GENERAL REQUIREMENTS
<br />1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL DIMENSIONS, PROJECT BOUNDARIES AND EXISTING
<br />CONDITIONS AT THE SITE PRIOR TO COMMENCEMENT OF WORK. THE CONTRACTOR SHALL CROSS-CHECK DETAILS AND
<br />DIMENSIONS SHOWN ON THE STRUCTURAL DRAWINGS WITH RELATED REQUIREMENTS ON OTHER CONSTRUCTION
<br />DOCUMENTS.
<br />
<br />2. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE STRUCTURAL ENGINEER OF RECORD (SEOR) OF ANY CONFLICTS
<br />BETWEEN THE STRUCTURAL DRAWINGS AND OTHER CONSTRUCTION DOCUMENTS OR EXISTING CONDITIONS. THE
<br />CONTRACTOR SHALL NOT ORDER MATERIAL, FABRICATE ELEMENTS, OR CONSTRUCT ANY PORTION OF STRUCTURE
<br />THAT IS IN CONFLICT UNTIL RESOLUTION IS MADE.
<br />3. WHEN DIMENSIONS ARE UNCLEAR, REQUEST CLARIFICATION FROM THE SEOR AND ARCHITECT. DO NOT SCALE
<br />DRAWINGS. UNLESS NOTED OTHERWISE, PLAN DIMENSIONS INDICATE CENTERLINE OF BEAMS AND COLUMNS, LIGHT-
<br />FRAMED WALLS ARE DIMENSIONED TO FACE OF STUDS, AND FOOTINGS ARE CENTERED UNDER THE ELEMENTS THEY
<br />SUPPORT.
<br />4. WHERE INFORMATION IS CONFLICTING WITHIN THE STRUCTURAL DOCUMENTS, SPECIFIC DETAILS SHALL GOVERN OVER
<br />TYPICAL DETAILS, WHICH HAVE PRECEDENCE OVER THESE NOTES, WHICH IN TURN OVERRULE PROJECT
<br />SPECIFICATIONS.
<br />5. DETAILS NOTED AS TYPICAL ON STRUCTURAL SHEETS SHALL APPLY IN ALL CASES UNLESS SPECIFICALLY SHOWN OR
<br />NOTED OTHERWISE. WHERE NO DETAIL IS INDICATED, CONSTRUCTION SHALL BE OF THE SAME NATURE AS FOR SIMILAR
<br />CASES OF CONSTRUCTION ON THIS PROJECT.
<br />
<br />6. THE ARCHITECT AND SEOR SHALL INTERPRET THE CONSTRUCTION DOCUMENTS IN CASE OF POSSIBLE CONFLICT OR
<br />DISCREPANCY BETWEEN STRUCTURAL AND OTHER DISCIPLINES.
<br />7. THE CONTRACTOR SHALL PROVIDE ALL NEW (N) MATERIALS TO PERFORM THE WORK INDICATED ON STRUCTURAL
<br />DOCUMENTS UNLESS NOTED AS EXISTING (E) OR SUPPLIED BY OTHERS. WRITTEN APPROVAL FROM THE SEOR SHALL
<br />BE OBTAINED PRIOR TO THE SUBSTITUTION OF ANY MATERIAL OR PRODUCT SPECIFIED ON THE STRUCTURAL
<br />DOCUMENTS.
<br />8. STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE, UNLESS OTHERWISE SHOWN THEY
<br />DO NOT INDICATE THE METHOD OF CONSTRUCTION OR NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY. THE
<br />CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN OF TEMPORARY ERECTION AIDS, FORMWORK, SCAFFOLDING,
<br />SAFETY MEASURES, SHORING OF ANY PORTION OF WORK, AND PROTECTION OF ADJACENT PROPERTIES. THE
<br />CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS,
<br />METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. VISITS TO THE SITE BY THE SEOR SHALL NOT INCLUDE
<br />OBSERVATION OR INSPECTION OF THE ABOVE ITEMS AND DO NOT IN ANY WAY RELIEVE THE CONTRACTOR OF HIS
<br />RESPONSIBILITIES FOR THE ABOVE.
<br />
<br />9. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH THE PERTINENT SECTIONS OF THE "CONSTRUCTION
<br />SAFETY ORDERS" ISSUED BY THE STATE OF CALIFORNIA, LATEST EDITION, AND ALL OSHA REQUIREMENTS AS THEY
<br />APPLY TO THIS PROJECT. THE SEOR AND THE OWNER DO NOT ACCEPT ANY RESPONSIBILITY FOR THE CONTRACTOR'S
<br />FAILURE TO COMPLY WITH THESE.
<br />10. ALL STRUCTURAL FRAMING SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING SHALL BE INSTALLED
<br />AND LEFT IN PLACE UNTIL ADEQUATE STRUCTURE IS CONSTRUCTED FOR STABILITY.
<br />11. CONSTRUCTION MATERIALS AND ERECTION LOADS SHALL BE DISTRIBUTED WHEN PLACED ON THE STRUCTURE SUCH
<br />THAT THEY DO NOT EXCEED DESIGN LIVE LOADS OR RESULT IN AN UNBALANCED CONDITION. MAXIMUM PERMANENT
<br />EQUIPMENT WEIGHTS, POSTED LOAD LIMITS OR OTHER RESTRICTIONS NOTED ON THE STRUCTURAL DRAWINGS SHALL
<br />NOT BE EXCEEDED WITHOUT PRIOR WRITTEN APPROVAL BY THE SEOR. UNLESS SPECIFICALLY STATED, THE
<br />STRUCTURE IS NOT DESIGNED TO SUPPORT TRAFFIC FROM CRANES OR OTHER HEAVY CONSTRUCTION VEHICLES.
<br />12. FLOOR, ROOF AND WALL OPENINGS, SLEEVES, INSERTS, EMBEDS, CONDUITS AND OTHER DISCIPLINE REQUIREMENTS
<br />MUST BE COORDINATED BEFORE THE CONTRACTOR PROCEEDS WITH CONSTRUCTION. THE EXACT DEPTH, EXTENT,
<br />AND LOCATION OF ALL FLOOR OR ROOF DEPRESSIONS, SLOPES, CURBS, PADS, TRENCHES, DRAINS AND OTHER
<br />FEATURES SHALL BE COORDINATED WITH THE CONSTRUCTION DOCUMENTS. THE STRUCTURAL DRAWINGS DO NOT
<br />NECESSARILY INDICATE ALL OF THESE ITEMS.
<br />13. CORE DRILLING OF CONCRETE OR MASONRY IS NOT PERMITTED WITHOUT PRIOR APPROVAL BY THE SEOR. CORES,
<br />WHERE APPROVED SHALL NOT CUT REINFORCEMENT. THE CONTRACTOR SHALL PRESENT ALL CORES TO THE
<br />INSPECTOR OF RECORD (IOR) FOR VERIFICATION.
<br />14. STRUCTURAL DRAWINGS INDICATE THE APPROXIMATE LOCATION OF EQUIPMENT AND THEIR SECONDARY FRAMING
<br />SUPPORTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK BETWEEN SUBCONTRACTORS AND
<br />CRAFTS IN ORDER TO PROVIDE NECESSARY DIMENSIONS IN A TIMELY MANNER TO ALL PARTIES AND DETAILERS
<br />INVOLVED.
<br />
<br />15. PROVIDE A SHIM SPACE AT HEADERS AND JAMBS TO ALLOW FOR SETTLEMENT AND MOVEMENT OF FRAMING. INSTALL
<br />WINDOWS, DOORS AND OTHER INSET ITEMS IN WALLS AFTER BUILDING LOADS ARE FULLY APPLIED.
<br />16. EXPANSION AND SEPARATION JOINT DIMENSIONS SHOWN INDICATE THE CLEAR DISTANCE REQUIRED. COMPONENTS
<br />COVERING OR CROSSING SUCH JOINTS MUST ACCOMMODATE THE JOINT FULLY CLOSING OR OPENING TO TWICE THE
<br />DIMENSION SHOWN, AS WELL AS RELATIVE LATERAL MOVEMENT ALONG THE JOINT. ALL PIPES, DUCTS, CONDUIT, ETC.,
<br />CROSSING SUCH JOINTS SHALL HAVE FLEXIBLE LINES WITH ADEQUATE RANGE OF MOTION.
<br />STRUCTURAL DESIGN CRITERIA__________________________________________________________
<br />CODES:DESIGN IS BASED ON THE 2022 CALIFORNIA BUILDING CODE
<br />LIVE LOADS (REDUCIBLE, UNO):
<br />ROOF, UNIFORM..................................................................................................................20 PSF
<br />TYPICAL OFFICE, UNIFORM + PARTITION ALLOWANCE................50 PSF + 15 PSF = 65 PSF
<br />WIND LOADS:
<br />RISK CATEGORY...........................................................................................................................II
<br />EXPOSURE....................................................................................................................................B
<br />ULTIMATE DESIGN WIDE SPEED, Vult............................................................................95 MPH
<br />INTERNAL PRESSURE COEFFICIENT, G Cpi.......................................................................± 0.18
<br />EARTHQUAKE LOADS:
<br />RISK CATEGORY..........................................................................................................................II
<br />SEISMIC IMPORTANCE FACTOR, Ie.........................................................................................1.0
<br />SITE CLASSIFICATION................................................................................................D-DEFAULT
<br />SPECTRAL ACCEL PARAMETERS (USGS ‘08)........................................SS = 1.265, S1 = 0.454
<br />DESIGN SPECTRAL ACCEL PARAMETERS.........................................SDS = 1.012, SD1 = 0.562
<br />SEISMIC DESIGN CATEGORY.....................................................................................................D
<br />SEISMIC FORCE RESISTING SYSTEM(S):
<br />NON STRUCTURAL COMPONENTS
<br />STRUCTURAL SUBMITTALS
<br />1. REVIEW OF SHOP DRAWINGS AND SUBMITTALS BY THE SEOR IS FOR GENERAL CONFORMANCE WITH THE
<br />INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. SEE THE STRUCTURAL SUBMITTAL SCHEDULE AND PROJECT
<br />SPECIFICATIONS FOR REQUIREMENTS.
<br />2. SHOP DRAWINGS FOR ITEMS SPECIFIED ON THE STRUCTURAL DOCUMENTS SHALL BE SUBMITTED TO THE SEOR FOR
<br />REVIEW PRIOR TO FABRICATION. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING DIMENSIONS, AND ALL ERRORS
<br />OF DETAILING, FABRICATION, AND FIT UP OF STRUCTURAL MEMBERS INCLUDING COORDINATION WITH OTHER
<br />TRADES.
<br />3. SHOP DRAWINGS SUBMITTED TO THE SEOR SHALL CONSIST OF ELECTRONIC FILES AND/OR TWO HARDCOPY SETS.
<br />ALLOW 10 BUSINESS DAYS FOR REVIEW BY THE SEOR UPON RECEIPT UNLESS ADVANCE NOTICE IS PROVIDED AND A
<br />REDUCED TIMEFRAME AGREED UPON. THE SEOR WILL RETURN ONE SET OF REVIEWED ELECTRONIC FILES OR
<br />HARDCOPY. SCHEDULE ALLOWANCE FOR REVIEWS AND PROCESSING TIME BY THE ARCHITECT, OWNER OR OTHER
<br />DISCIPLINES MAY BE REQUIRED.
<br />4. SHOP DRAWINGS AND SUBMITTALS DO NOT CONSTITUTE CHANGE ORDERS. ANY PROPOSED DEVIATION FROM THE
<br />STRUCTURAL DOCUMENTS MUST BE SUBMITTED IN WRITING AS A REQUEST FOR SUBSTITUTION FOR APPROVAL BY
<br />THE SEOR.
<br />5. SUBSTITUTION REQUESTS FOR MATERIALS SPECIFIED ON THE STRUCTURAL DOCUMENTS MAY BE CONSIDERED WITH
<br />MATERIALS HAVING EQUIVALENT OR GREATER CAPACITY AND PERFORMANCE. CURRENT EVALUATION REPORTS
<br />AND PRODUCT INFORMATION SHALL BE PROVIDED TO THE SEOR DEMONSTRATING EQUIVALENT QUALITIES OF THE
<br />MATERIAL TO BE SUBSTITUTED.
<br />6. EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND- OR SEISMIC- LATERAL FORCE
<br />RESISTING SYSTEM (LFRS), DESIGNATED SEISMIC SYSTEM, OR A WIND- OR SEISMIC-RESISTING COMPONENT LISTED
<br />IN THE STATEMENT OF SPECIAL INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE
<br />BUILDING OFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT.
<br />THE CONTRACTOR’S STATEMENT OF RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGEMENT OF AWARENESS OF THE
<br />SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTION.
<br />THE STRUCTURAL SUBMITTAL SCHEDULE BELOW IS A SUMMARY LIST AND MAY NOT BE ALL INCLUSIVE OF
<br />SUBMITTALS REQUIRED FOR THIS PROJECT. PROVIDE ALL SUBMITTALS NOTED ON THE CONTRACT DOCUMENTS
<br />AND AS REQUIRED BY THE ARCHITECT, BUILDING OFFICIAL AND OWNER’S REPRESENTATIVE.
<br />STRUCTURAL SUBMITTAL SCHEDULE
<br />GENERAL
<br />REQ’D: QUALIFICATION DATA FOR APPROVED INSTALLERS AND FABRICATORS
<br />REQ’D: CERTIFICATES OF CONFORMANCE FOR PREFABRICATED MEMBERS
<br />REQ’D: STATEMENT OF RESPONSIBILITY FOR LFRS CONSTRUCTION
<br />CONCRETE FORMWORK
<br />NOT REQ’D: MANUFACTURER’S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR PROPRIETARY
<br />MATERIALS INCLUDING FORM COATINGS, MANUFACTURED FORM SYSTEMS, TIES AND
<br />ACCESSORIES
<br />NOT REQ’D: SHOP DRAWINGS FOR FABRICATION AND ERECTION OF FORMWORK AND SHORING
<br />CONCRETE REINFORCEMENT
<br />REQ’D: MANUFACTURER’S PRODUCT DATA, SPECIFICATIONS AND INSTALLATION PROCEDURES FOR
<br />PROPRIETARY MATERIALS AND REINFORCEMENT
<br />REQ’D: STEEL PRODUCER’S CERTIFICATES OF MILL ANALYSIS, TENSILE AND BEND TESTS
<br />REQ’D: SHOP DRAWINGS FOR FABRICATION, BENDING AND PLACEMENT
<br />CAST-IN-PLACE CONCRETE
<br />REQ’D: DESIGN MIX FOR EACH CONCRETE MIXTURE, INDICATING LOCATION OF USE
<br />REQ’D: MATERIAL CERTIFICATES FOR CEMENT, AGGREGATES AND ADMIXTURES
<br />REQ’D: TEST CERTIFICATES FOR NON-POTABLE MIX WATER
<br />REQ’D: SHOP DRAWINGS FOR PROPOSED LOCATIONS OF CONSTRUCTION AND CONTROL JOINTS
<br />REQ’D: MINUTES FROM PREINSTALLATION CONFERENCE
<br />NOT REQ’D: MANUFACTURER’S PRODUCT DATA FOR WATERSTOPS, BONDING AGENTS, VAPOR RETARDERS,
<br />JOINT FILLER, CURING MATERIALS AND FLOOR TREATMENTS
<br />REQ’D: CERTIFICATION OF INSTALLERS FOR OVERHEAD ADHESIVE ANCHORS
<br />REQ’D: SHOP DRAWINGS FOR SHOTCRETE TEST PANELS AND MOCKUPS
<br />REQ’D: SHOTCRETE CONTRACTOR AND NOZZLEMENT QUALIFICATIONS
<br />MASONRY
<br />NOT REQ’D: DESIGN MIX FOR GROUT
<br />NOT REQ’D: MATERIAL TEST REPORTS
<br />STRUCTURAL STEEL
<br />REQ’D: MANUFACTURER’S MILL CERTIFICATES
<br />REQ’D: MILL TEST REPORTS
<br />REQ’D: SHOP DRAWINGS FOR FABRICATION AND ASSEMBLY OF MEMBERS
<br />REQ’D: ERECTION PLAN SEQUENCE AND PROCEDURES
<br />REQ’D: TEST REPORTS FOR SHOP AND FIELD WELDED AND BOLTED CONNECTIONS
<br />STEEL JOISTS
<br />REQ’D: SHOP DRAWINGS INDICATING LAYOUT AND DETAILS
<br />NOT REQ’D: MANUFACTURER’S MILL CERTIFICATES
<br />NOT REQ’D: ENGINEERING CALCULATIONS
<br />STEEL DECK
<br />REQ’D: SHOP DRAWINGS INDICATING TYPE, LAYOUT, DETAILS AND OPENINGS LARGER THAN 1 FOOT
<br />COLD-FORMED METAL FRAMING
<br />NOT REQ’D: SHOP DRAWINGS INDICATING LAYOUT AND DETAILS
<br />NOT REQ’D: ENGINEERING CALCULATIONS
<br />WELDING
<br />REQ’D: WELDING PROCEDURE SPECIFICATIONS (WPS)
<br />REQ’D: CERTIFICATES FOR ALL WELDERS VERIFYING CURRENT AWS QUALIFICATIONS
<br />ROUGH CARPENTRY
<br />NOT REQ’D: PRODUCT DATA FOR TREATMENTS AND PRESERVATIVES
<br />NOT REQ’D: MATERIAL CERTIFICATES FOR DIMENSION LUMBER
<br />PREFABRICATED WOOD PRODUCTS
<br />NOT REQ’D: SHOP DRAWINGS INDICATING LAYOUT AND DETAILS
<br />NOT REQ’D: ENGINEERING CALCULATIONS
<br />GLUE-LAMINATED BEAMS
<br />NOT REQ’D: SHOP DRAWINGS INDICATING LAYOUT
<br />NOT REQ’D: CERTIFICATE OF CONFORMANCE
<br />M/E/P COORDINATION
<br />REQ’D: SHOP DRAWINGS OF PROPOSED LAYOUT OF PIPES, DUCTS AND CONDUIT INDICATING DETAILS OF
<br />PENETRATIONS THROUGH STRUCTURE; GRAVITY AND SEISMIC FORCES OF SUPPORTS AND
<br />BRACING ON STRUCTURE
<br />DEFERRED APPROVALS
<br />REQ’D: DRAWINGS, AND AS APPLICABLE, STRUCTURAL DESIGN CALCULATIONS
<br />FOUNDATIONS
<br />REQ’D: INSTALLATION PLAN FOR PILES / MICROPILES
<br />REQ’D: AS BUILT RECORD SURVEY FOR PILES / MICROPILES
<br />SPECIAL INSPECTIONS SCHEDULE
<br />SOILS SUPPORTING FOUNDATIONS
<br />PERIODIC: VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL
<br />PERIODIC: VERIFY MATERIALS BELOW FOOTING ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.
<br />PERIODIC: PRIOR TO PLACEMENT OF CONTROLLED FILL, INSPECT SUBGRADE AND VERIFY THAT SITE HAS BEEN
<br />PREPARED PROPERLY
<br />CONTINUOUS: VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING PLACEMENT AND
<br />COMPACTION OF CONTROLLED FILLS
<br />PERIODIC: PERFORM CLASSIFICATION AND TESTING OF CONTROLLED FILL MATERIALS
<br />STRUCTURAL CONCRETE AND REINFORCEMENT
<br />PERIODIC: INSPECTIONS OF REINFORCING STEEL AND PLACEMENT
<br />PERIODIC: INSPECT BOLTS TO BE INSTALLED IN CONCRETE PRIOR TO AND DURING PLACEMENT OF CONCRETE
<br />PERIODIC: INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING
<br />FORMED
<br />PERIODIC: VERIFY USE OF REQUIRED DESIGN MIX
<br />PERIODIC: VERIFY COMPLIANCE OF NON-POTABLE MIX WATER
<br />CONTINUOUS: INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES
<br />CONTINUOUS: SAMPLING FRESH CONCRETE AND PERFORMING SLUMP AND AIR CONTENT TESTS & DETERMINING THE
<br />TEMPERATURE OF FRESH CONCRETE AT THE TIME OF MAKING SPECIMENS FOR STRENGTH TESTS
<br />PERIODIC: INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUE
<br />PERIODIC: VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO REMOVAL OF SHORES AND FORMS FROM
<br />BEAMS AND STRUCTURAL SLABS
<br />PERIODIC: ERECTION OF PRECAST CONCRETE MEMBERS
<br />PERIODIC: POST-INSTALLED AND ADHESIVE ANCHORS
<br />PERIODIC: VERIFY INSTALLER CERTIFICATIONS FOR OVERHEAD ADHESIVE ANCHORS
<br />CONTINUOUS: REBAR COUPLERS AND TERMINATORS, SELECT SPLICE SPECIMENS FOR TESTING
<br />CONTINUOUS: [DSA/OSHPD] POST-INSTALLED AND ADHESIVE ANCHORS
<br />STRUCTURAL STEEL
<br />PERIODIC: STRUCTURAL STEEL IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS SPECIFIED IN THE
<br />APPROVED CONSTRUCTION DOCUMENTS
<br />PERIODIC: STRUCTURAL STEEL MANUFACTURER’S CERTIFIED MILL TEST REPORTS REQUIRED
<br />PERIODIC: INSPECTION OF STEEL FRAME BRACING & STIFFENER DETAILS FOR COMPLIANCE WITH APPROVED
<br />CONSTRUCTION DOCUMENTS
<br />PERIODIC: STEEL FRAME MEMBER LOCATIONS
<br />PERIODIC: APPLICATION OF JOINT DETAILS AT EACH CONNECTION
<br />PERIODIC: HIGH-STRENGTH BOLTS, NUTS, AND WASHERS IDENTIFICATION MARKINGS TO CONFORM TO ASTM
<br />STANDARDS SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS, MANUFACTURER'S
<br />CERTIFICATE OF COMPLIANCE REQUIRED
<br />PERIODIC: INSPECTION OF HIGH-STRENGTH BOLTING BEARING-TYPE CONNECTIONS
<br />PERIODIC: INSPECTION OF SLIP-CRITICAL CONNECTIONS USING TURN-OF-NUT METHOD WITH MATCHMARKING,
<br />DIRECT TENSION INDICATOR METHOD, OR TWIST OFF BOLTS
<br />CONTINUOUS: INSPECTION OF SLIP-CRITICAL CONNECTIONS USING CALIBRATED WRENCH METHOD OR TURN-OF-NUT
<br />WITHOUT MATCHMARKING
<br />WELDING
<br />CONTINUOUS: COMPLETE AND PARTIAL PENETRATION GROOVE WELDS
<br />CONTINUOUS: FILLET WELDS > 5/16" AND MULTIPASS FILLET WELDS
<br />PERIODIC: FILLET WELDS ≤ 5/16"
<br />PERIODIC: METAL DECK WELDS
<br />PERIODIC: LIGHT GAUGE METAL WELDS
<br />PERIODIC: WELD FILLER MATERIAL IDENTIFICATION MARKINGS TO CONFORM TO AWS STANDARDS SPECIFIED IN
<br />THE APPROVED CONSTRUCTION DOCUMENTS, MANUFACTURE’S CERTIFICATION OF COMPLIANCE
<br />REQUIRED
<br />CONTINUOUS: WELDING OF REINFORCEMENT STEEL RESISTING SEISMIC FORCES, INDICATED ON PLANS AND DETAILS
<br />AS LFRS ELEMENT OR CONNECTIONS
<br />PERIODIC: VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER THAN ASTM A706
<br />CONTINUOUS: WELDING OF STIRRUPS, HOOPS OR TIES
<br />CONTINUOUS: REINFORCING WELDS IN CMU
<br />PERIODIC: ALL OTHER REINFORCEMENT WELDS, UNO
<br />ROUGH CARPENTRY / WOOD
<br />PERIODIC: FRAMING NAILS SIZE, TYPE AND FINISH
<br />PERIODIC: NAILING OF ROOF, WALL, & FLOOR SHEATHING
<br />PERIODIC: NAILING/BOLTING OF STRAPS, HOLDOWNS, BRACES AND DRAG STRUTS
<br />PERIODIC: MANUFACTURE OF STRUCTURAL GLUED-LAMINATED TIMBERS LARGER THAN 5-1/8" WIDE, 18" DEEP, OR
<br />CLEAR SPAN 32 FEET OR MORE
<br />PERIODIC: MANUFACTURE OF OPEN WEB TRUSSES
<br />PERIODIC: INSTALLATION OF TIMBER CONNECTORS
<br />PERIODIC: HIGH LOAD WOOD DIAPHRAGMS, VERIFY PANEL GRADE. THICKNESS, NOMINAL FRAMING SIZES AND
<br />FASTENERS PER APPROVED PLANS
<br />CONCRETE MASONRY
<br />PERIODIC: PROPORTIONS OF SITE- PREPARED MORTAR AND GROUT
<br />CONTINUOUS: PREPARATION OF GROUT & MORTAR SPECIMENS AND/OR PRISMS
<br />PERIODIC: VERIFICATION OF SIZE & LOCATION OF MASONRY UNITS
<br />PERIODIC: VERIFICATION OF SIZE, GRADE, TYPE AND PLACEMENT OF REINFORCING STEEL
<br />PERIODIC: VERIFICATION OF SIZE AND LOCATION OF ANCHORS OR EMBEDDED STRUCTURAL ELEMENTS
<br />INCLUDING OTHER DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES OR
<br />OTHER CONSTRUCTION
<br />PERIODIC: CONSTRUCTION OF MORTAR JOINTS
<br />PERIODIC: GROUT SPACE CLEAN PRIOR TO GROUTING
<br />CONTINUOUS: GROUT PLACEMENT PER CONSTRUCTION DOCUMENTS & CODE COMPLIANCE
<br />PERIODIC: COMPLIANCE WITH REQUIRED INSPECTION PROVISIONS OF CONSTRUCTION DOCUMENTS & APPROVED
<br />SUBMITTALS SHALL BE VERIFIED
<br />PERIODIC: PROTECTION OF MASONRY DURING COLD WEATHER BELOW 40˚F OR HOT WEATHER ABOVE 90˚F
<br />PERIODIC: POST-INSTALLED ANCHORS AND REINFORCEMENT
<br />CONTINUOUS: [DSA / OSHPD] POST-INSTALLED ANCHORS AND REINFORCEMENT
<br />COLD-FORMED STEEL FRAMING
<br />PERIODIC: SCREW ATTACHMENT, BOLTING, AND ANCHORING OF STRAPS, HOLDOWNS, BRACES, DRAG STRUTS,
<br />AND ROOF, WALLS AND FLOORS.
<br />PERIODIC: INSTALLATION OF STEEL DECKING PER SDI QA/QC STANDARDS
<br />STATEMENT OF SPECIAL INSPECTIONS
<br />1. THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS TO PROVIDE INSPECTIONS DURING CONSTRUCTION.
<br />THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO DEMONSTRATES COMPETENCE TO THE SATISFACTION OF
<br />THE BUILDING OFFICIAL FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING
<br />SPECIAL INSPECTION.
<br />2. SEE THE SPECIAL INSPECTIONS SCHEDULE AND PROJECT SPECIFICATIONS FOR REQUIREMENTS. IT IS SOLELY THE
<br />CONTRACTOR’S RESPONSIBILITY TO SEE THAT THESE INSPECTIONS ARE PERFORMED.
<br />3. SPECIAL INSPECTIONS ARE NOT REQUIRED WHERE THE WORK IS DONE ON THE PREMISES OF A FABRICATOR
<br />REGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION. APPROVED FABRICATORS MUST
<br />SUBMIT A CERTIFICATE OF COMPLIANCE FOR OFFSITE FABRICATIONS SUCH AS STRUCTURAL STEEL, PRECAST
<br />CONCRETE, GLUED LAMINATED TIMBER, ETC.
<br />4. ALL INSPECTIONS SHALL BE PERFORMED BY INDEPENDENT SPECIAL INSPECTORS. JOB SITE VISITS BY THE STRUCTURAL
<br />ENGINEER OR BUILDING OFFICIAL DO NOT CONSTITUTE AND ARE NOT A SUBSTITUTE FOR INSPECTIONS BY A SPECIAL
<br />INSPECTOR.
<br />5. ALL INSPECTION REPORTS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL AND SEOR. THE FINAL REPORTS BY THE
<br />SPECIAL INSPECTOR(S) MUST CERTIFY THAT THE ENTIRE STRUCTURAL SYSTEM COMPLIES WITH THE APPROVED PLANS
<br />AND SPECIFICATIONS.
<br />6. WORK REQUIRING SPECIAL INSPECTION SHALL BE INSPECTED BY THE SPECIAL INSPECTOR WHO IS PRESENT IN THE
<br />AREA WHERE THE WORK IS PERFORMED AND AT THE COMPLETION OF WORK. CONTINUOUS INSPECTION CONSISTS OF
<br />FULL-TIME INSPECTION; PERIODIC INSPECTION CONSISTS OF PART-TIME OR INTERMITTENT INSPECTION.
<br />7. THE SPECIAL INSPECTIONS SCHEDULE BELOW IS A SUMMARY LIST AND MAY NOT BE ALL INCLUSIVE OF INSPECTIONS
<br />REQUIRED FOR THIS PROJECT. THE CONTRACTOR SHALL CALL FOR ALL INSPECTIONS NOTED ON THE CONTRACT
<br />DOCUMENTS AND AS REQUIRED BY THE ARCHITECT, BUILDING OFFICIAL AND OWNER’S REPRESENTATIVE.
<br />No. 6250
<br />FFOHSIB
<br />RYAN W.
<br />REGISTEREDPROFESSIONALENGINEER
<br />STRUCTURALSTATEOFCALIFORNIA
<br />DATE:
<br />FOR BRANDOW & JOHNSTON
<br />STRUCTURAL+CIVIL ENGINEERS (B&J HBK, INC.)
<br />3300 IRVINE AVE. SUITE 245
<br />NEWPORT BEACH, CALIFORNIA 92660
<br />T:(949)862-8500 WWW.BJSCE.COM
<br />JOB#:
<br />1
<br />7
<br />
<br />8
<br />
<br />8
<br />
<br />0
<br />
<br />
<br />S
<br />
<br />k
<br />
<br />y
<br />
<br />
<br />P
<br />
<br />a
<br />
<br />r
<br />
<br />k
<br />
<br />
<br />C
<br />
<br />i
<br />
<br />r
<br />
<br />c
<br />
<br />l
<br />
<br />e
<br />
<br />,
<br />
<br />
<br />S
<br />
<br />u
<br />
<br />i
<br />
<br />t
<br />
<br />e
<br />
<br />2
<br />
<br />3
<br />
<br />0
<br />
<br />
<br />-
<br />I
<br />r
<br />
<br />v
<br />
<br />i
<br />
<br />n
<br />
<br />e
<br />
<br />,
<br />
<br />
<br />C
<br />
<br />A
<br />
<br />
<br />9
<br />
<br />2
<br />
<br />6
<br />
<br />1
<br />
<br />4
<br />t
<br />
<br />e
<br />
<br />
<br />l
<br />
<br />
<br />
<br />9
<br />
<br />
<br />4
<br />
<br />
<br />9
<br />
<br />
<br />
<br />.
<br />
<br />
<br />
<br />5
<br />
<br />
<br />5
<br />
<br />
<br />3
<br />
<br />
<br />
<br />.
<br />
<br />
<br />
<br />8
<br />
<br />
<br />9
<br />
<br />
<br />0
<br />
<br />
<br />0
<br />a
<br />r
<br />
<br />c
<br />
<br />h
<br />
<br />i
<br />
<br />t
<br />
<br />e
<br />
<br />c
<br />
<br />t
<br />
<br />u
<br />
<br />r
<br />
<br />e
<br />i
<br />n
<br />
<br />t
<br />
<br />e
<br />
<br />r
<br />
<br />i
<br />
<br />o
<br />
<br />r
<br />
<br />
<br />d
<br />
<br />e
<br />
<br />s
<br />
<br />i
<br />
<br />g
<br />
<br />n
<br />p
<br />l
<br />
<br />a
<br />
<br />n
<br />
<br />n
<br />
<br />i
<br />
<br />n
<br />
<br />g
<br />DA
<br />I
<br />M
<br />L
<br />E
<br />R
<br />
<br />A
<br />C
<br />P
<br />L
<br />30
<br />0
<br />9
<br />
<br />D
<br />A
<br />I
<br />M
<br />L
<br />E
<br />R
<br />
<br />S
<br />T
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />
<br />
<br />9
<br />2
<br />7
<br />9
<br />5
<br />S0.1
<br />GENERAL NOTES
<br />07/23/24
<br />NO. REMARKS DATE
<br />60% COMPLETE SET 05/28/24
<br />90% COMPLETE SET 07/12/24
<br />ISSUE FOR BID 07/16/24
<br />CITY SUBMITTAL 07/23/24
<br />NON-STRUCTURAL COMPONENTS
<br />PERIODIC: ERECTION AND FASTENING OF EXTERIOR CLADDING, INTERIOR AND EXTERIOR NONBEARING WALLS,
<br />AND INTERIOR AND EXTERIOR VENEER GREATER 30' HEIGHTS, EXTERIOR WALLS GREATER THAN 5
<br />PSF, AND INTERIOR WALLS MORE THAN 15 PSF
<br />PERIODIC: ANCHORAGE OF ELECTRICAL EQUIPMENT
<br />PERIODIC: ANCHORAGE OF SUSPENDED CEILING SYSTEMS
<br />PERIODIC: ANCHORAGE OF HVAC DUCTWORK THAT WILL CONTAIN HAZARDOUS MATERIALS
<br />PERIODIC: ANCHORAGE OF PIPING SYSTEMS AND MECHANICAL UNITS CONTAINING FLAMMABLE, COMBUSTIBLE
<br />OR HIGHLY TOXIC MATERIALS
<br />PERIODIC: ANCHORAGE OF ACCESS FLOORS AND ANCHORAGE OF STORAGE RACKS 8 FEET OR GREATER IN
<br />HEIGHT
<br />PERIODIC: FLEXIBLE CONNECTIONS OF UTILITIES CROSSING EXPANSION OR SEISMIC JOINTS
<br />PRESTRESSED CONCRETE
<br />PERIODIC: INSPECTION OF PRESTRESSNG TENDON PLACEMENT AND SIZES
<br />PERIODIC: VERIFICATION OF IN-SITU CONCRETE STRENGTH PRIOR TO STRESSING OF TENDONS IN
<br />POST-TENSIONED CONCRETE
<br />CONTINUOUS: APPLICATION OF PRESTRESSING LOADS
<br />CONTINUOUS: GROUTING OF BONDED PRESTRESSING TENDONS IN THE LFRS
<br />PIER FOUNDATIONS
<br />CONTINUOUS: OBSERVE DRILLING OPERATIONS AND MAINTAIN COMPLETE AND ACCURATE RECORDS FOR EACH PIER
<br />CONTINUOUS: VERIFY PLACEMENTS, LOCATIONS AND PLUMBNESS, CONFIRM PIER DIAMETERS, BELL DIAMETERS,
<br />LENGTHS, EMBEDMENT INTO BEDROCK (IF APPLICABLE) AND ADEQUATE END BEARING STRATA
<br />CAPACITY
<br />PILE FOUNDATIONS
<br />CONTINUOUS: VERIFY PILE MATERIALS, SIZES AND LENGTHS COMPLY WITH THE APPROVED CONSTRUCTION
<br />DOCUMENTS
<br />CONTINUOUS: DETERMINE CAPACITIES OF TEST PILES AND CONDUCT ADDITIONAL LOAD TESTS AS REQUIRED
<br />CONTINUOUS: OBSERVE DRIVING OPERATIONS AND MAINTAIN COMPLETE AND ACCURATE RECORDS FOR EACH PILE
<br />CONTINUOUS: VERIFY PLACEMENT, LOCATIONS AND PLUMBNESS, CONFIRM TYPE AND SIZE HAMMER, RECORD
<br />NUMBER OF BLOWS PER FOOT OF PENETRATION, DETERMINE REQUIRED PENETRATIONS TO ACHIEVE
<br />DESIGN CAPACITY, RECORD TIP AND BUTT ELEVATIONS AND DOCUMENT ANY PILE DAMAGE
<br />LE
<br />A
<br />V
<br />E
<br />
<br />B
<br />L
<br />A
<br />N
<br />K
<br />
<br />F
<br />O
<br />R
<br />
<br />C
<br />I
<br />T
<br />Y
<br />
<br />S
<br />T
<br />A
<br />M
<br />P
<br />3009 S Daimler St
<br />11/18/2024
|