Laserfiche WebLink
JOB NO.251045 <br />SHT 3 OF 6 <br />DATE 10/30/2025 <br />FOR Fan - Red Bull DES. BY AP <br />DESCRIPTION Fan Installation <br />Design Loads <br />Structure Gravity Loads: <br />Fan Self Weight =253 lb (Max - Including any Accessories) <br />Fan Impact Load (per CBC 1607.11.2) =51 lb (Max - Including any Accessories) <br />Roof Dead Load =12 psf (Min - Conservative for 5% Check) <br />Roof Live Load =20 psf (Min - Conservative for 5% Check) <br />Existing Structure and New Fan <br />NOTES <br />2. Distance between beam supporting fan and adjacent, parallel beam on each side is at least 20 feet. <br />4. Do not attach more than 1 fan to the same existing steel beam (including existing fans). <br />5. Length of extension tube is no more than 2'-0". Tube weight does not exceed 4.4 lbs per foot of length. <br />Contact structural engineer if any of these assumptions is not satisfied. <br />3. Contractor shall verify that no additional load is being supported by beam of interest, which was not <br />considered in the original design, including fans already installed. <br />1. Unsupported beam length between supports (i.e. two girders, two walls or one girder and one wall) is at <br />least 60 feet. <br />Fan installation See <br />Page 4 <br />Existing Steel Beam <br />Fan by supplier <br />(4) Guy Wires by Fan supplier, <br />wrap guy wires around <br />adjacent parallel beams on <br />each side ((2) wires per side)