CALL TOLL FREE 1 (800) 227-2600
<br />TWO WORKING DAYS BEFORE YOU DIG
<br />REVISIONS
<br />NO.DATE DESCRIPTION NO.DATE DESCRIPTION
<br />CONTRACTOR:
<br />CORONA CONSTRUCTION CO.
<br />615 E. ALLEN AVE.
<br />SAN DIMAS, CA 91773
<br />PHONE: 626-926-7487
<br />CA. LIC. #797455 CLASS A-B-HAZ C10
<br />EXPIRES 07/31/2025
<br />ELECTRICAL NOTES
<br />SITE ADDRESS:
<br />UNITED PACIFIC #5669
<br />1913 WEST EDINGER AVE.
<br />SANTA ANA, CA 92704
<br />SCALE:
<br />DRAWN BY:
<br />DATE:
<br />JOB NO.
<br />DRAWING NO.
<br />CHECKED BY:
<br />AS NOTED
<br />ETHAN BUI
<br />7/19/2023
<br />5669
<br />F6
<br />ALVARO CORONA
<br />SHEET
<br />F6
<br />B
<br />A
<br />C
<br />D
<br />E
<br />F
<br />G
<br />H
<br />I
<br />J
<br />B
<br />A
<br />C
<br />D
<br />E
<br />F
<br />G
<br />H
<br />I
<br />J
<br />21 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
<br />21 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
<br />L
<br />ICENSED CONTRACTOR
<br />STATE OF CAL IFORNIA
<br />CORONA CONSTRUCTION CO.
<br />797455
<br />EXPIRES 07/31/2025
<br />ELECTRICAL SPECIFICATIONS
<br />PART 1 - GENERAL
<br />1.01 SCOPE OF WORK:
<br />FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT AND PROVIDE ALL LABOR, TOOLS, TRANSPORTATION, SUPERINTENDENCE AND
<br />SERVICES REQUIRED AND NECESSARY TO COMPLETE THE WORK SHOWN ON THE DRAWINGS AND/OR SPECIFIED HEREIN. ALSO INCLUDE ALL
<br />OTHER WORK AND MISCELLANEOUS ITEMS, NOT SPECIFICALLY MENTIONED, BUT REASONABLY INFERRED FOR A COMPLETE INSTALLATION
<br />INCLUDING ALL ACCESSORIES AND APPURTENANCES REQUIRED FOR TESTING THE SYSTEM. IT IS THE INTENT OF THE DRAWINGS AND
<br />SPECIFICATIONS, THAT ALL SYSTEMS BE COMPLETE AND READY FOR OPERATION.
<br />1.02 REGULATORY REQUIREMENTS:
<br />CODE COMPLIANCE IS MANDATORY NOTHING IN THESE DRAWINGS AND SPECIFICATIONS PERMIT WORK NOT CONFORMING TO THESE CODES.
<br />WHERE WORK IS SHOWN TO EXCEED MINIMUM CODE REQUIREMENTS, COMPLY WITH DRAWINGS AND SPECIFICATIONS. ALL WORK AND
<br />MATERIALS SHALL COMPLY WITH THE LATEST RULES, CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE FOLLOWING:
<br /> 1. OCCUPATIONAL SAFETY AND HEALTH ACT STANDARDS (OSHA).
<br /> 2. NFPA 170: NATIONAL ELECTRIC CODE (NEC).
<br /> 3. NFPA #101: LIFE SAFETY CODE.
<br /> 4. STATE FIRE MARSHAL.
<br /> 5. LOCAL UTILITIES COMPANIES.
<br /> 6. LANDLORD REQUIREMENTS.
<br />1.03 LICENSE, FEES AND PERMITS:
<br />ELECTRICAL CONTRACTOR SHALL PAY FOR ALL LICENSES, PERMIT AND INSPECTION FEES REQUIRED BY THE AUTHORITY HAVING JURISDICTION
<br />AND SHALL ARRANGE FOR ALL REQUIRED INSPECTIONS.
<br />1.04 SAFETY AND INDEMNITY:
<br />THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS
<br />AND PROPERTY DURING PERFORMANCE OF WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL
<br />WORKING HOURS, NO ACT. SERVICE, DRAWING REVIEW OR CONSTRUCTION REVIEW BY THE OWNER, AND ENGINEERS OR THEIR
<br />CONSULTANTS, IS INTENDED TO INCLUDE REVIEW OF THE ADEQUACY OF THE CONTRACTOR'S SAFETY MEASURES IN OR NEAR THE
<br />CONSTRUCTION SITE.
<br />1.05 DRAWINGS AND SPECIFICATIONS:
<br />ALL DRAWINGS AND ALL DIVISIONS OF THESE SPECIFICATIONS SHALL BE CONSIDERED AS A WHOLE AND WORK OF THIS DIVISION SHOWN
<br />ANYWHERE THEREIN SHALL BE FURNISHED UNDER THIS DIVISION. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
<br />ARRANGEMENT OF EQUIPMENT AND WIRING. MOST DIRECT ROUTING OF CONDUITS AND WIRING IS NOT ASSURED. EXACT REQUIREMENT
<br />SHALL BE GOVERNED BY CONDITIONS OF THIS JOB. CONSULT ALL OTHER DRAWINGS IN PREPARATION OF THE BID. EXTRA LENGTHS OF WIRING
<br />OR ADDITION OF PULL OR JUNCTION BOXES, ETC., NECESSITATE BY SUCH CONDITIONS SHALL BE INCLUDED IN THE BID.
<br />1.06 CONDITIONS AT SITE:
<br />VISIT SITE OF THE WORK, COMPARE IT WITH THE DRAWINGS AND SPECIFICATIONS AS TO THE CONDITIONS UNDER WHICH WORK IS TO BE
<br />PERFORMED, ASCERTAIN AND CHECK ALL CONDITIONS AND ELEVATIONS AND TAKE ALL MEASUREMENTS WHICH MAY AFFECT THE WORK NO
<br />ALLOWANCE SHALL SUBSEQUENTLY BE MADE FOR ANY EXTRA EXPENSE OR CLAIMS DUE TO FAILURE OR NEGLECT UNDER THIS REQUIREMENT
<br />TO MAKE SUCH EXAMINATION, INCLUDING EXAMINATION OF RESTRICTED WORKING CONDITIONS OR SUCH OTHER DIFFICULTIES VISUALLY
<br />OBSERVED DURING SITE VISIT. CONTRACTOR IS RESPONSIBLE FOR BECOMING COMPLETELY FAMILIAR WITH THE ARCHITECTURAL TOOLS AND
<br />MATERIALS REQUIRED TO PRODUCE A COMPLETELY CONCEALED INSTALLATION AS INDICATED ON THE PLANS, SPECIFICATIONS, AND REQUIRED
<br />BY THE CODE.
<br />1.07 WORKMANSHIP AND CONTRACTOR'S QUALIFICATIONS:
<br />ONLY QUALITY WORKMANSHIP WILL BE ACCEPTED. HAPHAZARD OR POOR INSTALLATION WILL BE CAUSE FOR REJECTION OF THE WORK.
<br />1.08 SHOP DRAWINGS AND MATERIALS LISTS:
<br />SUBMIT TO OWNER IN A SINGLE PACKAGE SIX (6) COPIES OF COMPLETE SHOP DRAWINGS AND MATERIALS LIST, AS NOTED BELOW, FOR
<br />REVIEW WITHIN FIFTEEN (15) DAYS AFTER AWARD OF CONTRACT.
<br />SUBMITTALS REQUIRED AS FOLLOWS:
<br /> 1. WIRING DEVICES: SWITCHES, RECEPTACLES, DEVICE PLATES.
<br /> 2. SWITCHBOARD & ENCLOSURES FOR UTILITY COMPANY METERING.
<br /> 3. MAIN FUSED DISCONNECT SWITCH.
<br /> 4. PANEL BOARDS.
<br /> 5. DISCONNECT SWITCHES.
<br /> 6. LIGHTING FIXTURES, LAMPS AND LIGHTING CONTROL EQUIPMENT.
<br />1.09 SUBSTITUTIONS:
<br />ONE OR MORE MAKES OF MATERIALS OR METHODS MAY HAVE BEEN SPECIFIED TO ESTABLISH THE STANDARD OF QUALITY, WORKMANSHIP,
<br />FINISH AND DESIGN REQUIRED, BUT OTHER MATERIALS OR METHODS EQUAL IN QUALITY, WORKMANSHIP, FINISH, DESIGN, AND GUARANTEED
<br />PERFORMANCE, WILL BE ACCEPTED. HOWEVER, ALL CHANGES AND SUBSTITUTIONS SHALL BE REQUESTED IN LETTER FORM AND SHALL BE
<br />ACCOMPANIED WITH A STATEMENT OF THE AMOUNT OF MONEY TO BE RETURNED TO THE CONTRACT IF THE SUBSTITUTION IS PERMITTED. NO
<br />WORK INVOLVING MATERIALS SUBMITTED FOR SUBSTITUTION SHALL PROCEED UNTIL WRITTEN ACCEPTANCE IS RECEIVED FROM THE OWNER.
<br />THE OWNER IS THE SOLE JUDGE OF ACCEPTABILITY OF PREFERRED SUBSTITUTIONS. IF A SUBSTITUTION ITEM IS PERMITTED, AND ANY
<br />RE-DESIGN EFFORT IS THEREBY NECESSITATED. THE REQUIRED RE-DESIGN SHALL BE AT THE CONTRACTOR'S EXPENSE.
<br />1.10 COORDINATION:
<br />COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT AND TO PROVIDE CORRECT ROUGH-IN AND CONNECTION FOR EQUIPMENT
<br />FURNISHED UNDER OTHER TRADES THAT REQUIRE ELECTRICAL CONNECTIONS. INFORM CONTRACTORS OF OTHER TRADES OF THE REQUIRED
<br />ACCESS TO AND CLEARANCES AROUND ELECTRICAL EQUIPMENT TO MAINTAIN SERVICE ABILITY AND CODE COMPLIANCE. VERIFY EQUIPMENT
<br />DIMENSIONS AND REQUIREMENTS WITH PROVISIONS SPECIFIED UNDER THIS SECTION. CHECK ACTUAL JOB CONDITIONS BEFORE FABRICATING
<br />WORK. REPORT NECESSARY CHANGES IN TIME TO PREVENT NEEDLESS WORK. CHANGES OR ADDITIONS, SUBJECT TO ADDITIONAL COMPENSATION,
<br />WHICH ARE MADE WITHOUT WRITTEN AUTHORIZATION AND AN AGREED PRICE, SHALL BE AT THE CONTRACTOR'S RISK AND EXPENSE.
<br />1.11 CUTTING AND PATCHING:
<br />ALL CUTTING AND PATCHING REQUIRED FOR WORK OF THIS DIVISION IS INCLUDED HEREIN. COORDINATION WITH GENERAL CONTRACTOR AND
<br />OTHER TRADES IS IMPERATIVE. CONTRACTOR SHALL BEAR THE RESPONSIBILITY FOR AND THE ADDED EXPENSE OF ADJUSTING FOR IMPROPER
<br />HOLES, SUPPORTS, ETC.
<br />1.12 ACCEPTANCE DEMONSTRATION:
<br />UPON COMPLETION OF THE WORK, AT A TIME TO BE DESIGNATED BY THE OWNER, THE CONTRACTOR SHALL DEMONSTRATE FOR THE OWNER THE
<br />OPERATION OF THE ELECTRICAL INSTALLATION, INCLUDING ANY AND ALL SPECIAL ITEMS INSTALLED BY HIM OR INSTALLED UNDER HIS SUPERVISION.
<br />PROPERLY SET AUTOMATIC TIME SWITCHES TO PERFORM SWITCHING OPERATIONS IN ACCORDANCE WITH SCHEDULES PROVIDED BY THE OWNER'S
<br />REPRESENTATIVE, AND DEMONSTRATE (USING THE MANUFACTURER'S OPERATING INSTRUCTIONS) HOW TO OVERRIDE AND/OR TEST TIME
<br />SWITCHES PROGRAMMING.
<br />1.13 RECORD DRAWINGS, EQUIPMENT DATA:
<br />MAINTAIN ONE SET OF CLEAN WORKING DRAWINGS AT THE JOB SITE AND ENTER DAILY SUCH "AS-BUILT" INFORMATION AS FEEDER AND SERVICE
<br />ROUTES, PULL BOX LOCATIONS AND CHANGES IN LAYOUT OR ARRANGEMENT WHICH OCCUR DURING CONSTRUCTION DELIVER COMPLETED
<br />DRAWINGS TO THE OWNER. SUBMIT TO THE OWNER'S REPRESENTATIVE A SET OF "AS BUILT" DRAWINGS IN VELLUM AND CAD FILE. AS BUILT
<br />COMMENTS SHALL BE WRITTEN IN A LEGIBLE MANNER IN THE SAME STYLE AS THE CONTRACT DOCUMENTS. ALSO SUBMIT THREE COPIES OF DATA
<br />SHEETS OR OTHER CURRENT MANUFACTURERS' PUBLICATIONS FOR EACH ITEM OF ELECTRICAL EQUIPMENT FURNISHED FOR THE PROJECT
<br />INCLUDING AT LEAST THESE DATA:
<br /> 1. TECHNICAL DESCRIPTION AND REPLACEABLE PARTS LIST.
<br /> 2. PHYSICAL DESCRIPTION AND INSTALLATION INSTRUCTIONS.
<br /> 3. USER'S MANUAL AND OPERATION INSTRUCTIONS.
<br /> 4. MANUFACTURER'S WARRANTY.
<br />1.14 CLEAN-UP:
<br />RID THE PREMISES OF SCARP MATERIALS. TRASH AND DEBRIS BOTH DURING CONSTRUCTION AND AT COMPLETION OF THE PROJECT. LEAVE THE
<br />BUILDING AND SURROUNDING AREA IN A CLEAN AND ORDERLY CONDITION.
<br />1.15 GUARANTEE:
<br />GUARANTEE THE INSTALLATION IS FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER DATE OF
<br />CERTIFICATION OF FINAL PAYMENT AND PROMPTLY REMEDY ANY DEFECTS DEVELOPING DURING THIS PERIOD, WITHOUT CHARGE.
<br />1.16 TEMPORARY SERVICES
<br />PROVIDE ADEQUATE AND SAFE TEMPORARY ELECTRICAL POWER AND LIGHTING THROUGHOUT THE CONSTRUCTION AND FINISHING OF THE
<br />PREMISES. IN ADDITION TO SPECIAL OR UNUSUAL REQUIREMENTS, PROVIDE AT LEAST THESE ITEMS:
<br /> 1. THREE 20-AMP CIRCUITS FOR CONSTRUCTION POWER TOOLS. PROVIDE GFI TEMPORARY CIRCUITS WITH COVERPLATES TO MEET OSHA
<br /> REQUIREMENTS.
<br /> 2. THREE OR MORE LIGHT STRINGS SUSPENDED APPROXIMATELY ONE FOOT BELOW THE HEIGHT OF FINISH CEILING WITH LAMPS SPACED NOT
<br /> MORE THAN TWELVE FEET ON CENTERS. STRINGS SHALL BE RUN THE LENGTH OF THE STORE SPACE PARALLEL TO THE DEMISING WALLS, WITH
<br /> ONE STRING WITHIN EIGHT FEET OF EACH WALL AND ONE (OR MORE) INTERMEDIATE STRING(S) ARRANGED TO LIMIT THE SPACING BETWEEN
<br /> ROWS TO SIXTEEN FEET OR LESS.
<br /> 3. FLOOD LIGHTING AND TASK LIGHTING FOR PAINTING AND OTHER FINISH WORK.
<br /> 4. WHEN PERMANENT ELECTRICAL SERVICE IS OPERABLE, DISCONNECT AND REMOVE FROM THE PREMISES THE MATERIALS AND EQUIPMENT
<br /> FOR TEMPORARY POWER AND LIGHTING, AND RESTORE MODIFICATIONS AND REPAIR DAMAGE CAUSED BY THE INSTALLATION, USE OR
<br /> REMOVAL OF TEMPORARY SERVICE PROVISIONS.
<br />3.03 INSTALLATION OF WIRES:
<br /> A. PULL NO WIRE INTO ANY PORTION OF THE CONDUIT SYSTEM UNTIL ALL CONSTRUCTION WORK WHICH MIGHT DAMAGE THE WIRE HAS
<br /> BEEN COMPLETED.
<br /> B. INSTALL ALL WIRE CONTINUOUS FROM OUTLET TO OUTLET OR TERMINAL TO TERMINAL. SPLICES IN CABLES WHEN REQUIRED SHALL BE
<br /> MADE IN HANDHOLES, PULL BOXES OR JUNCTION BOXES. MAKE BRANCH CIRCUIT SPLICES IN OUTLET BOXES WITH 8” OF CORRECTLY
<br /> COLOR-CODED TAILS LEFT IN THE BOX.
<br /> C. SPLICES IN WIRES AND CABLES SHALL BE MADE UTILIZING MATERIALS AND METHODS DESCRIBED HEREIN BEFORE.
<br /> D. MAKE ALL GROUND, NEUTRAL AND LINE CONNECTIONS TO RECEPTACLE AND WIRING DEVICE TERMINALS AS RECOMMENDED BY
<br /> MANUFACTURE. PROVIDE GROUND JUMPER FROM OUTLET BOX TO GROUND TERMINAL OF DEVICES WHEN THE DEVICE IS NOT
<br /> APPROVED FOR GROUNDING THROUGH THE MOUNTING SCREWS.
<br /> E. PROVED BRADY WIRE MARKERS WHERE NUMBER OF CONDUCTORS IN A BOX EXCEEDS FOUR.
<br /> F. MEGGER AND RECORD INSULATION RESISTANCE OF ALL 600 VOLT INSULATED CONDUCTORS SIZE #4/0 AND LARGER USING 500 VOLT
<br /> MEGGER FOR ONE MINUTE. MAKE TESTS WITH CIRCUITS ISOLATED FROM SOURCE AND LOAD.
<br />3.04 WIRE COLOR CODE:
<br />COLOR CODING SHALL BE CONTINUOUS FOR WIRE #12AWG THROUGH #10 AWG. PHASE CONDUCTORS #8 AND LARGER AND CONDUCTORS OF
<br />ANY SIZE IN CABLE ASSEMBLES MAY HAVE COLORED PHASING TAPE AT TERMINATIONS. COLOR CODE WIRES AS FOLLOWS:
<br />VOLTAGE PHASE A PHASE B PHASE C NEUTRAL GROUND
<br /> 120/208V BLACK RED BLUE WHITE GREEN
<br /> 277/480V BROWN ORANGE YELLOW GRAY GREEN
<br />3.05 IDENTIFICATION:
<br /> A. PROVIDE DYMO LABELS ON ALL LIGHTING SWITCHES AND CONVENIENCE AND SPECIAL PURPOSE RECEPTACLES TO SHOW PANEL AND
<br /> CIRCUIT NUMBER TO WHICH THE DEVISE IS CONNECTED.
<br /> B. EACH PANEL BOARD SHALL CONTAIN A METAL-FRAMED CIRCUIT DIRECTORY INSIDE COVER, WITH PLASTIC PROTECTOR.
<br /> C. PANEL BOARD SCHEDULE: AFTER COMPLETION OF WORK, PROVIDE TYPEWRITTEN UPDATED PANEL BOARD SCHEDULES FOR ALL PANEL
<br /> BOARDS.
<br />3.06 REMODELING WORK
<br /> A. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION
<br /> CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION. WHERE CONSTRUCTION CHANGES REQUIRE,
<br /> OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND
<br /> SPLICE IN NEW WIRING.
<br /> B. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE REMOVED AND WHICH ARE NOT
<br /> REPLACES OR REUSED SHALL BE REMOVED, WHERE OUTLETS BOXES, ETC, ARE COMPLETELY REMOVES, THE CONTRACTOR SHALL CUT
<br /> OFF CONDUITS AND REMOVE WIRING.
<br /> C. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR
<br /> D. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE PLUG
<br /> CONDUIT, AND THE CONDUIT SHALL NOT PROTRUDE ABOVE THE FLOOR. OR IN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO
<br />REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.
<br /> E. REMOVE ALL EXISTING WIRING NOT REUSED OR REQUIRED TO MAINTAIN CONTINUITY TO CIRCUITS TO REMAIN.
<br /> F. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING
<br /> PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIRS DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF
<br /> THIS SPECIFICATION. CLOSE ALL OPENING. REPAIR ALL SURFACES. ETC. AS REQUIRED.
<br /> G. MAINTAIN CIRCUIT CONTINUITY TO AREAS OUTSIDE OF THIS WORK. PROVIDE NEW CONDUIT AND CONDUCTORS AS REQUIRED TO
<br /> MAINTAIN CONTINUITY AND MAINTAIN AREA AS EXISTING.
<br />3.07 GROUNDING:
<br /> A. ELECTRICAL SERVICES AND SEPARATELY DERIVED ALTERNATING CURRENT SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH NEC
<br /> ARTICLE 250-3 TO 250-26, INCLUSIVE.
<br /> B. GROUND NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT ENCLOSURES, FRAMES, CONDUCTOR RACEWAYS OR
<br /> CABLE TRAYS TO PROVIDE A LOW IMPENDENCE PATH FOR LINE-TO-GROUND FAULT CURRENT AND TO BAND ALL NON-CURRENT
<br /> CARRYING METAL PARTS TOGETHER. PROVIDE GROUND CONDUCTOR IN EACH RACEWAY SYSTEM IN ADDITION TO CONDUCTORS
<br /> SHOWN. EQUIPMENT GROUND CONDUCTOR SHALL BE ELECTRICALLY AND MECHANICALLY CONTINUOUS FROM THE ELECTRICAL
<br /> CIRCUIT SOURCE TO THE EQUIPMENT TO BE GROUNDED. SIZE GROUND CONDUCTORS PER NEC ARTICLE 250-95 UNLESS LARGER
<br /> CONDUCTORS ARE SHOWN ON DRAWINGS.
<br /> C. GROUNDING CONDUCTORS SHALL BE IDENTIFIED WITH GREEN INSULATION WHERE GREEN INSULATION IS NOT AVAILABLE ON LARGER
<br /> SIZES, BLACK INSULATION SHALL BE USED AND SUITABLY IDENTIFIED WITH GREEN TAPE AT EACH JUNCTION BOX OR DEVISE ENCLOSURE.
<br />HAZARDOUS LOCATION NOTES
<br />GENERAL INSTALLATION REQUIREMENTS/FUEL EQUIPMENT COMPATIBILITY:
<br /> 1. EARTH GROUND IS REQUIRED FOR PROPER EQUIPMENT OPERATION. EACH FUEL-ASSOCIATED DEVICE IS TO BE CONNECTED TO THE
<br /> GROUND BUS OF THE MAIN POWER PANEL WITH A GREEN INSULATED WIRE TO PROVIDE A SINGLE REFERENCE POINT FOR EARTH
<br /> GROUND. THE GROUND BUS BAR WILL THEN BE CONNECTED TO A COPPER CLAD GROUND ROD DRIVEN NO LESS THAN 9 FT. INTO THE
<br /> GROUND. GROUNDING SHALL MEET CEC SECTION 250 REQUIREMENTS.
<br /> 2. ALL FUEL EQUIPMENT (I.E. DISPENSERS, MONITORING SYSTEM. POS. AND STPS) MUST BE CONNECTED TO THE SAME ELECTRICAL PHASE.
<br /> 3. EQUIPMENT WHICH COULD POTENTIALLY CREATE ELECTRICAL NOISE OR POWER SURGES (E.G. COOLERS, COMPRESSORS. FLUORESCENT
<br /> LIGHTING, ETC.) SHALL NOT SHARE A CIRCUIT WITH POS EQUIPMENT.
<br /> 4. SUBMERSIBLE TURBINE PUMPS (STPS).
<br /> A. STP CONDUIT SHALL BE PVC COATED RIGID. STPS SHALL NOT SHARE A CIRCUIT WITH PIC OR POS EQUIPMENT. STP WIRING SHALL NOT
<br /> BE ROUTED THROUGH THE SAME RACEWAY AS THE PIC COMMUNICATION WIRES.
<br /> B. VARIABLE SPEED STP CONTROLLERS (I.E. RED JACKET OR FE PETRO) SHALL BE INSTALLED A MINIMUM OF 3 FT. FROM THE SAME
<br /> MODULE.
<br /> HAZARDOUS LOCATIONS SPECIFICATIONS:
<br /> A. PROVIDE EXPLOSION PROOF JUNCTION BOX AND SEAL OFF FITTINGS PER ARTICLES 514 OF THE CEC FOR HAZARDOUS LOCATIONS.
<br /> B. ALL CONDUIT AND WIRING TO FUEL DISPENSERS AND SUBMERSIBLE PUMPS SHALL BE INSTALLED AND USED IN ACCORDANCE WITH
<br /> FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE NFPA 30 AND APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE CALIFORNIA
<br /> ELECTRICAL CODE (CEC) ARTICLE 514. “MOTOR FUEL DISPENSING FACILITIES,” INCLUDING THE FOLLOWING: PROVIDE EXPLOSION
<br /> PROOF/SEAL-OFF FITTINGS ON ALL POWER SUPPLY LINES LOCATED AT FUEL DISPENSERS, SUBMERSIBLE PUMPS AND ANY OTHER
<br /> ELECTRICAL EQUIPMENT LOCATED IN A 20' RADIUS OF THE GASOLINE FUEL DISPENSER ISLAND. AN AREA PER FIGURE 5143 OF THE CEC
<br /> IS DEFINED AS A HAZARDOUS LOCATION WITHIN A 20' RADIUS FROM THE END OF EACH DISPENSER ALL ELECTRICAL EQUIPMENT AND
<br /> WIRING WITHIN THIS AREA SHALL BE PER CEC 514.
<br /> C. AN APPROVED SEAL (EXPLOSION PROOF/SEAL-OFF FITTING) SHALL BE PROVIDED IN EACH CONDUIT RUN ENTERING OR LEAVING A
<br /> DISPENSER OR ANY CAVITIES OR ENCLOSURES IN DIRECT COMMUNICATION THEREWITH. THE SEALING FITTING SHALL BE THE FIRST
<br /> FITTING AFTER THE CONDUIT EMERGES FROM THE EARTH OR CONCRETE. ADDITIONAL SEAL SHALL BE PROVIDED AT BOUNDARIES IN
<br /> ACCORDANCE WITH CEC SECTION 501.5 (A)(4) AND 501.5(BX2) APPLYING TO BOTH HORIZONTAL AS WELL AS VERTICAL BOUNDARIES
<br /> OF CLASS I LOCATIONS.
<br /> D. PROVIDE EXPLOSION PROOF/SEAL·OFF FITTING AT THE POINT OF CONDUIT STUB-UP ENTRANCE (AT PANEL BOARD) INTO THE SERVICE
<br /> BUILDING FOR ALL POWER SUPPLY CONDUITS TO FUEL DISPENSERS, SUBMERSIBLE PUMPS AND OTHER ELECTRICAL EQUIPMENT
<br /> LOCATED IN THE ABOVE DEFINED HAZARDOUS LOCATIONS.
<br /> E. ALL BELOW GRADE CONDUIT RUNNING THROUGH (ENTERING OR LEAVING - THEN THE ENTIRE CONDUIT RUN SHALL BE RGS) THE
<br /> CLASS I DIVISION 1 HAZARDOUS LOCATION AS DESCRIBED ABOVE AND AS DEFINED PER CEC ARTICLE 514 SHALL BE RGS. RIGID
<br /> NON-METALLIC CONDUIT (PVC) MAY ONLY BE USED AS LONG AS THE PROVISIONS OF CEC ARTICLE 514.8. EXCEPTION NO.2 ARE
<br /> STRICTLY ADHERED TO INCLUDING THE REQUIREMENTS FOR AN EQUIPMENT GROUNDING CONDUCTOR IN THE RIGID NON-METALLIC
<br /> CONDUIT AND THE EQUIPMENT GROUNDING CONDUCTOR MUST BE BONDED TO THE EXPLOSION-PROOF RACEWAY SYSTEM INSIDE
<br /> THE DISPENSER (THIS MAY BE ACCOMPLISHED BY TERMINATING THE EQUIPMENT GROUNDING CONDUCTOR ON THE GROUND
<br /> SCREW PROVIDED IN THE JUNCTION BOX). WHERE RIGID NON-METALLIC CONDUIT IS USED IT SHALL BE USED FOR THE LAST 2 FEET OF
<br /> THE UNDERGROUND RUN TO EMERGENCE OR POINT OF CONNECTION TO THE ABOVE GROUND RACEWAY.
<br /> F. EACH CIRCUIT LEADING TO OR THROUGH A DISPENSING PUMP SHALL BE PROVIDED WITH A SWITCH TO DISCONNECT
<br /> SIMULTANEOUSLY FROM THE SOURCE OF SUPPLY ALL AND CONDUCTORS OF THE CIRCUIT INCLUDING THE GROUNDED CONDUCTOR.
<br /> G. THE METAL PORTION OF DISPENSING PUMPS, METAL RACEWAYS AND ALL NON-CURRENTCARAYING METAL PARTS OF ELECTRIC
<br /> EQUIPMENT, REGARDLESS OF VOLTAGE, SHALL BE GROUNDED AS PROVIDED IN CEC ARTICLE 250.
<br /> ELECTRICAL EQUIPMENT, REGARDLESS OF VOLTAGE, SHALL BE GROUNDED AS PROVIDED IN CEC ARTICLE 250.
<br /> PART 2 - PRODUCTS
<br />2.01 MATERIAL APPROVAL
<br />ALL MATERIALS MUST BE NEW AND BEAR UNDERWRITER'S LABORATORIES LABEL. MATERIALS THAT ARE NOT COVERED BY UL TESTING
<br />STANDARDS SHALL BE TESTED AND APPROVED BY AN INDEPENDENT TESTING LABORATORY OR A GOVERNMENTAL AGENCY. MATERIAL NOT IN
<br />ACCORDANCE WITH THESE SPECIFICATIONS MAY BE REJECTED EITHER BEFORE OR AFTER INSTALLATION.
<br />2.02 CONDUITS AND OTHER RACEWAYS:
<br /> A. ALL POWER CONDUITS TO BE 3/4" PVC COATED.
<br /> B. LOW VOLTAGE CONDUITS TO BE 3/4" PVC WITH PVC COATED RIGID ENDS AS REQUIRED IN HAZARDOUS AREAS UNLESS NOTED
<br />OTHERWISE.
<br /> C. ELECTRICAL METALLIC TUBING (EMT): ELECTRO-GALVANIZED.
<br /> D. WIREWAY: CODE GAUGE STEEL, WITH KNOCKOUTS AND HINGED COVER, CORROSION RESISTANT GRAY BAKED ENAMEL FINISH.
<br /> E. PROVIDE FITTINGS AND ACCESSORIES APPROVED FOR THE PURPOSE EQUAL IN ALL RESPECTS TO THE CONDUIT OR RACEWAY. EMT
<br /> CONNECTORS AND COUPLINGS SHALL BE STEEL SETSCREW TYPE INDOORS AND STEEL COMPRESSION TYPE IN WET LOCATIONS AND
<br /> OUTDOORS.
<br />2.03 WIRES AND CABLES:
<br /> A. FOR POWER AND LIGHTING SYSTEM 600V OR LESS:
<br /> 1. CONDUCTOR: MINIMUM SIZE #12 AWG.
<br /> A. #12 AND #10 AWG SOLID COPPER.
<br /> B. #8 AWG AND LARGER SHALL BE STRANDED COPPER.
<br /> 2. INSULATION TYPE:
<br /> A. #12 TO #1 AWG: THWN FOR WET OR UNDERGROUND AND THHN FOR DRY LOCATIONS.
<br /> B. #1/0 THROUGH #4/0 AWG: XHHW (55 MILS).
<br /> C. #250 MCM AND LARGER: XHHW (65 MILS).
<br /> D. GROUNDING WIRE: TW.
<br /> B. FOR SIGNAL AND COMMUNICATIONS CIRCUIT:
<br /> 1. SPECIAL CABLES SHALL BE AS SPECIFIED ON DRAWINGS.
<br /> 2. CONDUCTORS FOR GENERAL USE SHALL BE STRANDED COPPER CONDUCTOR, #18 AWG MINIMUM, WITH THWN INSULATION FOR
<br /> UNDERGROUND OR WET LOCATIONS AND THHN INSULATION FOR DRY LOCATIONS.
<br /> C. ACCEPTABLE PRODUCTS: GENERAL ELECTRIC. ANACONDA, OKONITE, PARANITE OR TRIANGLE PRODUCTS CONFORMING OR EXCEEDING
<br /> APPLICABLE IPCEA STANDARDS.
<br />2.04 OUTLET BOXES, JUNCTION AND PULL BOXES:
<br /> A. OUTLET BOXES. 4” SQUARE X 1-1/2" DEEP (OR LARGER) GALVANIZED SHEET STEEL KO-TYPE WITH PLASTER RING AND COVER FOR
<br /> GENERAL INTERIOR USE AND CAST METAL TYPE FS OR FD WITH MATCHING SCREW COVERS FOR EXTERIOR AND EXPOSED INTERIOR
<br /> LOCATIONS (GASKETED IN DAMP OR WET LOCATIONS).
<br /> B. JUNCTION BOXES (FLOOR BOX NOT INCLUDED) SHALL BE SAME AS OUTLET BOXES UP TO 42 CU. IN. AND CODE-GAUGE STEEL IN LARGER
<br /> SIZES WITH SURFACE OR FLUSH-TYPE SCREW-MOUNTED TRIMCOVERS, BOTH BOXES AND COVERS INHIBITOR-PRIMED AND POINTED
<br /> INSIDE OUT.
<br /> C. PULL BOXES SHALL BE SAME AS JUNCTION BOXES UNLESS INDICATED OTHERWISE ON THE DRAWINGS, WITH COVERS.
<br /> D. TELEPHONE OUTLET BOXES SHALL BE THE TYPE AND SIZE REQUIRED BY THE SERVING TELEPHONE COMPANY BUT NOT SMALLER THAN
<br /> 4-11/16" SQUARE X 2-1/8” DEEP WITH SINGLE-GONG RING AND SIERRA #S-754N SPLIT PLATE BUSHING.
<br />2.05 WIRING DEVICES AND PLATES:
<br />UNLESS OTHERWISE INDICATED, ALL WIRING DEVICES AND COVER PLATES SHALL BE FURNISHED AND INSTALLED IN COLOR TO MATCH FINISH
<br />SURFACE WHERE IT IS LOCATED ON, IE, DARK BROWN, BEIGE, WHITE OR STAINLESS STEEL.
<br />2.06 CONDUIT HANGERS:
<br />FOR INDIVIDUAL CONDUIT RUNS NOT DIRECTLY FASTENED TO THE STRUCTURE, USE ROD HANGERS MANUFACTURED BY CADDY, UNISTRUT OR
<br />POWERSTRUT. FOR MULTIPLE CONDUIT RUNS, USE UNISTRUT OR POWERSTRUT TRAPEZE TYPE CONDUIT SUPPORT DESIGNED FOR MAXIMUM
<br />REFLECTION NOT GREATER THAN 1/8”.
<br />2.07 WIRE CONNECTORS:
<br />FOR WIRE SIZES #8 AWG AND SMALLER: INSULATED PRESSURE TYPE (WITH LIVE SPRING) RATED 105 DEGREES C, 600V, FOR BUILDING WIRING
<br />AND 1000V IN SIGNS OR FIXTURES, SCOTCHLOK OR IDEAL. FOR WIRE SIZE #6 AWG AND LARGER: T & B OR EQUIVALENT COMPRESSION TYPE
<br />WITH 3M #33+ OR PLYMOUTH "SLIPKNOT GREY" TAPE INSULATION.
<br />2.08 PANEL BOARDS:
<br /> A. CONSTRUCTION: CABINETS SHALL BE OF CODE GAUGE, GALVANIZED STEEL, SURFACE OR FLUSH MOUNTED AS INDICATED. DOORS SHALL
<br /> BE OF COLD-ROLLED STEEL WITH CONCEALED HINGES AND FLUSH CATCH AND LOCK. ALL PANELS SHALL BE KEYED ALIKE. PANELS
<br />LOCATED ADJACENT TO EACH OTHER SHALL HAVE IDENTICALLY SIZED ENCLOSURE AND TRIMS. MINIMUM PANEL WIDTH SHALL BE 20"
<br />FINISH EXPOSED PART WITH ONE COAT OF PRIMER AND ONE COAT OF LIGHT GREY ENAMEL SUITABLE FOR OVERPAINTING IT.
<br /> B. CIRCUIT BREAKERS: SHALL BE QUICK-MAKE, QUICK-BREAK, MOLDED CASE TYPE:
<br /> 1. 120/240 VOLT PANELS. SHALL BE GENERAL ELECTRIC TYPE “Q” LINE. BOLT-ON TYPE, WITH MINIMUM SYMMETRICAL INTERRUPTING
<br /> CAPACITY AS SHOWN.
<br /> 2. PROVIDE MULTI-POLE UNITS WITH COMMON TRIP ELEMENT.
<br /> 3. CIRCUIT BREAKERS USED ON "ON-OFF" CONTROL OF FLUORESCENT LIGHTING (PANEL BOARD SWITCHING) SHALL BE UNDERWRITERS'
<br /> LABORATORIES LISTED AND MARKED "SWD" TO INDICATE THEIR SUITABILITY.
<br /> C. IDENTIFICATION. PROVIDE SCREWED-ON (NO ADHESIVES) BAKELITE OR PHOTO-ETCHED METALLIC NAMEPLATE IDENTIFICATION ON
<br />OUTSIDE OF EACH PANEL SHOWING PANEL DESIGNATION, VOLTAGE AND PHASE IN MINIMUM 1/8" HIGH LETTERS. EACH PANEL SHALL
<br />CONTAIN A METAL-FRAMED CIRCUIT DIRECTORY INSIDE COVER, WITH PLASTIC PROTECTOR.
<br /> D. COMPLETE SHOP DRAWINGS ARE REQUIRED. SEE ARTICLE 1.08.
<br />2.09 MISCELLANEOUS MATERIALS:
<br /> A. SAFETY SWITCHES HEAVY DUTY TYPE, 480V OR 240V, HORSEPOWER RATED FOR MOTORS, FUSED OR NON-FUSED AS REQUIRED. MOUNT
<br />IN ENCLOSURE WITH NEMA RATING AS REQUIRED FOR THE SPECIFIC APPLICATION GENERAL ELECTRIC, SQUARE D OR WESTINGHOUSE.
<br />PART 3 - EXECUTION
<br />3.01 WIRING METHODS:
<br /> A. INSTALL ALL WIRING IN RACEWAY. OR USE MC GABLE WHERE APPROVED BY ALL APPLICABLE CODES AND REGULATIONS. CONDUIT
<br /> SHALL BE RIGID STEEL, IMC OR EMC AS FOLLOWS:
<br /> 1. ABOVE GROUND: USE RIGID STEEL, IMC OR EMT.
<br /> A. WET LOCATIONS: RIGID STEEL OR IMC ONLY.
<br /> B. LOCATIONS SUBJECT TO MECHANICAL INJURY RIGID STEEL OR IMC ONLY.
<br /> C. DRY LOCATIONS AND NOT SUBJECT TO MECHANICAL INJURY: EMT, IMC, OR RIGID STEEL CONDUIT.
<br /> 2. UNDERGROUND: USE RIGID STEEL
<br /> B. USE FLEXIBLE CONDUITS OR MC CABLE IN THE FOLLOWING APPLICATIONS:
<br /> 1. FINAL CONNECTIONS TO MOTOR.
<br /> 2. FINAL CONNECTIONS INTO AND OUT OF THE TRANSFORMER.
<br /> 3. FINAL CONNECTIONS TO VIBRATING EQUIPMENT.
<br /> 4. INTER-CONNECTIONS BETWEEN ALL LIGHT FIXTURES (NOT TO INCLUDE HOMERUN FROM FIXTURE OR DEVICE TO PANEL BOARD,
<br /> WHICH MUST BE RIGID).
<br /> 5. FINAL CONNECTIONS WHERE RIGID CONDUIT IS NOT PRACTICAL.
<br /> 6. IN WALLS (FOR LIGHT SWITCHES AND 120V POWER RECEPTACLES AND HVAC CONTROL EQUIPMENT).
<br /> C. FLEXIBLE METALLIC CONDUIT OR MC CABLE MUST BE THE SAME SIZE AS THE RIGID CONDUIT TO WHICH IT IS CONNECTED.
<br /> D. THE CONNECTION TO OUTDOOR EQUIPMENT MUST BE WEATHERPROOF. I.E. LIQUID TIGHT OR SEAL TIGHT.
<br /> E. MINIMUM SIZE OF CONDUIT SHALL BE 1/2" FOR INDIVIDUAL LIGHTING FIXTURE CONNECTIONS OR TO INDIVIDUAL LIGHT SWITCHES IF
<br /> APPROVED BY ALL APPLICABLE CODES MINIMUM SIZE FOR ALL OTHER LOCATIONS SHALL BE 3/4" IF HVAC CONTROL WIRING IS
<br /> REQUIRED TO BE RUN IN CONDUIT, IT SHALL BE A 3/4" MINIMUM, UNLESS OTHERWISE NOTED ON DRAWINGS. ALL IN/UNDER FLOOR
<br /> CONDUITS SHALL BE 3/4" MINIMUM SIZE.
<br />3.02 INSTALLATION OF CONDUITS:
<br /> A. GENERAL:
<br /> 1. RUN ALL CONDUIT CONCEALED UNLESS OTHERWISE NOTED OR SHOWN.
<br /> 2. RUN ALL CONDUIT PARALLEL TO OR AT RIGHT ANGLES TO CENTER LINES OF COLUMNS AND BEAMS.
<br /> 3. CONDUITS ABOVE CEILINGS SHALL NOT OBSTRUCT REMOVAL OF CEILING TILES, LIGHTING FIXTURES, AIR DIFFUSERS, ETC.
<br /> 4. CONDUITS SHALL NOT CROSS ANY DUCT SHAFT OR AREA DESIGNATED AS FUTURE DUCT SHAFT HORIZONTALLY. CONDUIT RISERS
<br /> WHEN ALLOWED IN DUCT SHAFT MUST BE COORDINATED WITH MECHANICAL WORK TO AVOID ANY CONFLICT.
<br /> B. CONDUIT SUPPORTS:
<br /> 1. SUPPORT CONDUITS WITH UNDERWRITER'S LABORATORIES LISTED STEEL CONDUIT SUPPORTS AT INTERVALS REQUIRED BY THE
<br /> NATIONAL ELECTRIC CODE. WIRES OR SHEET METAL STRIPS ARE NOT ACCEPTABLE FOR CONDUIT SUPPORT. USE CONDUIT HANGERS
<br /> FOR ALL CONDUITS NOT DIRECTLY FASTENED TO STRUCTURES AND FOR ALL MULTIPLE CONDUIT RUNS. DO NOT ATTACH ANY
<br /> CONDUIT TO MECHANICAL DUCTS AND PIPES.
<br /> 2. INDIVIDUAL CONDUITS 1/2" AND 3/4" SIZE FOR LIGHTING MAY BE SUPPORTED FROM CEILING. SUPPORT WIRES WITH CADDY CLIPS
<br /> ONLY IF ACCEPTABLE TO LOCAL CODE. ONLY ONE CONDUIT IS PERMITTED TO BE ATTACHED TO ANY CEILING SUPPORT WIRE. HANG
<br /> SUCH CONDUIT SO AS NOT TO AFFECT LEVEL OF CEILING OR LIFTING TILES.
<br /> 3. AVOID ATTACHING CONDUIT TO FAN PLENUMS. WHEN IT IS NECESSARY TO SUPPORT CONDUIT FROM FAN PLENUM, PROVIDE A
<br /> LENGTH OF FLEXIBLE CONDUIT BETWEEN PORTION ATTACHED FOR FAN PLENUM AND PORTION ATTACHED TO THE BUILDING TO
<br /> MINIMIZE TRANSMISSION OF VIBRATION TO THE BUILDING STRUCTURES.
<br /> C. CONDUIT PENETRATION:
<br /> 1. PENETRATING FIRE RATED FLOOR OR WALL: INSTALL CONDUIT IN CONDUIT SLEEVE OR FRAMED OPENING. SEAL PENETRATION WITH
<br /> FIRE RETARDANT SEALANT SPECIFIED HEREIN.
<br /> 2. PENETRATING ROOF OR EXTERIOR WALL: AVOID PENETRATING ROOF ORA EXTERIOR WALL WHERE POSSIBLE. WHERE PENETRATIONS
<br /> ARE NECESSARY, BUILDING WEATHERPROOF INTEGRITY MUST BE PRESERVED.
<br /> 3. PENETRATING SOUND INSULATED OR AIR PLENUM WALL: INSTALL CONDUIT IN CONDUIT SLEEVE AND SEAL PENETRATION AS
<br /> DETAILED ON THE DRAWINGS.
<br /> 4. PENETRATING NON-FIRE RATED DRY WALL: CONDUIT SLEEVES ARE NOT REQUIRED. PENETRATIONS MUST BE SEALED WITH PLASTER
<br /> PRIOR TO PAINTING. PENETRATIONS MADE AFTER WALL FINISH IS APPLIED MUST BE AS SMALL AS POSSIBLE AND PROVIDED WITH
<br /> ESCUTCHEONS, ONE ON EACH SIDE OF WALL.
<br /> 5. PENETRATING SUSPENDED CEILING: CUT HOLE AS SMALL AS POSSIBLE TO PERMIT CONDUIT PENETRATION. PROVIDE ESCUTCHEON
<br /> FOR EACH CONDUIT BELOW CEILING.
<br />CEC TABLE 514.3 (B)(1) - CLASS II, GROUP D LOCATIONS
<br />LOCATION UNDERGROUND TANK DIVISION EXTEND OF CLASSIFIED LOCATION
<br />FILL OPENING DIV.1 ANY PIT, BOX OR SPACE BELOW GRADE LEVEL. ANY PART OF WHICH IS WITHIN THE DIVISION 1 OR 2 CLASSIFIED
<br />LOCATION.
<br />DIV.2 UP TO 18 IN. ABOVE GRADE LEVEL WITHIN A HORIZONTAL RADIUS OF 10 FT. FROM A
<br />VENT -DISCHARGING UPWARD DIV.1 WITHIN 3 FT OF OPEN END VENT. EXTENDING IN ALL DIRECTIONS
<br />DISPENSING DEVICE DIV.2 SPACE BETWEEN 3 FT. AND 5 FT. OF OPEN END OF VENT, EXTENDING IN ALL DIRECTIONS.
<br />PITS DIV.1 ANY PIT, BOX, OR SPACE BELOW GRADE LEVEL, ANY PART OF WHICH IS WITHIN THE DIVISION 1 OR 2 CLASSIFIED LOCATION.
<br />DISPENSER SPACE CLASSIFICATION INSIDE THE DISPENSER ENCLOSURE IS COVERED IN
<br />"POWER OPERATED DISPENSING DEVISED FOR PETROLEUM PRODUCTS". ANSI/UL 67-1990
<br />DIV.2 WITHIN 18 IN, HORIZONTALLY IN ALL DIRECTIONS EXTENDING TO GRADE FROM (1) THE DISPENSER ENCLOSURE OR (2) THAT
<br />PORTION OF THE DISPENSER ENCLOSURE CONTAINING LIQUID HANDLING COMPONENTS.
<br />OUTDOOR DIV.2 UP TO 18 IN. ABOVE GRADE LEVEL WITHIN 20 FT. HORIZONTALLY OF ANY EDGE OF ENCLOSURE.
<br />REMOTE PUMP-OUTDOOR DIV.1 FROM ANY EDGE OF PUMP.
<br />DIV.2 WITHIN 3 FT. OF ANY EDGE OF PUMP, EXTENDING IN ALL DIRECTIONS. ALSO UP TO 1 BIN. ABOVE
<br />GRADE LEVEL WITHIN 10 FT. HORIZONTALLY FROM ANY EDGE OF PUMP.