ELECTRICAL CALCULATIONS FOR PVI-6000-OUTD-US <br />OPERATION VOLTAGE= 8 X 54.7= 437.6 V <br />OPERATING CURRENT= 2 X 5.98= 12.0 A <br />MAX PV VOLTAGE & CURRENT CALC'S FOR PVI-6000-OUTD-US <br />RECORD LOW TEMP.(°C): 2 <br />TEMP.COEFF (V/°CT -0.1766 <br />OPEN CIRCUIT VOLTAGE(Voc): 64.9 <br />MAX PV SYSTEM VOLTAGE (PER NEC 690.7) <br />(-0.1766)x(-(25-(2))x8)+(64.9x8)= 551.7 V <br />MAX PV CONTINUOUS CURRENT PER NEC 690.8(A)(1): <br />1.25 x Isc x # STRINGS <br />1.25 x 6.46 x2= 16.2 A <br />DC CONDUCTOR AMPACITY CALC'S <br /># OF STRINGS PER INVERTER: 2 <br /># OF INVERTERS PER CONDUIT: 2 <br />(FROM ARRAY TO INVERTER) <br />EXPECTED WIRE TEMP. (°C): 53 <br />TEMP CORRECTION PER TABLE 310.16: 0.76 <br /># OF CURRENT CARRYING CONDUCTORS: 4 <br />CIRCUIT FILL CORRECTION PER TABLE 310.15(B)(2)(a): 0.8 <br />CIRCUIT CONDUCTOR SIZE: AWG 10 THWN-2 <br />REQUIRED CIRCUIT CONDUCTOR AMPACITY <br />PER NEC 690.8 (A&B) (FROM PANELS TO INVERTER): <br />1.25 x 1.25 x Isc x# PER STRING <br />1.25 x 1.25 x 6.46 x1= 10.1 A <br />ELECTRICAL CALCULATIONS <br />FOR PVI-5000-OUTD-US (MPPT 1) <br />OPERATION VOLTAGE= 8 X 54.7= 437.6 V <br />OPERATING CURRENT= 1 X 5.98= 6.0 A <br />MAX PV VOLTAGE & CURRENT CALC'S <br />FOR PVI-5000-OUTD-US (MPPT 1) <br />RECORD LOW TEMP.(°C): 2 <br />TEMP.COEFF (V/°C): -0.1766 <br />OPEN CIRCUIT VOLTAGE(Voc): 64.9 <br />MAX PV SYSTEM VOLTAGE (PER NEC 690.7) <br />(-0.1766)x(-(25-(2))x8)+(64.9x8)= 551.1 V <br />MAX PV CONTINUOUS CURRENT PER NEC 690.8(A)(1): <br />1.25xlscx#STRINGS <br />1.25 x 6.46 x8= 8.1 A <br />ELECTRICAL CALCULATIONS <br />FOR PVI-5000-OUTD-US (MPPT 2) <br />OPERATION VOLTAGE= 7 X 54.7= 382.9 V <br />OPERATING CURRENT= 1 X 5.98= 6.0 A <br />MAX PV VOLTAGE & CURRENT CALC'S <br />FOR PVI-5000-OUTD-US (MPPT 2) <br />RECORD LOW TEMP.(°C): 2 <br />TEMP.COEFF (V/°C): -0.1766 <br />OPEN CIRCUIT VOLTAGE(Voc): 64.9 <br />MAX PV SYSTEM VOLTAGE (PER NEC 690.7) <br />(-0.1766)x(-(25-(2»xD+(64.9x7)= 482.7 V <br />MAX PV CONTINUOUS CURRENT PER NEC 690.8(A)(1): <br />1.25 x Isc x # STRINGS <br />1.25 x 6.46 x 1 = 8.1 A <br />DERATED AMPACITY OF CIRCUIT CONDUCTOR <br />PER NEC TABLE 310.16 <br />TEMP. CORR. PER NEC 310.16 x CONDUIT FILL CORR. <br />PER NEC 310.15(B)(2)(a) x CIRCUIT CONDUCTOR AMPACITY - <br />PER NEC TABLE 310.16 *3 0 <br />0.76 x 0.8 x 40 = 24.3A > 10. lA O.K.NJ E <br />S} <br />AC CONDUCTOR AMPACITY CALC'S <br />(FROM INVERTER TO MSP) <br /># OF INVERTER: 2 <br />& r JEXPECTED WIRE TEMP. (°C): 31 0 <br />0 0 <br />TEMP. CORR. PER NEC TABLE 310.16: 0.96 <br />CIRCUIT CONDUCTOR SIZE: AWG 6 THWN-2 <br /># OF CURRENT CARRYING CONDUCTORS: 3 <br />CONDUIT FILL CORR. PER NEC 310.15(B)(2)(a): 1 <br />CIRCUIT CONDUCTOR AMPACITY: 75A <br />18 <br />REQUIRED CIRCUIT CONDUCTOR AMPACITY g <br />PER NEC TABLE 690.8(B):O 6 <br />1.25 x MAX INVERTER OUTPUT CURRENT X # OF INVERTER ..&>g <br />(1.25 x 23) + (1.25 x 28) = 63.8A W $16< <br />DERATED AMPACITY OF CIRCUIT CONDUCTOR b %151 <br />PER NEC TABLE 310.16 661 302:2 <br />TEMP. CORR. PER NEC 310.16 x CONDUIT FILL CORR. :32=3 <br />O- 0-05 <br />PER NEC 310.15(B)(2)(a) x CIRCUIT CONDUCTOR AMPACITY <br />PER NEC TABLE 310.16 <br />TITLE: <br />0.96 xlx75 =72.0A >63.8A O.K. <br />70A PV BREAKER WILL BE PROVIDED CALCULATION <br />BACKFED 120% RULE PER NEC 690 <br />120% x BUS RATING>=MAIN BREAKER + PV BREAKER <br />120% x 225A>=200A+PV BREAKER <br />JOB NO: 20587APV BREAKER <= 70A DATE: 02/25/13 <br />70A<= 70A O.K.REV: 01 <br />PV 4