b.Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to CSA C22.2 No. 236- <br />11 (UL 1995) 4th edition burst test at 1775 psig. <br />c.Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to CSA C22.2 No. 236- <br />11 (UL 1995) 4th edition burst test at 1980 psig. <br />23 81 19.13.K Refrigerant Components <br />1.Refrigerant circuit shall include the following control, safety, and maintenance features <br />a.Thermostatic Expansion Valve (TXV) shall help provide optimum performance across the entire operating range. <br />Shall contain removable power element to allow change out of power element and bulb without removing the valve <br />body.(Orifice on ZX08, ZX09, ZX12, ZQ04, ZQ05 & ZQ06) <br />b.Refrigerant filter drier - Solid core design. <br />c.Service gauge connections on suction and discharge lines. <br />d.Pressure gauge access through a specially designed access port in the top panel of the unit. <br />2.There shall be gauge line access port in the skin of the rooftop, covered by a black, removable plug. <br />a.The plug shall be easy to remove and replace. <br />b.When the plug is removed, the gauge access port shall enable maintenance personnel to route their pressure <br />gauge lines. <br />c.This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the reading <br />with the compressor access panel on. <br />d.The plug shall be made of a leak proof, UV- resistant, composite material. <br />3.Compressors <br />a.Unit shall use fully hermetic, scroll compressor for each independent refrigeration circuit. <br />b.Compressor motors shall be cooled by refrigerant gas passing through motor windings. <br />c.Compressors shall be internally protected from high discharge temperature conditions. <br />d.Compressors shall be protected from an over-temperature and over-amperage conditions by an internal, motor <br />overload device. <br />e.Compressor shall be factory mounted on rubber grommets. <br />f.Compressor motors shall have internal line break thermal, current overload and high pressure differential <br />protection. <br />g.Crankcase heaters shall not be required for normal operating range, unless provided by the factory. <br />23 81 19.13.L Filter Section <br />1.Filters access is specified in the unit cabinet section of this specification. <br />2.Shall consist of factory-installed, low velocity, throw-away 2” or 4” thick fiberglass filters. <br />3.Units can accept 2” or 4” filters and have a field convertible toolless <br />23 81 19.13.M Evaporator Fan and Motor <br />1.Evaporator fan motor <br />a.Shall have permanently lubricated bearings. <br />b.Shall have inherent automatic reset thermal protection (Only on single-phase, belt-drive motors, three - phase, <br />belt-drive motors have internal thermostat used for external line-break control.). <br />3.Belt-driven Evaporator Fan <br />a.Belt drive shall include an adjustable-pitch motor pulley. <br />b.Shall use sealed, permanently lubricated ball-bearing type. <br />c.Blower fan shall be double-inlet type with forward-curved blades. <br />d.Shall be constructed from steel with a corrosion resistant finish and dynamically balanced. <br />23 81 19.13.N Condenser Fans and Motors <br />The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant <br />steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall have permanently <br />lubricated 60°C ball bearings internally protected against overload conditions and staged independently. A cleaning window shall <br />be provided on two sides of the units for coil cleaning. <br />1.Condenser fan motors <br />a.Shall be a totally enclosed motor. <br />Guide Specification for <br />York® Sun™ Core <br />Page: 17 <br />3925 S Bristol <br />St-HVAC12/23/2024