1. CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE INCLUSIVE OF CITY OF SANTA ANA AMENDMENTS, PERTINENT
<br />NFPA CODES AS WELL AS ALL RULES AND REGULATIONS OF LOCAL, STATE AND, FEDERAL AUTHORITIES HAVING JURISDICTION.
<br />2. THE DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE MAIN CONTRACT CONDITIONS, ELECTRICAL SPECIFICATIONS (DIVISION 26), THE MECHANICAL, PLUMBING
<br />AND FIRE PROTECTION DRAWINGS, THE ARCHITECTURAL DRAWINGS, THE STRUCTURAL ENGINEER'S DRAWINGS, THE TELECOMMUNICATIONS, AUDIO VISUAL AND
<br />SECURITY DRAWINGS (DIVISION 27 AND 28).
<br />3. CONTRACTOR SHALL EXECUTE THE WORK IN THE BEST AND MOST THOROUGH MANNER & TO THE SATISFACTION OF THE CONSULTING ENGINEER, WHO WILL
<br />INTERPRET THE MEANING OF THE DRAWINGS AND SPECIFICATIONS AND SHALL HAVE THE POWER TO REJECT ANY WORK AND MATERIALS WHICH, IN THEIR
<br />JUDGMENT, ARE NOT IN FULL ACCORDANCE THEREWITH.
<br />4. THE DRAWINGS SHOW THE VARIOUS CONDUIT AND PIPING SYSTEMS SCHEMATICALLY. CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY JUNCTION
<br />BOXES, PULL BOXES, SUPPORT AND ACCESSORIES TO MEET APPLICABLE CODES, BUILDING STANDARDS AND FULFILL CONTRACT DOCUMENTS. NO ADDED
<br />COMPENSATION WILL BE PERMITTED FOR VARIATIONS DUE TO FIELD CONDITIONS.
<br />5. DO NOT SCALE FROM THE DRAWINGS, IF IN DOUBT, REQUEST FURTHER INFORMATION.
<br />6. REFER TO THE ARCHITECTURAL DRAWINGS FOR SETTING OUT AND MOUNTING HEIGHT DETAILS OF ALL DEVICES, SWITCHES, ETC.
<br />7. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR THE SETTING OUT OF ALL CEILING MOUNTED COMPONENTS.
<br />8. ALL AREAS ASSOCIATED WITH WORK TO BE PERFORMED SHALL BE EXAMINED PRIOR TO BID SUBMISSION. NO ADDITIONAL COMPENSATION SHALL BE MADE FOR
<br />CONDITIONS FOUND DURING INSTALLATION.
<br />9. CONTRACTOR SHALL INCLUDE ALL LABOR, MATERIALS, AND APPURTENANCES REQUIRED FOR THE INSTALLATION AND TESTING OF ALL EQUIPMENT AND APPLIANCES
<br />INDICATED IN THESE DOCUMENTS. CONTRACTOR SHALL COMPLETE ALL WORK AND VERIFY THE OPERATION OF ALL EQUIPMENT IN A MANNER SATISFACTORY TO
<br />THE ARCHITECT AND ELECTRICAL CONSULTING ENGINEER.
<br />10. WHERE CONDUIT, CABLE, CABLE TRAY OR OTHER ELECTRICAL EQUIPMENT SUCH AS CUTOUT BOXES, LUMINARIES OR PANELBOARDS, PENETRATE RATED
<br />ASSEMBLIES, FIRE BARRIERS, FIRE WALLS, FIRE PARTITIONS, SMOKE BARRIERS, OR SMOKE PARTITIONS, THE ELECTRICAL CONTRACTOR SHALL PROVIDE AN
<br />APPROPRIATE FIRE OR SMOKE STOPPING SYSTEM THAT IS LISTED BY UNDERWRITERS LABORATORIES OR COMPLIES WITH THE APPROPRIATE ICC EVALUATION
<br />REPORT AND DOES NOT REDUCE THE RATING OF THE ASSEMBLY. ALL THROUGH AND MEMBRANE PENETRATIONS SHALL BE SUBMITTED TO THE ARCHITECT OF
<br />RECORD FOR APPROVAL PRIOR TO INSTALLATION. ALL ACCESS PANELS SHALL BE APPROVED AND LISTED FOR THE ASSEMBLY IN WHICH THEY ARE BEING
<br />INSTALLED. COMPLY WITH ALL REQUIREMENTS OF DIVISION 26 SPECIFICATIONS. SEE ARCHITECTURAL DRAWINGS FOR RATINGS OF ALL ASSEMBLIES. CONTRACTOR
<br />SHALL COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR PRIOR TO INSTALLATION.
<br />11. CONDUIT RUNS INDICATED ON PLAN ARE FOR REFERENCE ONLY. EXACT LOCATIONS AND ELEVATIONS SHALL BE DETERMINED AFTER COORDINATING WITH OTHER
<br />TRADES AND THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL SUPPLY, AS PART OF THEIR SHOP DRAWING SUBMISSION, THE EXACT LOCATION OF ALL
<br />CEILING MOUNTED EQUIPMENT AND CONDUIT RUNS, INCLUDING THE PROPOSED LOCATIONS AND THE MEANS OF SUPPORT. PROVIDE THE ARCHITECT AND
<br />STRUCTURAL ENGINEER THE ANTICIPATED LOAD AT THE POINTS OF ATTACHMENT PRIOR TO COMMENCEMENT OF WORK.
<br />12. CONTRACTOR SHALL VERIFY THE ELECTRICAL REQUIREMENTS OF ALL NEW EQUIPMENT TO BE USED. ALL SPECIAL PURPOSE OUTLETS INDICATED ON PLAN SHALL
<br />BE VERIFIED WITH THE EQUIPMENT MANUFACTURER AND OWNER PRIOR TO INSTALLATION. THE ELECTRICAL CONTRACTOR SHALL ENSURE PROPER WIRING AND
<br />COMPATIBILITY WITH ATTACHMENT PLUGS OR JUNCTION BOXES THAT MAY BE FURNISHED AS AN INTEGRAL PART OF THE EQUIPMENT.
<br />13. ALL RECEPTACLES SHALL BE ACCESSIBLE. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF EQUIPMENT RECEPTACLES WITH THE EQUIPMENT
<br />MANUFACTURER'S REQUIREMENTS, THE OWNER, AND THE AUTHORITY HAVING JURISDICTION.
<br />14. CONTRACTOR SHALL PROVIDE DISCONNECTS FOR ALL EQUIPMENT AS REQUIRED BY THESE DOCUMENTS AND THE ADOPTED CODES. COORDINATE ALL
<br />REQUIREMENTS AND LOCATIONS WITH THE AUTHORITY HAVING JURISDICTION, THE VENDORS APPROVED SHOP DRAWINGS AND FINAL EQUIPMENT LOCATIONS.
<br />15. CONTRACTOR SHALL COORDINATE ALL LOCATIONS AND HEIGHTS OF STUB-UPS AND STUB-OUTS AS WELL AS ALL OUTLETS IN FIELD.
<br />16. FINAL CONNECTIONS TO EQUIPMENT SHALL BE MADE ACCORDING TO VENDOR'S APPROVED SHOP DRAWINGS AND THE LISTING OF THE EQUIPMENT.
<br />17. ALL WORK AND/OR EQUIPMENT INSTALLED OUTDOORS SHALL BE APPROVED FOR USE IN WET LOCATIONS.
<br />18. ALL PARTS OF THE WORK AND ASSOCIATED EQUIPMENT SHALL BE TESTED AND ADJUSTED TO WORK PROPERLY AND BE IN PERFECT OPERATING CONDITION. THIS
<br />SHALL INCLUDE MEG-OHM TESTING BETWEEN PHASES, BETWEEN EACH PHASE AND THE GROUNDED CONDUCTOR, AND EACH PHASE AND THE EQUIPMENT GROUND
<br />FOR ALL FEEDERS, TAPS, SECONDARY CONDUCTORS , SWITCHBOARDS AND PANELBOARDS. FURNISH ALL TEST RESULTS TO THE ELECTRICAL CONSULTING
<br />ENGINEER FOR REVIEW PRIOR TO ENERGIZING EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL CORRECT ANY DEFECTS IDENTIFIED THOUGH THIS TESTING.
<br />19. PROVIDE ISOLATED GROUND TYPE OUTLETS WHERE THE "IG" SUBSCRIPT IS INDICATED.
<br />20. WALL-MOUNTED OUTLETS, SWITCHES, AND CONTROL DEVICES, SHOULD BE MOUNTED AT THE HEIGHTS INDICATED IN THESE DOCUMENTS. THE ELECTRICAL
<br />CONTRACTOR SHALL VERIFY AND FULLY COMPLY WITH, ALL AMERICANS WITH DISABILITIES REQUIREMENTS AND MEET ALL REQUIREMENTS ESTABLISHED BY THE
<br />HOUSING AND URBAN DEVELOPMENT (HUD) STANDARDS AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION.
<br />21. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A CITY OF SANTA ANA RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE CITY OF SANTA
<br />ANA, DEPARTMENT OF BUILDING AND SAFETY.
<br />22. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE MANDATED BY THE
<br />CALIFORNIA ELECTRICAL CODE ABOVE OR BELOW ELECTRICAL EQUIPMENT.
<br />23. ADEQUATE CLEARANCE AROUND AND ABOVE ELECTRICAL EQUIPMENT SHALL BE MAINTAINED PER CALIFORNIA ELECTRICAL CODE SECTION 110.26.
<br />24. ALL GROUNDING ELECTRODES THAT ARE PRESENT AT EACH BUILDING AND STRUCTURE, INCLUDING THE PHOTOVOLTAIC SYSTEM, SHALL BE BONDED TOGETHER.
<br />25. ALL WORK TO COMPLY WITH 2022 C.E.C. AND 2022 ENERGY EFFICIENCY STANDARDS.
<br />26. EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNDERGROUND CONDUCTORS AT THE POINT
<br />OF DISTRIBUTION PER C.E.C. 210.4 [B].
<br />27. G.F.C.I. PROTECTION REQUIRED FOR APPLIANCES IN DEDICATED SPACES AND RECEPTACLES NOT READILY ACCESSIBLE PER C.E.C. 210.8 [A].
<br />28. G.F.C.I. PROTECTION IS REQUIRED FOR ALL 125 VOLT, SINGLE PHASE 15 AND 20 AMP RECEPTACLES INSTALLED IN BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS
<br />AND WITHIN 6-FEET OF SINKS AS PER C.E.C. 210.8 [B].
<br />29. 125V, 15 AND 20 AMP RECEPTACLES ARE REQUIRED, PER C.E.C. 406.12, TO BE LISTED AS TAMPER RESISTANT.
<br />30. PROVIDE CARBON MONOXIDE ALARMS IN DWELLING UNITS WHERE FUEL BURNING APPLIANCES ARE INSTALLED AND/OR IN DWELLING UNITS WITH ATTACHED
<br />GARAGES PER C.R.C. R315.2.
<br />31. PROVIDE "ARC-FLASH" LABELING ON SWITCHBOARDS, DISTRIBUTION BOARDS AND PANELBOARDS.
<br />32. ALL NEWLY CONSTRUCTED MULTITENANT BUILDING ARE REQUIRED TO COMPLY WITH THE PHOTOVOLTAIC REQUIREMENTS IN CEnC 140.10(A) IF THE UTILITY
<br />PROVIDES EITHER A VIRTUAL NET METERING (VNEM) OR COMMUNITY SOLAR PROGRAM. THE ELECTRICAL CONTRACTOR AND EQUIPMENT MANUFACTURER SHALL
<br />PROVIDE PROVISIONS FOR THE CONNECTION OF CONDUCTORS TO THE EQUIPMENT TO COMPLY WITH THE LISTING OF THE EQUIPMENT AND THE CALIFORNIA
<br />ELECTRICAL CODE.
<br />33. UPON COMPLETION OF THIS PROJECT, PROVIDE THE PROJECT OWNER WITH AN APPROVED COPY OF THE CERTIFICATE OF OCCUPANCY AND OR A COPY OF THE
<br />FINAL APPROVAL OF THE ELECTRICAL SYSTEM.
<br />GENERAL NOTES
<br />1. ALL CONDUIT AND CABLE "HOME RUNS" SHALL CONSIST OF A SINGLE CIRCUIT PER CONDUIT FOR THREE PHASE CIRCUITS, AND SINGLE PHASE CIRCUITS SERVED BY
<br />AN OVERCURRENT PROTECTIVE DEVICE (OCPD) IN EXCESS OF 20 AMPERES SINGLE POLE.
<br />2. WHERE WIRE AND CONDUIT BRANCH CIRCUITS SHARE A CONDUIT HOME RUN, (OCPD LESS THAN OR EQUAL TO 20 AMPERES SINGLE POLE) THERE SHALL BE A
<br />MAXIMUM OF THREE CIRCUITS COMBINED IN A SINGLE RACEWAY TO THE PANELBOARD, UNLESS OTHERWISE NOTED. ALL CONDUCTORS SHALL BE DE-RATED PER
<br />CALIFORNIA ELECTRICAL CODE. COMBINING OF MULTIPLE HOME RUNS (MORE THAN THREE) IN A SINGLE CONDUIT IS NOT PERMITTED. WITH THE EXCEPTION OF
<br />FURNITURE FEED TYPE WIRING SYSTEMS THE SHARING OF NEUTRALS AND GROUNDING CONDUCTORS BETWEEN CIRCUITS IS NOT PERMITTED.
<br />3. CONTRACTOR SHALL VERIFY PHASE LOAD BALANCING ON POWER PANELS UPON COMPLETION OF THE ELECTRICAL INSTALLATION. INCLUDE RE-DISTRIBUTION OF
<br />CIRCUITS WITHIN PANELS TO BALANCE WITHIN A 10% WINDOW (±5%).
<br />4. UNLESS OTHERWISE NOTED ALL BRANCH CIRCUITS SHALL BE 20-AMPERE DEDICATED CIRCUITS WITH 3/4"C, #12, #12N, #12G MINIMUM.
<br />5. ALL CIRCUITS TO HAVE BOTH CONDUCTORS AND GROUND WIRE HOME RUN TO SERVICE PANEL.
<br />6. ALL FEEDER AND BRANCH CIRCUIT WIRING SHALL BE A MINIMUM SIZE OF AWG #12. METAL CLAD (MC) CABLING IS PERMITTED
<br />7. RIGID STEEL CONDUITS:
<br />7.1. USE FOR ALL SIZES WHERE DIRECTLY EXPOSED TO WEATHER; WHERE SUBJECT TO ABNORMAL CONDITIONS OF HEAT, COLD, MOISTURE, HUMIDITY, FUMES AND
<br />HAZARDOUS ELEMENTS; WHERE INSTALLED EXPOSED BELOW 7-1/2', IN AREAS WHERE SUBJECT TO MECHANICAL INJURY. USE FOR ALL CONDUIT IN ALL
<br />ELECTRICAL AND MECHANICAL EQUIPMENT ROOMS; FOR LOW VOLTAGE (UP TO 600 VOLTS) FEEDERS INSIDE OF BUILDING AND IN CONCRETE SLABS ON GRADE.
<br />7.2. FOR ALL BENDS IN CONDUITS 3” AND LARGER, AND OVER 50' IN LENGHT, USE LARGE RADIUS FACTORY MADE BENDS OR FIELD FABRICATE WITH A POWER
<br />BENDER.
<br />8. ELECTRICAL METALLIC TUBING (EMT)
<br />8.1. PERMITTED TO BE USED IN WET LOCATIONS WITH APPROVED FITTINGS.
<br />8.2. CONDUITS SHALL BE CONTINUOUS. CONDUCTORS SHALL NOT BE INSTALLED UNTIL THE RACEWAY SYSTEM IS COMPLETE.
<br />9. RIGID PLASTIC CONDUITS:
<br />9.1. ALL CONDUITS INSTALLED UNDERGROUND, OR ENCASED IN CONCRETE, SHALL BE SCHEDULE 40 PVC CONDUIT.
<br />9.2. MAKE ALL FITTINGS IN PLASTIC CONDUITS WATERTIGHT WITH APPROVED SOLVENT-WELD CEMENT SPECIFICALLY MANUFACTURED FOR THE PURPOSE. APPLY
<br />HEAT FOR BENDS SO THAT CONDUIT DOES NOT DISTORT OR DISCOLOR.
<br />10. PVC JACKETED STEEL CONDUITS:
<br />10.1. USE FOR ALL SIZES IN SOIL BELOW THE BUILDING.
<br />10.2. FOR ALL BENDS IN CONDUITS 1-1/4” AND LARGER, USE LARGE RADIUS FACTORY MADE BENDS OR FIELD FABRICATE WITH A POWER BENDER.
<br />CONDUIT AND CIRCUIT WIRING NOTES
<br />EQUIPMENT CALLOUT
<br />a. EQUIPMENT DESIGNATION
<br />b. EQUIPMENT LOADING IN KVA OR HP
<br />c. EQUIPMENT UTILIZATION VOLTAGE
<br />d. NUMBER OF POLES
<br />e. NUMBER OF WIRES
<br />f. RELEVANT NOTES
<br />a.
<br />b. KVA c. V d. P e. W
<br />f.
<br />(--A) - DENOTES CONTINUOUS CURRENT RATING IN AMPS
<br />(--P) - DENOTES NUMBER OF SWITCHED POLES
<br />HARD WIRED CONNECTION TO FIXED EQUIPMENT OR PACKAGED UNIT
<br />(NON-MOTOR)
<br />HARD WIRED CONNECTION TO MOTORIZED EQUIPMENT
<br />(MOTOR / FAN / PUMP / FAN COIL UNIT)
<br />UL LISTED DISCONNECT (UNFUSED):
<br />APPROVED FOR MOTOR USE AS APPLICABLE
<br />MATCH VOLTAGE AND POLES TO EQUIPMENT
<br />30A, 2 POLES, NEMA 1 U.O.N.
<br />UL LISTED DISCONNECT (FUSED):
<br />APPROVED FOR MOTOR USE AS APPLICABLE
<br />--AS - DENOTES SWITCH RATING IN AMPS
<br />--AF - DENOTES FUSE SIZE IN AMPS
<br />MATCH VOLTAGE AND POLES TO EQUIPMENT. NEMA 1 U.O.N
<br />PRE-WIRED UL LISTED MOTOR CONTROLLER (FURNISHED BY DIV 21, 22
<br />AND 23 U.O.N) COMPLETE WITH INTEGRAL OVERLOAD PROTECTIVE
<br />DEVICE.
<br />3R INDICATES NEMA SIZE, NEMA 1 U.O.N.
<br />PRE-WIRED CONTROL PANEL (FURNISHED BY DIV 21, 22 AND 23 U.O.N.)
<br />COMPLETE WITH INTEGRAL DISCONNECT AND OVERLOAD PROTECTIVE
<br />DEVICES. 3R INDICATES NEMA SIZE, NEMA 1 U.O.N.
<br />UL LISTED VARIABLE FREQUENCY DRIVE (FURNISHED BY DIV 21, 22 AND
<br />23 U.O.N.) COMPLETE WITH INTEGRAL DISCONNECT AND OVERLOAD
<br />PROTECTIVE DEVICES. 3R INDICATES NEMA SIZE, NEMA 1 U.O.N.
<br />HARD WIRED CONNECTION TO FIXED EQUIPMENT OR PACKAGED UNIT
<br />(NON-MOTOR) WITH TOGGLE SWITCH
<br />SINGLE PHASE MANUAL STARTER WITH OVERLOAD PROTECTION FOR
<br />FRACTIONAL HORSEPOWER MOTORS
<br />CIRCUIT BREAKER IN NEMA TYPE 1 ENCLOSURE:
<br />--A - DENOTES TRIP SETTING
<br />--P - DENOTES POLES
<br />PANELBOARD
<br />L - DENOTES LIGHTING AND MISCELLANEOUS 277V LOADS
<br />P - DENOTES POWER AND 120/208V LOADS
<br />Q - DENOTES EQUIPMENT AND/OR EXTERNAL SUPPLIES
<br />DRY TYPE ENERGY EFFICIENT TRANSFORMER PER SPECIFICATION:
<br />30kVA AND LARGER SHALL BE FLOOR STANDING U.O.N.
<br />115°C TEMPERATURE RISE U.O.N. AS 80°C ON SHEET E6.1
<br />VOLTAGES AND kVA RATING - AS PER SHEET E6.1
<br />K-RATING - STANDARD U.O.N. ON SHEET E6.1
<br />EQUIPMENT POWER
<br />--A
<br />--P
<br />30A
<br />2P
<br />30AS
<br />30AF
<br />3R
<br />3R
<br />VFD 3R
<br />S
<br />--A
<br />--P CB
<br />L-1A
<br />P-1A
<br />Q-1A
<br />AMP METER
<br />VOLT METER
<br />2P, 3W, AUTOMATIC TRANSFER SWITCH - #A DENOTES RATING
<br />PULL BOX SIZE PER CEC
<br />GROUND FAULT TRIP UNIT
<br />TRANSFORMER WITH SECONDARY GROUND
<br />(SEE TRANSFORMER SCHEDULE)
<br />SWITCH AND FUSE UNIT:
<br /> --AS - DENOTES SWITCH RATING IN AMPS
<br /> --AF - DENOTES FUSE SIZE IN AMPS
<br />MOLDED CASE CIRCUIT BREAKER (MCCB):
<br /> --A - DENOTES TRIP SETTING IN AMPS
<br /> --P - DENOTES NUMBER OF POLES
<br /> - DENOTES SHUNT TRIP
<br />AIR INSULATED CIRCUIT BREAKER
<br /> --AT - DENOTES TRIP SETTING IN AMPS
<br /> --AF - DENOTES FRAME SIZE
<br />(L)ONG TIME DELAY - OVERLOAD PROTECTION
<br />(S)HORT TIME DELAY - SHORT CIRCUIT WITH DELAYED TRIP
<br />(I)NSTANTANEOUS TRIP - SHORT CIRCUIT PROTECTION
<br />(G)ROUND FAULT PROTECTION
<br />GROUNDING RODS TO ACHIEVE A MAXIMUM IMPEDANCE OF 5@ TO
<br />GROUND PER SPECIFICATION 260526. RODS TO BE SPACED A MINIMUM
<br />OF 10' APART. QUANTITY AS REQUIRED TO ACHIEVE IMPEDANCE.
<br />SINGLE LINE DIAGRAM
<br />A
<br />V
<br />#AATS
<br />PB
<br />G
<br />--AS
<br />--AF
<br />CLASS 2000 DIGITAL kWH AND kW/DEMAND METER HOUSED IN
<br />MULTIPLE METER UNIT. REFER TO SPECIFICATION 262713 FOR
<br />FURTHER DETAILS
<br />--A
<br />--P
<br />MCCB
<br />ST
<br />ST
<br />--AT
<br />--AF
<br />L
<br />S
<br />I
<br />G
<br />SOLID
<br />STATE
<br />TRIP
<br />M
<br />20A, 125V, DUPLEX RECEPTACLE, NEMA 5-20R
<br />WIRING DEVICES
<br />20A, 125V, DUPLEX RECEPTACLE, WITH GROUND FAULT CIRCUIT
<br />INTERRUPTER, NEMA 5-20R.
<br />20A, 125V, ABOVE COUNTERTOP MOUNTED DUPLEX RECEPTACLE,
<br />NEMA 5-20R
<br />20A, 125V, ABOVE COUNTERTOP MOUNTED, DUPLEX RECEPTACLE,
<br />WITH GROUND FAULT CIRCUIT INTERRUPTER, NEMA 5-20R
<br />WALL / CEILING MOUNTED JUNCTION BOX. PROVIDE EXTENSION WHEN
<br />USED FOR FLEX CONNECTION. VERIFY LOCATION AND MOUNTING
<br />HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION.
<br />WEATHERPROOF WHEN INSTALLED OUTSIDE. PROVIDE DISCONNECT
<br />SWITCH WHERE INDICATED OR REQUIRED BY CODE.
<br />20 A 125V CONTROLLED DUPLEX RECEPTACLE
<br />20 A 125V CONTROLLED QUAD RECEPTACLE
<br />30A, 125V, 1Ø, 2P, 3W TWIST-LOCK RECEPTACLE.
<br />NEMA L5-30R
<br />30A, 250V, 1Ø, 2P, 3W TWIST-LOCK RECEPTACLE.
<br />NEMA L6-30R
<br />J
<br />2020 NEC
<br />2022 CEC
<br />2022 TITLE 24 PART 6
<br />RELEVANT CODE CYCLES
<br />DESCRIPTION
<br />KEYNOTE IDENTIFIER
<br />X - KEYNOTE NUMBER
<br />GENERAL SYMBOLS
<br />REVISION CHANGE
<br />X - DELTA NUMBER
<br />SYMBOL
<br />DETAIL/ENLARGED PLAN CALLOUT
<br />X - DETAIL/REFERENCE#
<br />EXXX - SHEET #
<br />SECTION IDENTIFIER
<br />X - SECTION #
<br />EXXX - SHEET #
<br />CABLE AND CONDUIT
<br />WHERE NO WIRE SIZE SHOWN, DEFAULT CIRCUIT HOMERUN
<br />INDICATES PANEL ORIGIN AND CIRCUIT NUMBER WITH:
<br />•3/4" CONDUIT, (1) #12 HOT PER CIRCUIT, (1) #12 NEUTRAL PER
<br />CIRCUIT AND (1) #12 GROUND PER CIRCUIT.
<br />•PROVIDE ADDITIONAL (1) #12 ISOLATED GROUND FOR DEVICES
<br />INDICATED WITH "IG"
<br />DESIGNATED CIRCUIT HOMERUN INDICATES PANEL ORIGIN, CIRCUIT
<br />NUMBER AND CONDUIT AND WIRING SIZES. REFER TO PANEL
<br />SCHEDULES AS WELL
<br />SHORT RADIUS ELBOW TURN-UP WITH INSIDE THREAD AND PLUG
<br />FLUSH WITH FLOOR. PROVIDE EXTENSION UP TO CAST JUNCTION
<br />BOX 6" A.F.F. U.O.N. ARROWS DENOTES CONNECTION TO
<br />DESIGNATION EQUIPMENT
<br />WIRING IN CONDUIT CONCEALED IN CEILING OR WALL.
<br />WIRING IN CONDUIT CONCEALED UNDER FLOOR OR UNDERGROUND
<br />CONDUIT TURNING UP
<br />CONDUIT TURNING DOWN
<br />CONDUIT STUB WITH WIRE PULL AND CAP
<br />CABLE SUPPORT BOX
<br />TELECOM CABLE TRAY, 8" WIDE X 2" DEEP, UON. COORDINATE
<br />LOCATION WITH DUCTWORK, PLUMBING, FIRE PROTECTION,
<br />ELECTRICAL, AND LIGHT FIXTURES.
<br />WALL MOUNTED MULTI-SERVICE ALUMINUM RACEWAY COMPLETE
<br />WITH RECEPTACLES AND OUTLETS AS INDICATED ON THE PLANS.
<br />MOUNTED AT 42" AFFL TO BOTTOM OF RACEWAY, ANODIZED SATIN
<br />FINISH. AS PER LEGRAND DS4000 OR APPROVED EQUAL.
<br />FURNISH SAMPLE FOR ARCHITECT APPROVAL PRIOR TO ORDERING
<br />X
<br />X
<br />X
<br />EXXX
<br />X
<br />EXXX
<br />NEUTRAL
<br />HOT
<br />GROUND
<br />P5C1-2
<br />P5C1-7
<br />3/4"C,1#8,#8N,#10G
<br />J
<br />CSB
<br />TELECOM SYMBOLS
<br />MULTI-SERVICE 6-GANG FLOOR BOX WITH (2) DUPLEX RECEPTACLES,
<br />20A (REFER TO WIRING DEVICES SYMBOLS) (1) GANG DATA, (1) GANG
<br />SPARE. INSTALL WITH FLOOR FINISH INSERT.
<br />AS LEGRAND EVOLUTION EFB6 SERIES OR APPROVED EQUAL
<br />RJ45 DATA OUTLET ('x' DENOTES NUMBER OF GANGS)
<br />TELEPHONE OUTLET
<br />COMBO DATA/TELEPHONE OUTLET
<br />'X'
<br />FIRE ALARM
<br />SMOKE DETECTOR
<br />CARBON MONOXIDE DETECTOR
<br />COMBO SMOKE / CARBON MONOXIDE DETECTOR
<br />SD
<br />CM
<br />SCM
<br />ABBREVIATIONS
<br />A AMPERES
<br />AC AIR CONDITIONER
<br />AERS ARC ENERGY REDUCTION SWITCH
<br />AFFL ABOVE FINISHED FLOOR LEVEL
<br />AFI ARC FAULT INTERRUPTION
<br />AHU AIR HANDLER UNIT
<br />AIC AMPERE INTERRUPTING CAPACITY RATING
<br />ATS AUTOMATIC TRANSFER SWITCH
<br />AWG AMERICAN WIRE GAUGE
<br />BFG BELOW FINISH GRADE
<br />C CONDUIT
<br />CATV CABLE ANTENNA TELEVISION SYSTEM
<br />CB CIRCUIT BREAKER
<br />CCTV CLOSED CIRCUIT TELEVISION
<br />CEC CALIFORNIA ELECTRICAL CODE
<br />CEnC CALIFORNIA ENERGY CODE
<br />CKT CIRCUIT
<br />CO CARBON MONOXIDE SENSOR
<br />C.O. CONDUIT ONLY
<br />CPT CONTROL POWER TRANSFORMER
<br />(E)EXISTING
<br />EF EXHAUST FAN
<br />EL ELEVATOR
<br />E.C. ELECTRICAL CONTRACTOR
<br />E, EM EMERGENCY
<br />EMT ELECTRICAL METALLIC TUBING
<br />FA FIRE ALARM
<br />FACP FIRE ALARM CONTROL PANEL
<br />FRA FIRE RISK ASSESSMENT
<br />FBO FURNISHED BY OTHERS
<br />FIBO FURNISHED AND INSTALLED BY OTHERS
<br />FCU FAN COIL UNIT
<br />FL FLOOR
<br />FLA FULL LOAD AMPERES
<br />FSD FIRE SMOKE DAMPER
<br />G.C. GENERAL CONTRACTOR
<br />GRD GROUND
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />HP HORSE POWER
<br />IG INSULATED GROUND
<br />INT ADDRESSABLE FIRE ALARM RELAY MODULE
<br />JB JUNCTION BOX
<br />kcmil THOUSAND CIRCULAR MILS
<br />kVA KILOVOLT AMPERES
<br />kW KILOWATT
<br />KX KITCHEN EXHAUST
<br />LBS LOAD BREAK SWITCH
<br />LSIG LONG-TIME, SHORT-TIME, INSTANTANEOUS,
<br />GROUND FAULT PROTECTION
<br />LTG LIGHTING
<br />LV LOW VOLTAGE
<br />LVR LOW VOLTAGE RELAY
<br />MGB MAIN GROUNDING BAR
<br />MCB MAIN CIRCUIT BREAKER
<br />MCC MOTOR CONTROL CENTER
<br />MCCB MOLDED CASE CIRCUIT BREAKER
<br />MCP MOTOR CONTROL PANEL
<br />M.C. MECHANICAL CONTRACTOR
<br />MD MOTORIZED DAMPER
<br />MGB MAIN GROUND BAR
<br />MIN MINIMUM
<br />MLO MAIN LUGS ONLY
<br />MMS MAINTENANCE MODE SWITCH
<br />MSB MAIN SWITCHBOARD
<br />MTD MOUNTED
<br />(N)NEW
<br />N NEUTRAL
<br />N/A NOT APPLICABLE
<br />NEC NATIONAL ELECTRICAL CODE
<br />NEMA NATIONAL ELECTRICAL MFG ASSOC.
<br />NRTL NATIONAL RECOGNIZED TESTING LABORATORY
<br />NTS NOT TO SCALE
<br />OC ON CENTER
<br />P POLES
<br />PB PULL BOX
<br />PH, Ø PHASE
<br />PV PHOTOVOLTAIC
<br />PVC POLYVINYL CHLORIDE
<br />PWR POWER
<br />PWCP PRE-WIRED CONTROL PANEL
<br />RFAP REMOTE FIRE ALARM ANNUNCIATOR PANEL
<br />RGB REFERENCE GROUND BAR
<br />RGS RIGID GALVANIZED STEEL
<br />SB SWITCHBOARD
<br />SCE SOUTHERN CALIFORNIA EDISON
<br />SF SUPPLY FAN
<br />SPD SURGE PROTECTIVE DEVICE
<br />SPDT SINGLE POLE DOUBLE THROW
<br />SPST SINGLE POLE SINGLE THROW
<br />SW DISCONNECT SWITCH
<br />SWGR SWITCHGEAR
<br />T/C TIME CLOCK
<br />TC TERMINAL CABINET
<br />TEL TELEPHONE
<br />TGB TELECOM GROUND BAR
<br />TTB TELEPHONE TERMINAL BOARD
<br />TV TELEVISION
<br />TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
<br />TX TOILET EXHAUST FAN
<br />TYP TYPICAL
<br />UG UNDERGROUND
<br />UON UNLESS OTHERWISE NOTED
<br />V VOLTS
<br />VA VOLTAMPS
<br />VAV VARIABLE AIR VOLUME BOX
<br />VD VIDEO DISPLAY
<br />VFD VARIABLE FREQUENCY DRIVE
<br />VT VAPORTIGHT
<br />W WATTS
<br />WM WALL MOUNTED
<br />WP WEATHERPROOF
<br />WT WATERTIGHT
<br />XFMR TRANSFORMER
<br />XP EXPLOSION PROOF
<br />ELECTRICAL SHEET INDEX
<br />NO.SHEET DESCRIPTION REMARKS
<br />1 E0.0 GENERAL NOTES -
<br />2 E0.1 CONSTRUCTION NOTES -
<br />3 E0.2 SPECIFICATIONS -
<br />4 E1.0 GROUND FLOOR POWER PLAN -
<br />5 E2.0 SINGLE LINE & PANEL SCHEDULE -
<br />20A, 125V, DUPLEX RECEPTACLE, WITH ARC FAULT CIRCUIT
<br />INTERRUPTER, NEMA 5-20R.
<br />20A, 125V, ABOVE COUNTERTOP MOUNTED, DUPLEX RECEPTACLE,
<br />WITH ARC FAULT CIRCUIT INTERRUPTER, NEMA 5-20R
<br />20A, 125V, LEGRAND FLOORBOX (OR EQUAL), CONFIGURABLE PER
<br />CLIENT REQUIREMENT, SEE NOTE ON PLAN, NEMA 5-20R
<br />20A, 125V, FLOORBOX, DUPLEX RECEPTACLE, 5-20R
<br />20A, 125V, FLOORBOX, QUADRUPLEX RECEPTACLE, 5-20R
<br />20A, 125V, LEGRAND FLOORBOX (OR EQUAL), CONFIGURABLE PER
<br />CLIENT REQUIREMENT, SEE NOTE ON PLAN, WITH ARC FAULT CURRENT
<br />INTERRUPTER NEMA 5-20R
<br />20A, 125V, FLOORBOX, DUPLEX RECEPTACLE, WITH ARC FAULT
<br />CURRENT INTERRUPTER, 5-20R
<br />20A, 125V, FLOORBOX, QUADRUPLEX RECEPTACLE, WITH ARC FAULT
<br />CURRENT INTERRUPTER, 5-20R
<br />20A, 125V, QUADRUPLEX RECEPTACLE, NEMA 5-20R
<br />20A, 125V, QUADRUPLEX RECEPTACLE, WITH GROUND FAULT CIRCUIT
<br />INTERRUPTER, NEMA 5-20R.
<br />20A, 125V, QUADRUPLEX RECEPTACLE, WITH ARC FAULT CIRCUIT
<br />INTERRUPTER, NEMA 5-20R.
<br />20A, 125V, ABOVE COUNTERTOP MOUNTED, QUADRUPLEX RECEPTACLE
<br />NEMA 5-20R
<br />20A, 125V, ABOVE COUNTERTOP MOUNTED, QUADRUPLEX
<br />RECEPTACLE, WITH GROUND FAULT CIRCUIT INTERRUPTER, NEMA
<br />5-20R
<br />20A, 125V, ABOVE COUNTERTOP MOUNTED, QUADRUPLEX
<br />RECEPTACLE, WITH ARC FAULT CIRCUIT INTERRUPTER, NEMA 5-20R
<br />REMOVE EXISTING 800A SERVICE, INSTALL NEW 2000A
<br />SERVICE 280/277V, INSTALL NEW (2) 800A DISTRIBUTION
<br />PANELS 480/277V, RECONNECT EXISTING PANEL HA AND
<br />DRY TRANSFORMER 75 KVA.
<br />SCOPE OF WORK
<br />COORDINATION NOTES
<br />1. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES TO ENSURE
<br />INSTALLATION IS MADE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALL
<br />EQUIPMENT LOCATIONS AND CONDUIT RUNS SUPPLIED AND/OR INSTALLED UNDER
<br />THIS SECTION SHALL BE INSTALLED TO AVOID CONFLICTS OR OBSTRUCTIONS TO
<br />OTHER TRADES.
<br />2. CONTRACTOR SHALL PROVIDE ALL NECESSARY PULL BOXES, VERTICAL SUPPORT
<br />BOXES, AND CONDUIT OFFSETS REQUIRED TO ACCOMPLISH THE ABOVE NOTED
<br />COORDINATION AT NO ADDITIONAL COST TO THE OWNER, WHETHER OR NOT
<br />INDICATED ON PLANS. ALL VERTICAL SUPPORT BOXES, PULL BOXES, ETC. SHALL BE
<br />INSTALLED WHERE REQUIRED TO FACILITATE PULLS AND AT CODE REQUIRED
<br />INTERVALS, AT A MINIMUM.
<br />3. REFER TO DIVISION 21, 22 AND 23 DRAWINGS AND SCHEDULES FOR WORK TO BE
<br />FURNISHED AND INSTALLED BY DIVISION 26 THAT ARE NOT SPECIFICALLY
<br />IDENTIFIED ON THE ELECTRICAL DRAWINGS. CONTRACTOR TO MAKE AN
<br />ALLOWANCE FOR PROVIDING 120V TO ALL BUILDING AUTOMATION NETWORK
<br />MANAGER CONTROL PANELS AND 24V NETWORK POWER SUPPLIES AS REQUIRED.
<br />4. ALL PLUMBING AND HVAC (DIVISION 21, 22 AND 23) EQUIPMENT COMPONENTS (FANS,
<br />COMPRESSORS, PUMPS, VFDs, MOTOR CONTROLLERS, STARTERS AND
<br />DISCONNECTS, ETC) THAT ARE REQUIRED AS PART OF THE SYSTEM, AND THAT ARE
<br />NOT FACTORY PRE-WIRED, ARE TO BE SUPPLIED (BY DIVISION 21, 22 OR 23 U.O.N)
<br />AND INSTALLED BY DIVISION 26 U.O.N. IF THE SUPPLIED VFD OR EQUIPMENT
<br />CONTROLLER IS NOT LOCATED WITHIN SIGHT OF A MOTOR AND IS NOT SUITABLE
<br />FOR USE AS A DISCONNECTING MEANS, THE ELECTRICAL CONTRACTOR SHALL
<br />PROVIDE A SEPARATE MOTOR DISCONNECT, AT THE MOTOR LOCATION, THAT IS
<br />PROPERLY SIZED AND IS SUITABLE FOR USE AS A DISCONNECTING MEANS FOR ALL
<br />MOTORS AND/OR EQUIPMENT SUPPLIED WITH MOTORS.
<br />5. THE LOCATION OF DIVISION 27 AND 28 POWER REQUIREMENTS IS SHOWN FOR
<br />REFERENCE ONLY. REFER TO DIVISION 27 AND 28 DRAWINGS FOR EXACT
<br />LOCATIONS. MOUNT POWER ADJACENT TO DIVISION 27 AND 28 BOXES. WHERE
<br />POWER IS REQUIRED IN THE CEILING, PROVIDE 60" OF SLACK TO ALLOW FINAL
<br />SERVICE LOCATION TO BE COORDINATED WITH DIVISION 27 AND DIVISION 28 DEVICE
<br />LOCATIONS. COORDINATE THE INSTALLATION WITH THE APPROPRIATE TRADES AND
<br />THE GENERAL CONTRACTOR PRIOR TO INSTALLATION.
<br />6. REFER TO DIVISION 27 AND DIVISION 28 DRAWINGS FOR CONDUIT, BOXES AND
<br />CABLE TRAY REQUIREMENTS.
<br />7. ALL MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION IN ACCORDANCE
<br />WITH CALIFORNIA ELECTRICAL CODE SECTION 430.31, 430.32.
<br />ARC ENERGY REDUCTION SWITCHAERS
<br />THE ELECTRICAL CONTRACTOR IS ADVISED TO COORDINATE
<br />WITH THE ENGINEER IN ADVANCE FOR ANY CHANGES FROM
<br />THE DESIGN SHOWN HEREIN. ANY EVALUATION OF FIELD
<br />CHANGES OR REWORK OF THE DRAWINGS DUE TO FIELD
<br />CHANGES BY THE CONTRACTOR WILL BE SUBJECT TO
<br />ADDITIONAL SERVICES FEES. APPROVAL BY THE ENGINEER
<br />OF FIELD CHANGES MADE WITHOUT PRIOR COORDINATION
<br />WILL BE AT THE SOLE DISCRETION OF THE ENGINEER.
<br />20A, 125V, SINGLE RECEPTACLE, NEMA 5-20R
<br />20A, 125V, SINGLE RECEPTACLE, WITH GROUND FAULT CIRCUIT
<br />INTERRUPTER, NEMA 5-20R.
<br />20A, 125V, CEILING-MOUNTED, DUPLEX RECEPTACLE, 5-20R
<br />20A, 125V, CEILING-MOUNTED, QUADRUPLEX RECEPTACLE, 5-20R
<br />20A, 125V, FLOORBOX, DUPLEX RECEPTACLE, WITH GROUND FAULT
<br />CIRCUIT INTERRUPTER, 5-20R
<br />20A, 125V, FLOORBOX, QUADRUPLEX RECEPTACLE, WITH GROUND
<br />FAULT CURRENT INTERRUPTER, 5-20R
<br />20A, 125V, LEGRAND FLOORBOX (OR EQUAL), CONFIGURABLE PER
<br />CLIENT REQUIREMENT, SEE NOTE ON PLAN, WITH GROUND FAULT
<br />CURRENT INTERRUPTER NEMA 5-20R
<br />NE
<br />W
<br />
<br />2
<br />0
<br />0
<br />0
<br />A
<br />
<br />S
<br />E
<br />R
<br />V
<br />I
<br />C
<br />E
<br />10
<br />0
<br />1
<br />
<br />S
<br />.
<br />
<br />G
<br />R
<br />A
<br />N
<br />D
<br />
<br />A
<br />V
<br />E
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />5
<br />ARCHITECT:
<br />CONSULTANTS:
<br />SEAL & SIGNATURE:
<br />ISSUED FOR:
<br />DESCRIPTION:DATE:
<br />KEY PLAN
<br />SHEET NAME:
<br />PROJECT NO.:
<br />DRAWN BY:
<br />CHECKED BY:
<br />SCALE:
<br />SHEET NO.:
<br />Copyright 120DEGREEZ 2019c
<br />NORTH
<br />San Diego | Los Angeles
<br />www.120degreez.com
<br />619.323.1515 | 310.364.5228
<br />Mechanical | Electrical | Plumbing
<br />MEP Project No.: 25−070
|