GENERAL POWER NOTES <br />(UNLESS OTHERWISE NOTED, SOME MAY NOT APPLY) <br />A.CONTRACTOR SHALL VERIFY ALL LOCATIONS, MOUNTING HEIGHTS, CONNECTIONS <br />AND REQUIREMENTS WITH OTHER TRADES, OWNER, ARCHITECT AND/OR TENANT <br />AS APPLICABLE PRIOR TO INSTALL AND ADJUST ACCORDINGLY. CONTRACTOR <br />SHALL REVIEW ALL OTHER TRADE'S DRAWINGS AND INCLUDE IN HIS BID ALL COSTS <br />APPLICABLE TO THE ELECTRICAL TRADE WHETHER SHOWN IN THESE DRAWINGS <br />OR NOT. <br />B.WHERE NEW CONDUITS ARE TO BE INSTALLED UNDERGROUND, CONTRACTOR <br />SHALL EMPLOY DIG-ALERT AND PROVIDE X-RAYS AS REQUIRED TO PREVENT <br />DAMAGE TO EXISTING UNDERGROUND UTILITIES. CONTRACTOR SHALL INCLUDE <br />ALL COSTS TO SAW CUT, TRENCH, BACK FILL, COMPACT AND PATCH TO MATCH <br />EXISTING. <br />C.ALL UNDERGROUND CONDUITS SHALL BE 3/4" MINIMUM. <br />D.ALL CONDUITS SHALL BE ROUTED BELOW ROOF STRUCTURE. ALL ROOF <br />PENETRATIONS SHALL BE SEALED AND WEATHERPROOFED. PROVIDE ROOF JACKS <br />AT ALL PENETRATIONS. <br />E.WHERE CIRCUIT CONDUCTOR SIZE EXCEEDS THE LUG RATING OF THE CIRCUIT <br />BREAKER, PROVIDE A LISTED PIN ADAPTOR. IF A LISTED PIN ADAPTOR IS NOT <br />AVAILABLE, PROVIDE A SPLICE BOX DIRECTLY ABOVE THE PANEL AND REDUCE THE <br />CONDUCTOR TO THE MAXIMUM SIZE FOR WHICH THE CIRCUIT BREAKER IS LISTED. <br />F.ALL 20A-125V RECEPTACLES LOCATED WITH 6FT OF A SINK SHALL BE GFI TYPE <br />WHETHER INDICATED ON PLANS OR NOT. <br />G.CONTRACTOR SHALL PROVIDE FINAL CONNECTIONS TO ALL HARDWIRED <br />EQUIPMENT. UTILIZE CONDUIT AND CONDUCTOR SIZE SHOWN. WHERE APPLICABLE, <br />FINAL 24" OF CONDUIT SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT SIZED <br />PER CODE. <br />H.PROVIDE PROTECTIVE, REMOVABLE STEEL BOLLARD AS REQUIRED TO PROTECT <br />ELECTRICAL EQUIPMENT FROM VEHICULAR AND FORKLIFT TRAFFIC. MAINTAIN <br />CODE REQUIRES CLEARANCE. <br />GENERAL LIGHTING NOTES <br />(UNLESS OTHERWISE NOTED, SOME MAY NOT APPLY) <br />A.CONTRACTOR SHALL VERIFY ALL LOCATIONS, MOUNTING HEIGHTS, CONNECTIONS <br />AND REQUIREMENTS WITH OTHER TRADES, OWNER, ARCHITECT AND/OR TENANT <br />AS APPLICABLE PRIOR TO INSTALL AND ADJUST ACCORDINGLY. CONTRACTOR <br />SHALL REVIEW ALL OTHER TRADE'S DRAWINGS AND INCLUDE IN HIS BID ALL COSTS <br />APPLICABLE TO THE ELECTRICAL TRADE WHETHER SHOWN IN THESE DRAWINGS <br />OR NOT. <br />B.PROVIDE A COMPLETE MANUFACTURED WIRING SYSTEM FOR ALL LIGHT FIXTURES <br />IN ACCESSIBLE CEILINGS. SYSTEM SHALL INCLUDE ALL CONNECTIONS TO <br />FIXTURES AND CONTROLS WITH ALL REQUIRED SYSTEM COMPONENTS. <br />MANUFACTURER SHALL PROVIDE SUBMITTALS FOR INSTALLATION WITH ALL PART <br />NUMBERS. EQUIPMENT SHALL BE AMERICAN CABLE COMPANY. EMERGENCY <br />FIXTURES AND NIGHT LIGHTS SHALL BE CONNECTED WITH TRADITIONAL CONDUIT <br />AND CONDUCTORS TO EMERGENCY CIRCUIT. MANUFACTURED WIRING SYSTEM <br />SHALL ONLY BE USED FOR NORMAL CIRCUITS AS SHOWN ON PLAN. <br />C.ALL EMERGENCY "EM" LIGHT FIXTURES SHALL BE WIRED AND/OR PROGRAMMED TO <br />TURN "ON", "OFF" AND/OR DIM AS APPLICABLE WITH AREA CONTROLS. WHEN <br />NORMAL POWER FAILS, THE EMERGENCY FIXTURES SHALL ILLUMINATE AT FULL <br />BATTERY OUTPUT, REGARDLESS OF THE AREA CONTROL POSITION. <br />D.ALL EMERGENCY "EM" LIGHT FIXTURES WITH INTEGRAL BATTERY PACKS SHALL <br />HAVE THEIR BATTERY PACKS CONNECTED TO THE AREA'S UNSWITCHED CIRCUIT <br />AS REQUIRED. <br />E.ALL WALL MOUNTED LIGHTING CONTROL DEVICES SHALL BE MOUNTED AT +44"AFF. <br />F.PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCHES AND <br />MOTION SENSORS, PER 404.2(C). <br />G.CONTRACTOR SHALL PROVIDE ALL CAT 5 CONNECTIONS BETWEEN DEVICES AS <br />REQUIRED TO MAKE SYSTEM OPERABLE. <br />H.CONTRACTOR SHALL PROVIDE ALL 0-10V DIMMING CONNECTIONS BETWEEN <br />DEVICES AS REQUIRED TO MAKE SYSTEM OPERABLE. PROVIDE ADDITIONAL <br />POWER PACKS FOR FIXTURES WITH 0-10 VOLT DIMMING AS REQUIRED. <br />I.CONTRACTOR SHALL ADJUST LOCATION OF SENSORS AND/OR ADD ADDITIONAL <br />SENSORS AS REQUIRED TO MAKE SYSTEM OPERABLE IN FINAL SPACE <br />CONFIGURATION. CONTRACTOR SHALL ALSO INCLUDE IN HIS BID COST TO ADJUST <br />PROGRAMMING TO MEET TENANT REQUIREMENTS BUT IN NO CASE SHALL SUCH <br />ADJUSTMENTS VIOLATE CODE. <br />J.CONTRACTOR SHALL VERIFY EXIT SIGN LOCATIONS, MOUNTING HEIGHTS WITH <br />ARCHITECT. CONTRACTOR SHALL COORDINATE DIRECTIONAL ARROWS AND FACES <br />WITH ARCHITECT. CONTRACTOR SHALL ADD ADDITIONAL EXIT SIGNS AS DIRECTED <br />BY AUTHORITY HAVING JURISDICTION. <br />K.CONTRACTOR SHALL INCLUDE IN HIS BID ALL CONDUIT, WIRE, EQUIPMENT, LABOR, <br />TESTING, ETC., NECESSARY TO PROVIDE A COMPLETE, OPERABLE AND CODE <br />COMPLIANT SYSTEM. CONTRACTOR SHALL VERIFY ALL LOCATIONS PRIOR TO <br />INSTALL. <br />PROVIDE 20A-120V DOUBLE DUPLEX RECEPTACLE. ONE DUPLEX SHALL BE <br />CONTROLLED PER TITLE 24 AND THE OTHER SHALL BE UNCONTROLLED. <br />CONTROLLED RECEPTACLE SHALL BE BLACK IN COLOR (OR GREEN IF <br />AVAILABLE). COORDINATE EXACT COLOR WITH ARCHITECT. THE CONTROLLED <br />RECEPTACLE SHALL BE PERMANENTLY MARKED TO DIFFERENTIATE FROM THE <br />UNCONTROLLED RECEPTACLE PER 406.3(E). PROVIDE 3#12-1#12G-1/2"C FROM <br />RECEPTACLE TO ASSOCIATED J-BOX. ROUTE CONTROLLED RECEPTACLE <br />CIRCUIT THROUGH THE APPLICABLE RECEPTACLE CONTROL POWER PACK, <br />SENSOR SWITCH #nPP20 PL. PROVIDE A SEPARATE POWER PACK FOR EACH <br />CONTROLLED CIRCUIT. POWER PACK SHALL BE CONTROLLED BY ROOM <br />OCCUPANCY SENSOR(S). <br />PROVIDE 20A-120V DUPLEX RECEPTACLE. ONE HALF OF THE DUPLEX SHALL BE <br />CONTROLLED PER TITLE 24 AND THE OTHER HALF SHALL BE UNCONTROLLED. <br />CONTROLLED OUTLET SHALL BE BLACK IN COLOR (OR GREEN IF AVAILABLE). <br />COORDINATE EXACT COLOR WITH ARCHITECT. THE CONTROLLED OUTLET <br />SHALL BE PERMANENTLY MARKED TO DIFFERENTIATE FROM THE <br />UNCONTROLLED OUTLET PER 406.3(E). PROVIDE 3#12-1#12G-1/2"C FROM <br />RECEPTACLE TO ASSOCIATED J-BOX. ROUTE CONTROLLED OUTLET CIRCUIT <br />THROUGH THE APPLICABLE RECEPTACLE CONTROL POWER PACK, SENSOR <br />SWITCH #nPP20 PL. PROVIDE A SEPARATE POWER PACK FOR EACH <br />CONTROLLED CIRCUIT. POWER PACK SHALL BE CONTROLLED BY ROOM <br />OCCUPANCY SENSOR(S). <br />ROUTE CONTROLLED RECEPTACLE CIRCUIT THROUGH POWER PACK, SENSOR <br />SWITCH #nPP20 PL. PROVIDE SEPARATE POWER PACK FOR EACH CONTROLLED <br />CIRCUIT. CONNECT TO ROOM OCCUPANCY SENSOR. WHERE OCCUPANCY <br />SENSOR IS NOT SHOWN, PROVIDE A COMPATIBLE CEILING SENSOR. <br />PROVIDE 20A-125V GFI DUPLEX RECEPTACLE. LOCATE RECEPTACLE BELOW <br />SINK FOR GARBAGE DISPOSAL. PROVIDE 20A-120V SWITCH TO CONTROL <br />RECEPTACLE. MOUNT SWITCH ABOVE COUNTER BACK SPLASH. <br />PROVIDE 20A-125V GFI DUPLEX RECEPTACLE FOR DISHWASHER. MOUNT BELOW <br />COUNTER. <br />PROVIDE 20A-125V DUPLEX RECEPTACLE FOR UNDER CABINET REFRIGERATOR. <br />MOUNT BELOW COUNTER. <br />PROVIDE 20A-125V DUPLEX RECEPTACLE WITH (2) BUILT-IN USB CHARGING <br />OUTLETS PER 406.3(F). VERIFY EXACT REQUIREMENTS PRIOR TO INSTALL. <br />PROVIDE 20A-125V DUPLEX CLOCK RECEPTACLE FOR TELEVISION. MOUNT AT <br />80" AFF OR AS DIRECTED BY ARCHITECT. PROVIDE SINGLE GANG MUD RING AND <br />COVER PLATE WITH 1-1/4" CO STUBBED 6" ABOVE ACCESSIBLE CEILING FOR AV <br />OR AS DIRECTED BY OWNER. MOUNT ADJACENT TO RECEPTACLE. <br />PROVIDE 20A-125V DUPLEX RECEPTACLE FOR TIME CLOCK. IN ADDITION, <br />PROVIDE DATA OUTLET ADJACENT TO RECEPTACLE WITH 3/4"CO STUBBED 6" <br />ABOVE ACCESSIBLE CEILING OR AS DIRECTED BY OWNER. <br />PROVIDE RECEPTACLE OR HARDWIRE CONNECTION TO CONDENSATE PUMP AS <br />REQUIRED BY MECHANICAL. WHERE HARDWIRE CONNECTION IS REQUIRED, <br />PROVIDE A LOCAL DISCONNECT PER CODE. CONNECT TO CONDENSATE PUMP <br />AS REQUIRED. <br />PROVIDE 20A-125V GFI DUPLEX RECEPTACLE. FOR COUNTERS TOPS, MOUNT <br />ABOVE BACK SPLASH OR AS DIRECTED BY ARCHITECT. OTHERWISE MOUNT AT <br />18" AFF. <br />PROVIDE 20A-125V GFI DUPLEX RECEPTACLE FOR MICROWAVE. VERIFY EXACT <br />LOCATION AND MOUNTING HEIGHTS PRIOR TO INSTALL. <br />PROVIDE 20A-125V GFCI RECEPTACLE FOR PLUG-IN CIRCULATION PUMP WITH <br />BUILT IN TIMER. VERIFY LOCATION WITH PLUMBING. MAINTAIN ACCESS. <br />PROVIDE 20A-125V WP/WR/GFCI RECEPTACLES WITHIN 25FT OF ALL <br />MECHANICAL EQUIPMENT. RECEPTACLES SHALL HAVE AN ENCLOSURE THAT IS <br />WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG IS INSERTED. THE <br />BOX SHALL BE LISTED AND IDENTIFIED AS "EXTRA DUTY" PER ART. 406.9. <br />PROVIDE SINGLE GANG MUD RING, OR AS DIRECTED BY TENANT, WITH (1) 1"CO <br />STUBBED 6" ABOVE ACCESSIBLE CEILING SPACE FOR DATA. MOUNT AT 18" AFF. <br />PROVIDE PULL LINE. <br />PROVIDE J-BOX IN CEILING FOR FUTURE CONNECTION TO POWER POLES AND <br />POWER PARTITIONS. VERIFY LOCATION WITH ARCHITECT PRIOR TO INSTALL. <br />PROVIDE 20A-125V DUPLEX RECEPTACLE IN CEILING FOR PROJECTOR. <br />PROVIDE J-BOX IN CEILING FOR PROJECTOR SCREEN. CONNECT TO SCREEN AS <br />REQUIRED. <br />PROVIDE FLUSH IN-FLOOR FIRE RATED COMBINATION POWER / TELEPHONE / <br />DATA POKE-THRU WITH QUADRAPLEX RECEPTACLE. PROVIDE WIREMOLD RC4 <br />SERIES OR EQUAL. COORDINATE EXACT LOCATION, REQUIREMENTS AND FINISH <br />WITH ARCHITECT PRIOR TO BID. ONE DUPLEX RECEPTACLE SHALL BE <br />CONTROLLED PER TITLE 24 ENERGY CODE. <br />PROVIDE FLUSH IN-FLOOR FIRE RATED COMBINATION POWER / TELEPHONE / <br />DATA POKE-THRU FOR FURNITURE FEED. PROVIDE WIREMOLD FURNITURE FEED <br />4FFATC OR EQUAL. CONNECT TO PARTITION SYSTEM AS REQUIRED. <br />COORDINATE EXACT LOCATION, REQUIREMENTS AND FINISH WITH ARCHITECT <br />PRIOR TO BID. <br />PROVIDE FLUSH IN-FLOOR CONCRETE RATED BOXES WITH QUADRAPLEX <br />RECEPTACLE AND TELEPHONE/DATA OUTLETS. PROVIDE POWER CONNECTION <br />AS SHOWN AND (1) 3/4"CO FOR TELEPHONE/DATA FROM DEVICE AND ROUTE TO <br />NEAREST WALL. STUB TELEPHONE/DATA CONDUIT TO 6" ABOVE ACCESSIBLE <br />CEILING SPACE. VERIFY EXACT LOCATION AND FINISH WITH ARCHITECT PRIOR <br />TO BID. ONE DUPLEX RECEPTACLE SHALL BE CONTROLLED PER TITLE 24 <br />ENERGY CODE. <br />PROVIDE FLUSH IN-FLOOR CONCRETE RATED JUNCTION BOXES WITH <br />PROVISIONS FOR WHIP CONNECTION TO MODULAR FURNITURE. PROVIDE <br />POWER CONNECTION AS SHOWN AND (1) 1-1/4"CO FOR TELEPHONE/DATA FROM <br />DEVICE AND ROUTE TO NEAREST WALL. STUB TELEPHONE/DATA CONDUIT TO 6" <br />ABOVE ACCESSIBLE CEILING SPACE. CONNECT TO MODULAR FURNITURE AS <br />REQUIRED. VERIFY EXACT LOCATION AND REQUIREMENTS PRIOR TO INSTALL. <br />PROVIDE POWER POLE WITH SEPARATE POWER AND DATA RACEWAYS. <br />COORDINATE EXACT LOCATION AND REQUIREMENTS. CONNECT TO MODULAR <br />FURNITURE AS REQUIRED. VERIFY EXACT LOCATION AND ADJUST <br />ACCORDINGLY. <br />PROVIDE IN-WALL J-BOXES WITH PROVISIONS FOR WHIP CONNECTIONS TO <br />MODULAR FURNITURE FOR POWER AND DATA. PROVIDE POWER CONNECTION <br />AS SHOWN AND (1) 1-1/4"CO FOR TELEPHONE/DATA. STUB TELEPHONE/DATA <br />CONDUIT TO 6" ABOVE ACCESSIBLE CEILING SPACE. CONNECT TO MODULAR <br />FURNITURE AS REQUIRED. VERIFY EXACT LOCATION AND REQUIREMENTS <br />PRIOR TO INSTALL. <br />PROVIDE J-BOX FOR TRANSFORMER FOR ELECTRONIC FAUCETS. VERIFY <br />LOCATION AND SIZE WITH PLUMBING. PROVIDE 3/4"C WITH LOW VOLTAGE <br />CONDUCTORS FROM ELECTRONIC FAUCETS AS REQUIRED. CONNECT TO <br />FAUCETS AS REQUIRED. <br />PROVIDE JUNCTION BOX FOR TRANSFORMER FOR ELECTRONIC FLUSH VALVES <br />AS REQUIRED. VERIFY EXACT LOCATION AND REQUIREMENTS WITH PLUMBING. <br />PROVIDE 3/4"C WITH LOW VOLTAGE CONDUCTORS FROM FLUSH VALVE <br />TRANSFORMER TO FLUSH VALVES AS REQUIRED. <br />CONNECT TO VAV BOXES AS REQUIRED. <br />CONNECT TO BY-PASS DAMPER SYSTEM TRANSFORMER 120-24V (BY <br />MECHANICAL). ELECTRICAL CONTRACTOR SHALL PROVIDE NEMA "1" <br />ENCLOSURE FOR SYSTEM TRANSFORMER, COORDINATE SIZE WITH <br />MECHANICAL CONTRACTOR. <br />CONNECT TO SMOKE FIRE DAMPER AS REQUIRED. PROVIDE DISCONNECT. <br />CONNECT TO ZONE DAMPER AS REQUIRED. <br />PROVIDE WP J-BOX AND CONNECT TO DUCT SMOKE DETECTOR AS REQUIRED. <br />CONNECT TO ZONEX SYSTEM TRANSFORMER 120-24V (BY MECHANICAL). <br />ELECTRICAL CONTRACTOR SHALL PROVIDE NEMA "1" ENCLOSURE FOR SYSTEM <br />TRANSFORMER, COORDINATE SIZE AND LOCATION WITH MECHANICAL <br />CONTRACTOR. <br />PROVIDE BOX AND CONNECT TO HAND DRYER AS REQUIRED. <br />ELEVATOR SERVICE DISCONNECT. SEE SINGLE LINE DIAGRAM FOR <br />SPECIFICATION. VERIFY EXACT LOCATION AND REQUIREMENTS WITH ELEVATOR <br />CONTRACTOR AND ADJUST ACCORDINGLY. <br />PROVIDE 30A-2P-240V HEAVY DUTY, FUSED DISCONNECT SWITCH WITH 20A <br />FUSES FOR CAB LIGHTS AND HVAC. CONNECT TO ELEVATOR CAB LIGHTS AS <br />REQUIRED. VERIFY EXACT LOCATION AND REQUIREMENTS WITH ELEVATOR <br />CONTRACTOR AND ADJUST ACCORDINGLY. <br />POWER SYMBOL LIST <br />(SOME MAY NOT BE USED) <br />COLD WATER SERVICE INTO BUILDING, VERIFY LOCATION <br />CONDUIT STUB OUT, VERIFY LOCATION <br />CONDUIT RISER UP, VERIFY LOCATION <br />CONDUIT HOMERUN TO PANEL AND BREAKERS INDICATED <br />UNDERGROUND CONDUIT, 3/4" MINIMUM <br />2#12-1#12G-1/2"C <br />CONDUIT RISER DOWN, VERIFY LOCATION <br />PULL BOX W/ TRAFFIC COVER <br />CW <br />PB <br />TELEPHONE / DATA OUTLET MOUNTED AT 18" AFF <br />DATA OUTLET MOUNTED AT 18" AFF <br />TELEPHONE OUTLET MOUNTED AT 18" AFF <br />CONDUIT RUN CONCEALED IN WALLS OR CEILINGS <br />MGB MAIN GROUND BUS <br />T <br />2#10-1#10G-1/2"C 2#8-1#8G-3/4"C <br />3#12-1#12G-1/2"C 3#10-1#10G-3/4"C 3#8-1#8G-1"C <br />4#12-1#12G-1/2"C 4#10-1#10G-3/4"C 4#8-1#8G-1"C <br />5#12-1#12G-1/2"C 5#10-1#10G-3/4"C 5#8-1#8G-1 1/4"C <br />6#12-1#12G-3/4"C 6#10-1#10G-3/4"C 6#8-1#8G-1 1/4"C <br />2#6-1#6G-3/4"C <br />3#6-1#6G-1"C <br />4#6-1#6G-1"C <br />5#6-1#6G-1 1/4"C <br />6#6-1#6G-1 1/4"C <br />4#12 H-2#12N-1#12G-1#12IG-3/4"C <br />POWERED PARTITION FEEDS <br />4#10H-2#10N-1#10G-1#10IG-1"C <br />4#8H-2#8N-1#8G-1#8IG-1 1/4"C 4#6H-2#6N-1#6G-1#6IG-1 1/2"C <br />20A-125V DUPLEX RECEPTACLE MOUNTED AT 18" AFF <br />20A-125V DOUBLE DUPLEX RECEPTACLE MOUNTED AT 18" AFF <br />SPECIAL USE RECEPTACLE, SEE PLANS FOR SPECIFICATIONS. MOUNT AT 18" <br />AFF OR AS OTHERWISE NOTED. <br />JUNCTION BOX, SIZE PER CODE. <br />DISCONNECT SWITCH, 600V-3P, NEMA 3R, FUSED, HEAVY DUTY, HORSEPOWER <br />RATED, AMP RATING AS REQUIRED. <br />COMBINATION MOTOR STARTER DISCONNECT SWITCH, 600V-3P, NEMA 3R, <br />FUSED, HEAVY DUTY, HORSEPOWER RATED, AMP RATING AND STARTER SIZE <br />AS REQUIRED <br />MOTOR OR EXHAUST FAN <br />THERMOSTAT <br />GENERAL SYMBOL LIST <br />(SOME MAY NOT BE USED) <br />THESE SPECIFICATIONS APPLY UNLESS OTHERWISE NOTED IN THESE DRAWINGS. <br />VERIFY ALL LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECT AND/OR OWNER. <br />SEE PLANS AND LUMINAIRE SCHEDULE FOR LIGHT FIXTURE SYMBOLS. <br />ALL OPERABLE PARTS AND BOXES FOR FUTURE OPERABLE PARTS SHALL BE INSTALLED <br />TO COMPLY WITH CURRENT ADA REQUIREMENTS. <br />SWITCHES, MOUNTED AT 44" AFF, SUBSCRIPT INDICATES CONTROL, ALL LINE VOLTAGE <br />SWITCHES SHALL BE RATED FOR LOAD AT 20A-277V FOR 277V CIRCUITS AND 20A-120V <br />FOR 120V CIRCUITS. <br />$ - SINGLE POLE LIGHT SWITCH <br />S3 - THREE WAY LIGHT SWITCH SP - SINGLE POLE LIGHT SWITCH WITH PILOT LIGHT <br />S4 - FOUR WAY LIGHT SWITCH SK - SINGLE POLE KEYED LIGHT SWITCH <br />SM - MANUAL MOTOR STARTER, HP RATED, NEMA 3R <br />SLV1 - LOW VOLTAGE CONTROL SWITCH <br />J <br />FF <br />BD <br />ZD <br />DSD <br />ZX <br />E <br />H <br />J <br />J <br />FF <br />J <br />J <br />J <br />P D <br />HD <br />J <br />PROVIDE LINE VOLTAGE, DUAL-TECHNOLOGY, WALL SWITCH OCCUPANCY <br />SENSOR. SENSOR SWITCH #WSX-PDT-WH. <br />PROVIDE SENSOR SWITCH nLIGHT ENABLED PHOTO SENSOR WITH BOTH <br />ON/OFF AND AUTOMATIC DIMMING CONTROL FOR DAYLIGHT HARVESTING. <br />SENSOR SWITCH nLIGHT # nCM-ADCX. VERIFY LOCATION PRIOR TO <br />INSTALLATION. <br />PROVIDE SENSOR SWITCH nLIGHT ENABLED PHOTO SENSOR WITH BOTH <br />ON/OFF AND AUTOMATIC DIMMING CONTROL FOR DAYLIGHT HARVESTING. <br />SENSOR SWITCH nLIGHT # nCM-ADCX-DZ (DUAL ZONE). VERIFY LOCATION PRIOR <br />TO INSTALLATION. <br />PROVIDE HIGH MOUNT SENSOR SWITCH nLIGHT ENABLED CEILING MOUNTED, <br />OCCUPANCY SENSOR #NCM-6-RJB FOR APPLICATIONS WHERE MOUNTING IS <br />15FT TO 45FT. PROVIDE POWER PACKS TO CONTROL LIGHTS AND/OR SWITCHED <br />RECEPTACLES, AS REQUIRED, FOR RECEPTACLES. PROVIDE SENSOR SWITCH <br />NLIGHT # nPP20-PL FOR EACH SWITCHED RECEPTACLE CIRCUIT. VERIFY <br />LOCATION PRIOR TO INSTALLATION. <br />PROVIDE SMALL MOTION SENSOR SWITCH nLIGHT ENABLED CEILING MOUNTED, <br />DUAL-TECHNOLOGY OCCUPANCY SENSOR WITH INTERNAL AUTOMATIC DIMMING <br />CONTROL PHOTOCELL AND LOW VOLTAGE AUXILIARY RELAY. SENSOR SWITCH <br />nLIGHT #nCM-PDT-9-ADCX-RJB-AR (OR ADC FOR 0-10V SYSTEMS AS <br />APPLICABLE). ENABLE AUTOMATIC DIMMING CONTROL WHERE DAYLIGHT <br />HARVESTING IS REQUIRED AND DISABLE IT IF SENSOR IS OUTSIDE OF DAYLIT <br />AREA. PROVIDE POWER PACKS TO CONTROL LIGHTS AND/OR SWITCHED <br />RECEPTACLES, AS REQUIRED, FOR RECEPTACLES. PROVIDE SENSOR SWITCH <br />nLIGHT # nPP20-PL FOR EACH SWITCHED RECEPTACLE CIRCUIT. VERIFY <br />LOCATION PRIOR TO INSTALLATION. <br />PROVIDE LARGE MOTION SENSOR SWITCH nLIGHT ENABLED CEILING MOUNTED, <br />DUAL-TECHNOLOGY OCCUPANCY SENSOR WITH INTERNAL AUTOMATIC DIMMING <br />CONTROL PHOTOCELL AND LOW VOLTAGE AUXILIARY RELAY. SENSOR SWITCH <br />nLIGHT #nCM-PDT-10-ADCX-RJB-AR (OR ADC FOR 0-10V SYSTEMS AS <br />APPLICABLE). ENABLE AUTOMATIC DIMMING CONTROL WHERE DAYLIGHT <br />HARVESTING IS REQUIRED AND DISABLE IT IF SENSOR IS OUTSIDE OF DAYLIT <br />AREA.PROVIDE POWER PACKS TO CONTROL LIGHTS AND/OR SWITCHED <br />RECEPTACLES, AS REQUIRED, FOR RECEPTACLES. PROVIDE SENSOR SWITCH <br />nLIGHT # nPP20-PL FOR EACH SWITCHED RECEPTACLE CIRCUIT. VERIFY <br />LOCATION PRIOR TO INSTALLATION. <br />PROVIDE SENSOR SWITCH nLIGHT ENABLED, DUAL-TECHNOLOGY, WALL SWITCH <br />OCCUPANCY SENSOR WITH DIMMING CONTROL. SENSOR SWITCH nLIGHT # <br />nWSX-PDT-LV-DX-WH. PROVIDE nAR40 AUXILIARY RELAY FOR HVAC ZONE <br />CONTROL AS REQUIRED. <br />PROVIDE SENSOR SWITCH nLIGHT ENABLED WALL POD WITH SINGLE CHANNEL, <br />ON/OFF AND RAISE LOWER CONTROL. SENSOR SWITCH nLIGHT # <br />nPODMA-DX-WH. VERIFY LOCATION PRIOR TO INSTALLATION. <br />PROVIDE SENSOR SWITCH nLIGHT ENABLED WALL POD WITH 2-CHANNELS, <br />ON/OFF AND RAISE LOWER CONTROL. SENSOR SWITCH nLIGHT # <br />nPODMA-2P-DX-WH. PROVIDE SEPARATE POWER PACK FOR EACH CHANNEL. <br />VERIFY LOCATION PRIOR TO INSTALLATION. <br />PROVIDE SENSOR SWITCH nLIGHT ENABLED WALL POD WITH 4-CHANNELS, <br />ON/OFF AND RAISE LOWER CONTROL. SENSOR SWITCH nLIGHT # <br />nPODMA-4P-DX-WH. PROVIDE SEPARATE POWER PACK FOR EACH CHANNEL. <br />VERIFY LOCATION PRIOR TO INSTALLATION. <br />PROVIDE SENSOR SWITCH NLIGHT ENABLED CORNER WALL MOUNTED, <br />DUAL-TECHNOLOGY OCCUPANCY SENSOR. SENSOR SWITCH NLIGHT <br />#nWV-PDT-16. PROVIDE POWER PACKS TO CONTROL LIGHTS AS REQUIRED. <br />PROVIDE nAR40 AUXILIARY RELAY FOR HVAC ZONE CONTROL AS REQUIRED. <br />PROVIDE SENSOR SWITCH nLIGHT DIMMING MODULE #0-10V DIMMING nPP16-D, <br />MOUNT ABOVE ACCESSIBLE CEILING PER MANUFACTURER'S REQUIREMENTS. <br />PROVIDE ONE MODULE FOR EACH CONTROL ZONE WITHIN EACH ROOM OR <br />CORRIDOR AS INDICATED BY LOWER CASE LETTER. CONNECT TO MODULAR <br />WIRING SYSTEM OR ROOM LIGHTING CIRCUIT AS REQUIRED. <br />PROVIDE UL924 LISTED SENSOR SWITCH nLIGHT DIMMING MODULE #0-10V <br />DIMMING nPP16D-ER, MOUNT ABOVE ACCESSIBLE CEILING PER <br />MANUFACTURER'S REQUIREMENTS. PROVIDE ONE MODULE PER ZONE. <br />CONNECT DIMMING MODULE TO NEAREST (CONSTANT HOT) UNSWITCHED <br />CIRCUIT AS REQUIRED. CONNECT TO MODULAR WIRING SYSTEM OR ROOM <br />LIGHTING CIRCUIT AS REQUIRED. <br />PROVIDE J BOX AND CONNECT TO MODULAR WIRING SYSTEM AS REQUIRED. <br />INDICATES APPLICABLE LIGHTING CONTROL DIAGRAM. SEE LIGHTING CONTROL <br />DIAGRAMS THESE DRAWINGS. <br />LIGHTING SYMBOL LIST <br />(SOME MAY NOT BE USED) <br />P1 <br />P2 <br />J <br />J <br />J <br />XX <br />S0 <br />6 <br />9 <br />10 <br />S1 <br />S2 <br />S4 <br />GENERAL LABELING AND MARKING NOTES <br />(UNLESS OTHERWISE NOTED, SOME MAY NOT APPLY) <br />A.PER 110.21, WHERE CAUTION, WARNING, OR DANGER SIGNS OR LABELS ARE <br />REQUIRED BY CODE, THE LABELS SHALL MEET THE FOLLOWING REQUIREMENTS: <br />(1)THE MARKING SHALL WARN OF THE HAZARDS USING EFFECTIVE WORDS, <br />COLORS, SYMBOLS, OR ANY COMBINATION THEREOF. <br />(2)THE LABEL SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING <br />METHOD AND SHALL NOT BE HANDWRITTEN. <br />EXCEPTION TO (2): PORTIONS OF LABELS OR MARKINGS THAT ARE VARIABLE, <br />OR THAT COULD BE SUBJECT TO CHANGES, SHALL BE PERMITTED TO BE <br />HANDWRITTEN AND SHALL BE LEGIBLE. <br />(3)THE LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE <br />ENVIRONMENT INVOLVED. <br />(4)THE LABEL SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED <br />PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE <br />OF THE EQUIPMENT. <br />(5)COORDINATE WITH OWNER FOR BUILDING STANDARDS. ALL LABELS SHALL <br />COMPLY WITH APPLICABLE CODES. <br />B.PER 110.16(A), ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, SWITCHGEAR, <br />PANELBOARDS, INDUSTRIAL CONTROL PANELS, METER SOCKET ENCLOSURES, AND <br />MOTOR CONTROL CENTERS, THAT IS IN OTHER THAN DWELLING UNITS, AND IS <br />LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE <br />WHILE ENERGIZED, SHALL BE FIELD OR FACTORY MARKED TO WARN QUALIFIED <br />PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. <br />C.PER 110.16(B), IN OTHER THAN DWELLING UNITS, IN ADDITION TO THE <br />REQUIREMENTS IN 110.16(A), A PERMANENT LABEL SHALL BE FIELD OR FACTORY <br />APPLIED TO SERVICE EQUIPMENT RATED 1200 AMPS OR MORE. THE LABEL SHALL <br />MEET THE REQUIREMENTS OF 110.21(B) AND CONTAIN THE FOLLOWING <br />INFORMATION: <br />(1)NOMINAL SYSTEM VOLTAGE <br />(2)AVAILABLE FAULT CURRENT AT THE SERVICE OVERCURRENT PROTECTIVE <br />DEVICES <br />(3)THE CLEARING TIME OF SERVICE OVERCURRENT PROTECTIVE DEVICES BASED <br />ON THE AVAILABLE FAULT CURRENT AT THE SERVICE EQUIPMENT <br />(4)THE DATE THE LABEL WAS APPLIED <br />D.PER 110.22(A), EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO <br />INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS <br />EVIDENT. IN OTHER THAN ONE- OR TWO-FAMILY DWELLINGS, THE MARKING SHALL <br />INCLUDE THE IDENTIFICATION OF THE CIRCUIT SOURCE THAT SUPPLIES THE <br />DISCONNECTING MEANS. <br />E.PER 110.22(C), EQUIPMENT ENCLOSURES FOR CIRCUIT BREAKERS OR FUSES <br />APPLIED IN COMPLIANCE WITH THE SERIES COMBINATION RATINGS MARKED ON <br />THE EQUIPMENT BY THE MANUFACTURER IN ACCORDANCE WITH 240.86(B) SHALL <br />BE LEGIBLY MARKED IN THE FIELD TO INDICATE THE EQUIPMENT HAS BEEN <br />APPLIED WITH A SERIES COMBINATION RATING. THE MARKING SHALL MEET THE <br />REQUIREMENTS IN 110.21(B) AND SHALL BE READILY VISIBLE AND STATE THE <br />FOLLOWING: <br />CAUTION — SERIES COMBINATION SYSTEM RATED ____ AMPERES. IDENTIFIED <br />REPLACEMENT COMPONENTS REQUIRED. <br />F.PER 110.24, SERVICE EQUIPMENT AT OTHER THAN DWELLING UNITS SHALL BE <br />LEGIBLY MARKED IN THE FIELD WITH THE AVAILABLE FAULT CURRENT. THE FIELD <br />MARKING(S) SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS <br />PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE <br />ENVIRONMENT INVOLVED. THE CALCULATION SHALL BE DOCUMENTED AND MADE <br />AVAILABLE TO THOSE AUTHORIZED TO DESIGN, INSTALL, INSPECT, MAINTAIN, OR <br />OPERATE THE SYSTEM. THE EQUIPMENT SHORT CIRCUIT CURRENT RATING SHALL <br />NOT BE LESS THAN THE AVAILABLE FAULT CURRENT. <br />G.PER 210.5, THE METHOD UTILIZED FOR CONDUCTORS ORIGINATING WITHIN EACH <br />BRANCH-CIRCUIT PANELBOARD OR SIMILAR BRANCH-CIRCUIT DISTRIBUTION <br />EQUIPMENT SHALL BE DOCUMENTED IN A MANNER THAT IS READILY AVAILABLE OR <br />SHALL BE PERMANENTLY POSTED AT EACH BRANCH-CIRCUIT PANELBOARD OR <br />SIMILAR BRANCH-CIRCUIT DISTRIBUTION EQUIPMENT. THE LABEL SHALL BE OF <br />SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND SHALL <br />NOT BE HANDWRITTEN. CONDUCTORS AND CABLES SHALL BE COLOR CODED BY <br />THE MANUFACTURER AT THE FACTORY FOR THE ENTIRE LENGTH. WRAPPING <br />COLOR TAPES ARE NOT PERMITTED. COLOR CODING SHALL BE AS FOLLOWS: <br />120/208V SYSTEM 277/480V SYSTEMS <br />PHASE A:BLACK BROWN <br />PHASE B:RED ORANGE <br />PHASE C:BLUE YELLOW <br />NEUTRAL:WHITE GREY <br />GROUND:GREEN GREEN <br />ISOLATED GROUND:GREEN/YELLOW STRIPE GREEN/YELLOW STRIPE <br />WHERE DEDICATED NEUTRALS ARE PROVIDED, USE COLOR SPIRAL TO MATCH <br />ASSOCIATED PHASE. <br />H.PER 408.4(A), EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY <br />IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE <br />IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF DETAIL THAT ALLOWS <br />EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT <br />CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE DESCRI⁠BED <br />ACCORDINGLY. THE IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY <br />THAT IS LOCATED ON THE FACE, INSIDE OF, OR IN AN APPROVED LOCATION <br />ADJACENT TO THE PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH <br />SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR SWITCHGEAR. NO CIRCUIT <br />SHALL BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF <br />OCCUPANCY. ALL NEW AND MODIFIED PANEL CARDS SHALL BE TYPED AND SHALL <br />INCLUDE DATE. RECREATE PANEL CARDS FOR ANY PANELS THAT ARE MODIFIED. <br />I.PER 408.4(B), ALL NEW AND MODIFIED SWITCHBOARDS, SWITCHGEAR, AND <br />PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE- OR TWO-FAMILY <br />DWELLINGS SHALL BE PERMANENTLY MARKED TO INDICATE EACH DEVICE OR <br />EQUIPMENT WHERE THE POWER ORIGINATES. THE LABEL SHALL INCLUDE PANEL <br />NAME AND FEEDER RATING WITH AMPS-VOLTS-PHASES-WIRES. <br />J.PER 450.14, WHERE A TRANSFORMER IS NOT WITHIN SIGHT OF ITS SUPPLY SIDE <br />DISCONNECT, PROVIDE A PERMANENT PLACARD ON THE TRANSFORMER <br />INDICATING THE LOCATION OF THE SUPPLY SIDE DISCONNECTING MEANS. THE <br />SUPPLY SIDE DISCONNECT SHALL BE LOCKABLE IN THE OPEN POSITION. <br />K.PROVIDE ALL OTHER LABELING REQUIRED BY CODE. <br />L.ALL LABELS AND MARKINGS SHALL BE TYPEWRITTEN. <br />M.ALL LABELS AND PLACARDS SHALL MEET BUILDING STANDARDS. <br />GENERAL NOTES <br />A.PRIOR TO BID, CONTRACTOR SHALL WALK THE SITE AND SHALL BE THOROUGHLY <br />FAMILIAR WITH THE CONDITIONS AND SHALL INCLUDE IN HIS BID ALL NECESSARY <br />CONDUIT, CONDUCTORS, SUPPORTS, ETC., WHETHER SHOWN ON THESE <br />DRAWINGS OR NOT, NECESSARY TO PROVIDE A COMPLETE OPERABLE SYSTEM <br />THAT MEETS THE DESIGN INTENT AND EDWARDS REQUIREMENTS. <br />B.PRIOR TO START OF WORK, CONTRACTOR SHALL NOTIFY EDWARDS AND ENGINEER <br />OF ANY FIELD CONDITIONS THAT MAY PREVENT MEETING THE DESIGN INTENT. <br />C.CONTRACTOR SHALL VERIFY ALL LOCATIONS, CONDUIT ROUTING, AND OTHER <br />REQUIREMENTS PRIOR TO INSTALLATION. <br />D.CONTRACTOR SHALL COORDINATE THE MOUNTING OF ALL CONDUIT AND OTHER <br />EQUIPMENT WITH STRUCTURAL AND EDWARDS PRIOR TO INSTALLATION. <br />CONTRACTOR SHALL ACQUIRE AND REVIEW ALL STRUCTURAL DRAWINGS RELATED <br />TO THIS PROJECT PRIOR TO BID AND SHALL INCLUDE ALL REQUIREMENTS IN HIS <br />BID. <br />E.CONDUIT SHALL BE ROUTED BELOW THE ROOF WHERE FEASIBLE. <br />F.ALL CONDUIT ROUTED ON THE ROOF SHALL BE SUPPORTED WITH DURA-BLOK <br />SUPPORTS, OR AS DIRECTED BY EDWARDS, AT CODE REQUIRED INTERVALS. <br />G.PRIOR TO INSTALLATION OF ANY CONDUIT OR EQUIPMENT, CONTRACTOR SHALL <br />DEMONSTRATE TO EDWARDS THE EXACT CONDUIT ROUTING AND LUMINAIRE <br />LOCATIONS VIA A NON-PERMANENT MEANS. <br />H.CONTRACTOR SHALL COORDINATE THE MOUNTING OF ALL EQUIPMENT WITH <br />STRUCTURAL PRIOR TO INSTALLATION. <br />I.CONTRACTOR SHALL NOT PENETRATE THE ROOF UNLESS PREVIOUSLY APPROVED <br />BY EDWARDS, STRUCTURAL AND ROOF CONTRACTOR. <br />J.ALL ROOF PENETRATIONS SHALL BE APPROVED BY EDWARDS AND ROOF <br />CONTRACTOR PRIOR TO INSTALLATION. ALL ROOF PENETRATIONS SHALL INCLUDE <br />A ROOF JACK AND SHALL BE WEATHERPROOFED PER THE ROOFING CONTRACTOR. <br />K.ALL CONDUITS ON ROOF SHALL BE PAINTED TO MATCH EXISTING OR AS DIRECTED <br />BY EDWARDS. CONDUITS THAT CROSS WALKING PATH SHALL BE PAINTED SAFETY <br />YELLOW OR AS DIRECTED BY OWNER. <br />L.ALL CONDUITS SUBJECT TO PHYSICAL DAMAGE SHALL BE IMC MINIMUM, OR AS <br />DIRECTED BY EDWARDS. <br />M.COORDINATE OF ALL LOCATIONS WITH MECHANICAL AND ADJUST AS NECESSARY. <br />N.PROVIDE CONTROLS CONDUITS AS DIRECTED BY MECHANICAL. <br />O.ALL CONDUIT CONNECTORS SHALL BE COMPRESSION TYPE. <br />REMARKSNO.DATE <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />in <br />t <br />e <br />r <br />i <br />o <br />r <br /> <br />d <br />e <br />s <br />i <br />g <br />n <br />pl <br />a <br />n <br />n <br />i <br />n <br />g <br />17 <br />8 <br />8 <br />0 <br /> <br />S <br />k <br />y <br /> <br />P <br />a <br />r <br />k <br /> <br />C <br />i <br />r <br />c <br />l <br />e <br />, <br /> <br />S <br />u <br />i <br />t <br />e <br /> <br />2 <br />3 <br />0 <br /> <br />- <br /> <br />I <br />r <br />v <br />i <br />n <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />1 <br />4 <br />t <br />e <br />l <br /> <br />9 <br />4 <br />9 <br />. <br />5 <br />5 <br />3 <br />. <br />8 <br />9 <br />0 <br />0 <br />Ed <br />w <br />a <br />r <br />d <br />s <br />DA <br />I <br />M <br />L <br />E <br />R <br /> <br />A <br />C <br />P <br />L <br />30 <br />0 <br />9 <br /> <br />D <br />A <br />I <br />M <br />L <br />E <br />R <br /> <br />S <br />T <br />R <br />E <br />E <br />T <br />. <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />23 <br />2 <br />7 <br />6 <br /> <br />S <br />O <br />U <br />T <br />H <br /> <br />P <br />O <br />I <br />N <br />T <br />E <br /> <br />D <br />R <br />. <br />, <br /> <br />U <br />N <br />I <br />T <br />1 <br />0 <br />2 <br />, <br />LA <br />G <br />U <br />N <br />A <br /> <br />H <br />I <br />L <br />L <br />S <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />5 <br />3 <br />O: <br /> <br />9 <br />4 <br />9 <br />- <br />4 <br />1 <br />9 <br />- <br />9 <br />9 <br />0 <br />8 <br /> <br />F <br />: <br /> <br />9 <br />4 <br />9 <br />- <br />4 <br />1 <br />9 <br />- <br />9 <br />8 <br />7 <br />0 <br />E0.2 <br />GENERAL NOTES AND <br />SYMBOLS <br />3009 S Daimler St <br />11/18/2024