PV SYSTEMAS INDICATEDJuly 30, 2024BERTA J SIBRIAN1930 S ARTESIA ST,SANTA ANA, CA 92704Clean Energy Solutions Inc.Address:1055 West 7th Street33rd Floor, Los Angeles,CA 90017Phone Number:(800) 994 1134Lic# 998787Class C-10CONTRACTORDesigned By: Intersolar CADwww.intersolarcad.comPV SYSTEM DC SIZE 4.40KWPV SYSTEM AC SIZE 4.07KWE 1.1FROM PV MODULES TO JBOXFROM JBOX TO INVERTER(2)1(1) #6 AWG BARE CU EGC,2 #10 AWG CU EGC,(3)3(1) #10 AWG CU EGC, MAXIMUM INVERTER OUTPUT CURRENT (A) TEMPERATURE FACTOR TEMPERATURE ADJUSTMENT (A)OUTPUT CALCULATIONSPV SYSTEM MAX DC OUTPUTPV SYSTEM MAX AC OUTPUT MAXIMUM POWER (W) PEAK PWR TRACKING VOLTAGE (V) CONSIDER CONTINUOUS COEFFICIENT SHORT CIRCUIT CURRENT (A) ADJUSTED CONDUCTOR AMPACITY (A)1.251.251.250.91(2)(1) Pmax (PTC Rating)1 1/2'' (TEMP - 39 + 22 = 61C)0.58 RACEWAY HEIGHT FROM ROOFADJST. FACTOR (1 thru 3 WIRES)1.0FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS3/4'' EMT TYPE CONDUIT1'' EMT TYPE CONDUITMAIN SERVICE PANEL RATINGBUSBAR RATINGMAIN BREAKERPV BACKFEED BREAKER SIZE120% RULE:MAX ALLOWED FEED40A*/*1.25*1.2511400 38018.1/ /18.10.581.031.2#10 AWG THWN-2WIRE CHARTWIRE CHART *11400 4.40 KW* *11373.70.994.07 KW CONSIDER CONTINUOUS COEFFICIENT CONSIDER CONTINUOUS COEFFICIENT200A200A240A200A ''MB'' + 40A "SOLAR" = 240A ≤ 240A MAXFROM INVERTER TO MAIN SERVICE PANEL CONSIDER CONTINUOUS (A) MAX NUMBER OF MODULES IN STRING11#10 AWG PV-WIREWIRE SIZECALCULATIONS11400LR5-54HABB-400M400 W373.7 W25.0380199.0 %25.0 * 1.25 / 0.9134.4 #8 AWG THWN-2SOLAR EDGE SE6000H-USSN25.0 * 1.2531.31930 S Artesia St11/27/2024