Laserfiche WebLink
NO SCALE P2.1 <br />1 <br />NO SCALE P2.1 <br />2 <br />NO SCALE <br />3 <br />NO SCALE <br />4 <br />NO SCALE <br />5 <br />NO SCALE <br />6 <br />NO SCALE <br />7 <br />P2.1 <br />P2.1 <br />P2.1 <br />P2.1 <br />P2.1 <br />NOTES: <br />1. ALL CONDENSATE PIPING SHALL BE COPPER TYPE "M". <br />2. ALL CONDENSATE PIPING SHALL BE INSULATED. <br />3. SEE PLANS FOR PIPE SIZES, BUT IN NO CASE SHALL BE SMALLER THAN AC UNIT CONNECTION. <br />4. VERIFY AC UNIT CONNECTION AND LOCATION OF VENT WITH AC UNIT MANUFACTURER. <br />5. AC UNIT WITH OVERFLOW SENSOR AND ALARM BY OTHERS. <br />"B""A"AC UNIT DRAIN <br />CONNECTION. (TYP) <br />FITTINGS OR "U" <br />BEND TRAP <br />CLEANOUT <br />PLUGSLOPE AT 1/8" PER <br />FOOT LENGTH TOWARD <br />DRAIN <br />SEE PLANS FOR <br />SIZE AND <br />CONTINUATION <br />BLOW THRU TYPE <br />A = SP + 1" MINIMUM <br />B = SP + 1/2" MINIMUM <br />A = (SP x 1.5) + 1" MINIMUM <br />B = (SP x 0.5) MINIMUM <br />DRAW THRU TYPE <br />SP = SYSTEM STATIC PRESSURE IN INCHES <br />VENT <br />CONDENSATE DRAIN DETAIL <br />ROD STIFFENER <br />(TYPICAL) <br />1 (MIN.) <br />1 <br />ALL THREADED <br />ROD (TYPICAL) <br />CHANNEL TRANSVERSE <br />BRACES - TYPICAL WHERE <br />REQUIRED BY CODE <br />(9'-4" MAX. LENGTH) <br />BOLT SLEEVE <br />CLEVIS HANGER ADJUSTABLE STEEL <br />YOKE PIPE ROLL <br />1" (MIN.) <br />1" <br />ADJUSTABLE <br />HINGE (TYPICAL) <br />ROLLER TYPE <br />PIPE HANGER <br />(FOR PIPING UNDER <br />EXPANSION / CONTRACTION) <br />STANDARD TYPE <br />PIPE HANGER <br />NOTE: <br />1.REFER TO CPC 2022, TABLE 313.3 FOR STANDARD <br />AND SEISMIC HANGER SPACING INFORMATION AND <br />REQUIREMENTS. <br />2.REFER TO STRUCTURAL DRAWINGS FOR HANGER <br />ATTACHMENTS TO STRUCTURE (TYP). <br />PIPE HANGER DETAIL <br />ADJUSTABLE HINGE <br />(TYPICAL) <br />ALL THREADED <br />ROD (TYPICAL) <br />CHANNEL LONGITUDINAL <br />BRACES - TYPICAL WHERE <br />REQUIRED BY CODE <br />(9'-4" MAX. LENGTH) <br />ROD STIFFENER <br />(TYPICAL) <br />1 (MIN.) <br />1 <br />CHANNEL TRANSVERSE <br />BRACES - TYPICAL WHERE <br />REQUIRED BY CODE <br />(9'-4" MAX. LENGTH) <br />ADJUSTABLE HINGE <br />LONGITUDINAL BRACE <br />HEX NUT & <br />SQUARE WASHERPIPE STRAPSEE NOTE 7 <br />CHANNEL (SIZE AS REQUIRED) <br />ADJUSTABLE HINGE <br />TRANSVERSE BRACE <br />NOTES: <br />1.ADJUSTABLE HINGES FOR LONGITUDINAL BRACES MAY BE ATTACHED ON EITHER SIDE ADJACENT TO THE ALL-THREADED ROD OR ATTACHED TO THE ALL-THREADED <br />ROD ITSELF. <br />2.ADJUSTABLE HINGES FOR THE TRANSVERSE BRACES MAY BE ATTACHED TO THE ALL-THREADED ROD. <br />3.TWO ADJUSTABLE HINGES MAY BE ATTACHED TO THE STRUT TRAPEZE USING THE SAME BOLT OR ALL-THREADED ROD. IT IS NOT NECESSARY TO INSTALL BOTH <br />TRANSVERSE BRACES AND LONGITUDINAL BRACES ON THE SAME TRAPEZE SUPPORT. EITHER SET OF BRACES MAY BE REMOVED TO FORM A LONGITUDINAL BRACE <br />ONLY, OR A TRANSVERSE BRACE ONLY, IF DESIRED. <br />4.LONGITUDINAL BRACES (WHEN NEEDED) MUST BE INSTALLED AT BOTH ENDS OF TRAPEZE. <br />5.THE EQUIPMENT SHOWN ON THE TRAPEZE IS GENERIC IN NATURE. ANY NUMBER OF PIPES, CONDUITS, DUCTWORK OR CABLE TRAY MAY BE SUPPORTED FOLLOWING <br />THE SYSTEM WEIGHT AND SUPPORT SPANS LISTED. REFER TO CPC 2022, FOR STANDARD AND SEISMIC HANGER SPACING INFORMATION AND REQUIREMENTS. <br />6.REFER TO STRUCTURAL DRAWINGS FOR ATTACHMENT OF HANGER SYSTEM TO STRUCTURE. <br />7.DETERMINE LENGTH OF TRAPEZE, MAKING SURE SUFFICIENT LENGTH IS PROVIDED TO ATTACH THE ALL-THREADED ROD AND BRACING ATTACHMENTS. <br />TRAPEZE PIPE HANGER DETAIL <br />1/2" COLD WATER FROM <br />NEAREST COLD WATER <br />SUPPLY (SEE PLAN) <br />SHUT-OFF VALVE <br />UNION (TYPICAL) <br />PRIME RITE BY PPP <br />TRAP PRIMER VALVE <br />WITH ACCESS PANEL <br />DISTRIBUTION BOX <br />FOR TWO OR MORE <br />CONNECTIONS <br />FINISHED <br />FLOOR <br />SLOPE <br />TRAP <br />VENTED <br />WASTE TO <br />SYSTEM <br />FLOOR SINK <br />NOTE: <br />SEE PLANS FOR PIPE, FLOOR SINK, AND <br />TRAP PRIMER LOCATIONS. <br />TRAP PRIMER VALVE SHALL BE MOUNTED A MINIMUM OF 12" <br />ABOVE FINISHED FLOOR FOR EVERY 20 FEET OF PRIMER PIPE. <br />TRAP PRIMER DETAIL <br />VENT PIPE THRU ROOF <br />COUNTERFLASHING SLEEVE <br />SEAMLESS LEAD FLASHING WITH <br />STEEL REINFORCED BOOT <br />("STONEMAN") OR EQUAL) <br />BUILT-UP ROOFING OVER <br />FLANGE, BY ROOFING <br />CONTRACTOR <br />EXISTING ROOF ASSEMBLY. (SEE <br />ARCHITECTURAL PLANS FOR <br />EXACT TYPE OF CONSTRUCTION) <br />HEIGHT AS REQ'D <br />BY CODE <br />HVAC AIR INTAKE <br />10' MIN <br />NOTES: <br />IF THIS DETAIL DIFFERS FROM THAT SHOWN ON THE <br />ARCHITECTURAL PLANS, THE ARCHITECTURAL <br />DETAIL SHALL BE FOLLOWED. <br />PIPE SUPPORT DETAIL ON ROOF <br />PIPING <br />OUTDOOR RATED GALVANIZED METAL CLAMP <br />LAG BOLT <br />14 GA. GALVANIZED <br />CHANNEL <br />PREFABRICATED RUBBER <br />SUPPORT BLOCK <br />W/UNISTRUT CHANEL <br />NOTES: <br />1. FOR PIPE SIZE 2-1/2" AND LESS. <br />2. PROVIDE SUPPORT AT 10' INTERVALS. <br />ISOLATION <br />ISOLATION <br />SECURE TO ROOF <br />TYPICAL VENT THRU ROOF DETAIL <br />REMARKSNO.DATE <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br />in <br />t <br />e <br />r <br />i <br />o <br />r <br /> <br />d <br />e <br />s <br />i <br />g <br />n <br />pl <br />a <br />n <br />n <br />i <br />n <br />g <br />17 <br />8 <br />8 <br />0 <br /> <br />S <br />k <br />y <br /> <br />P <br />a <br />r <br />k <br /> <br />C <br />i <br />r <br />c <br />l <br />e <br />, <br /> <br />S <br />u <br />i <br />t <br />e <br /> <br />2 <br />3 <br />0 <br /> <br />- <br /> <br />I <br />r <br />v <br />i <br />n <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />1 <br />4 <br />t <br />e <br /> <br />l <br /> <br />9 <br /> <br />4 <br /> <br />9 <br /> <br />. <br /> <br />5 <br /> <br />5 <br /> <br />3 <br /> <br />. <br /> <br />8 <br /> <br />9 <br /> <br />0 <br /> <br />0 <br />Ed <br />w <br />a <br />r <br />d <br />s <br />DA <br />I <br />M <br />L <br />E <br />R <br /> <br />A <br />C <br />P <br />L <br />30 <br />0 <br />9 <br /> <br />D <br />A <br />I <br />M <br />L <br />E <br />R <br /> <br />S <br />T <br />R <br />E <br />E <br />T <br />. <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />P2.1 <br />PLUMBING DETAILS <br />REFER TO ARCHITECTURE PLANS FOR <br />ADDITIONAL INFORMATION. <br />NO SCALE <br />8 <br />P2.1 <br />1" MIN. ABOVE FLOOD RIM <br />CONDENSATE DISCHARGE <br />FINISHED WALL <br />CONDENSATE DRAIN TO FLOOR SINK <br />ALL BRANCH PIPING <br />SHALL CONNECT TO <br />TOP OF MAIN <br />MINIMUM 0.1" PER <br />FOOT SLOPE <br />(TYPICAL) <br />COMPRESSED AIR MAIN <br />(SLOPE DOWN TOWARD <br />BLOW-OFF DRAIN VALVE) <br />TYPICAL AIR BRANCH <br />AIR SUPPLY PIPE DOWN TO <br />BALL VALVE, VERIFY EXACT <br />HEIGHT, SIZE & LOCATION <br />IN FIELD PRIOR TO <br />INSTALLATION <br />COMPRESSED AIR BRANCH DETAIL <br />3009 S Daimler St <br />11/18/2024