ARCHITECT/ OWNER MUST VERIFY WITH A SOUND ENGINEER THE
<br />LOCATION AND THE REQUIREMENT OF ALL MECHANICAL UNITS TO
<br />MAKE SURE THAT THE SOUND OF THE MECHANICAL UNITS DO NOT
<br />EXCEED THE REQUIRED DB.
<br />FIELD VERIFY ALL CONDITIONS
<br />DESIGN DRAWINGS ARE SCHEMATIC. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO
<br />BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT
<br />SHALL INCLUDE ALL LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO
<br />EXISTING CONDITIONS.
<br />THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING
<br />FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL
<br />COSTS TO MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER
<br />OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS
<br />COST.
<br />BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND
<br />ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN
<br />STRICT ACCORDANCE WITH
<br />GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR
<br />SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES
<br />BETWEEN GOVERNING CODES AND DESIGN INTENT.
<br />GREEN BUILDING NOTES
<br />IF THE HVAC SYSTEM IS USED DURING CONSTRUCTION, USE RETURN AIR FILTERS WITH A
<br />MERV OF 8. REPLACE ALL FILTERS IMMEDIATELY PRIOR TO OCCUPANCY.
<br />ALL DUCTS AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE
<br />COVERED WITH TAPE, PLASTIC, OR SHEET METAL UNTIL THE FINAL STARTUP OF THE HEATING,
<br />COOLING AND VENTILATING EQUIPMENT.
<br />AN AIR FILTER WITH A MINIMUM EFFICIENCY REPORTING VALUE (MERV) OF 8 OR HIGHER SHALL
<br />BE INSTALLED IN THE MECHANICAL SYSTEM FOR OUTSIDE AND RETURN AIR PRIOR TO
<br />OCCUPANCY.
<br />THE BUILDING SHALL MEET OR EXCEED THE PROVISIONS FOR MECHANICAL VENTILATION OF
<br />SECTION 1203 OF THE LOS ANGELES BUILDING CODE.
<br />BUILDING THAT USE DEMAND CONTROL VENTILATION SHALL HAVE CO2 SENSORS AND
<br />VENTILATION CONTROLS INSTALLED IN ACCORDANCE WITH THE REQUIREMENT OF CURRENT
<br />EDITION OF THE CALIFORNIA ENERGY CODE, CCR, TITLE24, PART 6, SECTION 121(C).
<br />DIFFUSERS & REGISTERS SCHEDULE
<br />25
<br />(IN WC)
<br />0.05
<br />NECK SIZE
<br />(IN)DIMENSIONS
<br />(IN)
<br />TYPE
<br />NO.
<br />MARK
<br />SEE PLAAN TITUS TMS OR EQUAL CD-1 CEILING SUPPLY
<br />OVERALL CFM RANGE
<br />NC
<br />MAX.MAX. S.P.REMARKS
<br />1
<br />ALL FINISHES AND FRAMES SHALL BE APPROVED BY ARCHITECT.
<br />PROVIDE BLACK NON-DETERIORATING BACKING FOR ALL DIFFRUSERS
<br />FRAME TYPE FOR ALL AIR INLETS/OUTLETS SHALL BE SUITABLE/COMPATIBLE WITH CEILING TYPE AND GRID THAT IS TO BE INSTALLED IN.
<br />1
<br />2
<br />3
<br />SUPPLY & RETURN GRILLES AND DIFFUSERS SHALL BE 10 NC BELOW THAT OF THE ROOM SERVED.4
<br />SEE PLAN24" X 24" / -RETURN, TRANSFER AIRRG-1, TAG SEE PLAN 350ZRL X X 1 260.125
<br />SEE PLAN 4-
<br />1 4-
<br />24X24
<br />25 0.05SEE PLAAN TITUS TMS OR EQUAL CD-2 CEILING SUPPLY SEE PLAN-
<br />1. PRIMARY CONDENSATE PIPING TO TERMINATE AT TAILPIECE OF LAVATORY/SINK
<br /> IN THE UNIT IT SERVES, MOP/FLOOR SINK OR OTHER BUILDING DEPARTMENT
<br /> APPROVED DEDICATED RECEPTOR.
<br />2. SECONDARY CONDENSATE PIPING TO TERMINATE AT EXTERIOR OBSERVABLE
<br /> LOCATION,INTERIOR OVER A LAVATORY/SINK OR USE A LISTED WET/FLOAT
<br /> SWITCH APPROVED BY LOCAL CITY BUILDING DEPT.
<br />3. ALL AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS, INCLUDING, BUT NOT
<br /> LIMITED TO, BUILDING CAVITIES, MECHANICAL CLOSETS, AIR-HANDLER BOXES
<br /> AND SUPPORT PLATFORMS USED AS DUCTS OR PLENUMS, SHALL BE
<br /> INSTALLED, SEALED AND INSULATED TO MEET THE REQUIREMENTS OF THE
<br /> 2019 CMC. SUPPLY-AIR AND RETURN-AIR DUCTS CONVEYING HEATED OR
<br /> COOLED AIR SHALL BE INSULATED TO A MINIMUM INSTALLED LEVEL
<br /> OF R-13 UNLESS DUCTS ARE IN CONDITIONED SPACE.
<br />4. AT THE TIME OF ROUGH INSTALLATION, OR DURING STORAGE ON THE
<br /> CONSTRUCTION SITE AND UNTIL FINAL STARTUP OF THE HEATING, COOLING, AND
<br /> VENTILATING EQUIPMENT, ALL DUCTS AND OF THE RELATED AIR DISTRIBUTION
<br /> COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL, OR
<br /> OTHER ACCEPTABLE METHODS TO REDUCE THE AMOUNT OF DUST, WATER, AND DEBRIS
<br /> WHICH MAY ENTER THE SYSTEM.
<br />5. CONTRACTOR AT THE TIME OF FINAL INSPECTION SHALL PLACE IN THE
<br /> BUILDING A MANUAL, COMPACT DISC, WEB-BASED REFERENCE OR OTHER
<br /> MEDIA WHICH INCLUDES ALL OF THE FOLLOWING:
<br /> 1. DIRECTIONS TO THE OWNER OR OCCUPANT THAT THE MANUAL SHALL REMAIN
<br /> WITH THE BUILDING THROUGHOUT THE LIFE CYCLE OF THE STRUCTURE.
<br /> 2. OPERATION AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AND
<br /> APPLIANCES, INCLUDING WATERSAVING DEVICES AND SYSTEMS,
<br /> HVAC SYSTEMS, WATER-HEATING SYSTEMS AND OTHER MAJOR
<br /> APPLIANCES AND EQUIPMENT.
<br /> 3. INFORMATION FROM LOCAL UTILITY, WATER AND WASTE RECOVERY
<br /> PROVIDERS ON METHODS TO FURTHER REDUCE RESOURCE CONSUMPTION,
<br /> INCLUDING RECYCLE PROGRAMS AND LOCATIONS.
<br /> 4. PUBLIC TRANSPORTATION AND/OR CARPOOL OPTIONS AVAILABLE IN THE AREA.
<br /> 5. EDUCATIONAL MATERIAL ON THE POSITIVE IMPACTS OF AN INTERIOR
<br /> RELATIVE HUMIDITY BETWEEN 30-60 PERCENT AND WHAT METHODS AN
<br /> OCCUPANT MAY USE TO MAINTAIN THE RELATIVE HUMIDITY LEVEL IN
<br /> THAT RANGE.
<br /> 6. INFORMATION ABOUT WATER-CONSERVING LANDSCAPE AND IRRIGATION
<br /> DESIGN AND CONTROLLERS WHICH CONSERVE WATER.
<br /> 7. INSTRUCTIONS FOR MAINTAINING GUTTERS AND DOWNSPOUTS AND THE
<br /> IMPORTANCE OF DIVERTING WATER AT LEAST 5 FEET AWAY FROM
<br /> THE FOUNDATION.
<br /> 8. INFORMATION ON REQUIRED ROUTINE MAINTENANCE MEASURES, INCLUDING,
<br /> BUT NOT LIMITED TO, CAULKING, PAINTING, GRADING AROUND THE
<br /> BUILDING, ETC.
<br /> 9. INFORMATION ABOUT STATE SOLAR ENERGY AND INCENTIVE PROGRAMS
<br /> AVAILABLE.
<br />DUCT SIZES.
<br />INTERFERENCES.
<br />REMARKS:
<br />VERIFY ALL DIMENSIONS AT THE SITE, MAKE ALL FIELD
<br />FABRICATION AND ERECTION OF SHEET METAL WORK. MAKE
<br />ALLOWANCES FOR BEAMS, PIPE OR OTHER OBSTRUCTION AND
<br />FOR WORK BY OTHER TRADES AND NOTIFY THE ARCHITECT
<br />IN THE EVENT OF ANY POTENTIAL INTERFERENCE. MAKE AN
<br />INITIAL VERIFICATION OF BEAM PENETRATIONS SHOWN ON
<br />STRUCTURAL DRAWINGS AND ADVISE OF ANY POTENTIAL
<br />MEASUREMENTS AND SHOP DRAWINGS NECESSARY FOR
<br />DUCT SIZES INDICATED ARE INSIDE DIMENSIONS WHICH MAY BE
<br />ALTERED BY CONTRACTOR TO OTHER DIMENSIONS TO AVOID
<br />INTERFERENCES AND CLEARANCE REQUIREMENTS. USE EQUAL
<br />FRICTION METHOD, 0.1"WG PER 100 FT. OF DUCT TO DETERMINE
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />16
<br />20
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />18
<br />24
<br />X
<br />X
<br />X
<br />10
<br />X
<br />12
<br />22
<br />30
<br />X
<br />X
<br />8
<br />12
<br />10
<br />16
<br />28
<br />40
<br />6
<br />8
<br />10
<br />16
<br />12
<br />X
<br />X
<br />X
<br />8
<br />10
<br />16
<br />X
<br />X
<br />X
<br />X
<br />X181501 TO 2000
<br />16
<br />12
<br />10
<br />9
<br />8
<br />7
<br />6
<br />WX14WX12WX10WX8WX6WX4
<br />RECTANGULAR DUCT (IN)
<br />(W IS DUCT WIDTH)
<br />ROUND
<br />DUCT
<br />(IN)
<br />DUCT SIZING
<br />UP TO 100
<br />101 TO 150
<br />(NON-SOUND-SENSITIVE ONLY - LOW PRESSURE DUCTWORK)
<br />151 TO 240
<br />401 TO 750
<br />241 TO 300
<br />300 TO 400
<br />1001 TO 1500
<br />X141824XX14751 TO 1000
<br />1 1/2" WIDE DUCT HANGER
<br />18 GA. MIN. @ MAX. 10FT. O.C.
<br />18 GA. MIN. @ MAX. 10FT. O.C.
<br />18 GA. MIN. @ MAX. 10FT. O.C.
<br />SHEET METAL DUCT & FITTING GAUGES
<br /> OF DUCT & FITTING
<br />MAX. DIA. OR WIDTH
<br />22
<br />24
<br />26
<br />METAL GAUGES
<br />G.I. SHEET
<br />12"& SMALLER
<br />31" THRU 54"
<br />13" THRU 30"
<br />REMARKS
<br />(IN.)
<br />DEFLECTION
<br />STATICMANUF. AND
<br />MODEL NO.
<br />ISOLATOR DATA
<br />OPERATING
<br />(LBS.)
<br />WEIGHTOSA
<br />(CFM)
<br />MIN.
<br />SENSIBLE
<br />(BTUH)(BTUH)
<br />TOTAL
<br />(IN.)
<br />ESP CFM V/PH/HZ
<br />ELECTRICAL DATA
<br />NOMINAL
<br />(TONS)
<br />SERVICE CAPACITYMANUFACTURER
<br />& MODEL NO.LOCATIONMARK NO.
<br />SUPPLY FAN COOLING CAPACITIES
<br />MCA MOCPFLA
<br />MIN.UNIT DIMENSIONS
<br />(L X W X H)
<br />EXISTING PACKAGED ROOFTOP HEAT PUMP UNITS SCHEDULE
<br />NET
<br />HEATING CAPACITY
<br />(BTUH)EER/SEER
<br />HSPF
<br />HP
<br />1a
<br />QUANT.
<br />* 1. CONTRACTOR TO VERIFY AND MAKE SURE THE UNIT HAS SMOKE DETECTOR , AND CONV. OUTLET AND CO2 SENSOR.
<br /> 2. REPLACE FILTERS WITH MINIMUM MERV13 RATED FILTERS PRIOR TO OCCUPENCY.
<br /> 3. VERIFY THE ELECTRICAL & MOCP REQUIREMENT. INFORM THE ELECTRICAL CONTRACTOR IF THERE IS ANY DISCREPANCY.
<br /> 4. RECHARGE REFRIGERATION GAS AS NEEDED.
<br />ROOF 5 (E).6 21001 (E)EXISTING SPACE (E)(E)HP UNIT 452924.9 (E)25058,000 41,200 57,000 208/3/60 (E)
<br />SERVICE THE UNIT AND REPLACE ANY DAMAGED PART.
<br />REPLACE FILTERS WITH MERV13 FILTERS PRIOR TO OCCUPANCY.
<br />HP
<br />1b ROOF 5 (E).6 21001 (E)EXISTING SPACE (E)(E)HP UNIT 452924.9 (E)25058,000 41,200 57,000 208/3/60 (E)
<br />SERVICE THE UNIT AND REPLACE ANY DAMAGED PART.
<br />REPLACE FILTERS WITH MERV13 FILTERS PRIOR TO OCCUPANCY.
<br />EXHAUST FAN SCHEDULE
<br />EF
<br />1
<br />SYMBOL MODELMAKE CFM
<br />ELECTRICAL
<br />W/HP
<br />S.P
<br />V Ø HZ
<br />WT.(LBS)SERVICE QTY.REMARKS
<br />DISC. SW., INTERLOCK WITH MOTION SENSOR.
<br />CLG. MNT'D. EXH. FAN, W/ BACKDRAFT DAMPER,
<br />COOK 100 120650.20 1 60 30 TOILET
<br />EXH.
<br />1
<br />W
<br />GEMINI GC-240
<br />EF
<br />2 DISC. SW., INTERLOCK WITH MOTION SENSOR.
<br />CLG. MNT'D. EXH. FAN, W/ BACKDRAFT DAMPER,
<br />COOK 100 120650.20 1 60 30 TOILET
<br />EXH.
<br />1
<br />W
<br />GEMINI GC-240
<br />EF
<br />3 DISC. SW., INTERLOCK WITH SWITCH ON WALL.
<br />CLG. MNT'D. EXH. FAN, W/ BACKDRAFT DAMPER,
<br />COOK 150 120750.20 1 60 30 LAB
<br />EXH.
<br />1
<br />W
<br />GEMINI GC-320
<br />EF
<br />4 DISC. SW., INTERLOCK WITH SWITCH ON WALL.
<br />CLG. MNT'D. EXH. FAN, W/ BACKDRAFT DAMPER,
<br />COOK 120 120750.20 1 60 30 LOUNGE
<br />EXH.
<br />1
<br />W
<br />GEMINI GC-320
<br />EF
<br />5 DISC. SW., INTERLOCK WITH T'STAT ON WALL.
<br />CLG. MNT'D. EXH. FAN, W/ BACKDRAFT DAMPER,
<br />COOK 200 1201700.20 1 60 30 UTILITY
<br />EXH.
<br />1
<br />W
<br />GEMINI GC-420
<br />EF
<br />6 DISC. SW., INTERLOCK WITH T'STAT ON WALL.
<br />CLG. MNT'D. EXH. FAN, W/ BACKDRAFT DAMPER,
<br />COOK 150 120750.20 1 60 30 OFFICE / IT ROOM
<br />EXH.
<br />1
<br />W
<br />GEMINI GC-320
<br />Scale
<br />Date
<br />Drawn By
<br />Checked By
<br />Project Number
<br />REVISIONS
<br />JOB SITE:
<br />PLAN:
<br />PHONE:
<br />PLAN CHECK / JOB NO.
<br />50 S DE LACEY AVE. STE. 210
<br />Pasadena, CA 91105
<br />THESE PLANS ARE FOR REVIEW ONLY AND NOT FOR CONSTRUCTION UNLESS THEY
<br />INCLUDE THE STAMP AND SIGNATURE OF ARCHITECT/ENGINEER AND THE
<br />APPROVAL OF THE APPROPRIATE GOVERNMENT AGENCY
<br />C-38176
<br />MARC A.
<br />ABDELSAYED
<br />RENEWAL
<br />DATE
<br />LICENSED A R CHITECT
<br />STATE OF C ALIFORNIA
<br />07/31/2025
<br />369
<br />ARCHITECTS
<br />As Noted
<br />CA
<br />N
<br />A
<br />M
<br />
<br />D
<br />E
<br />N
<br />T
<br />A
<br />L
<br />
<br />-
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />MARS
<br />NASRIN.P.
<br />07/29/2024
<br />MISC._24065
<br />No.Description Date
<br />1414 W. EDINGER AVE,
<br />SANTA ANA, CA. 92704
<br />.PERMIT 09/04/2024
<br />09
<br />/
<br />0
<br />4
<br />/
<br />2
<br />0
<br />2
<br />4
<br />_
<br />G
<br />C
<br />
<br />C
<br />o
<br />m
<br />m
<br />e
<br />n
<br />t
<br />1 P.C.COMMENTS 02/01/2025
<br />M-1.1
<br />MECHANICAL NOTES
<br />& SCHEDULES
|