Laserfiche WebLink
3. Please provide a detailed load schedule for the backup panel. <br />Please show the conductors, conduit(s), and AFCI breakers <br />required to achieve a code-compliant design. The distance WILL <br />BE greater than 6 feet per the site plan. Adjust conductor sizes <br />for the number of current carrying conductors in a single <br />conduit per CEC 310.15(C)(1). <br />We have added note that AFCI protection will be provided for <br />15A and 20A breakers that are relocated more than 6' from the <br />original breaker source. <br />E8.1 <br />4. The placard needs to be modified. An additional label is fine <br />but the wording on the placard itself needs to be changed. <br />Refer to CEC 705.10. <br />We have added the required wording on the placard. E9.1 <br />5. The backup panel must be rated a minimum of 150A also to <br />reflect the 150A circuit and circuit breaker. CEC 408.36 <br />We are using 125A backup load center because the loads <br />calculations is less than 125A. <br />E7 <br />6. Sheet index number updated on cover page E1 <br /> <br />2352 N Riverside <br />Dr1/23/2025