CONSTRUCTION NOTES <br />1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THE C.E.C. AND <br />THE NATIONAL ELECTRICAL SAFETY CODE, LOCAL CODES, ORDINANCES AND <br />THE REQUIREMENTS OF UTILITY COMPANIES FURNISHING SERVICES TO <br />INSTALLATION. <br />2. PROVIDE ALL WORK AND ITEMS NECESSARY FOR COMPLETE AND FUNCTIONAL <br />ELECTRICAL SYSTEM. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND <br />DO NOT NECESSARILY SHOW EVERY CONDUIT, BOX, CONDUCTOR OR SIMILAR <br />ITEMS FOR A COMPLETE INSTALLATION. <br />3. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND DETERMINE <br />CONDITIONS WHICH MAY AFFECT BID. ANY ITEMS NOT FULLY UNDERSTOOD <br />SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO <br />BIDDING. <br />4. REFERENCE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF DEVICES. <br />QUESTIONS CONCERNING THE LOCATION OF DEVICES AND EQUIPMENT SHALL <br />BE DIRECTED TO THE ARCHITECT. FAILURE TO COORDINATE REQUIREMENTS <br />SHALL IN NO WAY RESULT IN ADDITIONAL COMPENSATION BEING PROVIDED <br />TO THE CONTRACTOR. <br />5. WHEREVER THE WORD "PROVIDE” IS USED, IT MEANS, "FURNISH AND INSTALL <br />ALL REQUIRED EQUIPMENT FOR A COMPLETE INSTALLATION AND SHALL BE <br />FULLY OPERATIONAL.” <br />6. COORDINATE THE LOCATION OF ALL ELECTRICAL EQUIPMENT WITH OTHER <br />TRADES AND THE GENERAL CONTRACTOR PRIOR TO INSTALLATION. <br />7. REFER TO EQUIPMENT DRAWINGS FOR THE CHARACTERISTICS AND <br />REQUIREMENTS (SIZE, LOCATION, ETC.) OF MECHANICAL EQUIPMENT, UNLESS <br />OTHERWISE INDICATED. COORDINATE INSTALLATION AND LOCATION OF ALL <br />EQUIPMENT WITH MECHANICAL AND GENERAL CONTRACTORS PRIOR TO <br />INSTALLATION. VERIFY ALL OVERCURRENT PROTECTION DEVICE RATINGS, <br />WIRE SIZES AND THE SIZE OF ALL DISCONNECTING MEANS PRIOR TO <br />INSTALLATION. COORDINATE THE INSTALLATION OF THE EQUIPMENT WITH <br />MECHANICAL AND GENERAL CONTRACTORS PRIOR TO INSTALLATION. FOR <br />ITEMS TO BE FURNISHED AND/OR INSTALLED BY ELECTRICAL CONTRACTOR, <br />SEE MECHANICAL DRAWINGS. REFER TO THE MECHANICAL DRAWINGS <br />CONTROL DIAGRAMS FOR ALL TIME SWITCHES, RELAYS, STARTERS, <br />THERMOSTATS, CONDUIT FOR LINE/LOW VOLTAGE AS REQUIRED. ALL <br />EQUIPMENT SHALL COMPLY WITH CEC SECTIONS 110.9 AND 110.10 AND <br />SUITABLE FOR THE AVAILABLE FAULT CURRENT. <br />8. ALL SMOKE DETECTORS ARE NOT TO BE MOUNTED IN FRONT OF HVAC AIR <br />DIFFUSERS, SUPPLIES OR RETURNS. VERIFY AT THE JOB SITE & MAKE ALL <br />ADJUSTMENTS, WHERE REQUIRED PER CODE, NFPA 72 AND THE INSTALLATION <br />INSTRUCTIONS. <br />9. ALL SMOKE DETECTORS SHALL BE INTERCONNECTED AS REQUIRED BY NFPA <br />72. <br />10. PROVIDE CONDUCTORS AND RACEWAYS PER 2020 NATIONAL ELECTRICAL <br />CODE AND LOCAL CODES. <br />MATERIALS AND METHODS <br />11. RACEWAYS AND CABLES SHALL BE ROUTED CONCEALED WITHIN THE BUILDING <br />STRUCTURE WHERE POSSIBLE. WHERE RACEWAYS OR CABLES CANNOT BE <br />CONCEALED, IT SHALL BE INSTALLED PER PROJECT MANAGER'S DIRECTION. <br />ALL CONDUIT SHALL BE INSTALLED IN NEAT SYMMETRICAL LINES, HORIZONTAL <br />OR PERPENDICULAR TO BUILDING COLUMNS AND ROOF LINES. CONDUITS <br />SHALL BE GROUPED ON COMMON SUPPORTS WHEREVER POSSIBLE. <br />12. EXPOSED CONDUIT ROUTING: CONDUITS MAY BE ROUTED EXPOSED. WHERE <br />SUBJECT TO PHYSICAL DAMAGE, THEY SHALL BE PROTECTED OR BE GRC OR <br />IMC. <br />13. OUTDOOR EXPOSED CONDUIT ROUTING: CONDUITS ROUTED ON ROOF OR <br />EXPOSED TO WEATHER SHALL BE EMT, GRC, IMC, PVC OR LIQUID-TIGHT FLEX. <br />PROVIDE WATER-TIGHT CONNECTIONS AND FITTINGS. <br />14. CLEARANCES: VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE <br />THAT ACCESS CLEARANCES CAN BE MET PRIOR TO ORDERING AND <br />INSTALLATION OF EQUIPMENT. <br />15. CONNECTIONS: PROVIDE EMT, GRC, IMC, METALLIC FLEX, OR LIQUIDATE FLEX <br />CONDUITS FOR CONNECTIONS TO MOTORS OR MOTORIZED EQUIPMENT. <br />16. WIRING: PROVIDE MINIMUM #12 AWG WIRE SIZE. THE MINIMUM ALLOWED <br />RACEWAY SHALL BE BE 1/2”. FLEXIBLE CONDUIT AND FLEXIBLE CABLE IS <br />PERMISSIBLE THROUGHOUT THE BUILDING. <br />16.1. WIRING: PROVIDE MINIMUM #10 AWG COPPER CONDUCTOR SIZE IN 120V <br />BRANCH CIRCUIT HOME RUNS OVER 75’ IN LENGTH OR AS REQUIRED FOR <br />VOLTAGE DROP MITIGATION. SELECTION OF DEVICES WITH ADEQUATELY <br />SIZED CABLE TERMINATION TERMINALS IS THE RESPONSIBILITY OF THE <br />CONTRACTOR. <br />16.2. WIRING: POWER WIRING FOR BRANCH CIRCUITS SHALL BE COPPER FOR <br />#8 AWG CONDUCTORS AND SMALLER. CONDUCTORS #1 AWG AND <br />LARGER SHALL BE XHHW-2. <br />17. DISCONNECTS: PROVIDE DISCONNECTING MEANS, FUSED AND NON-FUSED, AS <br />SHOWN AND REQUIRED BY CODE FOR EQUIPMENT FURNISHED UNDER <br />ELECTRICAL, MECHANICAL AND PLUMBING SCOPES OF WORK. <br />18. FUSES: PROVIDE FUSES PER EQUIPMENT NAMEPLATE UNLESS OTHERWISE <br />INDICATED. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE <br />HOLDERS. <br />19. SUPPORT: SUPPORT LIGHT FIXTURES FROM BUILDING STRUCTURE. DO NOT <br />SUPPORT FIXTURES FROM SUSPENDED CEILINGS OR DRYWALL. <br />20. LABELS: ELECTRICAL PANELS, TIME SWITCHES, DISCONNECT WITCHES, <br />STARTERS, CONTACTORS, PULL BOXES, ETC. SHALL BE PERMANENTLY <br />LABELED TO IDENTIFY ITS DESIGNATION OR UNIT SERVED. ENCLOSURES <br />LARGER THAN 6’’X6”, PROVIDED FOR EQUIPMENT THAT IS COVERED BY <br />ARTICLE 700 OR 701, SHALL HAVE A PERMANENT IDENTIFICATION PLATE THAT <br />IS SUBSTANTIALLY ORANGE IN COLOR. <br />21. PAINTING: ELECTRICAL ENCLOSURES SHALL BE PAINTED ONLY AS REQUIRED <br />BY ARCHITECT. <br />22. COVER PLATES: PROVIDE AS FOLLOWS. SUBMIT SAMPLE OF EACH FOR <br />APPROVAL. <br />22.1. MECHANICAL AND ELECTRICAL ROOMS: GALVANIZED STEEL <br />22.2. ALL OTHER AREAS: REFER TO SPECIFICATIONS <br />23. CONTRACTOR SHALL VERIFY THE ELECTRICAL REQUIREMENTS OF ALL NEW <br />EQUIPMENT TO BE USED. ALL SPECIAL PURPOSE OUTLETS INDICATED ON PLAN <br />SHALL BE VERIFIED WITH THE EQUIPMENT MANUFACTURER AND OWNER <br />PRIOR TO INSTALLATION. THE ELECTRICAL CONTRACTOR SHALL ENSURE <br />PROPER WIRING AND COMPATIBILITY WITH ATTACHMENT PLUGS OR JUNCTION <br />BOXES THAT MAY BE FURNISHED AS AN INTEGRAL PART OF THE EQUIPMENT. <br />24. ALL RECEPTACLES INSTALLED ON THE ROOF OR EXTERNALLY SHALL BE <br />GFCI-PROTECTED AND LISTED AS WEATHER RESISTANT. <br />25. ELECTRICAL OUTLET BOXES SHALL BE HORIZONTALLY SEPARATED BY NOT <br />LESS THAN 24" FROM OUTLETS IN THE OPPOSITE WALL SURFACE AND BACK <br />SIDE OF BOXES SHALL BE SEALED WITH 1/8" RESILIENT SEALANT AND BACKED <br />BY A MINIMUM OF 2" THICK MINERAL FIBER INSULATION. <br />26. ALL FLOOR STANDING EQUIPMENT SHALL BE MOUNTED ON 4" HIGH CONCRETE <br />HOUSEKEEPING PADS. THE SIZE OF THE CONCRETE PAD SHALL BE <br />COORDINATED WITH THE EQUIPMENT SUPPLIER AND INSTALLATION <br />INSTRUCTIONS. EQUIPMENT PADS SHALL NOT EXTEND MORE THAN 6" <br />BEYOND THE EQUIPMENT. <br />SITE ELECTRICAL <br />27. TRENCHING: COORDINATE ALL TRENCH WORK WITH OTHER TRADES, <br />UTILITIES, AND THE GENERAL CONTRACTOR PRIOR TO COMMENCEMENT OF <br />WORK. VERIFY LOCATION OF DRAINAGE SYSTEMS AND STORM WATER <br />RETENTION SYSTEMS. <br />28. UNDERGROUND CONDUIT: PROVIDE PVC, SCHEDULE 40, 3/4” MINIMUM. <br />PROVIDE GRC OR IMC CONDUIT ELBOWS, OR CONCRETE ENCASEMENT, FOR <br />ALL BENDS OR CHANGES OF DIRECTION. BOND METALLIC ELBOWS ARE <br />REQUIRED BY THE CALIFORNIA ELECTRICAL CODE. <br />29. DIRECT-BURIED: CONDUITS FOR BRANCH CIRCUITS, FEEDERS, OR LOW <br />VOLTAGE WIRING, THAT ARE INSTALLED OUTSIDE BUILDINGS OR STRUCTURES <br />AND NOT INSTALLED UNDER PAVED DRIVEWAYS OR PARKING AREAS, SHALL <br />BE A MINIMUM OF 18" BELOW GRADE. WHERE CONCRETE ENCASEMENT IS <br />PROVIDED, BURIAL DEPTH MAY BE REDUCED AS INDICATED BY THE NATIONAL <br />ELECTRICAL CODE. PROVIDE MARKER TAPE, OR A TRACER WIRE, A MINIMUM <br />OF 6" ABOVE THE RACEWAY. RACEWAYS INSTALLED UNDER DRIVEWAYS, <br />ALLEYS, PARKING AREAS OR AREAS SUBJECT TO VEHICULAR TRAFFIC SHALL <br />BE A MINIMUM OF 24" BELOW THE BOTTOM OF THE PAVING MATERIALS, NO <br />EXCEPTIONS. PROVIDE MARKER TAPE AS INDICATED ABOVE. <br />30. BELOW SLAB: CONDUIT ROUTED BELOW ON-GRADE FLOOR SLABS SHALL BE <br />INSTALLED PRIOR TO CONCRETE PLACEMENT. ROUTE CONDUITS BELOW SLAB, <br />AS STRAIGHT AS POSSIBLE, TO MINIMIZE BENDS. <br />31. ALL CONDUITS PENETRATING THE BUILDING ENVELOPE FROM BELOW GRADE <br />SHALL FOLLOW WATERPROOFING REQUIREMENTS IN THE ARCHITECTURAL <br />DRAWINGS. <br />NEUTRALS <br />32. AT CONTRACTORS OPTION, NEUTRALS MAY BE SHARED ON COMBINED HOME <br />RUNS UNLESS THE CIRCUIT HAS A GFCI BREAKER, AN AFCI BREAKER, HAS AN <br />ISOLATED GROUND, OR IS FROM A PANEL WITH TVSS PROTECTION. ANY <br />NEUTRAL DOWNSTREAM FROM A DIMMER SHALL BE DEDICATED TO THE <br />DIMMED LOAD. THE CONTINUITY OF THE NEUTRAL CANNOT BE DEPENDANT ON <br />A DEVICE. <br />33. NEUTRAL WIRES SHOWN FOR TWO AND THREE POLE MECHANICAL AND <br />KITCHEN EQUIPMENT MAY BE OMITTED UPON VERIFICATION THAT THEY ARE <br />NOT REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT AND <br />INSTALLED PER THE MANUFACTURER’S INSTALLATION INSTRUCTIONS. <br />LIGHTING <br />34. PROVIDE LIGHT FIXTURES WITH PROPER FITTING FLANGES, MOUNTING <br />SUPPORTS, AND ACCESSORY ITEMS, LISTED BY AN APPROVED TESTING <br />LABORATORY FOR THE CONDITIONS OF USE. <br />35. GROUP SWITCHES IN A GANG BOX UNDER COMMON COVER PLATE, WHERE <br />APPLICABLE. <br />36. WHERE CONDUIT, CABLE, CABLE TRAY OR OTHER ELECTRICAL EQUIPMENT <br />SUCH AS CUTOUT BOXES, PANELBOARDS AND LUMINARES PENETRATE RATED <br />ASSEMBLIES, FIRE BARRIERS, FIRE WALLS, FIRE PARTITIONS, SMOKE <br />BARRIERS, OR SMOKE PARTITIONS, THE ELECTRICAL CONTRACTOR SHALL <br />PROVIDE AN APPROPRIATE FIRE OR SMOKE STOPPING SYSTEM THAT IS LISTED <br />BY UNDERWRITERS LABORATORIES OR COMPLIES WITH THE APPROPRIATE ICC <br />EVALUATION REPORT AND DOES NOT REDUCE THE RATING OF THE ASSEMBLY. <br />ALL THROUGH AND MEMBRANE PENETRATIONS SHALL BE SUBMITTED TO THE <br />ARCHITECT OF RECORD FOR APPROVAL PRIOR TO INSTALLATION. ALL <br />ACCESS PANELS SHALL BE APPROVED AND LISTED FOR THE ASSEMBLY IN <br />WHICH THEY ARE BEING INSTALLED. COMPLY WITH ALL REQUIREMENTS OF <br />DIVISION 26 SPECIFICATIONS. SEE ARCHITECTURAL DRAWINGS FOR RATINGS <br />OF ALL ASSEMBLIES. CONTRACTOR SHALL COORDINATE THIS WORK WITH THE <br />GENERAL CONTRACTOR PRIOR TO INSTALLATION. <br />37. WALL-MOUNTED OUTLETS, SWITCHES, AND CONTROL DEVICES, SHOULD BE <br />MOUNTED AT THE HEIGHTS INDICATED IN THESE DOCUMENTS. THE <br />ELECTRICAL CONTRACTOR SHALL VERIFY AND FULLY COMPLY WITH, ALL <br />AMERICANS WITH DISABILITIES REQUIREMENTS AND MEET ALL <br />REQUIREMENTS ESTABLISHED BY THE HOUSING AND URBAN DEVELOPMENT <br />(HUD) STANDARDS AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION. <br />38. ALL LIGHTING FIXTURES SHALL BE MOUNTED AS INDICATED IN THESE <br />DRAWINGS. <br />39. ALL CONTROL EQUIPMENT REQUIRING CERTIFICATION UNDER TITLE 24 TO BE <br />CERTIFIED BY THE CALIFORNIA ENERGY COMMISSION. <br />40. LIGHTING FIXTURES IN CONTACT WITH INSULATION TO BE IC RATED OR <br />PROVIDE 3 INCH MINIMUM CLEARANCE. <br />41. FIXTURES INSTALLED IN RATED CEILINGS SHALL BE INSTALLED IN AN MANNER <br />THAT DOES NOT REDUCE THE RATING OF THE ASSEMBLY. WHERE INSTALLED <br />IN A RATED ASSEMBLY IT MUST MEET THE MINIMUM REQUIREMENTS <br />ESTABLISHED BY UL OR ICC. <br />42. ALL RECESSED INCANDESCENT FIXTURES INSTALLED IN GYPBOARD CEILING <br />SHALL BE EQUIPPED WITH AUTO-RESETTING THERMAL PROTECTION. <br />43. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONFLICT BETWEEN LIGHT <br />FIXTURE LOCATIONS, MAIN RUNNERS, DUCTS, BUILDING STRUCTURE, ETC. <br />44. ALL LIGHT FIXTURES TO BE SELECTED BY ARCHITECT/OWNER, FURNISHED <br />AND INSTALLED BY CONTRACTOR. <br />45. ALL RECESSED DOWNLIGHTS TO BE THERMALLY PROTECTED PER N.E.C. & U.L. <br />REQUIREMENTS. <br />46. ALL LIGHT FIXTURES USED ON THE EXTERIOR OF THE BUILDING OR WHERE <br />SUBJECT TO WATER INFILTRATION, SHALL BE LISTED FOR WET LOCATIONS. <br />47. ALL EXTERIOR LIGHTING TO BE CONTROLLED BY PHOTO-CELL WITH TIME <br />SWITCH OVERRIDE, U.O.N. <br />48. LED DRIVER, FLUORESCENT BALLAST AND ALL ELECTRONIC PRODUCTS, SHALL <br />REQUIRED TO BE COMPLIANT WITH THE FCC CFR 47, AND UL. <br />49. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION AND ELEVATION OF <br />ALL LIGHTING FIXTURES AND ALL DEVICES. ALL WALL-MOUNTED DEVICE <br />HEIGHTS SHALL BE VERIFIED WITH THE ARCHITECT PRIOR TO ROUGH-IN. <br />50. VERIFY EXACT CEILING CONSTRUCTION WITH ARCHITECTURAL REFLECTED <br />CEILING PLAN AND PROVIDE LIGHTING FIXTURES WITH ALL NECESSARY <br />MOUNTING HARDWARE. <br />51. ALL RECESSED FIXTURES SHALL BE PROVIDED WITH ALL REQUIRED <br />STRUCTURAL SUPPORTS AS REQUIRED BY THE CURRENTLY ADOPTED ISSUE <br />OF THE IBC, OR CBC WHERE ADOPTED, IN ADDITION TO ANY LOCAL CODES. <br />FIXTURES SHALL NOT BE SUPPORTED BY GYPSUM BOARD. <br />52. ALL COVE MOUNTED FIXTURES SHALL EXTEND THE FULL LENGTH OF THE <br />COVE. CONTRACTOR TO FIELD MEASURE COVE LENGTH AND ORDER <br />QUANTITY OF FIXTURES AS REQUIRED. <br />53. ALL EMERGENCY BATTERY PACK FIXTURES (UNIT EQUIPMENT) SHALL BE <br />PROVIDED WITH A CONSTANT HOT CONNECTION TO THE CHARGING LEAD. SEE <br />GENERAL LIGHTING FIXTURE SCHEDULE NOTES FOR MORE INFORMATION. <br />54. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXIT SIGN <br />CHEVRONS AND NUMBER OF FACES PER EXIT SIGN. ANY DISCREPANCIES <br />BETWEEN EXIT SIGNS SHOWN ON THE ELECTRICAL AND ARCHITECTURAL <br />PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO <br />ORDERING EXIT SIGNS. <br />55. WHEN EXPOSED CEILINGS OR OPEN GRID CONDITIONS OCCUR. THE <br />CONTRACTOR WILL NEED TO PROVIDE THE FOLLOWING ITEMS: <br />55.1. ALL BRANCH CIRCUITS SHALL BE IN EMT. <br />55.2. ALL BRANCH CIRCUITS SHALL BE ROUTED, NEATLY TRAINED, AND IN <br />PARALLEL TO STRUCTURES OR DUCT WORK. THE TERM "TRAINED" <br />MEANS ALL PARALLEL CONDUITS SHALL MAINTAIN THE SAME SPATIAL <br />RELATIONSHIP WITH EACH OTHER FOR ENTIRE RUN TO INCLUDE RADIUS <br />BENDS AND SWEEPS. VISUALLY OBJECTIONABLE BRANCH CIRCUITS WILL <br />BE REROUTED AT THE REQUEST OF THE ARCHITECT AT NO ADDITIONAL <br />COST. <br />56. ALL LED REMOTE INDICATORS FOR DUCT DETECTORS AND FIRE/SMOKE <br />DAMPERS REQUIRED BY THE LOCAL AHJ SHALL BE LOCATED IN CEILINGS AND <br />COORDINATED WITH THE ARCHITECT PRIOR TO ANY ROUGH-IN. <br />57. RECESSED FIXTURES LOCATED IN A RATED ASSEMBLY SHALL BE PROVIDED <br />WITH A 5-SIDED RATED ENCLOSURE SO CONSTRUCTED AS TO PROVIDE THE <br />REQUIRED CLEARANCES BETWEEN THE FIXTURE AND THE ENCLOSURE AND <br />ALLOW FOR PROPER VENTILATION AS REQUIRED BY THE FIXTURE'S LISTING. <br />SEE NOTE #39 UNDER CONSTRUCTION NOTES FOR ADDITIONAL <br />REQUIREMENTS. <br />58. PROVIDE AN ADDITIONAL JUNCTION BOX ABOVE ALL PANELBOARDS, IN AN <br />ACCESSIBLE LOCATION, TO ALLOW FOR FUTURE CIRCUIT EXTENSIONS. <br />59. UNLESS SPECIFICALLY SHOWN AS (E). (R), (ER), (D), EXISTING OR NON-BOLD, <br />ALL ELECTRICAL DEVICES SHOWN ARE NEW. <br />60. CONTRACTOR TO PROVIDE COMPLETE SET OF SHOP DRAWINGS INDICATING <br />ALL DEVICES AND WIRING ASSOCIATED WITH THE SYSTEM FOR APPROVAL TO <br />THE ENGINEER OF RECORD. <br />61. EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED AT ALL <br />TIMES AND SHALL BE CONNECTED TO AN EMERGENCY POWER SYSTEM <br />(BATTERIES, UNIT EQUIPMENT OR STANDBY GENERATOR, THAT ARE SUITABLE <br />FOR THE PURPOSE) THAT WILL AUTOMATICALLY ILLUMINATE THE EXIT SIGNS <br />FOR A DURATION OF NOT LESS THAN 90 MINUTES. <br />62. THE MEANS OF EGRESS WILL BE ILLUMINATED TO A LEVEL OF NOT LESS THAN <br />ONE FOOT-CANDLE AT THE WALKING SURFACE, ALONG THE PATH OF TRAVEL, <br />AT ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS <br />OCCUPIED. <br />63. LOW VOLTAGE LIGHTING <br />63.1. PROVIDE LOW VOLTAGE TRANSFORMERS IN NEARBY ACCESSIBLE <br />CEILING SPACE. <br />63.2. PROVIDE LOW VOLTAGE CONDUCTORS SIZED PER MANUFACTURER’S <br />GUIDELINES TO MINIMIZE VOLTAGE DROP. <br />LIGHTING CONTROL <br />64. THE MAXIMUM LIGHTING POWER THAT MAY BE CONTROLLED FROM A SINGLE <br />SWITCH OR AUTOMATIC CONTROL SHALL NOT EXCEED THAT WHICH IS <br />PROVIDE BY A TWENTY AMPERE CIRCUIT LOADED TO NOT MORE THAN EIGHTY <br />PERCENT. A MASTER CONTROL MAY BE INSTALLED PROVIDED THE INDIVIDUAL <br />SWITCHES RETAIN THEIR CAPABILITY TO FUNCTION INDEPENDENTLY. <br />65. BATTERY BALLASTS & EMERGENCY FIXTURES SHALL BE CONNECTED TO AN <br />UNSWITCHED LEG OF THE DESIGNATED CIRCUIT. <br />66. EMERGENCY COMMUNICATION: PROVIDE A 2-WAY COMMUNICATION SYSTEM <br />PER CBC 1007. <br />67. ACCESS PANELS: CONTRACTOR IS RESPONSIBLE FOR PROVIDING THEIR OWN <br />ACCESS PANELS FOR ACCESS TO THEIR EQUIPMENT. CONTRACTOR SHALL <br />SUBMIT A FULL PLAN SHOWING LOCATIONS TO THE GENERAL CONTRACTOR <br />PRIOR TO INSTALLATION. SEE CONSTRUCTION NOTE #39 FOR ADDITIONAL <br />REQUIREMENTS. <br />68. COMBINATION MOTOR-STARTERS THE CONTROL TRANSFORMERS IN ALL <br />COMBINATION MOTOR-STARTERS SHALL HAVE 120 VOLT COILS. <br />FIRE PROTECTION <br />69. OPENINGS IN FIRE RATED ASSEMBLIES FOR ELECTRICAL CONDUIT, BUS DUCT, <br />AND OTHER EQUIPMENT SHALL BE SEALED WITH FIRE CAULK OR OTHER <br />MATERIAL SUITABLE FOR MAINTAINING THE INTEGRITY OF THE FIRE RATING. <br />SEE CONSTRUCTION NOTE #39 FOR ADDITIONAL REQUIREMENTS. <br />BUS DUCT <br />70. NOT USED. <br />DIMENSIONS <br />71. MEASUREMENTS, WHERE SHOWN, ARE FROM FACE OF METAL FRAMING TO <br />CENTER OF THE BOX. ALL DIMENSIONS SHALL BE VERIFIED WITH THE <br />GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION. <br />ADA REQUIREMENTS <br />72. RECEPTACLE OUTLETS SHALL BE LOCATED NOT LESS THAN 15 INCHES ABOVE <br />THE FLOOR TO THE BOTTOM OF THE OPERABLE PART. <br />73. LIGHT SWITCHES SHALL BE INSTALLED WITH THE TOP OF THE OPERABLE <br />PART TO BE WITHIN 34-46 INCHES OF THE FLOOR. <br />74. ALL WORK MUST COMPLY WITH THE MOST RECENT ADA STANDARDS, HUD <br />REQUIREMENTS AND CBC REQUIREMENTS FOR ACCESSIBLE AND ADAPTABLE <br />UNITS. <br />75. PLACEMENT OF ALL OUTLETS AND CONTROL DEVICES SHALL BE <br />COORDINATED WITH THE GENERAL CONTRACTOR, ARCHITECT AND <br />AUTHORITY HAVING JURISDICTION AT ROUGH IN AND PRIOR TO THE <br />INSTALLATION OF RACEWAYS OR CABLING. <br />76. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO VERIFY THE PLACEMENT <br />AND LOCATION OF ALL ELECTRICAL EQUIPMENT TO MEET THESE <br />REQUIREMENTS PRIOR TO THE INSTALLATION OF RACEWAYS OR CABLING. <br />THERE SHALL BE NO ALLOWANCES MADE FOR FAILURE TO COMPLY WITH <br />THESE NOTES. <br />ARTICLE 300 — GENERAL REQUIREMENTS FOR WIRING METHODS AND <br />MATERIALS (300.5) <br />TABLE 300.5 MINIMUM COVER REQUIREMENTS, 0 TO 1000 VOLTS, NOMINAL, BURIAL IN MILLIMETERS (INCHES) <br />TYPE OF WIRING METHOD OR CIRCUIT <br />LOCATION OF WIRING METHOD OR CIRCUIT <br />COLUMN 1 <br />DIRECT BURIAL <br />CABLES OR <br />CONDUCTORS <br />COLUMN 2 <br />RIGID METAL <br />CONDUIT OR <br />INTERMEDIATE <br />METAL CONDUIT <br />COLUMN 3 <br />NONMETALLIC <br />RACEWAYS LISTED <br />FOR DIRECT BURIAL <br />WITHOUT CONCRETE <br />ENCASEMENT OR <br />OTHER APPROVED <br />RACEWAYS <br />COLUMN 4 <br />RESIDENTIAL <br />BRANCH CIRCUITS <br />RATED 120 VOLTS <br />OR LESS WITH GFCI <br />PROTECTION AND <br />MAXIMUM <br />OVERCURRENT <br />PROTECTION OF 20 <br />AMPERES <br />COLUMN 5 <br />CIRCUITS FOR <br />CONTROL OF <br />IRRIGATION AND <br />LANDSCAPE <br />LIGHTING LIMITED <br />TO NOT MORE THAN <br />30 VOLTS AND <br />INSTALLED WITH <br />TYPE UF OR IN <br />OTHER IDENTIFIED <br />CABLE OR RACEWAY <br />mm. in. mm. in. mm. in. mm. in. mm. in. <br />ALL LOCATIONS NOT SPECIFIED <br />BELOW 600 24 150 6 450 18 300 12 150 6 <br />IN TRENCH BELOW 50 mm (2 in.) THICK <br />CONCRETE OR EQUIVALENT 450 18 150 6 300 12 150 6 150 6 <br />UNDER A BUILDING <br />0 0 <br />0 0 0 0 <br />0 0 0 0 <br />(IN RACEWAY OR <br />TYPE MC OR TYPE MI <br />CABLE IDENTIFIED <br />FOR DIRECT BURIAL) <br />(IN RACEWAY OR <br />TYPE MC OR TYPE MI <br />CABLE IDENTIFIED <br />FOR DIRECT BURIAL) <br />(IN RACEWAY OR <br />TYPE MC OR TYPE MI <br />CABLE IDENTIFIED <br />FOR DIRECT BURIAL) <br />UNDER MINIMUM OF 102 mm (4 in.) THICK <br />CONCRETE EXTERIOR SLAB WITH NO <br />VEHICULAR TRAFFIC AND THE SLAB <br />EXTENDING NOT LESS THAN 152 mm (6 in.) <br />BEYOND THE UNDERGROUND INSTALLATION <br />450 18 100 4 100 4 <br />150 6 150 6 <br />(DIRECT BURIAL) (DIRECT BURIAL) <br />100 4 100 4 <br />(IN RACEWAY) (IN RACEWAY) <br />UNDER STREETS, HIGHWAYS, ROADS, <br />ALLEYS, DRIVEWAYS, AND PARKING LOTS 600 24 600 24 600 24 600 24 600 24 <br />ONE- AND TWO-FAMILY DWELLING <br />DRIVEWAYS AND OUTDOOR PARKING <br />AREAS, AND USED ONLY FOR <br />DWELLING-RELATED PURPOSES <br />450 18 450 18 450 18 300 12 450 18 <br />IN OR UNDER AIRPORT RUNWAYS, <br />INCLUDING ADJACENT AREAS WHERE <br />TRESPASSING PROHIBITED <br />450 18 450 18 450 18 450 18 450 18 <br />Notes: <br />1. Cover is defined as the shortest distance in millimeters (inches) measured between a point on the top surface of any direct-buried conductor, cable, conduit, or other <br />raceway and the top surface of finished grade, concrete, or similar cover. <br />2. Raceways approved for burial only where concrete encased shall require concrete envelope not less than 50 mm (2 in.) thick. <br />3. Lesser depths shall be permitted where cables and conductors rise for terminations or splices or where access is otherwise required. <br />4. Where one of the wiring method types listed in Columns 1 through 3 is used for one of the circuit types in Columns 4 and 5, the shallowest depth of burial shall be permitted. <br />5. Where solid rock prevents compliance with the cover depths specified in this table, the wiring shall be installed in metal or nonmetallic raceway permitted for direct burial. The <br />raceways shall be covered by a minimum of 50 mm (2 in.) of concrete extending down to rock. <br />NE <br />W <br /> <br />2 <br />0 <br />0 <br />0 <br />A <br /> <br />S <br />E <br />R <br />V <br />I <br />C <br />E <br />10 <br />0 <br />1 <br /> <br />S <br />. <br /> <br />G <br />R <br />A <br />N <br />D <br /> <br />A <br />V <br />E <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />ARCHITECT: <br />CONSULTANTS: <br />SEAL & SIGNATURE: <br />ISSUED FOR: <br />DESCRIPTION:DATE: <br />KEY PLAN <br />SHEET NAME: <br />PROJECT NO.: <br />DRAWN BY: <br />CHECKED BY: <br />SCALE: <br />SHEET NO.: <br />Copyright 120DEGREEZ 2019c <br />NORTH <br />San Diego | Los Angeles <br />www.120degreez.com <br />619.323.1515 | 310.364.5228 <br />Mechanical | Electrical | Plumbing <br />MEP Project No.: 25−070