINAL PUNCH. <br />I.COLOR OF ALL LIGHTING CONTROL DEVICES SHALL BE APPROVED BY ARCHITECT. <br />2.16 EMERGENCY LIGHTING INVERTERS - NOT USED. <br />2.17 ELECTRICAL IDENTIFICATION <br />A.USE A SINGLE TYPE OF IDENTIFICATION PRODUCT FOR EACH APPLICATION. USE COLORS PRESCRIBED BY ANSI A13.1, NFPA 70, AND THESE SPECIFICATIONS. <br />B.RACEWAY AND CABLE LABELS: COMPLY WITH ANSI A13.1, TABLE 3, FOR MINIMUM SIZE OF LETTERS FOR LEGEND AND MINIMUM LENGTH OF COLOR FIELD FOR EACH <br />RACEWAY AND CABLE SIZE. <br />C.COLORED ADHESIVE MARKING TAPE FOR RACEWAYS, WIRES, AND CABLES: SELF-ADHESIVE VINYL TAPE, NOT LESS THAN 1 INCH WIDE BY 3 MILS THICK. <br />D.TAPE MARKERS FOR WIRE: VINYL OR VINYL-CLOTH, SELF-ADHESIVE, WRAPAROUND TYPE WITH PREPRINTED NUMBERS AND LETTERS. <br />E.COLOR-CODING CABLE TIES: TYPE 6/6 NYLON, SELF-LOCKING TYPE. COLORS TO SUIT CODING SCHEME. <br />F.ENGRAVED-PLASTIC LABELS, SIGNS, AND INSTRUCTION PLATES: ENGRAVING STOCK, MELAMINE PLASTIC LAMINATE PUNCHED OR DRILLED FOR MECHANICAL <br />FASTENERS 1/16-INCH MINIMUM THICKNESS FOR SIGNS UP TO 20 SQ. IN. AND 1/8-INCH MINIMUM THICKNESS FOR LARGER SIZES. ENGRAVED LEGEND IN BLACK <br />LETTERS ON WHITE BACKGROUND. <br />G.INTERIOR WARNING AND CAUTION SIGNS: COMPLY WITH 29 CFR, CHAPTER XVII, PART 1910.145. PREPRINTED, ALUMINUM, BAKED-ENAMEL-FINISH SIGNS, PUNCHED <br />OR DRILLED FOR MECHANICAL FASTENERS, WITH COLORS, LEGEND, AND SIZE APPROPRIATE TO THE APPLICATION. <br />H.EXTERIOR WARNING AND CAUTION SIGNS: COMPLY WITH 29 CFR, CHAPTER XVII, PART 1910.145. WEATHER-RESISTANT, NON-FADING, PREPRINTED, <br />CELLULOSE-ACETATE BUTYRATE SIGNS WITH 0.0396-INCH (1-MM), GALVANIZED-STEEL BACKING, WITH COLORS, LEGEND, AND SIZE APPROPRIATE TO THE <br />APPLICATION. 1/4-INCH GROMMETS IN CORNERS FOR MOUNTING. <br />I.FASTENERS FOR NAMEPLATES AND SIGNS: SELF-TAPPING, STAINLESS-STEEL SCREWS OR NO. 10/32 STAINLESS-STEEL MACHINE SCREWS WITH NUTS AND FLAT <br />AND LOCK WASHERS. <br />2.18 ACCEPTABLE MANUFACTURERS: <br />A.RECEPTACLES: HUBBELL, LEVITON, PASS & SEYMOUR. <br />B.LIGHT SWITCHES: HUBBELL, LEVITON, PASS & SEYMOUR. <br />C.LINE VOLTAGE DIMMER SWITCHES: LUTRON, LEVITON. <br />D.RACEWAYS: NATIONAL WIRE PRODUCTS, TRIANGLE OR REPUBLIC. <br />E.WIRE/CABLE: SOUTHWIRE, GENERAL CABLE, CERRO. <br />F.METAL CLAD CABLE: AFC, SOUTHWIRE. <br />G.FITTINGS, COUPLINGS, BUSHINGS, CONNECTORS: OZ GEDNEY, BURNDY, NEPCO, THOMAS AND BETTS. <br />H.DISCONNECT SWITCHES: EATON, GE, SQUARE "D" OR SIEMENS. <br />I.FUSES: BUSSMAN, MERSEN. <br />J.CIRCUIT BREAKERS: EATON, GE, SQUARE "D" OR SIEMENS. <br />K.PANELBOARDS: EATON, GE, SQUARE "D" OR SIEMENS. MATCH BUILDING STANDARD. <br />L.TRANSFORMERS: EATON, GE, SQUARE D, OR SIEMENS. MATCH BUILDING STANDARD. <br />M.EXIT SIGNS: LITHONIA LIGHTING OR MATCH BUILDING STANDARD. <br />N.LIGHTING CONTROL: nLIGHT OR MATCH BUILDING STANDARD. <br />O.FLOOR BOXES POKE-THRU'S: HUBBELL, WIREMOLD. <br />P.WIREWAYS: HUBBELL, WIREMOLD. <br />Q.INVERTERS: LITHONIA LIGHTING, MYERS POWER PRODUCTS. <br />R.TENANT SUBMETERING: EMON DMON CORPORATION OR MATCH BUILDING STANDARDS. <br />PART 3 EXECUTION <br />3.01 GENERAL <br />A.PERFORM THE WORK AT SUCH TIME AND IN SUCH MANNER AS TO MINIMIZE INTERFERENCE WITH BUILDING'S NORMAL OPERATION. NOTIFY BUILDING MANAGEMENT <br />REPRESENTATIVES IN ADVANCE EACH TIME A SERVICE OUTAGE OR INTERRUPTION WILL BE REQUIRED FOR THE PERFORMANCE OF SOME PHASE OF THE WORK. <br />SCHEDULE SUCH SERVICE OUTAGE OR INTERRUPTION, ONLY AFTER HAVING RECEIVED APPROVAL OF DATE, HOUR, AND TIME INTERVAL REQUIRED THEREOF. <br />SCHEDULE OF WORK AS DIRECTED SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE. <br />B.OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANCE RATED WALLS, PARTITIONS, FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING <br />APPROVED METHODS. SEALANT SHALL BE RATED FOR 3 HOURS. TELECOMMUNICATION CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING FIRE STOPPING IN <br />'IT' CONDUITS/SLEEVES/PENETRATIONS AFTER 'IT' WIRES ARE PULLED. <br />C.PROVIDE 277/480 VOLT DANGER LABELING AT ALL EQUIPMENT AND JUNCTION/PULL BOXES PER CODE. <br />D.MAINTAIN GROUND CONTINUITY THROUGHOUT ALL SYSTEMS. <br />E.MAINTAIN CONTINUITY AND PROTECT ALL EXISTING CIRCUITS TO REMAIN SERVING EQUIPMENT WITHIN BASE BUILDING CORE AREAS OR OTHER TENANT AREAS <br />AFFECTED BY THE ALTERATION WORK. CONTRACTOR SHALL BE RESPONSIBLE TO TRACE ALL EXISTING CIRCUITS TO REMAIN ORIGINATING FROM PANELBOARDS, <br />AND SUBMIT FINDINGS TO ENGINEER FOR CLARIFICATION PRIOR TO THE START OF ANY PANELBOARD WORK. WHENEVER IT IS REQUIRED THAT AN EXISTING <br />CIRCUIT BE MODIFIED, REVISED, DISCONNECTED OR REMOVED IT SHALL BE UNDERSTOOD THAT THE CIRCUIT SHALL BE RECONNECTED AND SERVICE <br />RE-ESTABLISHED IN THE REMAINING PORTION OF THE CIRCUIT AFFECTED BY THE ALTERNATION. <br />F.PRIOR TO ANY CHASING, CHOPPING, OR CORE DRILLING BEING PERFORMED, THE CONTRACTOR SHALL FIELD INVESTIGATE CONDITIONS AND COORDINATE WITH <br />ALL APPROPRIATE TRADES TO ENSURE THAT WORK WILL BE IN HARMONY WITH OTHER WORK AND NOT AFFECTED ANY EXISTING BUILDING SYSTEMS. X-RAY SLABS <br />IF REQUIRED. THIS WORK MUST BE APPROVED BY BUILDING MANAGEMENT PRIOR TO PROCEEDING. ALL CORING/CHASING WILL BE DONE ON OVERTIME. <br />3.02 ELECTRICAL EQUIPMENT INSTALLATION <br />A.HEADROOM MAINTENANCE: IF MOUNTING HEIGHTS OR OTHER LOCATION CRITERIA ARE NOT INDICATED, ARRANGE AND INSTALL COMPONENTS AND EQUIPMENT TO <br />PROVIDE THE MAXIMUM POSSIBLE HEADROOM. <br />B.MATERIALS AND COMPONENTS: INSTALL LEVEL, PLUMB, AND PARALLEL AND PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS, UNLESS <br />OTHERWISE INDICATED. <br />C.EQUIPMENT: INSTALL TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT OF COMPONENTS. CONNECT FOR EASE OF DISCONNECTING, WITH <br />MINIMUM INTERFERENCE WITH OTHER INSTALLATIONS. <br />D.RIGHT OF WAY: GIVE TO RACEWAYS AND PIPING SYSTEMS INSTALLED AT A REQUIRED SLOPE. <br />3.03 RACEWAY APPLICATION <br />A.USE THE FOLLOWING RACEWAYS FOR OUTDOOR INSTALLATIONS: <br />1.EXPOSED: RMC. <br />2.CONCEALED: RMC. <br />3.CONNECTION TO VIBRATING EQUIPMENT: LFMC. <br />4.BOXES AND ENCLOSURES: NEMA 250, TYPE 3R OR TYPE 4. <br />B.USE THE FOLLOWING RACEWAYS FOR INDOOR INSTALLATIONS: <br />1.EXPOSED: EMT. <br />2.CONCEALED: EMT OR MC CABLE IF INSTALLED PER SPECIFICATIONS. <br />3.CONNECTION TO VIBRATING EQUIPMENT: FMC; EXCEPT IN WET OR DAMP LOCATIONS, USE LFMC. <br />4.DAMP OR WET LOCATIONS: RMC. <br />5.OUTSIDE TENANT SPACE: EMT <br />C.BOXES AND ENCLOSURES: NEMA 250, TYPE 1, UNLESS OTHERWISE INDICATED. <br />3.04 RACEWAY AND CABLE INSTALLATION <br />A.CONCEAL RACEWAYS AND CABLES, UNLESS OTHERWISE INDICATED, WITHIN FINISHED WALLS, CEILINGS, AND FLOORS. <br />B.INSTALL RACEWAYS AND CABLES AT LEAST 6 INCHES AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES. LOCATE HORIZONTAL RACEWAY <br />RUNS ABOVE WATER AND STEAM PIPING. <br />C.USE TEMPORARY RACEWAY CAPS TO PREVENT FOREIGN MATTER FROM ENTERING. <br />D.MAKE CONDUIT BENDS AND OFFSETS SO ID IS NOT REDUCED. KEEP LEGS OF BENDS IN THE SAME PLANE AND STRAIGHT LEGS OF OFFSETS PARALLEL, UNLESS <br />OTHERWISE INDICATED. <br />E.USE RACEWAY AND CABLE FITTINGS COMPATIBLE WITH RACEWAYS AND CABLES AND SUITABLE FOR USE AND LOCATION. <br />F.INSTALL RACEWAYS EMBEDDED IN SLABS IN MIDDLE THIRD OF SLAB THICKNESS WHERE PRACTICAL, AND LEAVE AT LEAST 1-INCH CONCRETE COVER. OBTAIN <br />STRUCTURAL ENGINEER'S APPROVAL PRIOR TO INSTALLATION. <br />G.SECURE RACEWAYS TO REINFORCING RODS TO PREVENT SAGGING OR SHIFTING DURING CONCRETE PLACEMENT. <br />H.SPACE RACEWAYS LATERALLY TO PREVENT VOIDS IN CONCRETE. <br />I.INSTALL CONDUIT LARGER THAN 1-INCH TRADE SIZE PARALLEL TO OR AT RIGHT ANGLES TO MAIN REINFORCEMENT. WHERE CONDUIT IS AT RIGHT ANGLES TO <br />REINFORCEMENT, PLACE CONDUIT CLOSE TO SLAB SUPPORT. <br />J.TRANSITION FROM NONMETALLIC TUBING TO SCHEDULE 80 NONMETALLIC CONDUIT, RIGID STEEL CONDUIT, OR IMC BEFORE RISING ABOVE FLOOR. <br />K.MAKE BENDS IN EXPOSED PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL. USE FACTORY ELBOWS ONLY WHERE ELBOWS CAN <br />BE INSTALLED PARALLEL; OTHERWISE, PROVIDE FIELD BENDS FOR EXPOSED PARALLEL RACEWAYS. <br />L.INSTALL PULL WIRES IN EMPTY RACEWAYS. USE NO. 14 AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN 200-LB TENSILE <br />STRENGTH. LEAVE AT LEAST 12 INCHES OF SLACK AT EACH END OF THE PULL WIRE. <br />M.INSTALL TELEPHONE AND SIGNAL SYSTEM RACEWAYS, 2-INCH TRADE SIZE AND SMALLER, IN MAXIMUM LENGTHS OF 100 FEET AND WITH A MAXIMUM OF TWO <br />90-DEGREE BENDS OR EQUIVALENT. SEPARATE LENGTHS WITH PULL OR JUNCTION BOXES WHERE NECESSARY TO COMPLY WITH THESE REQUIREMENTS, IN <br />ADDITION TO REQUIREMENTS ABOVE. <br />N.CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION, NOISE TRANSMISSION, OR MOVEMENT WITH A MAXIMUM OF 72-INCH FLEXIBLE CONDUIT. INSTALL <br />LFMC IN WET OR DAMP LOCATIONS. INSTALL SEPARATE GROUND CONDUCTOR ACROSS FLEXIBLE CONNECTIONS. <br />O.SET FLOOR BOXES LEVEL AND TRIM AFTER INSTALLATION TO FIT FLUSH TO FINISHED FLOOR SURFACE. <br />3.05 WIRING <br />A.FEEDERS: TYPE THHN/THWN INSULATED CONDUCTORS IN RACEWAY. <br />B.UNDERGROUND FEEDERS AND BRANCH CIRCUITS: TYPE THWN OR SINGLE-WIRE, TYPE UF INSULATED CONDUCTORS IN RACEWAY. <br />C.BRANCH CIRCUITS: TYPE THWN OR THHN/THWN INSULATED CONDUCTORS IN RACEWAY WHERE EXPOSED. METAL-CLAD CABLE SHALL BE PERMITTED WHERE <br />PERMITTED BY AUTHORITIES HAVING JURISDICTION AND WHEN APPROVED BY LANDLORD RULES AND REGULATIONS. METAL-CLAD CABLE SHALL NOT BE <br />INSTALLED WITHIN ELECTRIC CLOSETS OR DIRECTLY INTO PANELBOARDS. <br />D.REMOTE-CONTROL SIGNALING AND POWER-LIMITED CIRCUITS: TYPE THHN/THWN INSULATED CONDUCTORS IN RACEWAY FOR CLASSES 1, 2, AND 3, UNLESS <br />OTHERWISE INDICATED. <br />E.MULTI-WIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A MEANS TO DISCONNECT SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT THE PANELBOARD <br />WHERE THE BRANCH CIRCUIT ORIGINATES. <br />F.WIRE CONNECTORS AND SPLICES: UNITS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS SUITABLE FOR SERVICE INDICATED. <br />G.METAL CLAD (TYPE MC) FOR CONCEALED BRANCH CIRCUITRY IN TENANT SPACE ONLY MAYBE USED WHEN APPROVED BY BUILDING MANAGEMENT AND WHERE <br />PERMITTED BY CODE. <br />H.EMT SHALL BE USED OUTSIDE TENANT SPACE AND IN BUILDING CLOSETS. <br />I.METAL CLAD (TYPE MC) SHALL NOT BE INSTALLED INTO PANELBOARDS. <br />J.ALL CONDUCTORS SHALL BE SOFT 98% MINIMUM CONDUCTIVITY PROPERLY REFINED COPPER, TYPE THHN/THWN INSULATED RATED AT 600V, UNLESS OTHERWISE <br />NOTED. <br />K.THE MINIMUM WIRE SIZE FOR BRANCH CIRCUITS SHALL BE NO. 12 AWG EXCEPT 120 VOLT CIRCUITS OVER 100' IN LENGTH SHALL BE NO. 10 AWG. <br />L.ALL FEEDER CONDUCTORS SHALL BE SIZED FOR MAXIMUM 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL ALSO BE SIZED FOR 2.5% VOLTAGE DROP. <br />M.TAG ALL FEEDERS IN ALL PULL BOXES, GUTTER SPACES, AND WIREWAYS THROUGH WHICH THEY PASS. <br />N.TERMINATE STRANDED CONDUCTORS NO. 8 AWG AND LARGER, AT SWITCHBOARDS, TRANSFORMERS, UPS SYSTEMS WITH COMPRESSION TYPE CONNECTORS. <br />TERMINATE WITH MECHANICAL LUGS AT PANELBOARDS. <br />O.JOIN OR TAP STRANDED CONDUCTORS (NO. 6 AWG AND LARGER) WITH PRESSURE INDENT TYPE CONNECTORS BURNDY, NEPCO, OR O.Z./GEDNEY WITH <br />COMPOSITION INSULATING COVERS. <br />P.SPLICES IN BRANCH WIRING (NO. 8 AWG AND SMALLER) SHALL BE TWISTED AND MADE MECHANICALLY TIGHT; THEN SECURED WITH PIGTAIL CONNECTORS, CRIMP <br />TYPE CONNECTORS SHALL NOT BE USED. UTILIZE UL LISTED, "SILICON FILLED" PIGTAIL CONNECTORS WHERE LOCATED IN WET ENVIRONMENTS OR OUTDOORS. <br />Q.SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE NEC/NYCEC BASED ON CONDUCTOR SIZE AND VERTICAL DISTANCE. <br />R.WALL MOUNTED DEVICES SHALL BE FED VERTICALLY. HORIZONTAL RUNS THROUGH PARTITIONS SHALL NOT BE PERMITTED, EXCEPT IN LOW HEIGHT PARTITIONS <br />OR WHERE NOTED ON DRAWINGS. <br />S.INSTALL WIRING AT OUTLETS WITH AT LEAST 12 INCHES OF SLACK CONDUCTOR AT EACH OUTLET. <br />T.CONNECT OUTLET AND COMPONENT CONNECTIONS TO WIRING SYSTEMS AND TO GROUND. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, ACCORDING TO <br />MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A. <br />3.06 SUPPORTS <br />A.DAMP LOCATIONS AND OUTDOORS: HOT-DIP GALVANIZED MATERIALS OR NONMETALLIC, U-CHANNEL SYSTEM COMPONENTS. <br />B.DRY LOCATIONS: STEEL MATERIALS. <br />C.SUPPORT CLAMPS FOR PVC RACEWAYS: CLICK-TYPE CLAMP SYSTEM. <br />D.SELECTION OF SUPPORTS: COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />E.STRENGTH OF SUPPORTS: ADEQUATE TO CARRY PRESENT AND FUTURE LOADS, TIMES A SAFETY FACTOR OF AT LEAST FOUR; MINIMUM OF 200-LB DESIGN LOAD. <br />F.INSTALL SUPPORT DEVICES TO SECURELY AND PERMANENTLY FASTEN AND SUPPORT ELECTRICAL COMPONENTS. <br />G.INSTALL INDIVIDUAL AND MULTIPLE RACEWAY HANGERS AND RISER CLAMPS TO SUPPORT RACEWAYS. PROVIDE U-BOLTS, CLAMPS, ATTACHMENTS, AND OTHER <br />HARDWARE NECESSARY FOR HANGER ASSEMBLIES AND FOR SECURING HANGER RODS AND CONDUITS. <br />H.SUPPORT PARALLEL RUNS OF HORIZONTAL RACEWAYS TOGETHER ON TRAPEZE- OR BRACKET-TYPE HANGERS. <br />I.SIZE SUPPORTS FOR MULTIPLE RACEWAY INSTALLATIONS SO CAPACITY CAN BE INCREASED BY A 25 PERCENT MINIMUM IN THE FUTURE. <br />J.SUPPORT INDIVIDUAL HORIZONTAL RACEWAYS WITH SEPARATE, MALLEABLE-IRON PIPE HANGERS OR CLAMPS. <br />K.INSTALL 1/4-INCH DIAMETER OR LARGER THREADED STEEL HANGER RODS, UNLESS OTHERWISE INDICATED. <br />L.SPRING-STEEL FASTENERS SPECIFICALLY DESIGNED FOR SUPPORTING SINGLE CONDUITS OR TUBING MAY BE USED INSTEAD OF MALLEABLE-IRON HANGERS FOR <br />1-1/2-INCH (AND SMALLER RACEWAYS SERVING LIGHTING AND RECEPTACLE BRANCH CIRCUITS ABOVE SUSPENDED CEILINGS AND FOR FASTENING RACEWAYS TO <br />SLOTTED CHANNEL AND ANGLE SUPPORTS. <br />M.ARRANGE SUPPORTS IN VERTICAL RUNS SO THE WEIGHT OF RACEWAYS AND ENCLOSED CONDUCTORS IS CARRIED ENTIRELY BY RACEWAY SUPPORTS, WITH NO <br />WEIGHT LOAD ON RACEWAY TERMINALS. <br />N.SEPARATELY SUPPORT CAST BOXES THAT ARE THREADED TO RACEWAYS AND USED FOR FIXTURE SUPPORT. SUPPORT SHEET-METAL BOXES DIRECTLY FROM <br />THE BUILDING STRUCTURE OR BY BAR HANGERS. IF BAR HANGERS ARE USED, ATTACH BAR TO RACEWAYS ON OPPOSITE SIDES OF THE BOX AND SUPPORT THE <br />RACEWAY WITH AN APPROVED FASTENER NOT MORE THAN 24 INCHES FROM THE BOX. <br />O.INSTALL METAL CHANNEL RACKS FOR MOUNTING CABINETS, PANELBOARDS, DISCONNECT SWITCHES, CONTROL ENCLOSURES, PULL AND JUNCTION BOXES, <br />TRANSFORMERS, AND OTHER DEVICES UNLESS COMPONENTS ARE MOUNTED DIRECTLY TO STRUCTURAL ELEMENTS OF ADEQUATE STRENGTH. <br />P.INSTALL SLEEVES FOR CABLE AND RACEWAY PENETRATIONS OF CONCRETE SLABS AND WALLS UNLESS CORE-DRILLED HOLES ARE USED. INSTALL SLEEVES FOR <br />CABLE AND RACEWAY PENETRATIONS OF MASONRY AND FIRE-RATED GYPSUM WALLS AND OF ALL OTHER FIRE-RATED FLOOR AND WALL ASSEMBLIES. INSTALL <br />SLEEVES DURING ERECTION OF CONCRETE AND MASONRY WALLS. <br />Q.SECURELY FASTEN ELECTRICAL ITEMS AND THEIR SUPPORTS TO THE BUILDING STRUCTURE, UNLESS OTHERWISE INDICATED. PERFORM FASTENING ACCORDING <br />TO THE FOLLOWING UNLESS OTHER FASTENING METHODS ARE INDICATED: <br />1.WOOD: FASTEN WITH WOOD SCREWS OR SCREW-TYPE NAILS. <br />2.MASONRY: TOGGLE BOLTS ON HOLLOW MASONRY UNITS AND EXPANSION BOLTS ON SOLID MASONRY UNITS. <br />3.NEW CONCRETE: CONCRETE INSERTS WITH MACHINE SCREWS AND BOLTS. <br />4.EXISTING CONCRETE: EXPANSION BOLTS. <br />5.INSTEAD OF EXPANSION BOLTS, THREADED STUDS DRIVEN BY A POWDER CHARGE AND PROVIDED WITH LOCK WASHERS MAY BE USED IN EXISTING <br />CONCRETE. <br />6.STEEL: WELDED THREADED STUDS OR SPRING-TENSION CLAMPS ON STEEL. <br />7.FIELD WELDING: COMPLY WITH AWS D1.1. <br />8.WELDING TO STEEL STRUCTURE MAY BE USED ONLY FOR THREADED STUDS, NOT FOR CONDUITS, PIPE STRAPS, OR OTHER ITEMS. <br />9.LIGHT STEEL: SHEET-METAL SCREWS. <br />10.FASTENERS: SELECT SO THE LOAD APPLIED TO EACH FASTENER DOES NOT EXCEED 25 PERCENT OF ITS PROOF-TEST LOAD. <br />3.07 CUTTING, PATCHING AND FIRESTOPPING <br />A.ALL CUTTING AND PATCHING REQUIRED TO THE EXISTING BUILDING STRUCTURE FOR THE WORK SHALL BE INCLUDED UNDER THIS CONTRACT AND BE <br />ACCEPTABLE TO THE LANDLORD. OBTAIN WRITTEN APPROVAL FROM LANDLORD BEFORE ANY CUTTING IS CARRIED OUT. <br />B.WHERE CONDUITS PASS THROUGH FIRE RATED WALLS OR FLOORS, PROVIDE FIRE STOPPING MATERIAL LISTED WITH, AND BEAR LABEL OF CSA AND ULC, AND <br />MAINTAIN SAME FIRE RATING OF BUILDING COMPONENT PENETRATION. <br />C.APPLY FIRESTOPPING TO CABLE AND RACEWAY PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES TO ACHIEVE FIRE-RESISTANCE RATING OF THE <br />ASSEMBLY. <br />D.CUT, CHANNEL, CHASE, AND DRILL FLOORS, WALLS, PARTITIONS, CEILINGS, AND OTHER SURFACES REQUIRED TO PERMIT ELECTRICAL INSTALLATIONS. PERFORM <br />CUTTING BY SKILLED MECHANICS OF TRADES INVOLVED. <br />E.REPAIR AND REFINISH DISTURBED FINISH MATERIALS AND OTHER SURFACES TO MATCH ADJACENT UNDISTURBED SURFACES. INSTALL NEW FIREPROOFING <br />WHERE EXISTING FIRESTOPPING HAS BEEN DISTURBED. REPAIR AND REFINISH MATERIALS AND OTHER SURFACES BY SKILLED MECHANICS OF TRADES INVOLVED. <br />3.08 ELECTRICAL FURNITURE SYSTEMS <br />A.THE ELECTRIFIED FURNITURE VENDOR WILL SUPPLY ALL RECEPTACLES, FURNITURE TASK LIGHTING FIXTURES, WIRING HARNESSES, CONNECTORS AND FITTINGS <br />TO THE ELECTRICAL CONTRACTOR FOR THE COMPLETE WIRING INSTALLATION. ALL WIRING AND COMPONENTS SHALL BE INSTALLED AS DIRECTED BY VENDOR. <br />B.ELECTRICAL CONTRACTOR SHALL FURNISH AN 18" MAXIMUM LIQUID TIGHT FLEXIBLE CONDUIT CONNECTIONS WITH REQUIRED PHASE CONDUCTORS, NEUTRAL <br />CONDUCTORS AND GROUND CONDUCTORS AS INDICATED FROM WALL OR FLOOR OUTLET. <br />C.THE FURNITURE VENDOR SHALL CHALK THE FURNITURE SYSTEM OUTLINE ON THE FLOOR FOR COORDINATION OF POWER AND COMMUNICATION IN-FEED <br />LOCATIONS. IN-FEED LOCATIONS INDICATED ON PLAN DOCUMENTS ARE FOR CLARITY PURPOSES. IN-FEED LOCATIONS AND QUANTITY SHALL BE APPROVED IN <br />FIELD BY ARCHITECT AND FURNITURE SYSTEM VENDOR PRIOR TO INSTALLATION. <br />1.08 OPERATION AND MAINTENANCE MANUALS <br />A.PROVIDE 2 (TWO) SETS OF OPERATION AND MAINTENANCE MANUALS SUBMITTED IN HARD COVER 3-RING BINDERS. INCLUDE THE FOLLOWING INFORMATION IN THE <br />OPERATIONS AND MAINTENANCE MANUALS: <br />1.NAMES AND ADDRESS OF LOCAL SUPPLIERS FOR THE ITEMS INCLUDED. <br />2.TECHNICAL DATA, PRODUCT DATA, SUPPLEMENTED BY BULLETINS, COMPONENT ILLUSTRATIONS, EXPLODED VIEWS, TECHNICAL DESCRIPTIONS OF ITEMS, <br />AND PARTS LISTS. ADVERTISING OR SALES LITERATURE IS NOT ACCEPTABLE. <br />3.THE CONSULTANTS REVIEWED SHOP DRAWINGS. <br />4.CERTIFICATE(S) OF ACCEPTANCE FROM THE AUTHORITIES INSPECTION DEPARTMENT. <br />5.VERIFICATION REPORTS AND CERTIFICATE(S) FOR ANY NEW FIRE ALARM COMPONENTS OR TIE-INS AND ANY BASE BUILDING TIE-INS FOR MISCELLANEOUS <br />SYSTEMS (I.E. SECURITY, LIGHTING CONTROL, DIGITAL METERING). <br />6.LOAD BALANCE REPORT. <br />7.WRITTEN GUARANTEE. <br />8.LIST OF EACH FIXTURE TYPE IDENTIFYING TYPE OF LAMP, WATTAGE AND MANUFACTURER'S CONTACT INFO. <br />B.REVIEW INFORMATION PROVIDED IN THE MAINTENANCE INSTRUCTIONS AND MANUALS WITH THE TENANT'S OPERATING PERSONNEL AND LANDLORD'S OPERATING <br />PERSONNEL WHERE BASE BUILDING SYSTEMS ARE REVISED, TO ENSURE A COMPLETE UNDERSTANDING OF THE ELECTRICAL EQUIPMENT AND SYSTEMS AND <br />THEIR OPERATION. <br />1.10 CONTRACT DOCUMENTS <br />A.THE DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC PERFORMANCE DRAWINGS ONLY, INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATE <br />THE GENERAL ARRANGEMENT AND APPROXIMATE SIZE AND LOCATION OF ELECTRICAL EQUIPMENT. THE DRAWINGS DO NOT INTEND TO SHOW ARCHITECTURAL, <br />INTERIOR DESIGN, MECHANICAL, STRUCTURAL OR BASE BUILDING DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR A THOROUGH KNOWLEDGE OF SAME <br />BEFORE PROCEEDING WITH THE WORK. <br />B.DO NOT SCALE OR MEASURE DRAWINGS, BUT OBTAIN INFORMATION REGARDING ACCURATE DIMENSIONS FROM THE DIMENSIONS SHOWN ON THE DESIGN <br />CONSULTANT/ARCHITECT'S DRAWINGS, OR BY SITE MEASUREMENTS. <br />C.ANY DISCREPANCIES BETWEEN DRAWINGS AND/OR SPECIFICATIONS AND EXISTING CONDITIONS, MUST BE REFERRED TO THE DESIGN CONSULTANT/ARCHITECT <br />BEFORE ANY WORK AFFECTED IS BEGUN. <br />D.COOPERATE AND COORDINATE WITH OTHER CONTRACTORS IN LAYING OUT OF WORK SO AS NOT TO CONFLICT WITH THE WORK OF OTHER CONTRACTORS. <br />CARRY OUT WORK PROMPTLY AS PER CONSTRUCTION SCHEDULE AND COORDINATE WITH WORK OF OTHER CONTRACTORS. <br />E.MAKE, AT NO ADDITIONAL COST, ANY CHANGES OR ADDITIONS TO MATERIALS AND EQUIPMENT NECESSARY TO ACCOMMODATE STRUCTURAL CONDITIONS <br />(OFFSETS AROUND BEAMS, COLUMN, ETC.) <br />2.08 CIRCUIT BREAKERS <br />A.FOR PANELBOARD APPLICATIONS, CIRCUIT BREAKERS SHALL BE BOLTED TO THE PANELBOARD BUS BARS. WHERE CIRCUIT BREAKERS ARE INSTALLED IN EXISTING <br />PANELBOARD BREAKERS SHALL BE OF THE SAME MANUFACTURER AND INTERRUPTING RATING. BREAKERS SHALL BE COMPATIBLE WITH EXISTING PANELBOARD. <br />B.CIRCUIT BREAKERS SHALL BE "THERMAL MAGNETIC" TYPE, QUICK-MAKE, QUICK- BREAK, TRIP-FREE WITH NON-WELDING CONTACTS COMPENSATED FOR AMBIENT <br />TEMPERATURES AND SHALL HAVE A MINIMUM SHORT CIRCUIT RATING OF 10,000 AMPERES SYMMETRICAL FOR 120/280V PANELS AND 14,000 AMPERES <br />SYMMETRICAL FOR 277/480V PANELS OR HIGHER WHERE NOTED. <br />C.MULTI-WIRE BRANCH CIRCUITS SUPPLYING POWER TO MORE THAN ONE DEVICE OR EQUIPMENT SHALL BE PROVIDED WITH A MEANS TO DISCONNECT <br />SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE BRANCH CIRCUIT ORIGINATES. CONTRACTOR SHALL COORDINATE WITH <br />LOCAL AHJ THE MEANS REQUIRED TO MEET NYCEC/NEC SECTIONS 210.4(B). CONTRACTOR SHALL REMOVE AND REPLACE ALL EXISTING CIRCUIT BREAKERS THAT <br />CAN NOT BE RETROFITTED WITH TIE BARS AS REQUIRED TO COMPLY WITH REQUIREMENT. <br />D.TANDEM BREAKERS MAY NOT BE UTILIZED. <br />E.PROVIDE BREAKER LOCKS FOR ALL NEW AND EXISTING BREAKERS SERVING EXIT LIGHTS, EMERGENCY LIGHTING AND EMERGENCY BATTERY PACKS. <br />F.WHERE INDICATED TO BE LSI TYPE, CIRCUIT BREAKERS SHALL BE SOLID-STATE ELECTRONIC TRIP WITH FIELD-ADJUSTABLE LONG-TIME AND SHORT-TIME PICKUP <br />LEVELS, LONG-TIME AND SHORT-TIME TIME ADJUSTMENTS, INSTANTANEOUS TRIP. PROVIDE ADJUSTABLE GROUND FAULT PICKUP AND TIME DELAY WHERE <br />INDICATED. <br />2.01 RACEWAYS <br />A.EMT: ANSI C80.3, ZINC-COATED STEEL, WITH SET-SCREW OR COMPRESSION FITTINGS. ELECTRIC METALLIC TUBING SHALL BE INDUSTRY STANDARD THIN WALL <br />CONDUIT, HOT DIPPED GALVANIZED STEEL (1/2" MIN, 4" MAX). <br />B.FMC: ZINC-COATED STEEL. THE FLEXIBLE METALLIC CONDUIT SHALL BE OF THE GROUNDING TYPE. IT SHALL CONSIST OF GALVANIZED STEEL TAPE FORMED INTO <br />AN INDUSTRY STANDARD INTERLOCKING COIL (1/2" MIN). <br />C.RMC: ANSI C80.1, HOT-DIPPED GALVANIZED STEEL WITH THREADED FITTINGS. RIGID METAL CONDUIT SHALL BE INDUSTRY STANDARD STEEL CONDUIT (1/2" MIN, 4" <br />MAX). <br />D.RACEWAY FITTINGS: SPECIFICALLY DESIGNED FOR THE RACEWAY TYPE WITH WHICH USED. <br />E.FOR ALL SIZES OF CONDUIT LARGER THAN 1-1/2", USE STANDARD ELBOW. <br />F.CONDUIT SHALL BE SECURELY FASTENED IN PLACE AND HANGERS, SUPPORTS OR FASTENINGS SHALL BE PROVIDED AT EACH ELBOW AND AT EACH END OF EACH <br />STRAIGHT RUN TERMINATED AT A BOX OR CABINET. <br />G.PROVIDE EXPANSION FITTINGS IN EACH CONDUIT RUN WHEREVER IT CROSSES AN EXPANSION JOINT AND WHEREVER THE CONDUIT LENGTH EXCEEDS 200 FEET. <br />H.UNLESS OTHERWISE INDICATED OR SPECIFIED, ALL WIRING SHALL BE INSTALLED CONCEALED. <br />I.FEEDERS AND BRANCH CIRCUITRY ABOVE HUNG CEILING AND IN PARTITIONS SHALL BE RUN IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE NOTED. <br />REFER TO WIRING SECTION BELOW FOR SITUATIONS WHERE MAC CABLE MAY BE ACCEPTABLE. <br />J.FINAL CONNECTIONS TO MOTORS, LIGHT FIXTURES, TRANSFORMERS, AND EQUIPMENT SUBJECT TO VIBRATION WILL BE DONE WITH FLEXIBLE METALLIC CONDUIT. <br />LENGTH SHALL NOT EXCEED 6 FEET. <br />K.ALL CONDUIT IN MECHANICAL ROOMS, ELECTRICAL CLOSETS AND WHERE CONCEALED IN CONCRETE OR INSTALLED OUTDOORS SHALL BE EMT. <br />L.ALL CONDUITS INSTALLED IN CONCRETE OR OUTDOORS SHALL BE PROVIDED WITH WEATHERPROOF CONNECTORS. <br />M.ALL METAL CONDUIT TERMINATING IN A METAL ENCLOSURE SHALL HAVE AN INSULATED BUSHING. PROVIDE "GROUNDING" TYPE BUSHING WHERE REQUIRED. <br />N.WHERE CONDUITS ARE RUN IN THE CEILING SPACE OF THE FLOOR BELOW, THEY SHALL BE CONTINUOUS AND HAVE NO JUNCTION OR PULL BOXES UNLESS PRIOR <br />APPROVAL IS GIVEN BY BUILDING MANAGEMENT/CLIENT. <br />O.INSTALL CONDUITS TO CONSERVE HEADROOM, PARALLEL AND PERPENDICULAR TO BUILDING LINES. DO NOT CLIP CONDUITS TO CEILING HANGER. <br />P.WALL COMMUNICATIONS CONDUIT SHALL BE REAMED AND INSTALLED COMPLETE WITH INSULATED BUSHINGS AT EACH END. <br />2.10 TRANSFORMERS - NOT USED. <br />1.11 INTENT <br />A.IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS THAT THE CONTRACTOR PROVIDE COMPLETE AND OPERATIONAL SYSTEMS AS REQUIRED. WHERE <br />DIFFERENCES OCCUR, THE MAXIMUM CONDITION SHALL GOVERN. <br />B.ANY MISCELLANEOUS ITEMS, HARDWARE, DEVICES, WIRING, ETC., NOT SPECIFICALLY DESCRIBED, BUT REQUIRED FOR THE OPERATION OF THE SYSTEM, MUST BE <br />PROVIDED AND INCLUDED AS PART OF THE BID. <br />2.11 TENANT SUB-METERING - NOT USED. <br />1.14 ACCESS DOORS <br />A.WHEREVER ANY BASE BUILDING EQUIPMENT REQUIRES ACCESSIBILITY, MAINTENANCE OR ADJUSTMENT, PROVIDE ACCESS DOORS APPROVED BY DESIGN <br />CONSULTANT/ARCHITECT AND LANDLORD. <br />B.ACCESS DOORS SHALL BE FINISHED TO MATCH ADJACENT SURFACES. <br />C.IN ALL DRYWALL CEILING AREAS, CONTRACTOR SHALL REMOVE AND RELOCATE ALL EXISTING JUNCTION BOXES TO ACCESSIBLE CEILING SPACE. <br />D.PROVIDE ACCESS PANELS FOR ALL NEW AND EXISTING DEVICES AS REQUIRED. <br />G. FOR TEMPORARY POWER, FURNISH AND INSTALL WIRING FOR ADEQUATE LIGHT AND SMALL TOOLS POWER FOR THE PROJECT. THIS SHALL INCLUDE STRINGERS, <br />LAMPS, OUTLETS, BREAKERS, AND FUSING, AS IT IS NECESSARY. ALL TEMPORARY WIRING SHALL BE REMOVED FROM SPACE AT COMPLETION OF PROJECT. <br />H. FURNISH AND INSTALL A MINIMUM 1" EMPTY CONDUIT FOR ALL WALL MOUNTED LOW VOLTAGE EQUIPMENT JUNCTION BOXES. CONDUIT SHALL BE STUBBED 6" <br />ABOVE HUNG CEILING AND TURNED TOWARDS TERMINATION CLOSET ABOVE ACCESSIBLE CEILING AREA. <br />I. COORDINATE WITH THE BUILDING OWNER FOR ANY SERVICE INTERRUPTION OF EXISTING SYSTEMS AND GIVE NOTICE AS REQUIRED BY BUILDING RULES AND <br />REGULATIONS OR A MINIMUM OF FIVE (5) DAYS PRIOR TO ANY WORK, WHICHEVER IS MORE STRINGENT. CONTRACTOR IS TO PERFORM WORK ON PREMIUM TIME SO <br />AS TO NOT DISTURB EXISTING TENANTS ON OTHER FLOORS. <br />J. WHEN USING TEMPORARY LIGHTING, THE CONTRACTOR SHALL CLEARLY LABEL PANELS AND BREAKERS USED FOR LIGHTING. LOCATION OF PANELS TO BE SHOWN <br />ON FLOOR PLAN POSTED AT ENTRANCE TO WORK AREA. PROPER TEMPORARY LIGHTING AND POWER MUST BE INSTALLED AND MAINTAINED IN ALL WORK AREAS. <br />CONNECTIONS TO EXISTING STAIRWELL AND EXIT LIGHT SYSTEMS ARE NOT PERMITTED. <br />K. THE CONTRACTOR SHALL CUT BACK TO THE FLOOR, WALL OR CEILING, REMOVE WIRING AND PLUG BOTH ENDS OF CONCEALED CONDUITS MADE OBSOLETE BY <br />THIS ALTERNATION. EXPOSED CONDUITS, WIREWAYS, OUTLET BOXES, PULL BOXES, HANGERS, ETC. MADE OBSOLETE BY THE ALTERNATION WORK SHALL BE <br />REMOVED, UNLESS OTHERWISE NOTED. <br />L. IT IS POSSIBLE THAT THERE WILL BE CERTAIN REMOVALS AND RELOCATIONS OF THE EXISTING ELECTRICAL INSTALLATION NECESSARY FOR THE SATISFACTORY <br />PERFORMANCE OF THE WORK. THESE CHANGES CANNOT BE COMPLETELY DETAILED ON THE DRAWINGS, BUT MUST BE CONSIDERED BY THE CONTRACTOR WHILE <br />REVIEWING THE EXISTING CONDITIONS AT THE SITE AND PREPARING THE PROPOSAL. <br />SHEET <br />PA / PM: <br />JOB NO.: <br />DRAWN BY: <br />CAUTION: 24"x36" <br />RE <br />M <br />A <br />R <br />K <br />S <br />DA <br />T <br />E <br />de <br />b <br />s <br />@ <br />s <br />h <br />p <br />a <br />r <br />t <br />n <br />e <br />r <br />s <br />. <br />n <br />e <br />t <br />ma <br />r <br />c <br />o <br />h <br />@ <br />s <br />h <br />p <br />a <br />r <br />t <br />n <br />e <br />r <br />s <br />. <br />n <br />e <br />t <br />(7 <br />1 <br />4 <br />) <br />3 <br />9 <br />0 <br />. <br />8 <br />6 <br />0 <br />0 <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br /> <br />a <br />n <br />d <br /> <br />p <br />l <br />a <br />n <br />n <br />i <br />n <br />g <br />PA <br />R <br />T <br />N <br />E <br />R <br />S <br />ww <br />w <br />. <br />s <br />h <br />p <br />a <br />r <br />t <br />n <br />e <br />r <br />s <br />. <br />n <br />e <br />t <br />07 <br />- <br />0 <br />3 <br />- <br />2 <br />0 <br />2 <br />4 <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />S <br />U <br />B <br />M <br />I <br />T <br />T <br />A <br />L <br />UN <br />I <br />T <br />E <br />D <br /> <br />M <br />E <br />D <br />I <br />C <br />A <br />L <br /> <br />I <br />M <br />A <br />G <br />I <br />N <br />G <br /> <br />H <br />E <br />A <br />L <br />T <br />H <br />C <br />A <br />R <br />E <br />80 <br />0 <br /> <br />N <br />. <br /> <br />T <br />U <br />S <br />T <br />I <br />N <br /> <br />A <br />V <br />E <br />N <br />U <br />E <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />TE <br />N <br />A <br />N <br />T <br /> <br />I <br />M <br />P <br />R <br />O <br />V <br />E <br />M <br />E <br />N <br />T <br /> <br />F <br />O <br />R <br />: <br />Un <br />i <br />t <br />e <br />d <br /> <br />M <br />e <br />d <br />i <br />c <br />a <br />l <br /> <br />I <br />m <br />a <br />g <br />i <br />n <br />g <br /> <br />H <br />e <br />a <br />l <br />t <br />h <br />c <br />a <br />r <br />e <br />SU <br />I <br />T <br />E <br /> <br />- <br /> <br />H <br />Mechanical . Electrical . Plumbing <br />225 E Broadway, Suite 101A <br />Glendale, CA 91205 <br /># 213.820.3683 <br />Hestrada@elogicsce.com <br />EL <br />E <br />C <br />T <br />R <br />I <br />C <br />A <br />L <br /> <br />S <br />P <br />E <br />C <br />I <br />F <br />I <br />C <br />A <br />T <br />I <br />O <br />N <br />S <br />E0.02 <br />SA <br />URABH JAGD ISH PANDY <br />AREG <br />I <br />STERED PROF E SS IONAL ENGI <br />NE <br />ER <br />ELECTR ICALSTATE OF CALIFORNIA <br />E-23194 <br />EXP. 6-30- 46 <br />800 N Tustin Ave Unit <br />#H1/23/2025