Laserfiche WebLink
SHEET TITLE: <br />SCALE: <br />SHEET NO. <br />PR <br />O <br />J <br />E <br />C <br />T <br />DA <br />T <br />E <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />PROJECT NUMBER: <br />OWNER / CLIENT: <br />DATE ISSUED: <br />DATE SUBMITTED: <br />DRAWN BY: <br />CHECKED BY: <br />THESE DRAWINGS ARE THE PROPERTY <br />OF TREEIUM INC AND SHALL NOT BE <br />USED ON ANY OTHER WORK EXCEPT <br />BY AGREEMENT WITH TREEIUM INC <br />48 <br />2 <br />1 <br /> <br />L <br />A <br />N <br />K <br />E <br />R <br />S <br />H <br />I <br />M <br /> <br />B <br />L <br />V <br />D <br /> <br />S <br />T <br />E <br /> <br />F <br /> <br /># <br />4 <br />4 <br />5 <br /> <br />NO <br />R <br />T <br />H <br /> <br />H <br />O <br />L <br />L <br />Y <br />W <br />O <br />O <br />D <br />, <br /> <br />C <br />A <br />31 <br />0 <br />. <br />6 <br />9 <br />4 <br />. <br />0 <br />8 <br />3 <br />5 <br />WW <br />W <br />. <br />A <br />V <br />D <br />E <br />S <br />I <br />G <br />N <br />. <br />L <br />A <br />AV <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br />AVD24D019 <br />Debbini, Lubna <br />General Notes <br />GN <br />To <br />w <br />n <br />e <br />r <br /> <br />A <br />D <br />U <br />11 <br />0 <br />8 <br /> <br />N <br /> <br />T <br />o <br />w <br />n <br />e <br />r <br /> <br />S <br />t <br /> <br />& <br /> <br />1 <br />1 <br />0 <br />8 <br /> <br />N <br />To <br />w <br />n <br />e <br />r <br /> <br />S <br />t <br />r <br />e <br />e <br />t <br /> <br /># <br />2 <br />Sa <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />3 <br />ER/CB <br />Checker <br />--- <br />1. The construction shall not restrict a five-foot clear and unobstructed access to <br />any water or power distribution facility (Power poles, pull-boxes, transformers, <br />vaults, pumps, valves, meters, appurtenances, etc.) or to the location of the <br />hook-up. The construction shall not be within ten feet of any power lines - <br />whether or not the lines are located on the property. Failure to comply may <br />cause construction delays and/or additional expenses.” Obtain approval from <br />Real Estate Business Unit of DWP (213) 367-0562. <br />2. Obtain permits from Public Works prior to Construction for: <br />a. Temporary pedestrian protection as required by LABC Section 3306. <br />b. For any construction near any street or public area. <br />3. Outlets along wall counter space, island and peninsula counter space in <br />kitchens shall have a maximum spacing of 48". (210-52 NEC) <br />4. The first light in the new and remodeled bathrooms and kitchen shall be an <br />energy efficient light meeting a minimum of 40 Lumens per watt (e.g. fluorescent <br />lamp).(T-24, Sec. 130(b) & 150(k)) <br />5. Every space intended for human occupancy shall be provided with natural <br />light by means of exterior glazed openings in accordance with Section R303.1 or <br />shall be provided with artificial light that is adequate to provide an average <br />illumination of 6 foot-candles over the area of the room at a height of 30 inches <br />above the floor level. (R303.1) <br />6. A copy of the evaluation report and/or conditions of listing shall be made <br />available at the job site <br />7. The sprinkler system shall be approved by Plumbing Division prior to <br />installation. <br />8. Plumbing fixtures are required to be connected to a sanitary sewer or to an <br />approved sewage disposal system (R306.3) <br />9. Kitchen sinks, lavatories, bathtubs, showers, bidets, laundry tubs and washing <br />machine outlets shall be provided with hot and cold water and connected to an <br />approved water supply (R306.4) <br />10. Automatic garage door openers, if provided, shall be listed in accordance <br />with UL 325. (R309.4) <br />11. Los Angeles City Electrical Test Lab Research Report is required to use an <br />electro-mechanical lift for provided parking spaces. <br />12. “A maintenance of vehicle lift system (2-levels or more) affidavit ” shall be <br />approved andrecorded prior to issuing a building permit. <br />13. A minimum of 65 percent of the nonhazardous construction and demolition <br />waste shallbe recycle and/or salvage for reuse in accordance with California <br />Green Building Standards Code, Chapter 4 Division 4.4. (R324) <br />14. Finish materials including adhesives, sealants, caulks, paints and coating, <br />aerosol paints and systems and composite wood products shall meet the volatile <br />organic compound (VOC) emission limits in accordance with the California <br />Green Building Standards Code, Chapter 4 Division 4.5. (R330) <br />15. When a vapor retarder is required, a capillary break shall be installed in <br />accordance with the California Green Building Standards Code, Chapter 4, <br />Division 4.5. (R506.2.3.1) <br />16. Annular space around pipes, electric cables, conduits or other openings in <br />bottom/sole plates at exterior walls shall be protected against the passage of <br />rodents by closing such openings in accordance with the California Green <br />Building Standards Code, Chapter 4, Division 4.4. (R602.3.4.1) <br />A. BATHROOMS <br />1. All shower enclosures, regardless of shape, shall have a minimum finished <br />interior area of not less than 1024 square inches (0.66 m2) and shall be capable <br />of encompassing a 30 inch diameter (0.76 m) circle. The minimum area and <br />dimensions shall be maintained to a point 70 inches (1.8 m) above the shower <br />drain outlet. (Plumbing Code Section 410.4) <br />2. Bathtub and shower floors, walls above bathtubs with a showerhead, and <br />shower compartments shall be finished with a nonabsorbent surface. Such wall <br />surfaces shall extend to a height of not less than 6 feet above the floor (R307.2). <br />3. Provide ultra low flush water closets for all new construction. Existing shower <br />heads and toilets must be adapted for low water consumption. <br />4. A min 12" sq. access panel to the bathtub trap slip joint connection is <br />required. (Plumbing Code Section 405.2) <br />5. Provide 15" minimum between the center of water closet to any side wall. <br />(Calif. Plumb. Code 407.6) <br />6. Provide 24" clear spacce infront of any water closet . (Calif. Plumb. Code <br />407.6) <br />B. LAUNDRY ROOM <br />1. Clothes dryer(s) located in an area that is habitable or containing fuel burning <br />appliances shall be exhausted to the outside or to an area which is not habitable <br />and does not contain other fuel burning appliances (but not beneath the building <br />or in the attic area). (M.C. 504.3.1) <br />2. A 4" clothes dryer moisture exhaust duct is limited to a 14 feet length with two <br />elbows from the clothes dryer to the point of termination. Reduce this length by 2 <br />feet for every elbow in excess of 2. (M.C. 504.3.2, M.C. 908) <br />C. MEANS OF EGRESS <br />1. Provide 32" wide doors to all interior accessible rooms within a dwelling unit. <br />(LARC Section R311.2, LABC Section 6304.1) <br />2. Provide emergency egress from sleeping rooms. Min.- 24" clear ht, 20" clear <br />width, 5.7 sq.ft. min. area. (LARC Section R310, LABC Section 1029) <br />3. Occupied roofs shall be provided with exits as required for stories. <br />4. Provide minimum 9 sf window wells (with fixed ladder) at escape and rescue <br />opening windows below grade. (R310.2.3) <br />14. 50 percent of nonhazardous construction and demolition waste shall be recycled and/or <br />salvaged for reuse in accordance with the California Green Building Code, Chapter 4, <br />Division 4.4. (R324) <br />H. STRUCTURAL REQUIREMENTS <br />1. Provide lead hole 40%-70% of threaded shank dia. and full dia. for smooth shank <br />portion of Lag Bolts. <br /> <br />2. All bolt holes, other than Lag Bolt holes, shall be drilled 1/32 to 1/16" oversized. <br />3. Provide lateral support for the top of interior non-bearing walls when manufactured <br />trusses are used. (LABC 1607.13) <br />4. Provide double joists under parallel bearing partitions. (LARC Sec. R502.4, LABC <br />Section 2308.8.4) <br />5. Provide full length studs (balloon frame) on exterior walls of rooms with vaulted ceiling. <br />(LARC Section R602.3, LABC Section 2308.9,Table 2308.9.1). <br />6. All roof and shear wall nailing shall utilize common nails or galvanized box. Nail guns <br />using “Clipped head” or Sinker nails are not acceptable. (LARC Table R602.3(1), LABC <br />Table 2304.9.1) <br />7. Roof nailing to be inspected before covering. Face grain of plywood shall be <br />Perpendicular to supports. Floor shall have tongue and groove or blocked panel edges. <br />Plywood spans shall conform with Table 2304.7(3). (LABC Section 2304.7) <br />8. All horizontal joints occurring in braced wall panels shall occur over blocking equal in <br />size to the studding. (LARC Section R602.10.8, LABC Section 2308.9.3) <br />9. Stucco shear walls shall utilize furring, galvanized nails (having a minimum 11 ga., <br />1-1/2" long, 7/16" diameter head, and furred out a min of 1/4") to attach the lath to the <br />studs. Staples shall not be used.” (Table 2507.2). Self furring lath approved by a Los <br />Angeles Research Report is permitted. <br />10. Structural wood shear walls shall be covered with minimum two layers 15# <br /> felt underlay prior to placing finish material. <br />11. Shop welds must be performed in a LA City Bldg. Dept. licensed fabricator ’s shop. <br />12. Plate washers are required for all hold downs. (LABC Table 2306.4.1) <br />13. Foundation sills shall be Douglas-Fir (Group II Lumber ) pressure treated or foundation <br />grade Redwood.(LABC Section .2304.11.2.4). <br />14. Hold-down connector bolts into wood framing require approved plate washers; and <br />hold-downs shall be tightened just prior to covering the wall framing. <br />15. All bolt holes shall be drilled a maximum of 1/16" oversized AND inspector shall verify at <br />job site. <br />16. Cutting, Notching, and Boring of Wood Framing Members . (LARC R602.6, LABC Sec. <br />2089.10, 11)(see diagrams below). <br />Bored Holes D/3 <br />2 x 6 = 1 13/16" <br />2 x 8 = 2 7/16" <br />2 x 10 = 3 1/16" <br />2 x 12 = 3 3/4" <br />GENERAL NOTES <br />D. GRADING AND FOUNDATION <br />1. If adverse soil conditions are encountered, a soils investigation report may be required. <br /> (LARC Section R401.4) <br />2. Foundation and floor slabs shall conform to the following or the recommendation of an <br />approved soils report : <br />a. Depth of footings below the natural and finished grades shall not be less than 24 <br />inches for exterior and 18 inches for interior footings. <br />b. Exterior walls and interior bearing walls shall be supported on continuous <br />footings. <br />c. Footings shall be reinforced with a minimum 4 - ½ -inch diameter deformed <br />reinforcing bars. Two bars shall be placed within 4 inches of the bottom of the <br />footing and two bars within 4 inches of the top of the footings. <br />d. The soil below an interior concrete slab shall be saturated with moisture to a <br />depth of 18 inches prior to placing the concrete. <br />e. Concrete floor slabs on grade shall be placed on a 4" fill of coarse aggregate or <br />on a moisture barrier membrane. The slabs shall be at least 3½ inch thick and shall be <br />reinforced with #4 rebars at 16 inch on center in both directions. <br />3. Concrete slabs on expansive soil, compacted fill or slopes over 1:10 shall be placed on <br />a 4-inch fill of coarse aggregate or on a 2" sand bed covered moisture barrier <br />membrane. The slabs shall be at least 3-1/2 inches thick and reinforced with #4 bars <br />spaced at intervals not exceeding 16 inches on center each way. <br />(LABC Section 1808.6 , LARC Section R403.1.8, R506.1) <br />4. Provide Under-floor net ventilation opening size and locations equal to 1 sq. ft. for each <br />150 sq. ft. of under floor area and an access opening through the floor (18 ” x 24” min) or <br />an opening through a perimeter wall not less than (16 ” x 24” min). (LARC R408, LABC <br />Section 2304.11.9, 1203.3) <br />5. Openings shall be as close to corners as practicable and shall provide cross ventilation <br />along the length of at least two opposite sides. Opening shall have 1/4 inch corrosion <br />resistant metal mesh covering. (LABC Section 1203.3, LARC R408.2) <br />6. Provide corrosion resistant weep screed below the stucco a minimum of 4" above earth <br />or 2" above paved area. (LARC Section R703.6.2.1, LABC Section 2512.1.2) <br />7. Provide rain gutters and convey rain water to the street. (LARC R903.4, LABC 1503.4.1, <br />7013.9) <br />E. ZONING NOTES <br />1. A/C units and water heaters are not allowed in the required side yards and front yard <br />unless specifically allowed by exception per Information bulletin P/ZC 2002-006. <br />G. SPECIAL HAZARDS <br />1. Glazing in hazardous locations shall be tempered. (LARC R308, LABC Section 2406.4) <br />Fixed or operable panels in swinging, sliding and bifold doors and fixed or operable panels <br />adjacent to doors; Fixed or operable window panels with panes larger than 9 square feet <br />and are less than 18 inches above the floor, have a top edge greater than 36 inches above <br />the floor and have one or more walking surfaces within 36 inches, measured horizontally <br />and in a straight line, of the glazing. Glazing in guards and railings, adjacent to wet <br />surfaces, adjacent to stairs and ramps, and adjacent to bottom stair landings. <br />2. Each light of safety glazing material installed in hazardous locations shall be identified <br />by a permanent label that specifies the labeler, and states that safety glazing material <br />has been utilized in such installations. <br />3. Unit Skylights shall be labeled by a LA City Approved Labeling Agency. Such label <br />shall state the approved labeling agency name, product designation and performance <br />grade rating (research report not required). (R308.6.9) <br />4. Pre-fab fireplaces are required to have manufacturer, model, and Underwriter <br />Laboratories certification (or ICC). <br />5. Provide an approved spark arrester for the chimney of a fireplace, stove, or barbecue <br />which uses fuel burning material.” (L.A.M.C. 57.20.25 ) <br />6. An approved Seismic gas shutoff valve will be installed on the fuel gas line on the down <br />stream side of the utility meter and be rigidly connected to the exterior of the building or <br />structure containing the fuel gas piping.”(Per Ordinance 171,874-for work over $10,000.) <br />7. Water heater must be strapped to wall. Section 508.2, LAPC. See Information Bulletin <br />P/PC 2011-003 “How to Brace Your Water Heater ” for details. <br />8. For existing pool on site, provide an alarm for doors to the dwelling that form a part of <br />the pool enclosure. The alarm shall sound continuously for a min. of 30 seconds when <br />the door is opened. It shall automatically reset and be equipped with a manual means to <br />deactivate (for 15 seconds. Max.) for a single opening. The deactivation switch shall be <br />at least 54" above the floor. (6109 of LABC) <br />9. For existing pool on site, provide anti –entrapment cover meeting the current ASTM or <br />ASME for the suction outlets of the swimming pool, toddler pool and spa for single <br />family dwellings per Assembly Bill (AB)No. 2977. (3162B) <br />10. Smoke detectors shall be provided for all dwelling units intended for human occupancy, <br />upon the owner’s application for a permit for alterations, repairs, or additions, exceeding <br />one thousand dollars ($1,000). (R314.6.2) <br />11. An approved smoke alarm shall be installed in each sleeping room & hallway or area <br />giving access to a sleeping room, and on each story and basement for dwellings with <br />more than one story. Smoke alarms shall be interconnected so that actuation of one <br />alarm will activate all the alarms within the individual dwelling unit. In new construction <br />smoke alarms shall receive their primary power source from the building wiring and <br />shall be equipped with battery back up and low battery signal. (R314) <br />12. An approved carbon monoxide alarm shall be installed in dwelling units <br /> and in sleeping units within which fuel-burning appliances are installed and in dwelling units <br />that have attached garages. Carbon monoxide alarm shall be provided outside of each <br />separate dwelling unit sleeping area in the immediate vicinity of the bedroom(s) and on <br />every level of a dwelling unit including basements. (R315) <br />13. Where a permit is required for alterations, repairs or additions exceeding one thousand <br />dollars ($1,000), existing dwellings or sleeping units that have attached garages or <br />fuel-burning appliances shall be provided with a carbon monoxide alarm in accordance <br />with Section R315.1. Carbon monoxide alarms shall only be required in the specific <br />dwelling unit or sleeping unit for which the permit was obtained. (R315.2.2) <br />14. 50 percent of nonhazardous construction and demolition waste shall be recycled and/or <br />salvaged for reuse in accordance with the California Green Building Code, Chapter 4, <br />Division 4.4. (R324) <br />FLOOR PLAN NOTES: <br />1. ALL EXTERIOR DOORS SHALL BE WEATHER STRIPPED. <br />1.1 THE LAND AT REQUIRED OUT-SWINGING DOOR SHALL NOT BE MORE THAN 1 1/2" LOWER THAN THE TOP. <br />1.2 THE LANDING AT IN-SWINGING DOORS AND DOORS OTHER THAN THE REQUIRED EGRESS SHALL NOT BE <br />THAN 7 3/4" BELOW THE TOP OF THE THRESHOLD. <br />2. WALL INSULATION SHALL BE R-15 <br />3. ROOF INSULATION SHALL BE R-38 <br />4. UNDER FLOOR INSULATION SHALL BE R-19 <br />5.. ALL RECEPTACLES IN KITCHEN, BATH AND GARAGE SHALL BE GF1. OUTSIDE RECEPTACLES SHALL BE <br />WEATHERPROOF. <br />6. LAMPS USED IN LUMINAIRES FOR GENERAL LIGHTING IN KITCHEN AND BATHROOM SHALL HAVE EFFICIENCY OF NOT <br />LESS THAN 40 LUMENS PER WATT. <br />7. ALL WINDOWS SHOULD BE DUAL PANEL <br />8. ALL BEDROOMS AND HALL AREAS THAT ACCESS BEDROOMS SHALL HAVE SMOKE DETECTORS, HARD WIRE WITH <br />BATTERY. <br />9. PROVIDE 30”X22” ATTIC ACCESS SWITCH & LIGHT & RECP. <br />10. FANS SHALL HAVE 5 AIR CHANGES PER HOUR. <br />11. WALL COVERING SHALL BE CEMENT PLASTER. TITLE OR APPROVED EQUAL TO 72 ” INCHES ABOVE DRAIN AT <br />SHOWERS OR TUBS WITH SHOWERS. MATERIALS OTHER THAN STRUCTURAL ELEMENTS SHALL BE MOISTURE <br />RESISTANT. GLASS ENCLOSURE DOORS AND PANELS MUST BE LABELED CATEGORY ll. SWING DOOR OUTWARD. NET <br />AREA OF SHOWER RECEPTOR SHALL NOT BE LESS THAN 1.024 SQ IN OF FLOOR. <br />12. GLAZING IN THE FOLLOWING LOCATIONS SHOULD BE OF SAFETY GLAZING MATERIAL IN ACCORDANCE WITH <br />SECTION 2406.4 (SEE EXCEPTIONS): <br />A) WHERE THE BOTTOM EXPOSED EDGE OF THE WINDOW GLAZING IS LESS THAN 60 INCHES ABOVE A STANDING <br />SURFACE AND DRAIN INLET OF TUBS AND SHOWERS. @ POWDER ROOM OFF OF KITCHEN. <br />13. SMOKE DETECTORS ARE REQUIRED IN EACH SLEEPING ROOM, OUTSIDE EACH SEPARATE SLEEPING AREA IN THE <br />IMMEDIATE VICINITY OF THE BEDROOMS, ON EACH STORY, BASEMENT AND HABITABLE ATTICS. <br />13.1. SMOKE ALARMS SHALL COMPLY WITH SPECIFIC LOCATION REQUIREMENTS PER NFPA 72 SECTION 29.8.3.4 [CRC <br />R314.3.3] <br />13.2. SMOKE ALARMS SHALL BE INSTALLED FOR NEW CONSTRUCTION AND ALTERATION [CRC R314.2.1, R314.2.2] <br />13.3. BATTERY OPERATED SMOKE ALARMS PERMITTED IN EXISTING BUILDINGS WHERE NO CONSTRUCTION IS TAKING <br />PLACE OR IN BUILDING UNDERGOING ALTERATION OR REPARATION THAT DO NOT RESULT IN THE REMOVAL OF <br />INTERIOR WALLS, OR CEILING FINISHES, UNLESS THERE IS AN ATTIC, CRAWL SPACE OR BASEMENT. [CRC R314.6, <br />EXCEPTIONS 1,3] <br />13.4. SMOKE ALARMS SHALL BE INTERCONNECTED SUCH THAT THE ACTIVATION OF ONE ALARMS IN THE INDIVIDUAL <br />DWELLING UNIT [CRC R314.4] <br />13.5. SMOKE DETECTORS SHALL BE “HARD WIRED ” AND SHALL BE EQUIPPED WITH BATTERY BACKUP. [CRC R314.6] <br />14. CARBON MONOXIDE ALARM [CRC R315.3]: <br />SHALL BE INSTALLED OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS <br />AND ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENT <br />14.1. CARBON MONOXIDE ALARM SHALL BE INSTALLED FOR NEW CONSTRUCTION AND ALTERATION [CRC R314.2.1, <br />R314.2.2] <br />14.2. CO ALARMS SHALL BE “HARD WIRED ” AND SHALL BE EQUIPPED WITH BATTERY BACK UP. <br />14.3. CO ALARMS SHALL BE INTERCONNECTED SUCH THAT THE ACTIVATION OF ONE ALARMS IN THE INDIVIDUAL <br />DWELLING UNIT [CRC R314.4] <br />14.4 CO ALARMS SHALL BE INSTALLED FOR COMPLIANCE WITH UL 2034, UL 217, UL 2075 AND MAINTAINED PER NFPA 720 <br />[CRC R315.1.1, CRC R315.6.1, CRC 315.6.2] <br />14.5 CO ALARMS SHALL BE INSTALLED FOR COMPLIANCE WITH UL 2034, UL 217, UL 2075 AND MAINTAINED PER NFPA 720 <br />[CRC 315.1.1, CRC 315.6.1, CRC 315.6.2] <br />15. THE ELEVATION OF LANDING SHALL NOT EXCEED 7 1/2 INCH DIFFERENCE THAN THE THRESHOLD OF THE DOORWAY <br />(IF DOOR DOES NOT SWING OVER THE LANDING). BACK UP. <br />16. ALL STAIRWAYS SHALL HAVE AN ILLUMINATION LEVEL ON TREAD RUNS OF NOT LESS THAN 1 FOOT CANDLE (11 LUX). <br />17. FOR CLOTHES DRYER: <br />16.1 A MINIMUM 4” MOISTURE EXHAUST DUCT MUST BE PROVIDED <br />CMC 504.4.2.1 <br />16.2 DRYER EXHAUST CANNOT EXCEED 14 FT. WITH A MAX OF TWO 90 DEG. ELBOWS <br />CMC 504.4.2.2 <br />16.3. A FLEXIBLE DUCT CANNOT EXTEND MORE THAN 6 FT. AND CANNOT BE CONCEALED <br />CMC 504.4.2.2 <br />18. A MINIMUM OF 1” OF SPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF <br />SHEATHING AND AT THE LOCATION OF VENTS FOR VAULTED CEILING OR FLAT ROOFS [CRC R806.3] <br />OPENINGS SHALL HAVE CORROSION-RESISTANT WIRE MESH OR OTHER APPROVED MATERIAL WITH <br />1/16 INCH MIN. AND 1/4 INCH IN MAX. OPENING <br />A MINIMUM OF 1-INCH AIRSPACE SHALL BE PROVIDED BETWEEN INSULATION AND ROOF SHEATHING <br />UNVENTED ATTIC ASSEMBLIES SHALL MEET ALL THE CONDITIONS IN SECTION R806.4 <br />1108 N Towner St & <br />#212/13/2024