b.High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist the <br />installer and service technician to correctly wire and or troubleshoot the rooftop unit. <br />4.Automatic reset,/motor thermal overload protector. <br />5.Heating section shall be provided with the following minimum protections: <br />a.High-temperature limit switches. <br />b.Induced draft motor speed sensor. <br />c.Flame rollout switch. <br />d.Flame proving controls <br />  <br />23 09 93 Sequence of Operations for HVAC Controls <br />  <br />23 09 93.13 Decentralized, Rooftop Units <br />23 09 93.13 INSERT SEQUENCE OF OPERATION <br />  <br />23 40 13 Panel Air Filters <br />  <br />23 40 13.13 Decentralized, Rooftop Units <br />23 40 13.13.A Standard filter section <br />1.Shall consist of factory-installed, low velocity, disposable 2" or 4" thick fiberglass filters of commercially available sizes. <br />2.Units can accept 2” or 4” filters and have a field convertible toolless <br />3.Filters shall be accessible through an access panel with toolless removal as described in the unit cabinet section of this <br />specification (23 81 19.13.H). <br />  <br />23 81 19 Self-Contained Air Conditioners <br />  <br />23 81 19.13 Small-Capacity Self-Contained Air Conditioners <br />23 81 19.13.A General <br />1.Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a fully hermetic scroll compressor(s) <br />for cooling duty and gas combustion for heating duty. <br />2.Factory assembled, single-piece heating and cooling rooftop unit. Contained within the unit enclosure shall be all <br />factory wiring, piping, controls, and special features required prior to field start-up. <br />3.Unit shall use environmentally sound, R-410A refrigerant. <br />4.Unit shall be installed in accordance with the manufacturer’s instructions. <br />5.Unit must be selected and installed in compliance with local, state, and federal codes. <br />23 81 19.13.B Quality Assurance <br />1.Unit meets ASHRAE 90.1 minimum efficiency requirements. <br />2.ZY units are Energy Star certified. <br />3.Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360. <br />4.Unit shall be designed to conform to ASHRAE 15, 2001. <br />5.Unit shall be UL- tested and certified in accordance with ANSI Z21.47 -2012/CSA 2.3-2012, CSA C22.2 No. 236-11 (UL <br />1995) 4th edition and CSA C22.2 No. 3 - M 1988 <br />6.Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation. <br />7.Unit casing shall be capable of withstanding 750-hour salt spray exposure per ASTM B117 (scribed specimen). <br />8.Unit shall be designed in accordance with ISO 9001, and shall be manufactured in a facility registered by; ISO 9001. <br />9.Roof curb shall be designed to conform to NRCA Standards. <br />10.Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit; will be stored <br />at the factory, and must be available upon request. <br />11.Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain. <br />12.Unit shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability. <br />Guide Specification for <br />York® Sun™ Core <br />Page: 14 <br />3925 S Bristol <br />St-HVAC12/23/2024