1. CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE INCLUSIVE OF CITY OF SANTA ANA AMENDMENTS, PERTINENT <br />NFPA CODES AS WELL AS ALL RULES AND REGULATIONS OF LOCAL, STATE AND, FEDERAL AUTHORITIES HAVING JURISDICTION. <br />2. THE DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE MAIN CONTRACT CONDITIONS, ELECTRICAL SPECIFICATIONS (DIVISION 26), THE MECHANICAL, PLUMBING <br />AND FIRE PROTECTION DRAWINGS, THE ARCHITECTURAL DRAWINGS, THE STRUCTURAL ENGINEER'S DRAWINGS, THE TELECOMMUNICATIONS, AUDIO VISUAL AND <br />SECURITY DRAWINGS (DIVISION 27 AND 28). <br />3. CONTRACTOR SHALL EXECUTE THE WORK IN THE BEST AND MOST THOROUGH MANNER & TO THE SATISFACTION OF THE CONSULTING ENGINEER, WHO WILL <br />INTERPRET THE MEANING OF THE DRAWINGS AND SPECIFICATIONS AND SHALL HAVE THE POWER TO REJECT ANY WORK AND MATERIALS WHICH, IN THEIR <br />JUDGMENT, ARE NOT IN FULL ACCORDANCE THEREWITH. <br />4. THE DRAWINGS SHOW THE VARIOUS CONDUIT AND PIPING SYSTEMS SCHEMATICALLY. CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY JUNCTION <br />BOXES, PULL BOXES, SUPPORT AND ACCESSORIES TO MEET APPLICABLE CODES, BUILDING STANDARDS AND FULFILL CONTRACT DOCUMENTS. NO ADDED <br />COMPENSATION WILL BE PERMITTED FOR VARIATIONS DUE TO FIELD CONDITIONS. <br />5. DO NOT SCALE FROM THE DRAWINGS, IF IN DOUBT, REQUEST FURTHER INFORMATION. <br />6. REFER TO THE ARCHITECTURAL DRAWINGS FOR SETTING OUT AND MOUNTING HEIGHT DETAILS OF ALL DEVICES, SWITCHES, ETC. <br />7. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR THE SETTING OUT OF ALL CEILING MOUNTED COMPONENTS. <br />8. ALL AREAS ASSOCIATED WITH WORK TO BE PERFORMED SHALL BE EXAMINED PRIOR TO BID SUBMISSION. NO ADDITIONAL COMPENSATION SHALL BE MADE FOR <br />CONDITIONS FOUND DURING INSTALLATION. <br />9. CONTRACTOR SHALL INCLUDE ALL LABOR, MATERIALS, AND APPURTENANCES REQUIRED FOR THE INSTALLATION AND TESTING OF ALL EQUIPMENT AND APPLIANCES <br />INDICATED IN THESE DOCUMENTS. CONTRACTOR SHALL COMPLETE ALL WORK AND VERIFY THE OPERATION OF ALL EQUIPMENT IN A MANNER SATISFACTORY TO <br />THE ARCHITECT AND ELECTRICAL CONSULTING ENGINEER. <br />10. WHERE CONDUIT, CABLE, CABLE TRAY OR OTHER ELECTRICAL EQUIPMENT SUCH AS CUTOUT BOXES, LUMINARIES OR PANELBOARDS, PENETRATE RATED <br />ASSEMBLIES, FIRE BARRIERS, FIRE WALLS, FIRE PARTITIONS, SMOKE BARRIERS, OR SMOKE PARTITIONS, THE ELECTRICAL CONTRACTOR SHALL PROVIDE AN <br />APPROPRIATE FIRE OR SMOKE STOPPING SYSTEM THAT IS LISTED BY UNDERWRITERS LABORATORIES OR COMPLIES WITH THE APPROPRIATE ICC EVALUATION <br />REPORT AND DOES NOT REDUCE THE RATING OF THE ASSEMBLY. ALL THROUGH AND MEMBRANE PENETRATIONS SHALL BE SUBMITTED TO THE ARCHITECT OF <br />RECORD FOR APPROVAL PRIOR TO INSTALLATION. ALL ACCESS PANELS SHALL BE APPROVED AND LISTED FOR THE ASSEMBLY IN WHICH THEY ARE BEING <br />INSTALLED. COMPLY WITH ALL REQUIREMENTS OF DIVISION 26 SPECIFICATIONS. SEE ARCHITECTURAL DRAWINGS FOR RATINGS OF ALL ASSEMBLIES. CONTRACTOR <br />SHALL COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR PRIOR TO INSTALLATION. <br />11. CONDUIT RUNS INDICATED ON PLAN ARE FOR REFERENCE ONLY. EXACT LOCATIONS AND ELEVATIONS SHALL BE DETERMINED AFTER COORDINATING WITH OTHER <br />TRADES AND THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL SUPPLY, AS PART OF THEIR SHOP DRAWING SUBMISSION, THE EXACT LOCATION OF ALL <br />CEILING MOUNTED EQUIPMENT AND CONDUIT RUNS, INCLUDING THE PROPOSED LOCATIONS AND THE MEANS OF SUPPORT. PROVIDE THE ARCHITECT AND <br />STRUCTURAL ENGINEER THE ANTICIPATED LOAD AT THE POINTS OF ATTACHMENT PRIOR TO COMMENCEMENT OF WORK. <br />12. CONTRACTOR SHALL VERIFY THE ELECTRICAL REQUIREMENTS OF ALL NEW EQUIPMENT TO BE USED. ALL SPECIAL PURPOSE OUTLETS INDICATED ON PLAN SHALL <br />BE VERIFIED WITH THE EQUIPMENT MANUFACTURER AND OWNER PRIOR TO INSTALLATION. THE ELECTRICAL CONTRACTOR SHALL ENSURE PROPER WIRING AND <br />COMPATIBILITY WITH ATTACHMENT PLUGS OR JUNCTION BOXES THAT MAY BE FURNISHED AS AN INTEGRAL PART OF THE EQUIPMENT. <br />13. ALL RECEPTACLES SHALL BE ACCESSIBLE. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF EQUIPMENT RECEPTACLES WITH THE EQUIPMENT <br />MANUFACTURER'S REQUIREMENTS, THE OWNER, AND THE AUTHORITY HAVING JURISDICTION. <br />14. CONTRACTOR SHALL PROVIDE DISCONNECTS FOR ALL EQUIPMENT AS REQUIRED BY THESE DOCUMENTS AND THE ADOPTED CODES. COORDINATE ALL <br />REQUIREMENTS AND LOCATIONS WITH THE AUTHORITY HAVING JURISDICTION, THE VENDORS APPROVED SHOP DRAWINGS AND FINAL EQUIPMENT LOCATIONS. <br />15. CONTRACTOR SHALL COORDINATE ALL LOCATIONS AND HEIGHTS OF STUB-UPS AND STUB-OUTS AS WELL AS ALL OUTLETS IN FIELD. <br />16. FINAL CONNECTIONS TO EQUIPMENT SHALL BE MADE ACCORDING TO VENDOR'S APPROVED SHOP DRAWINGS AND THE LISTING OF THE EQUIPMENT. <br />17. ALL WORK AND/OR EQUIPMENT INSTALLED OUTDOORS SHALL BE APPROVED FOR USE IN WET LOCATIONS. <br />18. ALL PARTS OF THE WORK AND ASSOCIATED EQUIPMENT SHALL BE TESTED AND ADJUSTED TO WORK PROPERLY AND BE IN PERFECT OPERATING CONDITION. THIS <br />SHALL INCLUDE MEG-OHM TESTING BETWEEN PHASES, BETWEEN EACH PHASE AND THE GROUNDED CONDUCTOR, AND EACH PHASE AND THE EQUIPMENT GROUND <br />FOR ALL FEEDERS, TAPS, SECONDARY CONDUCTORS , SWITCHBOARDS AND PANELBOARDS. FURNISH ALL TEST RESULTS TO THE ELECTRICAL CONSULTING <br />ENGINEER FOR REVIEW PRIOR TO ENERGIZING EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL CORRECT ANY DEFECTS IDENTIFIED THOUGH THIS TESTING. <br />19. PROVIDE ISOLATED GROUND TYPE OUTLETS WHERE THE "IG" SUBSCRIPT IS INDICATED. <br />20. WALL-MOUNTED OUTLETS, SWITCHES, AND CONTROL DEVICES, SHOULD BE MOUNTED AT THE HEIGHTS INDICATED IN THESE DOCUMENTS. THE ELECTRICAL <br />CONTRACTOR SHALL VERIFY AND FULLY COMPLY WITH, ALL AMERICANS WITH DISABILITIES REQUIREMENTS AND MEET ALL REQUIREMENTS ESTABLISHED BY THE <br />HOUSING AND URBAN DEVELOPMENT (HUD) STANDARDS AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION. <br />21. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A CITY OF SANTA ANA RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE CITY OF SANTA <br />ANA, DEPARTMENT OF BUILDING AND SAFETY. <br />22. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE MANDATED BY THE <br />CALIFORNIA ELECTRICAL CODE ABOVE OR BELOW ELECTRICAL EQUIPMENT. <br />23. ADEQUATE CLEARANCE AROUND AND ABOVE ELECTRICAL EQUIPMENT SHALL BE MAINTAINED PER CALIFORNIA ELECTRICAL CODE SECTION 110.26. <br />24. ALL GROUNDING ELECTRODES THAT ARE PRESENT AT EACH BUILDING AND STRUCTURE, INCLUDING THE PHOTOVOLTAIC SYSTEM, SHALL BE BONDED TOGETHER. <br />25. ALL WORK TO COMPLY WITH 2022 C.E.C. AND 2022 ENERGY EFFICIENCY STANDARDS. <br />26. EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNDERGROUND CONDUCTORS AT THE POINT <br />OF DISTRIBUTION PER C.E.C. 210.4 [B]. <br />27. G.F.C.I. PROTECTION REQUIRED FOR APPLIANCES IN DEDICATED SPACES AND RECEPTACLES NOT READILY ACCESSIBLE PER C.E.C. 210.8 [A]. <br />28. G.F.C.I. PROTECTION IS REQUIRED FOR ALL 125 VOLT, SINGLE PHASE 15 AND 20 AMP RECEPTACLES INSTALLED IN BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS <br />AND WITHIN 6-FEET OF SINKS AS PER C.E.C. 210.8 [B]. <br />29. 125V, 15 AND 20 AMP RECEPTACLES ARE REQUIRED, PER C.E.C. 406.12, TO BE LISTED AS TAMPER RESISTANT. <br />30. PROVIDE CARBON MONOXIDE ALARMS IN DWELLING UNITS WHERE FUEL BURNING APPLIANCES ARE INSTALLED AND/OR IN DWELLING UNITS WITH ATTACHED <br />GARAGES PER C.R.C. R315.2. <br />31. PROVIDE "ARC-FLASH" LABELING ON SWITCHBOARDS, DISTRIBUTION BOARDS AND PANELBOARDS. <br />32. ALL NEWLY CONSTRUCTED MULTITENANT BUILDING ARE REQUIRED TO COMPLY WITH THE PHOTOVOLTAIC REQUIREMENTS IN CEnC 140.10(A) IF THE UTILITY <br />PROVIDES EITHER A VIRTUAL NET METERING (VNEM) OR COMMUNITY SOLAR PROGRAM. THE ELECTRICAL CONTRACTOR AND EQUIPMENT MANUFACTURER SHALL <br />PROVIDE PROVISIONS FOR THE CONNECTION OF CONDUCTORS TO THE EQUIPMENT TO COMPLY WITH THE LISTING OF THE EQUIPMENT AND THE CALIFORNIA <br />ELECTRICAL CODE. <br />33. UPON COMPLETION OF THIS PROJECT, PROVIDE THE PROJECT OWNER WITH AN APPROVED COPY OF THE CERTIFICATE OF OCCUPANCY AND OR A COPY OF THE <br />FINAL APPROVAL OF THE ELECTRICAL SYSTEM. <br />GENERAL NOTES <br />1. ALL CONDUIT AND CABLE "HOME RUNS" SHALL CONSIST OF A SINGLE CIRCUIT PER CONDUIT FOR THREE PHASE CIRCUITS, AND SINGLE PHASE CIRCUITS SERVED BY <br />AN OVERCURRENT PROTECTIVE DEVICE (OCPD) IN EXCESS OF 20 AMPERES SINGLE POLE. <br />2. WHERE WIRE AND CONDUIT BRANCH CIRCUITS SHARE A CONDUIT HOME RUN, (OCPD LESS THAN OR EQUAL TO 20 AMPERES SINGLE POLE) THERE SHALL BE A <br />MAXIMUM OF THREE CIRCUITS COMBINED IN A SINGLE RACEWAY TO THE PANELBOARD, UNLESS OTHERWISE NOTED. ALL CONDUCTORS SHALL BE DE-RATED PER <br />CALIFORNIA ELECTRICAL CODE. COMBINING OF MULTIPLE HOME RUNS (MORE THAN THREE) IN A SINGLE CONDUIT IS NOT PERMITTED. WITH THE EXCEPTION OF <br />FURNITURE FEED TYPE WIRING SYSTEMS THE SHARING OF NEUTRALS AND GROUNDING CONDUCTORS BETWEEN CIRCUITS IS NOT PERMITTED. <br />3. CONTRACTOR SHALL VERIFY PHASE LOAD BALANCING ON POWER PANELS UPON COMPLETION OF THE ELECTRICAL INSTALLATION. INCLUDE RE-DISTRIBUTION OF <br />CIRCUITS WITHIN PANELS TO BALANCE WITHIN A 10% WINDOW (±5%). <br />4. UNLESS OTHERWISE NOTED ALL BRANCH CIRCUITS SHALL BE 20-AMPERE DEDICATED CIRCUITS WITH 3/4"C, #12, #12N, #12G MINIMUM. <br />5. ALL CIRCUITS TO HAVE BOTH CONDUCTORS AND GROUND WIRE HOME RUN TO SERVICE PANEL. <br />6. ALL FEEDER AND BRANCH CIRCUIT WIRING SHALL BE A MINIMUM SIZE OF AWG #12. METAL CLAD (MC) CABLING IS PERMITTED <br />7. RIGID STEEL CONDUITS: <br />7.1. USE FOR ALL SIZES WHERE DIRECTLY EXPOSED TO WEATHER; WHERE SUBJECT TO ABNORMAL CONDITIONS OF HEAT, COLD, MOISTURE, HUMIDITY, FUMES AND <br />HAZARDOUS ELEMENTS; WHERE INSTALLED EXPOSED BELOW 7-1/2', IN AREAS WHERE SUBJECT TO MECHANICAL INJURY. USE FOR ALL CONDUIT IN ALL <br />ELECTRICAL AND MECHANICAL EQUIPMENT ROOMS; FOR LOW VOLTAGE (UP TO 600 VOLTS) FEEDERS INSIDE OF BUILDING AND IN CONCRETE SLABS ON GRADE. <br />7.2. FOR ALL BENDS IN CONDUITS 3” AND LARGER, AND OVER 50' IN LENGHT, USE LARGE RADIUS FACTORY MADE BENDS OR FIELD FABRICATE WITH A POWER <br />BENDER. <br />8. ELECTRICAL METALLIC TUBING (EMT) <br />8.1. PERMITTED TO BE USED IN WET LOCATIONS WITH APPROVED FITTINGS. <br />8.2. CONDUITS SHALL BE CONTINUOUS. CONDUCTORS SHALL NOT BE INSTALLED UNTIL THE RACEWAY SYSTEM IS COMPLETE. <br />9. RIGID PLASTIC CONDUITS: <br />9.1. ALL CONDUITS INSTALLED UNDERGROUND, OR ENCASED IN CONCRETE, SHALL BE SCHEDULE 40 PVC CONDUIT. <br />9.2. MAKE ALL FITTINGS IN PLASTIC CONDUITS WATERTIGHT WITH APPROVED SOLVENT-WELD CEMENT SPECIFICALLY MANUFACTURED FOR THE PURPOSE. APPLY <br />HEAT FOR BENDS SO THAT CONDUIT DOES NOT DISTORT OR DISCOLOR. <br />10. PVC JACKETED STEEL CONDUITS: <br />10.1. USE FOR ALL SIZES IN SOIL BELOW THE BUILDING. <br />10.2. FOR ALL BENDS IN CONDUITS 1-1/4” AND LARGER, USE LARGE RADIUS FACTORY MADE BENDS OR FIELD FABRICATE WITH A POWER BENDER. <br />CONDUIT AND CIRCUIT WIRING NOTES <br />EQUIPMENT CALLOUT <br />a. EQUIPMENT DESIGNATION <br />b. EQUIPMENT LOADING IN KVA OR HP <br />c. EQUIPMENT UTILIZATION VOLTAGE <br />d. NUMBER OF POLES <br />e. NUMBER OF WIRES <br />f. RELEVANT NOTES <br />a. <br />b. KVA c. V d. P e. W <br />f. <br />(--A) - DENOTES CONTINUOUS CURRENT RATING IN AMPS <br />(--P) - DENOTES NUMBER OF SWITCHED POLES <br />HARD WIRED CONNECTION TO FIXED EQUIPMENT OR PACKAGED UNIT <br />(NON-MOTOR) <br />HARD WIRED CONNECTION TO MOTORIZED EQUIPMENT <br />(MOTOR / FAN / PUMP / FAN COIL UNIT) <br />UL LISTED DISCONNECT (UNFUSED): <br />APPROVED FOR MOTOR USE AS APPLICABLE <br />MATCH VOLTAGE AND POLES TO EQUIPMENT <br />30A, 2 POLES, NEMA 1 U.O.N. <br />UL LISTED DISCONNECT (FUSED): <br />APPROVED FOR MOTOR USE AS APPLICABLE <br />--AS - DENOTES SWITCH RATING IN AMPS <br />--AF - DENOTES FUSE SIZE IN AMPS <br />MATCH VOLTAGE AND POLES TO EQUIPMENT. NEMA 1 U.O.N <br />PRE-WIRED UL LISTED MOTOR CONTROLLER (FURNISHED BY DIV 21, 22 <br />AND 23 U.O.N) COMPLETE WITH INTEGRAL OVERLOAD PROTECTIVE <br />DEVICE. <br />3R INDICATES NEMA SIZE, NEMA 1 U.O.N. <br />PRE-WIRED CONTROL PANEL (FURNISHED BY DIV 21, 22 AND 23 U.O.N.) <br />COMPLETE WITH INTEGRAL DISCONNECT AND OVERLOAD PROTECTIVE <br />DEVICES. 3R INDICATES NEMA SIZE, NEMA 1 U.O.N. <br />UL LISTED VARIABLE FREQUENCY DRIVE (FURNISHED BY DIV 21, 22 AND <br />23 U.O.N.) COMPLETE WITH INTEGRAL DISCONNECT AND OVERLOAD <br />PROTECTIVE DEVICES. 3R INDICATES NEMA SIZE, NEMA 1 U.O.N. <br />HARD WIRED CONNECTION TO FIXED EQUIPMENT OR PACKAGED UNIT <br />(NON-MOTOR) WITH TOGGLE SWITCH <br />SINGLE PHASE MANUAL STARTER WITH OVERLOAD PROTECTION FOR <br />FRACTIONAL HORSEPOWER MOTORS <br />CIRCUIT BREAKER IN NEMA TYPE 1 ENCLOSURE: <br />--A - DENOTES TRIP SETTING <br />--P - DENOTES POLES <br />PANELBOARD <br />L - DENOTES LIGHTING AND MISCELLANEOUS 277V LOADS <br />P - DENOTES POWER AND 120/208V LOADS <br />Q - DENOTES EQUIPMENT AND/OR EXTERNAL SUPPLIES <br />DRY TYPE ENERGY EFFICIENT TRANSFORMER PER SPECIFICATION: <br />30kVA AND LARGER SHALL BE FLOOR STANDING U.O.N. <br />115°C TEMPERATURE RISE U.O.N. AS 80°C ON SHEET E6.1 <br />VOLTAGES AND kVA RATING - AS PER SHEET E6.1 <br />K-RATING - STANDARD U.O.N. ON SHEET E6.1 <br />EQUIPMENT POWER <br />--A <br />--P <br />30A <br />2P <br />30AS <br />30AF <br />3R <br />3R <br />VFD 3R <br />S <br />--A <br />--P CB <br />L-1A <br />P-1A <br />Q-1A <br />AMP METER <br />VOLT METER <br />2P, 3W, AUTOMATIC TRANSFER SWITCH - #A DENOTES RATING <br />PULL BOX SIZE PER CEC <br />GROUND FAULT TRIP UNIT <br />TRANSFORMER WITH SECONDARY GROUND <br />(SEE TRANSFORMER SCHEDULE) <br />SWITCH AND FUSE UNIT: <br /> --AS - DENOTES SWITCH RATING IN AMPS <br /> --AF - DENOTES FUSE SIZE IN AMPS <br />MOLDED CASE CIRCUIT BREAKER (MCCB): <br /> --A - DENOTES TRIP SETTING IN AMPS <br /> --P - DENOTES NUMBER OF POLES <br /> - DENOTES SHUNT TRIP <br />AIR INSULATED CIRCUIT BREAKER <br /> --AT - DENOTES TRIP SETTING IN AMPS <br /> --AF - DENOTES FRAME SIZE <br />(L)ONG TIME DELAY - OVERLOAD PROTECTION <br />(S)HORT TIME DELAY - SHORT CIRCUIT WITH DELAYED TRIP <br />(I)NSTANTANEOUS TRIP - SHORT CIRCUIT PROTECTION <br />(G)ROUND FAULT PROTECTION <br />GROUNDING RODS TO ACHIEVE A MAXIMUM IMPEDANCE OF 5@ TO <br />GROUND PER SPECIFICATION 260526. RODS TO BE SPACED A MINIMUM <br />OF 10' APART. QUANTITY AS REQUIRED TO ACHIEVE IMPEDANCE. <br />SINGLE LINE DIAGRAM <br />A <br />V <br />#AATS <br />PB <br />G <br />--AS <br />--AF <br />CLASS 2000 DIGITAL kWH AND kW/DEMAND METER HOUSED IN <br />MULTIPLE METER UNIT. REFER TO SPECIFICATION 262713 FOR <br />FURTHER DETAILS <br />--A <br />--P <br />MCCB <br />ST <br />ST <br />--AT <br />--AF <br />L <br />S <br />I <br />G <br />SOLID <br />STATE <br />TRIP <br />M <br />20A, 125V, DUPLEX RECEPTACLE, NEMA 5-20R <br />WIRING DEVICES <br />20A, 125V, DUPLEX RECEPTACLE, WITH GROUND FAULT CIRCUIT <br />INTERRUPTER, NEMA 5-20R. <br />20A, 125V, ABOVE COUNTERTOP MOUNTED DUPLEX RECEPTACLE, <br />NEMA 5-20R <br />20A, 125V, ABOVE COUNTERTOP MOUNTED, DUPLEX RECEPTACLE, <br />WITH GROUND FAULT CIRCUIT INTERRUPTER, NEMA 5-20R <br />WALL / CEILING MOUNTED JUNCTION BOX. PROVIDE EXTENSION WHEN <br />USED FOR FLEX CONNECTION. VERIFY LOCATION AND MOUNTING <br />HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION. <br />WEATHERPROOF WHEN INSTALLED OUTSIDE. PROVIDE DISCONNECT <br />SWITCH WHERE INDICATED OR REQUIRED BY CODE. <br />20 A 125V CONTROLLED DUPLEX RECEPTACLE <br />20 A 125V CONTROLLED QUAD RECEPTACLE <br />30A, 125V, 1Ø, 2P, 3W TWIST-LOCK RECEPTACLE. <br />NEMA L5-30R <br />30A, 250V, 1Ø, 2P, 3W TWIST-LOCK RECEPTACLE. <br />NEMA L6-30R <br />J <br />2020 NEC <br />2022 CEC <br />2022 TITLE 24 PART 6 <br />RELEVANT CODE CYCLES <br />DESCRIPTION <br />KEYNOTE IDENTIFIER <br />X - KEYNOTE NUMBER <br />GENERAL SYMBOLS <br />REVISION CHANGE <br />X - DELTA NUMBER <br />SYMBOL <br />DETAIL/ENLARGED PLAN CALLOUT <br />X - DETAIL/REFERENCE# <br />EXXX - SHEET # <br />SECTION IDENTIFIER <br />X - SECTION # <br />EXXX - SHEET # <br />CABLE AND CONDUIT <br />WHERE NO WIRE SIZE SHOWN, DEFAULT CIRCUIT HOMERUN <br />INDICATES PANEL ORIGIN AND CIRCUIT NUMBER WITH: <br />•3/4" CONDUIT, (1) #12 HOT PER CIRCUIT, (1) #12 NEUTRAL PER <br />CIRCUIT AND (1) #12 GROUND PER CIRCUIT. <br />•PROVIDE ADDITIONAL (1) #12 ISOLATED GROUND FOR DEVICES <br />INDICATED WITH "IG" <br />DESIGNATED CIRCUIT HOMERUN INDICATES PANEL ORIGIN, CIRCUIT <br />NUMBER AND CONDUIT AND WIRING SIZES. REFER TO PANEL <br />SCHEDULES AS WELL <br />SHORT RADIUS ELBOW TURN-UP WITH INSIDE THREAD AND PLUG <br />FLUSH WITH FLOOR. PROVIDE EXTENSION UP TO CAST JUNCTION <br />BOX 6" A.F.F. U.O.N. ARROWS DENOTES CONNECTION TO <br />DESIGNATION EQUIPMENT <br />WIRING IN CONDUIT CONCEALED IN CEILING OR WALL. <br />WIRING IN CONDUIT CONCEALED UNDER FLOOR OR UNDERGROUND <br />CONDUIT TURNING UP <br />CONDUIT TURNING DOWN <br />CONDUIT STUB WITH WIRE PULL AND CAP <br />CABLE SUPPORT BOX <br />TELECOM CABLE TRAY, 8" WIDE X 2" DEEP, UON. COORDINATE <br />LOCATION WITH DUCTWORK, PLUMBING, FIRE PROTECTION, <br />ELECTRICAL, AND LIGHT FIXTURES. <br />WALL MOUNTED MULTI-SERVICE ALUMINUM RACEWAY COMPLETE <br />WITH RECEPTACLES AND OUTLETS AS INDICATED ON THE PLANS. <br />MOUNTED AT 42" AFFL TO BOTTOM OF RACEWAY, ANODIZED SATIN <br />FINISH. AS PER LEGRAND DS4000 OR APPROVED EQUAL. <br />FURNISH SAMPLE FOR ARCHITECT APPROVAL PRIOR TO ORDERING <br />X <br />X <br />X <br />EXXX <br />X <br />EXXX <br />NEUTRAL <br />HOT <br />GROUND <br />P5C1-2 <br />P5C1-7 <br />3/4"C,1#8,#8N,#10G <br />J <br />CSB <br />TELECOM SYMBOLS <br />MULTI-SERVICE 6-GANG FLOOR BOX WITH (2) DUPLEX RECEPTACLES, <br />20A (REFER TO WIRING DEVICES SYMBOLS) (1) GANG DATA, (1) GANG <br />SPARE. INSTALL WITH FLOOR FINISH INSERT. <br />AS LEGRAND EVOLUTION EFB6 SERIES OR APPROVED EQUAL <br />RJ45 DATA OUTLET ('x' DENOTES NUMBER OF GANGS) <br />TELEPHONE OUTLET <br />COMBO DATA/TELEPHONE OUTLET <br />'X' <br />FIRE ALARM <br />SMOKE DETECTOR <br />CARBON MONOXIDE DETECTOR <br />COMBO SMOKE / CARBON MONOXIDE DETECTOR <br />SD <br />CM <br />SCM <br />ABBREVIATIONS <br />A AMPERES <br />AC AIR CONDITIONER <br />AERS ARC ENERGY REDUCTION SWITCH <br />AFFL ABOVE FINISHED FLOOR LEVEL <br />AFI ARC FAULT INTERRUPTION <br />AHU AIR HANDLER UNIT <br />AIC AMPERE INTERRUPTING CAPACITY RATING <br />ATS AUTOMATIC TRANSFER SWITCH <br />AWG AMERICAN WIRE GAUGE <br />BFG BELOW FINISH GRADE <br />C CONDUIT <br />CATV CABLE ANTENNA TELEVISION SYSTEM <br />CB CIRCUIT BREAKER <br />CCTV CLOSED CIRCUIT TELEVISION <br />CEC CALIFORNIA ELECTRICAL CODE <br />CEnC CALIFORNIA ENERGY CODE <br />CKT CIRCUIT <br />CO CARBON MONOXIDE SENSOR <br />C.O. CONDUIT ONLY <br />CPT CONTROL POWER TRANSFORMER <br />(E)EXISTING <br />EF EXHAUST FAN <br />EL ELEVATOR <br />E.C. ELECTRICAL CONTRACTOR <br />E, EM EMERGENCY <br />EMT ELECTRICAL METALLIC TUBING <br />FA FIRE ALARM <br />FACP FIRE ALARM CONTROL PANEL <br />FRA FIRE RISK ASSESSMENT <br />FBO FURNISHED BY OTHERS <br />FIBO FURNISHED AND INSTALLED BY OTHERS <br />FCU FAN COIL UNIT <br />FL FLOOR <br />FLA FULL LOAD AMPERES <br />FSD FIRE SMOKE DAMPER <br />G.C. GENERAL CONTRACTOR <br />GRD GROUND <br />GFCI GROUND FAULT CIRCUIT INTERRUPTER <br />HP HORSE POWER <br />IG INSULATED GROUND <br />INT ADDRESSABLE FIRE ALARM RELAY MODULE <br />JB JUNCTION BOX <br />kcmil THOUSAND CIRCULAR MILS <br />kVA KILOVOLT AMPERES <br />kW KILOWATT <br />KX KITCHEN EXHAUST <br />LBS LOAD BREAK SWITCH <br />LSIG LONG-TIME, SHORT-TIME, INSTANTANEOUS, <br />GROUND FAULT PROTECTION <br />LTG LIGHTING <br />LV LOW VOLTAGE <br />LVR LOW VOLTAGE RELAY <br />MGB MAIN GROUNDING BAR <br />MCB MAIN CIRCUIT BREAKER <br />MCC MOTOR CONTROL CENTER <br />MCCB MOLDED CASE CIRCUIT BREAKER <br />MCP MOTOR CONTROL PANEL <br />M.C. MECHANICAL CONTRACTOR <br />MD MOTORIZED DAMPER <br />MGB MAIN GROUND BAR <br />MIN MINIMUM <br />MLO MAIN LUGS ONLY <br />MMS MAINTENANCE MODE SWITCH <br />MSB MAIN SWITCHBOARD <br />MTD MOUNTED <br />(N)NEW <br />N NEUTRAL <br />N/A NOT APPLICABLE <br />NEC NATIONAL ELECTRICAL CODE <br />NEMA NATIONAL ELECTRICAL MFG ASSOC. <br />NRTL NATIONAL RECOGNIZED TESTING LABORATORY <br />NTS NOT TO SCALE <br />OC ON CENTER <br />P POLES <br />PB PULL BOX <br />PH, Ø PHASE <br />PV PHOTOVOLTAIC <br />PVC POLYVINYL CHLORIDE <br />PWR POWER <br />PWCP PRE-WIRED CONTROL PANEL <br />RFAP REMOTE FIRE ALARM ANNUNCIATOR PANEL <br />RGB REFERENCE GROUND BAR <br />RGS RIGID GALVANIZED STEEL <br />SB SWITCHBOARD <br />SCE SOUTHERN CALIFORNIA EDISON <br />SF SUPPLY FAN <br />SPD SURGE PROTECTIVE DEVICE <br />SPDT SINGLE POLE DOUBLE THROW <br />SPST SINGLE POLE SINGLE THROW <br />SW DISCONNECT SWITCH <br />SWGR SWITCHGEAR <br />T/C TIME CLOCK <br />TC TERMINAL CABINET <br />TEL TELEPHONE <br />TGB TELECOM GROUND BAR <br />TTB TELEPHONE TERMINAL BOARD <br />TV TELEVISION <br />TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION <br />TX TOILET EXHAUST FAN <br />TYP TYPICAL <br />UG UNDERGROUND <br />UON UNLESS OTHERWISE NOTED <br />V VOLTS <br />VA VOLTAMPS <br />VAV VARIABLE AIR VOLUME BOX <br />VD VIDEO DISPLAY <br />VFD VARIABLE FREQUENCY DRIVE <br />VT VAPORTIGHT <br />W WATTS <br />WM WALL MOUNTED <br />WP WEATHERPROOF <br />WT WATERTIGHT <br />XFMR TRANSFORMER <br />XP EXPLOSION PROOF <br />ELECTRICAL SHEET INDEX <br />NO.SHEET DESCRIPTION REMARKS <br />1 E0.0 GENERAL NOTES - <br />2 E0.1 CONSTRUCTION NOTES - <br />3 E0.2 SPECIFICATIONS - <br />4 E1.0 GROUND FLOOR POWER PLAN - <br />5 E2.0 SINGLE LINE & PANEL SCHEDULE - <br />20A, 125V, DUPLEX RECEPTACLE, WITH ARC FAULT CIRCUIT <br />INTERRUPTER, NEMA 5-20R. <br />20A, 125V, ABOVE COUNTERTOP MOUNTED, DUPLEX RECEPTACLE, <br />WITH ARC FAULT CIRCUIT INTERRUPTER, NEMA 5-20R <br />20A, 125V, LEGRAND FLOORBOX (OR EQUAL), CONFIGURABLE PER <br />CLIENT REQUIREMENT, SEE NOTE ON PLAN, NEMA 5-20R <br />20A, 125V, FLOORBOX, DUPLEX RECEPTACLE, 5-20R <br />20A, 125V, FLOORBOX, QUADRUPLEX RECEPTACLE, 5-20R <br />20A, 125V, LEGRAND FLOORBOX (OR EQUAL), CONFIGURABLE PER <br />CLIENT REQUIREMENT, SEE NOTE ON PLAN, WITH ARC FAULT CURRENT <br />INTERRUPTER NEMA 5-20R <br />20A, 125V, FLOORBOX, DUPLEX RECEPTACLE, WITH ARC FAULT <br />CURRENT INTERRUPTER, 5-20R <br />20A, 125V, FLOORBOX, QUADRUPLEX RECEPTACLE, WITH ARC FAULT <br />CURRENT INTERRUPTER, 5-20R <br />20A, 125V, QUADRUPLEX RECEPTACLE, NEMA 5-20R <br />20A, 125V, QUADRUPLEX RECEPTACLE, WITH GROUND FAULT CIRCUIT <br />INTERRUPTER, NEMA 5-20R. <br />20A, 125V, QUADRUPLEX RECEPTACLE, WITH ARC FAULT CIRCUIT <br />INTERRUPTER, NEMA 5-20R. <br />20A, 125V, ABOVE COUNTERTOP MOUNTED, QUADRUPLEX RECEPTACLE <br />NEMA 5-20R <br />20A, 125V, ABOVE COUNTERTOP MOUNTED, QUADRUPLEX <br />RECEPTACLE, WITH GROUND FAULT CIRCUIT INTERRUPTER, NEMA <br />5-20R <br />20A, 125V, ABOVE COUNTERTOP MOUNTED, QUADRUPLEX <br />RECEPTACLE, WITH ARC FAULT CIRCUIT INTERRUPTER, NEMA 5-20R <br />REMOVE EXISTING 800A SERVICE, INSTALL NEW 2000A <br />SERVICE 280/277V, INSTALL NEW (2) 800A DISTRIBUTION <br />PANELS 480/277V, RECONNECT EXISTING PANEL HA AND <br />DRY TRANSFORMER 75 KVA. <br />SCOPE OF WORK <br />COORDINATION NOTES <br />1. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES TO ENSURE <br />INSTALLATION IS MADE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ALL <br />EQUIPMENT LOCATIONS AND CONDUIT RUNS SUPPLIED AND/OR INSTALLED UNDER <br />THIS SECTION SHALL BE INSTALLED TO AVOID CONFLICTS OR OBSTRUCTIONS TO <br />OTHER TRADES. <br />2. CONTRACTOR SHALL PROVIDE ALL NECESSARY PULL BOXES, VERTICAL SUPPORT <br />BOXES, AND CONDUIT OFFSETS REQUIRED TO ACCOMPLISH THE ABOVE NOTED <br />COORDINATION AT NO ADDITIONAL COST TO THE OWNER, WHETHER OR NOT <br />INDICATED ON PLANS. ALL VERTICAL SUPPORT BOXES, PULL BOXES, ETC. SHALL BE <br />INSTALLED WHERE REQUIRED TO FACILITATE PULLS AND AT CODE REQUIRED <br />INTERVALS, AT A MINIMUM. <br />3. REFER TO DIVISION 21, 22 AND 23 DRAWINGS AND SCHEDULES FOR WORK TO BE <br />FURNISHED AND INSTALLED BY DIVISION 26 THAT ARE NOT SPECIFICALLY <br />IDENTIFIED ON THE ELECTRICAL DRAWINGS. CONTRACTOR TO MAKE AN <br />ALLOWANCE FOR PROVIDING 120V TO ALL BUILDING AUTOMATION NETWORK <br />MANAGER CONTROL PANELS AND 24V NETWORK POWER SUPPLIES AS REQUIRED. <br />4. ALL PLUMBING AND HVAC (DIVISION 21, 22 AND 23) EQUIPMENT COMPONENTS (FANS, <br />COMPRESSORS, PUMPS, VFDs, MOTOR CONTROLLERS, STARTERS AND <br />DISCONNECTS, ETC) THAT ARE REQUIRED AS PART OF THE SYSTEM, AND THAT ARE <br />NOT FACTORY PRE-WIRED, ARE TO BE SUPPLIED (BY DIVISION 21, 22 OR 23 U.O.N) <br />AND INSTALLED BY DIVISION 26 U.O.N. IF THE SUPPLIED VFD OR EQUIPMENT <br />CONTROLLER IS NOT LOCATED WITHIN SIGHT OF A MOTOR AND IS NOT SUITABLE <br />FOR USE AS A DISCONNECTING MEANS, THE ELECTRICAL CONTRACTOR SHALL <br />PROVIDE A SEPARATE MOTOR DISCONNECT, AT THE MOTOR LOCATION, THAT IS <br />PROPERLY SIZED AND IS SUITABLE FOR USE AS A DISCONNECTING MEANS FOR ALL <br />MOTORS AND/OR EQUIPMENT SUPPLIED WITH MOTORS. <br />5. THE LOCATION OF DIVISION 27 AND 28 POWER REQUIREMENTS IS SHOWN FOR <br />REFERENCE ONLY. REFER TO DIVISION 27 AND 28 DRAWINGS FOR EXACT <br />LOCATIONS. MOUNT POWER ADJACENT TO DIVISION 27 AND 28 BOXES. WHERE <br />POWER IS REQUIRED IN THE CEILING, PROVIDE 60" OF SLACK TO ALLOW FINAL <br />SERVICE LOCATION TO BE COORDINATED WITH DIVISION 27 AND DIVISION 28 DEVICE <br />LOCATIONS. COORDINATE THE INSTALLATION WITH THE APPROPRIATE TRADES AND <br />THE GENERAL CONTRACTOR PRIOR TO INSTALLATION. <br />6. REFER TO DIVISION 27 AND DIVISION 28 DRAWINGS FOR CONDUIT, BOXES AND <br />CABLE TRAY REQUIREMENTS. <br />7. ALL MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION IN ACCORDANCE <br />WITH CALIFORNIA ELECTRICAL CODE SECTION 430.31, 430.32. <br />ARC ENERGY REDUCTION SWITCHAERS <br />THE ELECTRICAL CONTRACTOR IS ADVISED TO COORDINATE <br />WITH THE ENGINEER IN ADVANCE FOR ANY CHANGES FROM <br />THE DESIGN SHOWN HEREIN. ANY EVALUATION OF FIELD <br />CHANGES OR REWORK OF THE DRAWINGS DUE TO FIELD <br />CHANGES BY THE CONTRACTOR WILL BE SUBJECT TO <br />ADDITIONAL SERVICES FEES. APPROVAL BY THE ENGINEER <br />OF FIELD CHANGES MADE WITHOUT PRIOR COORDINATION <br />WILL BE AT THE SOLE DISCRETION OF THE ENGINEER. <br />20A, 125V, SINGLE RECEPTACLE, NEMA 5-20R <br />20A, 125V, SINGLE RECEPTACLE, WITH GROUND FAULT CIRCUIT <br />INTERRUPTER, NEMA 5-20R. <br />20A, 125V, CEILING-MOUNTED, DUPLEX RECEPTACLE, 5-20R <br />20A, 125V, CEILING-MOUNTED, QUADRUPLEX RECEPTACLE, 5-20R <br />20A, 125V, FLOORBOX, DUPLEX RECEPTACLE, WITH GROUND FAULT <br />CIRCUIT INTERRUPTER, 5-20R <br />20A, 125V, FLOORBOX, QUADRUPLEX RECEPTACLE, WITH GROUND <br />FAULT CURRENT INTERRUPTER, 5-20R <br />20A, 125V, LEGRAND FLOORBOX (OR EQUAL), CONFIGURABLE PER <br />CLIENT REQUIREMENT, SEE NOTE ON PLAN, WITH GROUND FAULT <br />CURRENT INTERRUPTER NEMA 5-20R <br />NE <br />W <br /> <br />2 <br />0 <br />0 <br />0 <br />A <br /> <br />S <br />E <br />R <br />V <br />I <br />C <br />E <br />10 <br />0 <br />1 <br /> <br />S <br />. <br /> <br />G <br />R <br />A <br />N <br />D <br /> <br />A <br />V <br />E <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />ARCHITECT: <br />CONSULTANTS: <br />SEAL & SIGNATURE: <br />ISSUED FOR: <br />DESCRIPTION:DATE: <br />KEY PLAN <br />SHEET NAME: <br />PROJECT NO.: <br />DRAWN BY: <br />CHECKED BY: <br />SCALE: <br />SHEET NO.: <br />Copyright 120DEGREEZ 2019c <br />NORTH <br />San Diego | Los Angeles <br />www.120degreez.com <br />619.323.1515 | 310.364.5228 <br />Mechanical | Electrical | Plumbing <br />MEP Project No.: 25−070