b.Shall use permanently lubricated bearings. <br />c.Shall have inherent thermal overload protection with an automatic reset feature. <br />d.All models shall use a shaft-down design except shaft-up on ZX14 & ZY12 size with rain shield. <br />2.Condenser Fans <br />a.Shall be a direct-driven propeller type fan. <br />b.Shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynamically balanced. <br />23 81 19.13.O Special Features Options and Accessories <br />1.IntelliSpeed-Staged Air Volume System (ZX08-14 & ZY08-12) <br />a.Evaporator fan motor: <br />(1.)Shall have permanently lubricated bearings. <br />(2.)Shall have a maximum continuous bhp rating for continuous duty operation; no safety factors above that <br />rating. <br />(3.)Shall be Variable Frequency duty and 2-speed control. <br />(4.)Shall contain motor shaft grounding ring to prevent electrical bearing fluting damage by safely diverting <br />harmful shaft voltages and bearing currents to ground. <br />2.Variable Frequency Drive (VFD). Only available on 2-speed indoor fan motor option (IntelliSpeed) <br />INSERT MITSUBISHI DRIVE SPECIFICATIONS <br />3.Standard Integrated Economizers: <br />a.Integrated, gear-driven opposing modulating blade design type capable of simultaneous economizer and <br />compressor operation. <br />b.Independent modules for vertical or horizontal return configurations shall be available. Vertical return modules shall <br />be available as a factory installed option. <br />c.Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or return <br />shall not be acceptable. <br />d.Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or humidity <br />are below setpoints. <br />e.Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for positive air <br />stream control. <br />f.Standard models shall be equipped with low- leakage dampers, not to exceed 2% leakage at 1 in. wg pres- sure <br />differential. Economizers will come with Actuator and module that is tied to Smart Equipment™ <br />(1.)Combined minimum and DCV maximum damper position potentiometers with compressor staging re-lay. <br />(2.)Functions with solid state analog enthalpy or dry bulb changeover control sensing. <br />(3.)Contain LED indicates for:when free cooling is availablewhen module is in DCV mode when exhaust fan <br />contact is closed <br />7.Condenser Coil Hail Guard Assembly (Factory installed option on 3-phase models. Field installed on all 3 and 1 phase <br />models): <br />a.Shall protect against damage from hail. <br />b.Shall be of louvered style. <br />Guide Specification for <br />York® Sun™ Core <br />Page: 18 <br />3925 S Bristol <br />St-HVAC12/23/2024