A.Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on the 24-volt <br />transformer side. <br />B.Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the <br />following standard safety devices trip and shut off compressor: <br />C.Loss-of-charge/Low-pressureswitch. <br />D.High-pressure switch. <br />E.Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, an LED (light-emitting diode) indicator <br />shall flash a diagnostic code that indicates which safety switch has tripped. <br />F.Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection. <br />G.Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up. <br />H.Unit control board shall have on-board diagnostics and fault code display. <br />I.Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0 ºF. <br />J.Control board shall monitor each refrigerant safety switch independently. <br />K.Control board shall retain last 5 fault codes in non-volatile memory, which will not be lost in the event of a power loss. <br /> <br />23 09 23.13.B RTU Open-multi-protocol, direct digital controller <br />1.Shall be ASHRAE 62-2001 compliant. <br />2.Shall include built-in protocol for BACNET , Modbus , and Johnson N2. <br />3.Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers <br />4.Baud rate Controller shall be selectable using a dip switch. <br />5.Shall have an LED display independently showing the status of serial communication,running, errors, power, all digital <br />outputs, and all analog inputs. <br />6.Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air quality, <br />outdoor air quality, compressor lock- out, fire shutdown, enthalpy switch, and fan status/filter status/ humidity/ remote <br />occupancy. <br />7.Software upgrades will be accomplished by either local or remote download. No software upgrades through chip <br />replacements are allowed. <br /> <br />23 09 33 Electric and Electronic Control System for HVAC <br /> <br />23 09 33.13 Decentralized, Rooftop Units <br />23 09 33.13.A General <br />1.Shall be complete with self- contained low- voltage control circuit protected by a resettable circuit breaker on the 24-v <br />transformer side. Transformer shall have 75VA capability. <br />2.Shall utilize color-coded wiring. <br />3.Shall include a central control terminal board to conveniently and safely provide connection points for vital control <br />functions such as: smoke detectors, phase monitor, gas controller, economizer, thermostat, DDC control options, and <br />low and high pressure switches. <br />4.The heat exchanger shall be controlled by an integrated gas controller (IGC) microprocessor. See heat exchanger <br />section of this specification. <br />23 09 33.23.B Safeties <br />1.Compressor over-temperature, over-current. High internal pressure differential. <br />2.Low-pressure switch. <br />a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pressure <br />switches. They shall physically prevent the cross- wiring of the safety switches between circuits 1 and 2. <br />b.Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist the <br />installer and service technician to correctly wire and or troubleshoot the rooftop unit. <br />3.High pressure switch. <br />a.Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pressure <br />switches. They shall physically prevent the cross-wiring of the safety switches between circuits 1 and 2. <br />Guide Specification for <br />York® Sun™ Core <br />Page: 13 <br />3925 S Bristol <br />St-HVAC12/23/2024