ELECTRICAL NOTES <br />ELECTRICAL LAMP NOTES <br />1.NEW BOXES USED AT LUMINAIRE OR LAMP HOLDER OUTLETS IN A CEILING SHALL BE <br />REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF 50LBS. BOXES USED <br />AT LUMINAIRE OUTLETS IN WALLS SHALL BE DESIGNED FOR THE PURPOSE AND SHALL <br />BE MARKED ON THE INTERIOR INDICATING THE MAXIMUM WEIGHT OF THE LUMINAIRE <br />PERMITTED, IF OTHER THAN 50LBS, OUTLET BOXES OR SYSTEMS USED AS THE SOLE <br />SUPPORT OF CEILING FANS SHALL BE LISTED AND MARKED BY THE MANUFACTURE AS <br />SUITABLE FOR THIS PURPOSE PER SECTION 314.27 CEC-2022. <br />ENERGY EFFICIENT NOTES <br />1. ELECTRICAL BALLASTS IF 13 WATTS OR MORE. <br />2. RECESSED CANS IN INSULATED CEILINGS"IC" TYPE & CERTIFIED AIRTIGHT. <br />3. SWITCH ALL HIGH-EFFICACY LIGHTS SEPERATLY FROM LOW-EFFICACY LIGHTS. <br />4. ALL LIGHTS SHALL BE HIGH EFFICACY(15 WATTS OR LESS PROVIDED 40 LUMEN PER WATT <br />(15-40 WATTS PROVIDED 50 LUMENS PER WATT AND OVER 40 WATTS PROVIDE 60 <br />LUMENS PER WATT) UNLESS: <br />i. IN KITCHENS UP TO 50% OF HARDWIRED WATTS MAY BE LOW-EFFICIACY. <br />ii. IN BATHROOMS, GARAGES, LAUNDRY & UTILITY ROOMS HAVE A MANUAL SWITCH FOR ON <br />AND A VACCANCY-SENSOR FOR OFF OR HAVE ELECTRIC DIMMER SWITCHES. <br />iv. OUTDOOR BUILDING LIGHTS HAVE A MOTION SENSOR ON AND PHOTO-CELL SENSOR <br />OFF. <br />5. PERMANENT LIGHTING SHALL COMPLY WITH THE MANDATORY MEASURES LISTED ON <br />FORMS MF-1R. <br />6. PROVIDE MINIMUM STUD/RAFTER SIZING TO ACCOMMODATE INSULATION.WHERE 1" <br />RAFTER SPACE VENTILATION IS REQUIRED PER CBC SECTION 1203.2 <br />7. PROVIDE 2X14 AND 2X6 FOR R-38 AND R-19 RESCEPTIVELY. <br />GC 4.506.1 - BATHROOM EXAUST FANS: MECHANICAL EXAUST FANS <br />WHICH EXAUST DIRECTLY FROM BATHROOMS SHALL COMPLY WITH THE <br />FOLLOWING. <br />A. FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE <br />OUTSIDE THE BUILDING. <br />B. UNLESS FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE <br />VENTILATION SYSTEM, FANS MUST BE CONTROLLED BY A HUMIDSTAT <br />WHICH SHALL BE READILY ACCESSIBLE. <br />HUMIDSTAT CONTROLS SHALL BE CAPABLE OF ADJUSTMENT BETWEEN <br />RELATIVE HUMIDITY RANGES OF 50% TO 80%. <br />ELECTRICAL NOTES <br />MECHANICAL NOTES <br />1.EXHAUST DUCTS SHALL TERMINATE OUTSIDE THE BUILDING AND SHALL BE <br />EQUIPPED WITH BACKDRAFT BAMPERS OR WITH MOTORIZED DAMPERS <br />THAT AUTOMATICALLY SHUT WHERE THE SYSTEMS OR SPACES SERVED <br />ARE NOT IN USES. PER CMC SECTION 504.1.1. <br />2.ENVIRONMENTAL AIR DUCT EXHAUST SHALL TERMINATE NOT LESS THAN 3 <br />FEET FROM PROPERTY LINE, 10 FEET FROM A FORCED AIR INLET, AND 3 <br />FEET FROM OPENING INTO THE BUILDINGS. ENVIRONMENTAL EXHAUST <br />DUCT SHALL NOT DISCHARGE ONTO A PUBLIC WALKWAY. PER CMC <br />SECTION 502.2.1. <br />3.EXHAUST OPENINGS TERMINATING TO THE OUTDOORS SHALL BE COVERED <br />WITH A CORROSION RESISTANT SCREEN HAVING NOT LESS THAN 1 <br />4 OF AN <br />INCH OPENINGS AND SHALL HAVE NOT MORE THAN 1 <br />2 INCH OF AN <br />OPENINGS. PER CMC SECTION 502.1. <br />PLUMBING NOTES <br />1.NO PLUMBING SYSTEM OR PORTION THEREOF SHALL BE COVERED, <br />CONCEALED OR PUT INTO USE UNTIL INSPECTED AND APPROVED BY <br />AUTHORITY HAVING JURISDICTION. PER SECTION 105.1. CPC-2022. <br />2.NEW PLUMBING WORK AND SUCH PORTION OF EXISTING SYSTEMS AS <br />AFFECTED BY NEW WORK, OR CHANGES, SHALL BE INSPECTED BY THE <br />AUTHORITY HAVING JURISDICTION TO ENSURE COMPLIANCE WITH THE <br />REQUIREMENTS OF THIS CODE AND TO ENSURE THAT THE INSTALLATION AND <br />CONSTRUCTION OF THE PLUMBING IS IN ACCORDANCE WITH APPROVED <br />PLANS. PER SECTION 105.2. CPC-2022. <br />3.EACH VENT PIPE OR STACK SHALL EXTEND THROUGH ITS FLASHING AND <br />SHALL TERMINATE VERTICALLY NOT LESS THAN 6 INCHES ABOVE THE ROOF <br />NOR LESS THAN 1 FOOT FROM A VERTICAL SURFACE. PER SECTION 906.1. <br />CPC-2022. <br />4.THE LOCAL RESPONSIBLE BUILDING OFFICIAL OF ANY CITY, COUNTY OR CITY <br />AND COUNTY, SHALL AUTHORIZED BY PERMIT THE USE OF CPVC FOR HOT <br />AND COLD WATER DISTRIBUTION SYSTEMS WITHIN THE INTERIOR OF <br />RESIDENTIAL BUILDINGS. PER SECTION 604.1.1. CPC-2022. <br />5.RESIDENTIAL BUILDINGS UNDERGOING PERMITTED ALTERATIONS, ADDITIONS <br />OR IMPROVEMENTS SHALL REPLACE NONCOMPLIANT PLUMBING FIXTURES <br />WITH WATER-CONSERVING PLUMBING FIXTURES. PER SECTION 401.3. <br />CPC-2022. <br />6.MINIMUM SLOPE OF SEWER AND DRAINAGE PIPING 2%. POR SECTION 708. <br />CPC-2022. <br />ELECTRICAL NOTES <br />1.ALL NEW LIGHTING SHALL BE HIGH EFFICACY, PER CEC TABLE 150.0(k)1A. <br />2.THE INTERMITTENT LOCAL EXHAUST AIRFLOW RATES SHALL BE A MINIMUM OF 75 CFM <br />FOR BATHROOMS. <br />3.- <br />4.EXHAUST FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE <br />OUTSIDE THE BUILDING. <br />5.ALL OUTDOOR LIGHTING SHALL BE CONTROLLED BY A MANUAL ON AND OFF SWITCH <br />THAT DOES NOT OVERRIDE TO ON AND ONE OF THE FOLLOWING: CONTROLLED BY <br />PHOTOCELL AND MOTION SENSOR, PHOTO CONTROL AND AUTOMATIC SWITCH <br />CONTROL, ASTRONOMICAL TIME CLOCK, OR ENERGY MANAGEMENT CONTROL SYSTEM. <br />WASTE AND VENT PIPING SHALL BE ABS SCHEDULE 40 <br />PIPE AND FITTINGS <br />WATER PIPING SHALL BE COPPER TYPE "L" HARD DRAWN <br />WITH 95-5 TIN ANTIMONY SOLDER <br />GAS PIPING SHALL BE SCHEDULE 40 BLACK STEEL <br />THREADED OR WELD FITTINGS <br />LEGEND <br />WASTE PIPE <br />VENT PIPE <br />COLD WATER PIPE <br />HOT WATER PIPE <br />GAS PIPE <br />HOT WATER RETURN <br />MATERIAL TYPE <br />PLUMBING NOTES <br />E.E. NOTE <br />ALL NEW LIGHTING INSTALLED IN RESIDENTIAL UNITS IS REQUIRED TO BE RATED AS HIGH <br />EFFICACY AS REQUIRED BY SECTION 150.0(k), TABLE 150-0-A. AT LEAST ONE LUMINAIRE <br />INSTALLED IN BATHROOMS, LAUNDRY ROOMS, AND UTILITY ROOMS SHALL BE CONTROLLED <br />BY A VACANCY SENSOR PER 150.0(k)(2)(J). <br />DRYER DUCT NOTE <br />DRYER DUCT SHALL BE OF METAL AND MIN 4". EXHAUST DUCT SHALL NOT EXCEED <br />14' LENGTH, COMBINED HORIZONTAL AND VERTICAL, INCLUDING TWO 90 DEGREE <br />ELBOWS. TWO FEET SHALL BE DEDUCTED FOR EACH 90 DEGREE ELBOW IN <br />EXCESS OF TWO PER 504.4.2.1 & 504.4.2.2 CMC. <br />NOTE: <br />SMOKE DETECTOR SHALL SOUND AN ALARM AUDIBLE IN ALL SLEEPING AREAS SMOKE <br />DETECTORS SHALL BE HARD-WIRED TO HOUSE CIRCUITRY & EQUIPPED W/BATTERY PER <br />SECTION 310.9.1.3 & 4 CRC-2022. <br />1.HOUSEHOLD COOKING APPLIANCES SHALL HAVE A VERTICAL CLEARANCE <br />ABOVE THE COOKING TOP OF NOT LESS THAN 30 INCHES TO COMBUSTIBLE <br />MATERIAL OR METAL CABINETS (921.3.2, 921.4 CMC) <br />2.CLOTHES DRYER MOISTURE EXHAUST DUCTS SHALL BE TERMINATE OUTSIDE <br />THE BUILDING AND HAVE A BACK-DRAFT DAMPER. EXHAUST DUCT IS LIMITED <br />TO 14'-0" WITH TWO ELBOWS. THIS SHALL BE REDUCED 2'-0" FOR EVERY <br />ELBOW IN EXCESS OF TWO. PER SECTION 504.3.2 CMC-2022. <br />3.EACH BATHROOM CONTAINING A BATHTUB, SHOWER COMBINATION SHALL BE <br />MECHANICALLY VENTILATED FOR PURPOSES OF HUMIDITY CONTROL IN <br />ACCORDANCE WITH CMC, CHAPTER 4 AND CGBSC, CHAPTER 4, DIVISION 4.5 <br />HUMIDITY CONTROL SHALL BE CAPABLE OF ADJUSTMENT BETWEEN A RELATIVE <br />HUMIDITY RANGE OF LESS THAN OR EQUAL TO 50% TO A MAXIMUM OF 80% <br />(R303.3.1 CRC) <br />4.WHEN A CLOTH DRYER IS LOCATED IN A CLOSET, AN OPENING OF NOT LESS <br />THAN 100 SQUARE INCHES FOR MAKEUP AIR SHALL BE PROVIDED IN THE <br />DOOR OR BY OTHER APPROVED MEANS. (504.1.1(1) CMC. <br />MECHANICAL NOTES <br />WATER CLOSETS - 1.28 GAL/FLUSH <br />PLUMBING FIXTURES - <br /> - WATER CONSERVATION <br />PER CGBC-4.303 <br />SINGLE SHOWERHEAD - 1.8 GPM AT 80 PSI <br />MULTIPLE SHOWERHEADS - 1.8 GPM AT 80 PSI. <br />LAVATORY FAUCETS - MAX 1.2 GPM AT 60 PSI. <br />KITCHEN FAUCETS - 1.8 GPM AT 60 PSI. <br />MIN 0.8 GPM AT 20 PSI. <br />GAS WATER HEATER <br />COMPONENTS PER SECTION 150.0(n)(1) CEC-2022 <br />A.DEDICATED 125 VOLTS, 20 AMP ELECTRICAL RECEPTACLE, CONNECTED TO <br />THE ELECTRICAL PANEL WITH 120/240 VOLT 3 CONDUCTOR, 10 AWG <br />COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE WATER HEATER & <br />ACCESSIBLE TO THE WATER HEATER WITH NO OBSTRUCTIONS, IN ADDITION: <br />II. BOTH ENDS OF THE UNUSED CONDUCTOR SHALL BE LABELED WITH THE <br />WORD "SPARE" & BE ELECTRICALLY ISOLATED. <br />III. A RESERVED SINGLE POLE CIRCUIT BREAKER SPACE IN THE ELECTRICAL <br />PANEL ADJACENT TO THE CIRCUIT BREAKER FOR THE BRANCH CIRCUIT 1 <br />ABOVE & LABELED WITH THE WORDS "FUTURE 214V USE" <br />B.A CATEGORY III OR IV VENT, OR A TYPE B VENT WITH STRAIGHT PIPE <br />BETWEEN THE OUTSIDE TERMINATION AND THE SPACE WHERE THE WATER <br />HEATER IS INSTALLED; AND <br />C.A CONDENSATE DRAIN THAT IS NO MORE THAN 2 INCHES HIGHER THAN THE <br />BASE OF THE INSTALLED WATER HEATER, AND ALLOWS NATURAL DRAINING <br />WITHOUT PUMP ASSISTANCE; AND <br />D.A GAS SUPPLY LINE WITH A CAPACITY OF AT LEAST 200,000 BTU/HR <br />1.ALL HOT WATER PIPE SHALL BE FULLY INSULATED PER 609.11 CPC-2022. <br />2.ALL HOSE BIBS MUST HAVE AN APPROVED ANTI-SIPHON DEVICE. <br />(CPC-603.5.7) <br />3.WATER CLOSETS SHALL HAVE AN AVERAGE WATER CONSUMPTION OF NOT <br />MORE THAN 1.28 GALLONS PER FLUSH. (411.2 CPC) <br />4.SHOWER HEADS SHALL HAVE A WATER FLOW NOT TO EXCEED 1.8 <br />GALLONS PER MINUTE AT 80 PSI. (408.2 CPC) <br />5.THE MAXIMUM FLOW RATE OF LAVATORY FAUCETS SHALL NOT EXCEED 1.2 <br />GALLONS PER MINUTE AT 60 PSI. (403.7 CPC) <br />6.FAUCETS IN KITCHENS SHALL HAVE A WATER FLOW NOT TO EXCEED 1.8 <br />GALLONS PER MINUTE AT 60 PSI AND MAY TEMPORARILY INCREASE THE <br />FLOW ABOVE THE MAXIMUM RATE, BUT NOT TO EXCEED 2.2 GALLONS PER <br />MINUTE, AND MUST DEFAULT TO MAXIMUM FLOW RATE OF 1.8 GALLONS <br />PER MINUTE. (407.2.1.1 CPC) <br />7.DOMESTIC DISHWASHER REQUIRE AN APPROVED DISHWASHER AIR GAP <br />FITTING ON THE DISCHARGE SIDE OF THE DISHWASHER. LISTED AIR GAPS <br />SHALL BE INSTALLED WITH THE FLOOD-LEVEL (FL) MARKING AT OR ABOVE <br />THE FLOOD-LEVEL OF THE SINK OR DRAIN BOARD, WHICHEVER IS HIGHER. <br />(CPC 807.3) <br /> NOTE <br />1.A RECEPTACLE INSTALLED OUTDOORS IN A LOCATION PROTECTED FROM THE <br />WEATHER OR IN OTHER DAMP LOCATIONS SHALL HAVE AN ENCLOSURE FOR THE <br />RECEPTACLE THAT IS WEATHERPROOF WHEN THE RECEPTACLE IS COVERED. <br />(ATTACHMENT PLUG CAP NOT INSERTED AND THE RECEPTACLE COVERS CLOSED) PER <br />CEC 406.9(A) AND 406.9(B)(2). <br />2.RECEPTACLES SHALL BE INSTALLED NO MORE THAN 6 FEET. CEC 210.52(A)(1) <br />COMPLY WITH CITY CODE SEC. 5-112(B) <br />NOTE: <br />A.THE PANEL OR SUB-PANEL SHALL PROVIDE CAPACITY TO INSTALL A 40-AMPERE <br />MINIMUM DEDICATED BRNACH CIRCUIT AND SPACE(S) RESERVED TO PERMIT <br />INSTALLATION OF A BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE. <br />B.THE SERVICE PANEL OR SUB-PANEL CIRCUIT DIRECTORY SHALL IDENTIFY THE <br />OVERCURRENT PROTECTIVE DEVICE SPACE(S) RESERVED FOR FUTURE EV CHARGING AS <br />EV CAPABLE. THE RACEWAY TERMINATION LOCATION SHALL BE PERMANENT AND <br />VISIBLY MARKED EV CAPABLE. <br />NOTE: <br />LUMINARIES THAT ARE RECESSED INTO CEILINGS SHALL HAVE AIRTIGHT HOUSING TO <br />PREVENT CONDITIONED AIR ESCAPING INTO THE CAVITY OR ATTIC, OR UNCONDITIONED AIR <br />INFILTRATING FROM THE CEILING OR ATTIC INTO THE CONDITIONED SPACE (AT-LISTED). <br />LUMINARIES THAT ARE RECESSED INTO INSULATED CEILINGS ARE REQUIRED TO BE RATED <br />FOR INSULATION CONTACT ("IC-RATED"). <br />NOTE: <br />ALL SINGLE FAMILY OUTDOOR LIGHTING SHALL BE HIGH EFFICACY AND MUST BE <br />CONTROLLED BY A MANUEL ON & OFF SWITCH AND ONE OF THE FOLLOWING AUTOMATIC <br />CONTROL TYPES: <br />·PHOTOCONTROL AND MOTION SENSOR <br />·PHOTOCONTROL AND AUTOMATIC TIME SWITCH CONTROL <br />·ASTRONOMICAL TIME CLOCK CONTROL <br />·EMCS <br />EVSE CHARGING NOTES <br />1.INSTALL A LISTED RACEWAY TO ACCOMMODATE A DEDICATED 208/240-VOLT BRANCH <br />CIRCUIT. THE RACEWAY SHALL NOT BE LESS THAN TRADE SIZE 1 (NOMINAL 1-INCH <br />INSIDE DIAMETER). THE RACEWAY SHALL ORIGINATE AT THE MAIN SERVICE OR <br />SUBPANEL AND SHALL TERMINATE INTO A LISTED CABINET, BOX OR OTHER <br />ENCLOSURE IN CLOSE PROXIMITY TO THE PROPOSED LOCATION OF AN EV CHARGER. <br />(SECTION 4.106.4.1 CGB-2022) <br />2.RACEWAYS ARE REQUIRED TO BE CONTINUOUS AT ENCLOSED, INACCESSIBLE OR <br />CONCEALED AREAS AND SPACES. (PER SECTION 4.106.4.1 CGB-2022) <br />3.THE SERVICE PANEL AND/OR SUBPANEL SHALL PROVIDE CAPACITY TO INSTALL A <br />40-AMPERE 208/240-VOLT MINIMUM DEDICATED BRANCH CIRCUIT AND SPACE(S) <br />RESERVED TO PERMIT INSTALLATION OF A BRANCH CIRCUIT OVERCURRENT <br />PROTECTIVE DEVICE.(SECTION 4.106.4.1 CGB-2022) <br />4.THE SERVICE PANEL OR SUBPANEL CIRCUIT DIRECTORY SHALL IDENTIFY THE <br />OVERCURRENT PROTECTIVE DEVICE SPACE(S) RESERVED FOR FUTURE EV CHARGING <br />AS "EV CAPABLE". THE RACEWAY TERMINATION LOCATION SHALL BE PERMANENTLY AND <br />VISIBLY MARKED AS "EV CAPABLE". (SECTION 4.1.106.1.1 CGB-2022) <br />(E) EDISON SERVICE <br />220 A <br />ONE LINE DIAGRAM <br />(EXISTING) <br />PANEL <br />120/240V <br />4 W <br />GROUNDING TO MIN 1 #4 CU <br />GROUNDING ELECTRODE CONDUCTOR <br />OR 20 FT #4 UFFER GROUND REBARD <br />ON FTG <br />Category Panelboards, Power Distribution <br />Mfg Name Square D <br />Mfg Part Num QO34MQ220 <br />Graybar ID <br />Description Panelboard Enclosure/Box <br />Maximum Voltage Rating: 208Y/ 120 VAC <br />Mains Ampere Rating: 220 <br />Interior Type: Fixed Mains Lug <br />Three Phase-Four Wire <br />Breakers: 42 >> QO Breakers, bolted <br />Item Features 3 <br />Compatibility 220A <br />KITCHEN EXHAUST NOTE <br />MONOXIDE ALARM REQUIREMENTS: <br />FOR DWELLING UNIT CONSTRUCTION HAVING AN ATTACHED GARAGE OR FUEL-BURNIG <br />APPLIANCES, AN APPROVED CARBON MONOXIDE ALARM UL 2034/2075 SHALL BE <br />INSTALLED, MAINTAINCE AND CONNECTED IN THE FOLLOWING LOCATIONS/MANNER: <br />a) outside of each sleeping area in the immediate vicinity of the bedroom(s). <br />b) On every level of a dwelling unit including basements. <br />c) Where more than one CO alarm is installed, the alarm shall be interconnected in a <br />manner that activation of one alarm shall activated all of the alarms. <br />1. SMOKE ALARMS SHALL BE LISTED PER UL 217, INSTALLED PER NFPA 72 AND SHALL BE <br />CALIF. STATE FIRE MARSHALL LISTED. <br />2. SMOKE ALARMS SHALL BE INSTALLED MAINTAINED AND CONNECTED IN THE FOLLOWING <br />LOCATIONS/MANNER: [R314.3,.4,.5] <br />a.IN EACH SLEEPING ROOM. <br />b.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE <br />BEDROOMS. <br />c.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING BASEMENT AND SPLIT <br />LEVELS. <br />d.WHEN MORE THAN ONE SMOKE ALARM IS INSTALLED, THE ALARM DEVICES SHALL BE <br />INTERCONNECTED IN SUCH A MANNER THAT THE ACTIVATION OF ONE ALARM WILL <br />ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL UNIT. THE ALARM SHALL BE CLEARLY <br />AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE LEVELS WITH ALL INTERVENING <br />DOORS CLOSED. <br />e.SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING <br />WHERE SUCH WIRING IS SERVED FROM COMMERCIAL SOURCE AND SHALL BE EQUIPPED <br />WITH BATTERY BACKUP. <br />1.THIS CLASSIFICATION APPLIES ONLY TO ROOMS THAT ARE NOT KITCHENS, <br />BATHROOMS, GARAGES, LAUNDRY ROOMS, CLOSETS, OR UTILITY ROOMS. ALL <br />INSTALLED LUMINARIES SHALL BE EITHER BE HIGH EFFICACY AND SHALL BE <br />CONTROLLED BY A VACANCY SENSOR OR DIMMER. <br />2.IN SINGLE-FAMILY RESIDENCIES, ALL LUMINARIES MOUNTED TO THE BUILDING (OR TO <br />EITHER BUILDING ON THE SAME LOT) SHALL BE HIGH EFFICACY LUMINARIES, AND SHALL <br />BE CONTROLLED BY A MOTION SENSOR AND ALSO BY A PHOTOCONTROL, <br />ASTRONOMICAL TIME CLOCK, OR ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) <br />(outdoor ceiling fans with lights) <br />3.FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT <br />GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT GRADE LEVEL AND <br />NOT MORE THAN 6'-6" ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK <br />OF THE DWELLING. ALL EXTERIOR OUTLETS SHALL BE PROTECTED BY GFCI AND BE <br />WEATHER PROOF. [2022 CEC - SECTION 406.8]. <br />4.ALL EXTERIOR OUTLETS SHALL BE GFCI (no longer an exception for height) [2022 CEC - <br />SECTION 210.8]. IN ADDITION, THE RECEPTACLE SHALL HAVE AN ENCLOSURE THAT IS <br />WEATHERPROOF WHEN THE RECEPTACLE IS COVERED (attachment plug cap not inserted <br />and receptacle cover closed). ALL 15- AND 20- ampere, 125- AND 250-volt <br />NONLOCKING RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE. [2022 CEC - <br />SECTION 406.9]. <br />1.ANY HALLWAY 10' OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE. SHOW <br />RECEPTACLES ON THE PLANS. (210.52 (H) CEC) <br />2.ELECTRICAL BOXES SHALL HAVE DRYWALL, PLASTER, OR PLASTERBOARD SURFACES <br />FINISHED SO THERE WILL BE NO GAPSOR OPEN SPACES GREATER THAN 1/8" AT THE <br />EDGE OF THE BOX PER ARTICLE 314.21 (CEC). IN WALLS OR CEILINGS BOXES SHALL BE <br />INSTALLED SO THAT THE FRONT EDGE OF THE BOX OR PLASTER RING SHALL NOT BE <br />RECESSED MORE THAN 1/4" FROM NON-COMBUSTIBLE FINISH SURFACE AND SHALL BE <br />FLUSHED WITH A COMBUSTIBLE SURFACE PER ARTICLE 314.20 (CEC). <br />3. ALL BRANCH CIRCUITS THAT SUPPLY 125-VOLT, SINGLE- PHASE, 15 - AND 20 - <br />AMPERE OUTLETS OR DEVICES INSTALLED IN DWELLING UNIT KITCHEN, FAMILY ROOMS, <br />DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, <br />RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS OR SIMILAR ROOMS OR <br />AREAS SHALL BE PROTECTED BY AN ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION TYPE <br />LISTED TO PROVIDE PROTECTION OF THE ENTIRE BRANCH CIRCUIT. <br />4. NEW BOXES USED AT LUMINARIES OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE <br />REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF 50 LBS. USED AT LUMINAIRE <br />OUTLETS IN WALLS SHALL BE DESIGNED FOR THE PURPOSE AND SHALL BE MARKED ON THE <br />INTERIOR INDICATING THE MAXIMUM WEIGHT OF THE LUMINAIRE PERMITTED, IF OTHER THAN <br />50 LBS. OUTLET BOXES OR SYSTEM USED AS THE SOLE SUPPORT OF CEILING FANS SHALL <br />BE LISTED AND MARKED BY THE MANUFACTURES AS SUITABLE FOR THIS PURPOSE. (314.27 <br />CEC). <br />NOTES: <br />ENERGY CONSERVATION <br />1.BATHROOMS, LAUNDRY ROOM, PANTRIES, UTILITY/STORAGE ROOMS AND GARAGE SHALL <br />HAVE AT LEAST ONE FIXTURE CONTROLLED BY A VACANCY SENSOR. CEnC 150.0(k)(2)(1)) <br />2.ANNULAR SPACES AROUND PIPES, ELECTRICAL CABLES, CONDUITS OR OTHER OPENINGS <br />IN BOTTOM/SOLE PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE <br />PASSAGE OF RODENTS BY CLOSING SUCH OPENINGS IN ACCORDANCE WITH THE <br />CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), CHAPTER 4 DIVISION 4.4. <br />1. RECEPTACLE OUTLETS SHALL BE TAMPER RESISTANT. <br />2. ----- <br />3. A DEDICATED 20-AMP CIRCUIT SHALL BE PROVIDED TO SERVE THE REQUIRED <br />BATHROOM OUTLETS. THIS CIRCUIT CANNOT SUPPLY ANY OTHER OUTLETS (INCLUDING <br />BATHROOM LIGHTING AND FANS). <br />4. CLOTHES DRYER AND ELECTRIC RANGES SHALL HAVE A 4- WIRE GROUNDED ELECTRICAL <br />OUTLET. <br />5. ALL RECESSED LIGHT FIXTURES SHALL BE IC RATED OR FIXTURES NOT IDENTIFIED FOR <br />CONTACT WITH INSULATION SHALL HAVE ALL RECESSED PARTS SPACED AT LEAST 1/2" FROM <br />COMBUSTIBLE MATERIALS AND 3" FROM THERMAL INSULATION. <br />6. TWO SMALL-APPLIANCE BRANCH CIRCUITS FOR THE KITCHEN LIMITED TO SUPPLYING WALL <br />AND COUNTER OUTLETS ONLY. ADDITIONAL CIRCUIT SHALL BE PROVIDED TO SUPPLY OTHER <br />APPLIANCES, SUCH GARBAGE DISPOSAL, DISH WASHER, AND OTHERS. <br />7. ALL 120 VOLT, SINGLE PHASE, 15 AND 20-AMPERE BRANCH CIRCUITS SUPPLYING <br />OUTLETS INSTALLED IN DWELLING UNIT FAMILY ROOMS, KITCHENS, DINING ROOMS, LIVING <br />ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, <br />CLOSETS, HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED <br />ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION <br />OF THE BRANCH CIRCUIT. <br />8. ----- <br />1.WET AND DAMP LOCATIONS. LUMINAIRES INSTALLED IN WET OR DAMP LOCATIONS <br />SHALL BE INSTALLED SUCH THAT WATER CANNOT ENTER OR ACCUMULATE IN WIRING <br />COMPARTMENTS, LAMPHOLDERS, OR OTHER ELECTRICAL PARTS. ALL LUMINAIRES <br />INSTALLED IN WET LOCATIONS SHALL BE MARKED, "SUITABLE FOR WET LOCATIONS." ALL <br />LUMINAIRES INSTALLED IN DAMP LOCATIONS SHALL BE MARKED "SUITABLE FOR WET <br />LOCATIONS" OR "SUITABLE FOR DAMP LOCATIONS. PER CEC-2022 SECTION 410.10 (A) <br />2.BATHTUB AND SHOWER AREAS.NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-, <br />CABLE-, OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR <br />CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN A ZONE MEASURED 900 <br />MM (3 FT) HORIZONTALLY AND 2.5 M (8 FT) VERTICALLY FROM THE TOP OF THE <br />BATHTUB RIM OR SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING AND <br />INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER STALL. LUMINAIRES <br />LOCATED WITHIN THE ACTUAL OUTSIDE DIMENSION OF THE BATHTUB OR SHOWER TO A <br />HEIGHT OF 2.5 M (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER <br />THRESHOLD SHALL BE MARKED FOR DAMP LOCATIONS, OR MARKED FOR WET <br />LOCATIONS WHERE SUBJECT TO SHOWER SPRAY. PER CEC-2022 SECTION 410.10 (D) <br />LUMINAIRES WET & DAMP <br />LOCATION NOTE <br />KITCHEN SHALL BE PROVIDED WITH EXHAUST FAN DUCTED TO THE OUTSIDE WITH A MINIMUM VENTILATION RATE OF 110 CFM. THE <br />RANGE HOOD OVER THE STOVE MAY BE USED TO MEET THIS REQUIREMENT, BUT THE RANGE HOOD MUST VENT TO THE OUTSIDE; <br />RE-CIRCULATING RANGE HOODS CANNOT BE USED. <br />ELECTRICAL UTILITIES SHALL BE RUN UNDERGROUND. <br />C.M. <br />SMOKE ALARMS: <br />1.Where more than one smoke alarm is required to be installed within an individual dwelling or sleeping unit, the <br />smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the <br />alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with <br />all intervening doors closed. Per section R314.4 CRC-2022 and NFPA-72-2022. <br />2.Smoke alarms shall receive their primary power from the building wiring provided that such wiring is served from <br />a commercial source and shall be equipped with a battery backup. Smoke alarms with integral strobes that are <br />not equipped with battery backup shall be connected to an emergency electrical system. Smoke alarms shall <br />emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other <br />than as required for overcurrent protection. Per section R314.6 CRC-2022 and NFPA-72-2022. <br />CARBON MONOXIDE ALARMS: <br />1.Carbon monoxide alarms shall be listed in accordance with UL 2034. Combination carbon monoxide and <br />smoke alarms shall be listed in accordance with UL 217 and UL 2034. Per section R315.1 CRC-2022 and <br />NFPA-72-2022. <br />2.Carbon monoxide alarms in dwelling units shall be installed and maintained in accordance with the <br />manufacturer's published instructions in the following locations: Outside of each separate sleeping area in <br />the immediate vicinity of the bedrooms. On every occupiable level of a dwelling unit, including basements. <br />Where a fuel-burning appliance is located within a bedroom or its attached bathroom, a carbon monoxide <br />alarm shall be installed within the bedroom. Per section R315.3 CRC-2022 and NFPA-72-2022. <br />ELECTRICAL RECEPTACLE OUTLETS, SWITCHES AND CONTROLS SHALL BE LOCATED NO MORE THAN 48” MEASURED FROM THE TOP OF <br />THE OUTLET BOX AND NOT LESS THAN 15” MEASURED FROM THE BOTTOM OF THE OUTLET BOX ABOVE THE FINISH FLOOR. PER <br />R327.1.2 CRC-2022. <br />OUTLETS, SWITCHES HEIGHT NOTE <br />A) ADDS AUTO-OFF CONTROLS FOR LIGHTING IN DRAWERS AND CABINETS. <br />B) UNDERSHELF, DISPLAY CABINETS, SWITCHED OUTLETS CONTROLLED SEPARATE FROM CEILING LIGHTING. <br />C) LIGHTING IN HABITABLE SPACES SHALL HAVE ACCESSIBLE WALL-MOUNTED DIMMING CONTROLS. <br />PER CENC SECTION 150.0(K)2 <br />INDOOR LIGHTING CONTROLS NOTES <br />DOORBELL per R327.1.4 <br />Doorbell buttons or controls, when installed, shall not exceed 48 inches above exterior floor or landing, <br />measured from the top of the doorbell button assembly. Where doorbell buttons integrated with other <br />features are required to be installed above 48 inches measured from the exterior floor or landing, a <br />standard doorbell button or control shall also be provided at a height not exceeding 48 inches above <br />exterior floor or landing, measured from the top of the doorbell button or control. <br />THE LOCATION OF ELECTRICAL SERVICE <br />PANEL MUST BE APPROVED BY EDISON. <br />AGING-IN-PLACE NOTE: <br />Newly constructed residences subject to the requirements of the CRC must be designed for the following <br />aging-in-place and fall prevention requirements. (R327) <br />At least one bathroom on the entry level shall be provided with the following reinforcement for grab bars. (When <br />there is no bathroom on the entry level at least one bathroom on the second or third floor of the dwelling shall <br />comply with this section.) <br />i. Reinforcement shall be solid lumber. <br />ii. Reinforcement shall be not less than 2x8 nominal lumber. <br />iii. Reinforcement shall be located between 32 inches and 39 ¼ inches above the finished floor flush with the wall <br />framing. <br />iv. Water closet reinforcement shall be installed on both side walls of the fixture, or one side wall and the back <br />wall. <br />v. Shower reinforcement shall be continuous where wall framing is provided. <br />vi. Bathtub and combination bathtub/shower reinforcement shall be continuous on each end of the bathtub and the <br />back wall. <br />Additionally, back wall reinforcement for a lower grab bar shall be provided within the bottom edge located not <br />more than 6 inches above the bathtub rim. See detail #5 sheet A-3. <br />Electrical receptacle outlets, switches, and controls (including controls for heating ventilation and air conditioning) <br />intended to be used by the occupants shall be located not more than 48 inches measured from the top of the <br />outlet box and not less than 15 inches measured from the bottom of the outlet box above the finish floor. <br />Doorbell buttons or controls, when installed, shall not exceed 48 inches above exterior floor or landing, measured <br />from the top of the doorbell assembly <br />SURGE PROTECTION PER 230.67 CEC-2022: <br />(A) Surge-Protective Device <br />All services supplying dwelling units shall be provided with a surge-protective device (SPD) <br />(B)Location <br />The SPD shall be an integral part of the service equipment or shall be located immediately <br />adjacent thereto. <br />Exception: The SPD shall not be required to be located in the service equipment as required in <br />(B) if located at each next level distribution equipment downstream toward the load <br />(C)Type <br />The SPD shall be a Type 1 or Type 2 SPD. <br />CONTRACTOR/INSPECTOR SHALL VERIFY ON SITE <br />(GAS SERVICES NOT APPLICABLE IF ALL ELECTRICAL) <br />OWNER/CLIENT <br />PROJECT LOCATION <br />PROJECT TITLE <br />SHEET TITLE <br />DATE <br />AS SHOWN <br />SCALE <br />02 / 24 <br />D R A F T I N G S E R V I C E <br />TE <br />L <br /> <br />: <br /> <br /> <br /> <br />( <br />9 <br />5 <br />1 <br />) <br /> <br />9 <br />9 <br />2 <br />- <br />7 <br />2 <br />3 <br />4 <br />ju <br />a <br />n <br />. <br />g <br />o <br />n <br />z <br />a <br />l <br />e <br />z <br />. <br />1 <br />9 <br />7 <br />1 <br />@ <br />h <br />o <br />t <br />m <br />a <br />i <br />l <br />. <br />c <br />o <br />m <br />FI <br />N <br />. <br />G <br />. <br />S <br />& <br /> <br />P <br />WA <br />R <br />D <br />F. <br />M <br />. <br />C <br />. <br />FR <br />. <br /> <br />D <br />R <br />. <br /> <br />VL <br />. <br /> <br />S <br />L <br />. <br />KE <br />E <br />P <br /> <br />L <br />A <br />B <br />E <br />L <br /> <br />O <br />N <br /> <br />T <br />H <br />E <br /> <br />W <br />A <br />T <br />E <br />R <br /> <br />H <br />E <br />A <br />T <br />E <br />R <br />3. <br /> <br /> <br /> <br />W <br />A <br />T <br />E <br />R <br /> <br />T <br />O <br /> <br />B <br />E <br /> <br />5 <br />0 <br /> <br />G <br />A <br />L <br />L <br />O <br />N <br />S <br /> <br />M <br />I <br />N <br />. <br />1. <br /> <br /> <br /> <br />A <br />L <br />L <br /> <br />H <br />O <br />R <br />I <br />Z <br />O <br />N <br />T <br />A <br />L <br /> <br />C <br />E <br />I <br />L <br />I <br />N <br />G <br /> <br />D <br />R <br />Y <br />W <br />A <br />L <br />L <br /> <br />A <br />P <br />P <br />L <br />I <br />E <br />D <br /> <br />T <br />O <br /> <br />T <br />R <br />U <br />S <br />S <br />E <br />S <br />2. <br /> <br /> <br /> <br />A <br />L <br />L <br /> <br />E <br />X <br />T <br />E <br />R <br />I <br />O <br />R <br /> <br />W <br />I <br />N <br />D <br />O <br />W <br />S <br /> <br />T <br />O <br /> <br />B <br />E <br /> <br />W <br />H <br />I <br />T <br />E <br />. <br /> <br />R <br />E <br />F <br />E <br />R <br /> <br />T <br />O <br /> <br />P <br />L <br />A <br />N <br /> <br />FO <br />R <br /> <br />S <br />I <br />Z <br />E <br /> <br />A <br />N <br />D <br /> <br />E <br />X <br />T <br />E <br />R <br />I <br />O <br />R <br /> <br />E <br />L <br />E <br />V <br />A <br />T <br />I <br />O <br />N <br /> <br />F <br />O <br />R <br /> <br />A <br />L <br />L <br /> <br />B <br />R <br />E <br />A <br />K <br />- <br />U <br />P <br />S <br />SH <br />A <br />L <br />L <br /> <br />B <br />E <br /> <br />5 <br />/ <br />8 <br />" <br /> <br />G <br />Y <br />P <br />S <br />U <br />M <br /> <br />B <br />O <br />A <br />R <br />D <br />SI <br />N <br />G <br />L <br />E <br /> <br />H <br />U <br />N <br />G <br />OP <br />T <br />I <br />O <br />N <br />A <br />L <br />SL <br />I <br />D <br />E <br />R <br /> <br />O <br />R <br /> <br />S <br />L <br />I <br />D <br />I <br />N <br />G <br />FI <br />X <br />E <br />D <br /> <br />G <br />L <br />A <br />S <br />S <br />CE <br />I <br />L <br />I <br />N <br />G <br />EL <br />E <br />V <br />A <br />T <br />I <br />O <br />N <br />F. <br />G <br />. <br />S. <br />H <br />. <br />SL <br />. <br />OP <br />T <br />. <br />CL <br />' <br />G <br />. <br />EL <br />E <br />V <br />. <br />W/ <br />SH <br />E <br />L <br />F <br /> <br />& <br /> <br />P <br />O <br />L <br />E <br />FR <br />E <br />N <br />C <br />H <br /> <br />D <br />O <br />O <br />R <br />FL <br />O <br />O <br />R <br /> <br />M <br />A <br />T <br />E <br />R <br />I <br />A <br />L <br /> <br />C <br />H <br />A <br />N <br />G <br />E <br />FI <br />N <br />I <br />S <br />H <br /> <br />G <br />R <br />A <br />D <br />E <br />WI <br />T <br />H <br />WA <br />R <br />D <br />R <br />O <br />B <br />E <br />VI <br />N <br />I <br />L <br /> <br />S <br />L <br />I <br />D <br />E <br />R <br />G& <br />S <br /> <br />A <br />r <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />a <br />l <br /> <br />D <br />e <br />s <br />i <br />g <br />n <br /> <br />a <br />n <br />d <br /> <br />P <br />l <br />a <br />n <br />n <br />i <br />n <br />g <br />JU <br />A <br />N <br /> <br />G <br />O <br />N <br />Z <br />A <br />L <br />E <br />Z <br />12 <br />5 <br />9 <br />4 <br /> <br />M <br />i <br />c <br />h <br />i <br />g <br />a <br />n <br /> <br />S <br />t <br />, <br /> <br />G <br />r <br />a <br />n <br />d <br /> <br />T <br />e <br />r <br />r <br />a <br />c <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />3 <br />1 <br />3 <br />AB <br />B <br />R <br />E <br />V <br />I <br />A <br />T <br />I <br />O <br />N <br />S <br /> <br />TY <br />P <br />I <br />C <br />A <br />L <br /> <br /> <br />N <br />O <br />T <br />E <br />S <br />PL <br />A <br />N <br />S <br /> <br />P <br />R <br />E <br />P <br />A <br />R <br />E <br /> <br />B <br />Y <br />: <br />SHEET <br />Mailing address: <br />JC IMP EXP INC <br />14881 ALDER LN, TUSTIN, <br />CA 92780-6742 <br />PROPOSED (2) TWO NEW <br />ADU's. <br />200 AMP. <br />125 AMP. <br />(N) ADU SUB PANEL <br />SUB PANEL CONNECTIONS <br />(E) ELEC METER <br />(3#2 & 1#6 GND) <br />(1)1-1/2C, 80 FEET <br />(E) UNIT 210-1/2 <br />200 AMP. <br />125 AMP. <br />(N) ADU SUB PANEL <br />(E) ELEC METER <br />(3#2 & 1#6 GND) <br />(1)1-1/2C, 80 FEET <br />(E) UNIT 210 <br />(N) UNIT 101 <br />(N) UNIT 100 <br />2010 AND 2012 N BUSH <br />AVE #100 AND #101, SANTA <br />ANA, CA 92706-2818 <br />05-E-1 <br />REG <br />ISTERED PROF E S S IONAL ENGI <br />NE <br />ER <br />STATE OF CAL IFORNIA <br />NO. C-31397 <br />EXP. 12/31/2024 <br />C I V I L <br />LEO A . A GUILERA <br />2010 & 2012 N Bush Ave, <br />#100 and #1012/21/2025