Section 220.82 Dwelling Unit <br />Part #1 - Section 220.82 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft: <br />Amps Box A (VA) <br />15.63 3750 <br />Part #2 - Section 220.82 <br />Size in VA Size in VA <br />1500 N/A <br />3000 N/A <br />1000 N/A <br />600 N/A <br />1000 N/A <br />1600 N/A <br />5760 N/A <br />3840 N/A <br />N/A N/A <br />N/A Amps Box B (VA) <br />N/A 76.25 18300 <br />Total VA from Parts #1 and #2 combined:Box A + Box B =22050 <br />Total VA 22050 <br />First 10,000 VA @ 100%10000 Remaining VA @ 40% <br />Remaining VA =12050 12050 x 40% =4820 VA <br />Adding First 10,000 VA 10000 VA <br />Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:14820 VA <br />Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:61.75 Amps <br />Part #3 - Section 220.82 (C) Heating and A/C loads: <br />*Combine the larger loads of either the Heating or the A/C loads togther <br />100% of all the Heating or A/C loads in VA:0 VA <br />100% of all the Heating or A/C loads in Amps:0.00 A <br />VA Volts Amps <br />Parts #1 & #2 14820 240 61.75 <br />Part #3 0 240 0.00 <br />Total VA for all Parts:14,820 <br />Totals Service/Feeder Load 61.75 <br />#ESTAMP <br />Laundry <br />Appliance Circuit(s) <br />Dishwasher(s) <br />Disposal(s) <br />Dedicated circuit <br />House <br />Square Footage <br />1250 <br />Article 220 - Service/Feeder calculation for (address): <br />5313 W Henderson Pl <br />Santa Ana, CA 92704 <br />Building VA (watts) <br />3750 <br />Amps <br />15.625 <br />Job Code <br />109R-313VALA <br />Totals from all Parts <br />Dedicated circuit <br />Total for Part #1: <br />Refrigerator(s) <br />Microwave(s) <br />Totals for Part #2: <br />Dryer <br />OTHER <br />5313 W Henderson <br />Pl2/5/2025