(N) FRANKLIN WH <br />aGATE X <br />[CRD-PCS NEM] <br />(N) 125A BACKED UP <br /> LOADS PANEL 120/240V <br />NEMA 3R UL LISTED <br />(N) 40A <br /> (N) 30A <br />RELOCATING LOADS <br />TO BACKED UP LOADS PANEL <br />(NO EV OR LOADS OVER 30A) <br />(N) (1) <br />FRANKLIN WH <br />aPOWER X <br />CAPACITY: 13.6kWh <br />CONT. POWER: 5kW <br />PEAK POWER: 10kW <br />FRANKLINWH <br />TECHNOLOGIES <br />CO,.LTD./aPOWER X <br />[240V] [SI1-SB] <br />**IMPORTANT NOTE** <br />SEE INSTALL MANUAL FOR PLACEMENT OF CT's <br />(N) VISIBLE/ <br />LOCKABLE <br />AC DISCONNECT <br />30A AC NON-FUSED <br />240V, NEMA3R <br />EATON <br />DG221URB,240V <br />30A,2P,3R <br />(N) 100A <br />4 <br />4 <br />5 5 <br />JUNCTION BOX <br />NEMA 3R <br />2 <br />1 20A <br />20A <br />DC <br />AC <br />+ - <br />~ ~ <br />DC <br />AC <br />+ - <br />~ ~ <br />DC <br />AC <br />+ - <br />~ ~ <br />DC <br />AC <br />+ - <br />~ ~ <br />DC <br />AC <br />+ - <br />~ ~ <br />DC <br />AC <br />+ - <br />~ ~ <br />BRANCH 1: (12) LONGI <br />LR5-54HABB-400M MODULES W/ <br />ENPHASE IQ8PLUS-72-2-US MICROINVERTERS <br />BRANCH 2: (12) LONGI <br />LR5-54HABB-400M MODULES W/ <br />ENPHASE IQ8PLUS-72-2-US MICROINVERTERS <br />1 <br />ENPHASE Q CABLE TO BE ATTACHED TO <br />RAIL MIN. 3-1/2" ABOVE ROOF SURFACE <br />(N) 125A ENPHASE <br />IQ COMBINER 5C BOX <br />W/ ENPHASE IQ GATEWAY <br />X-IQ-AMI-240-5C <br />120/240V NEMA 3R <br />GATEWAY <br />3 <br />10/15A <br />PER MANUFACTURER'S SPECIFICATIONS, IQ GATEWAY FOR <br />MONITORING IN IQ COMBINER CAN ACCEPT EITHER 10A OR 15A <br />BREAKER. IQ GATEWAY MONITORING BREAKER IN IQ COMBINER <br />SUBJECT TO EQUIPMENT AVAILABILITY BY DISTRIBUTOR <br />METER NUMBER: 222013518729 <br />ROOFTOP CONDUIT SHALL BE A MINUMUM <br />OF 7/8" ABOVE THE ROOF SURFACE <br />(E) GROUNDING <br />ELECTRODE <br />(COPPER) <br />GROUND ROD <br />MAIN (E) 200A <br />(N) 100A <br />M <br />BI-DIRECTIONAL <br />UTILITY METER <br />1PH/240V <br />(E) 200A/200A MAIN <br />SERVICE PANEL <br />240/120V 1-PH, 3-W <br />MAIN BONDING JUMPER <br />TO UTILITY GRID <br />(OVERHEAD) <br />SOLAR BREAKER LOCATED AT <br />THE FURTHEST END OF BUS <br />BAR FROM THE MAIN BREAKER <br />! <br />DO NOT INSTALL ANY <br />ADDITIONAL BREAKERS IN <br />PANEL <br />WARNING <br />IF RELOCATING <br />CIRCUITS MORE THAN <br />6' AFCI PROTECTION <br />REQUIRED <br />ALL LOADS TO BE <br />RELOCATED FROM MSP <br />(EXCEPT 50A A/C LOAD) <br />POINT OF INTERCONNECTION <br />LOAD SIDE 705.12(B)(3)(3) <br />(E) 50A <br />CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS <br />ID CONDUCTOR (CU)CONDUIT CONDUCTORS <br />IN CONDUIT EGC TEMP. CORR. <br />FACTOR <br />CONT. <br />CURRENT <br />MAX. CURRENT <br />(125%)BASE AMP.DERATED <br />AMP. <br />TERM. TEMP. <br />RATING <br />2 #10 THWN-2, in conduit 3/4" EMT 4 & (1)G #8 0.91 SEE CALCS SEE CALCS 40 36.4 90 <br />1 #12 Q CABLE, in open air N/A N/A #10 0.91 SEE CALCS SEE CALCS 30 27.3 90 <br />3 #8 THWN-2, in conduit 3/4" EMT 3 & (1)G #8 0.91 29.04 36.3 55 50.05 90 <br />4 <br />5 <br />#3 THWN-2, in conduit 1" EMT 3 & (1)G #8 0.91 115 104.65 90 <br />#10 THWN-2, in conduit 3/4" EMT 3 & (1)G #8 0.91 20.8 26 40 36.4 90 <br />BRANCH CALCULATIONS <br />BRANCH CIRCUIT DETAILS BRANCH 1 BRANCH 2 <br />INVERTERS PER BRANCH 12 12 <br />CONTINUOUS AC CURRENT 14.52 14.52 <br />MAX AC CURRENT (125%) 18.15 18.15 <br />SYSTEM SUMMARY <br />ARRAY PTC POWER <br />MODULE SPECS <br />LONGI <br />LR5-54HABB-400M <br />PMAX <br />400W <br />PTC <br />376W <br />ISC <br />13.72A <br />IMP <br />12.93A <br />VOC <br />37.05V <br />VMP <br />30.94V <br />TEMP. COEFF. OF VOC <br />-0.265 <br />INVERTER SPECS <br />IQ8PLUS-72-2-US <br />AC VOLTAGE <br />240V <br />GROUND <br />0.97 <br />MAX OCPD <br />20A <br />RATED POWER <br />290W <br />MAX OUTPUT <br />1.21A <br />MAX INPUT <br />20A <br />MAX INPUT <br />60V <br />EFFICIENCY <br />0.97CEC <br />ARRAY STC POWER <br />9600W <br />9024W <br />MAX AC CURRENT <br />MAX AC POWER <br />290W <br />DESIGN <br />TEMPERATURES <br />ASHRAE <br />2% HIGH <br />30°C <br />2°C <br />ASHRAE <br />EXTREME LOW 29.04A <br />AHJ/UTILITY NOTES: <br />INSTALLER NOTES: <br />ENPHASE MICROINVERTERS RSD COMPLIANT PER 690.12 <br />DESIGNER: TAYLOR BICKFORD <br />NEW PV SYSTEM: 9600W DC / 6960W AC <br />Jose Luis Melgoza <br />1902 Monica Ln, Santa Ana, CA 92706 <br />APN: 10104209 <br />DATE: 10/4/2024 TIME: 09:43 AM <br />DRAWING TITLE: <br />DRAWING PAGE: <br />SCALE:DESIGNER SIGNATURE: <br />LINE DIAGRAM & <br />DESIGN TABLES <br />006 LD1 <br />BETTER EARTH ELECTRIC INC. <br />16720 MARQUARDT AVE CERRITOS <br />CERRITOS, CA 90703 <br />PHONE #: (888) 373-9379 <br />LIC #: C10-1024460 <br />JURISDICTION STAMPS <br />This item has been digitally <br />signed and sealed on <br />03/31/26 <br />Oct 10, 2024 <br />1902 W Monica Ln <br />12/2/2024