Laserfiche WebLink
ENGINEERED PLANS COMPLETED BY ENGINEERS IN THE USA <br />VANDERVOORT, DAVID <br />2307 NORTH TOWNER STREET <br />SANTA ANA, CA 92706 <br /> PN/PARCEL NO: 00121406 <br />EXO ENERGY <br />1358 LA MIRADA DRIVE <br />SAN MARCOS, CA 92071 <br />(208) 351-4153 <br />MICHAEL ESPINOZA <br />CSLB: 1063308 <br />CONDUCTOR CALCULATIONS <br />MODULE <br />MANUFACTURER/ MODEL <br />HANWHA Q.CELL BLK <br />ML-G10+ 400 <br />PMAX 400 W <br />VOC 45.3 V <br />VMP 37.13 V <br />IMP 10.77 A <br />ISC 11.14 A <br />TEMPERATURE COOEFFICIENT OF PMAX -0.034 %/°C <br />TEMPERATURE COEFFICIENT OF VOC -0.27 %/°C <br />INVERTER <br />MANUFACTURER/ MODEL ENPHASE IQ8PLUS-72-2-US <br />MAX AC OUTPUT 1.21 A <br />AC OUTPUT VOLTAGE 240 V <br />MAX DC INPUT VOLTAGE 60 V <br />MAX INPUT CURRENT 20 A <br />WEIGHTED CEC EFFICIENCY 97.00% <br />INVERTER WATTAGE 290 W <br />TAG 1 (SEE E-1)TAG 2 (SEE E-1)TAG 3 (SEE E-1)TAG 4 (SEE E-1) <br />UNDER MODULES, NOT IN CONDUIT #10 AWG MAX CURRENT = 30A #10 AWG MAX CURRENT = 30A #3 AWG MAX CURRENT = 100A <br />#12 AWG MAX CURRENT = 20A <br />ENPHASE IQ8PLUS-72-2-US MAX OUTPUT = 21.78A <br />8.47 A FOR CIRCUIT 1 8.47 A FOR CIRCUIT 1 21.78 * 1.25 (SAFETY FACTOR) = 27.225A 21.78 * 1.25 (SAFETY FACTOR) = 27.225A <br />13.31 A FOR CIRCUIT 2 13.31 A FOR CIRCUIT 2 RECOMMENDED OCPD = 30 TESLA POWERWALL OCPD = 30 <br />EXISITING SYSTEM MAX OUTPUT= 32A <br />32*1.25(SAFETY FACTOR) = 40 <br />TOTAL OUTPUT CURRENT = 27.225+30+40 = 97.225A <br />RECOMMENDED OCPD = 100 <br />EQUIPMENT INFORMATION <br />E-2 <br />DATE:7/26/2024 <br />swyssling@wysslingconsulting.com <br />(201) 874-3483 <br />DESIGN ENGINEER <br />SOLAR COMPANY/CLIENT <br />76 N. MEADOWBROOK DRIVE <br />ALPINE, UTAH 84004 <br />EQUIPMENT <br />INFORMATION <br />2307 N Towner St <br />8/23/2024