Laserfiche WebLink
1.INTENT <br />1.1. THESE PLANS, AND ALL ASSOCIATED DOCUMENTS, ARE CONSIDERED TO BE CONTRACT DOCUMENTS AND AS SUCH, CANNOT BE AMENDED OR MODIFIED <br />WITHOUT THE PRIOR WRITTEN CONSENT OF 120 DEGREEZ ENGINEERING. <br />1.2. FURNISH AND INSTALL A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM IN ACCORDANCE WITH PLANS AND SPECIFICATIONS. <br />1.3. ALL DRAWINGS ARE SCHEMATIC BY DESIGN AND THE REQUIRED INSTALLATION SHALL NOT BE LIMITED TO WHAT IS DEPICTED HEREIN. ALL APPURTENANCES <br />REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM MUST BE INCLUDED IN THE CONTRACTORS BID AND WORK. <br />1.4. WHEREVER USED IN THESE DOCUMENTS THE WORD OR TERM "SHALL" IS TO BE INTERPRETED AS FOLLOWS: MANDATORY LANGUAGE AND IS WITHOUT <br />EXCEPTION. <br />2.GENERAL <br />2.1. THE CONTRACTOR SHALL VISIT THE JOB SITE TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR BID OR WORK. NO <br />ALLOWANCES WILL BE MADE FOR EXISTING CONDITIONS OR THE CONTRACTORS FAILURE TO ACCOMMODATE EXISTING CONDITIONS ON ANY BID. <br />2.2. IT IS THE CONTRACTORS RESPONSIBILITY TO OBTAIN CLARIFICATION OF ANY APPARENT CONFLICT OR INCONSISTENCY IN THE DRAWINGS, SPECIFICATIONS OR <br />DESIGN PRIOR TO THEIR BID IN WRITING FROM THE ENGINEER. OTHERWISE THE CONTRACTOR ACCEPTS FULL RESPONSIBILITY TO CORRECT (AT THEIR COST) <br />ANY SUCH ITEMS AS NECESSARY TO MEET THE INTENT OF THESE DOCUMENTS AND ANY ADOPTED CODE OR NATIONAL STANDARD AS INTERPRETED BY THE <br />ENGINEER. <br />2.3. ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE MOST RECENT EDITIONS OF THE NATIONAL ELECTRIC CODE (NEC), UBC., IBC, ICC, IECC AND ANY <br />APPLICABLE CITY AND/OR STATE CODES AND ORDINANCES, THE AMERICANS WITH DISABILITIES ACT, E.P.A. REGULATIONS (INCLUDING EPACT 2020), ANSI <br />STANDARDS, UL STANDARDS AS WELL AS ANY AND ALL UTILITY COMPANY REQUIREMENTS. THE FOREGOING CODES AND REGULATIONS ARE REQUIREMENTS <br />AND ARE INCORPORATED IN THIS SPECIFICATION FOR THIS WORK BY REFERENCE. ALL INSTALLATIONS BY THE CONTRACTOR SHALL MEET LATEST ADOPTED <br />CODES WITHOUT EXCEPTION. <br />2.4. THE CONTRACTOR SHALL COORDINATE AND PROVIDE INFORMATION AS REQUIRED TO ALL SERVING UTILITIES IN A TIMELY MANNER AND IS NECESSARY TO <br />PROVIDE THE SERVICE REQUIRED AND MEET UTILITY REQUIREMENTS. IMMEDIATE COORDINATION WILL BE REQUIRED FOR MOST PROJECTS. FIELD COORDINATE <br />ALL REQUIREMENTS PRIOR TO TRENCHING. <br />2.5. REFER TO ARCHITECTURAL, MECHANICAL, CIVIL, STRUCTURAL DRAWINGS AND/OR EQUIPMENT SUPPLIERS DRAWINGS AND SPECIFICATIONS FOR EXACT <br />EQUIPMENT LOCATIONS, LOADS AND ADDITIONAL REQUIREMENTS. REPRESENTATIONS OF THE WORK SPECIFIC TO THE OTHER DISCIPLINES IS SHOWN ON THE <br />ELECTRICAL DRAWINGS FOR CONVENIENCE ONLY AND SHALL NOT SOLELY BE RELIED UPON FOR THE PLACEMENT OF EQUIPMENT. <br />2.6. THE CONTRACTOR ASSUMES RESPONSIBILITY FOR ALL EQUIPMENT THEY SUPPLY. ALL EQUIPMENT SHALL BE INSTALLED STRICTLY PER MANUFACTURES <br />RECOMMENDATIONS, THE LISTING OF THE EQUIPMENT AND ALL CODES. OTHERWISE THE CONTRACTOR ASSUMES RESPONSIBILITY (AT THEIR COST) TO <br />CORRECT AND REMEDY ANY INSTALLATION NOT IN COMPLIANCE WITH THE MANUFACTURES RECOMMENDATIONS, LISTING(S) AND INTENTIONS AS INTERPRETED <br />BY THE ENGINEER. SEE SECTION 2.3. <br />2.7. THE CONTRACTOR SHALL NOT ENGAGE IN THE RE-DESIGN OR "VALUE ENGINEERING" OF THIS PROJECT WITHOUT PRIOR WRITTEN APPROVAL FROM 120 DEGREEZ <br />ENGINEERING AND THE OWNER. ALL DEVIATIONS FROM THESE DOCUMENTS ARE REQUIRED TO BE APPROVED OF IN WRITING BY THE ENGINEER PRIOR TO <br />INSTALLATION. THE ELECTRICAL CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ANY DEVIATION FROM THESE DOCUMENTS <br />INCLUDING THE COST TO RE-DESIGN. ELECTRICAL CONTRACTOR, AT COMMENCEMENT OF WORK, ACCEPTS ALL REQUIREMENTS AND STIPULATIONS OUTLINED <br />IN THE PROPOSAL PROVIDED BY 120 DEGREEZ ENGINEERING AND ACCEPTED BY THE PERSON IN RESPONSIBLE CHARGE OF THE PROJECT. ADDITIONALLY A <br />DETAILED ACCOUNTING OF ANY DEVIATIONS MUST BE SUBMITTED TO 120 DEGREEZ ENGINEERING AND THE OWNER PRIOR TO COMMENCEMENT OF WORK FOR <br />APPROVAL. <br />2.8. ANY VARIANCE OR EXCEPTIONS TO THE DRAWINGS AND SPECIFICATIONS MUST BE REQUESTED AND APPROVED IN WRITING. INTERIM VERBAL APPROVALS WILL <br />ONLY BE PROVIDED WHEN THE ENGINEER DETERMINES THIS TO BE JUSTIFIED AND MUST BE CONFIRMED IN WRITING TO BE FINAL. ROUTE ALL RFI's, AND RFC's <br />VIA GENERAL CONTRACTOR AND THROUGH THE ARCHITECT. <br />2.9. THE CONTRACTOR IS RESPONSIBLE TO OBTAIN ALL NECESSARY PERMITS, VARIANCES, AND APPROVALS, ETC. (AT THEIR COST) WHICH MAY BE REQUIRED FOR <br />COMPLETION OF THIS WORK. <br />2.10. PRIOR TO ROUGH-IN, THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF ALL LIGHT FIXTURES AND WIRING DEVICES: TO INCLUDE <br />MOUNTING HEIGHT AND LOCATIONS. ALL CONFLICTS SHALL BE REPORTED TO THE ENGINEER/ARCHITECT. PRIOR TO ROUGH-IN. FAILURE TO COORDINATE WILL <br />REQUIRE THE CONTRACTOR TO FIX ERRORS AT HIS COST. <br />2.11. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT AND SUPPORT FOR PROGRESS AND FINAL INSPECTIONS. THIS INCLUDES COMPLETE ACCESS TO ALL <br />EQUIPMENT. ADDITIONALLY A COMPLETE SET OF SPARE FUSES FOR ALL FUSES USED AND A 10% SUPPLY OF ALL LIGHT BULBS PROVIDED IN FIXTURES (TO A <br />MAXIMUM OF (1) CASE FOR EACH STYLE) SHALL BE PROVIDED TO THE OWNER AT FINAL INSPECTION. <br />3.RECONSTRUCTION (TO INCLUDE TENANT IMPROVEMENTS) <br />3.1. ALL RECONSTRUCTION OF EXISTING FACILITIES AND EQUIPMENT SHALL REQUIRE COMPLETE RENOVATION (MAKE GOOD AS NEW) FOR ALL EXISTING EQUIPMENT <br />UPON WHICH WORK IS INCLUDE THESE FOLLOWING REQUIREMENTS: <br />3.1.1. VERIFICATION OF EXISTING SES GROUNDING COMPLIANCE WITH NEC ARTICLE 250. <br />3.1.2. VERIFICATION OF CABLE SIZE AND AMPACITY OF EXISTING FEEDERS AND BRANCH CIRCUITS WITH NEC TABLE 310.15. <br />3.1.3. VERIFICATION OF EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250.122 AND GROUNDING AND BONDING OF LINE SIDE EQUIPMENT PER NEC TABLE <br />250.66. <br />3.1.4. VERIFICATION OF GROUNDING ELECTRODE SYSTEMS, ALL SYSTEM BONDING JUMPERS AND MAIN BONDING JUMPERS PER NEC ARTICLE 250. <br />3.1.5. VERIFICATION OF THE INTEGRITY OF THE GROUNDING AND BONDING SYSTEM AND VERIFY COMPLIANCE WITH NEC 250.4. <br />3.1.6. EXISTING LIGHT FIXTURES TO BE REUSED MUST BE CLEANED, RE-LAMPED, AND RESTORED TO "LIKE NEW" CONDITION. <br />3.1.7. EXISTING PANELBOARDS, SWITCH BOARDS, AND TRANSFORMERS WHICH ARE INCLUDED IN THIS PROJECT SHALL HAVE PREVENTATIVE MAINTENANCE <br />PREFORMED TO INCLUDE VERIFICATION OF ALL TERMINATIONS AS WELL AS CLEANING AND INSPECTION. <br />3.1.8. VERIFY PROPER WORKING CONDITION OF ALL EXISTING EMERGENCY FIXTURES AND EXIT SIGNS. REPAIR OR REPLACE AS REQUIRED. <br />3.2. IN THE EVENT THAT INSPECTION REVEALS DISCREPANCIES AND/OR NON-COMPLIANCE, THE OWNER AND THE ENGINEER SHALL BE NOTIFIED IN WRITING BEFORE <br />MAKING ALL REQUIRED CORRECTIONS.. <br />4.MATERIALS AND METHODS <br />4.1. THE USE OF ELECTRICAL METALLIC TUBING (EMT) IS ACCEPTABLE IN ACCORDANCE WITH NEC ARTICLE 358. EMT FITTINGS SHALL BE COMPRESSION TYPE OR SET <br />SCREW TYPE. EMT SHALL BE PROVIDED WITH A AN ADDITIONAL COPPER GROUND WIRE SIZED PER NEC 250.122. MINIMUM TRADE CONDUIT SIZE SHALL BE 1/2". <br />ALL HOME RUNS SHALL BE 3/4" TRADE SIZED EMT. <br />4.2. ALL CONDUITS INSTALLED UNDERGROUND SHALL HAVE PVC COATED G.R.C. ELBOWS NO EXCEPTIONS. <br />4.3. WHERE SYSTEMS FURNITURE IS INDICATED, THE MINIMUM NEUTRAL CONDUCTOR SIZE SHALL BE #10 A.W.G. COPPER. <br />4.4. CONDUCTORS SHALL BE 600V COPPER (98% CONDUCTIVITY). MINIMUM LINE VOLTAGE WIRE SIZE IS #12 A.W.G. ALL CONDUCTORS SHALL HAVE 90 DEGREE RATED <br />INSULATION. <br />4.5. CONDUCTORS #6 AND SMALLER SHALL HAVE THHN/THHW-2 INSULATION. #4 AND LARGER SHALL HAVE XHHW-2 INSULATION. <br />4.6. ALL WIRING DEVICES SHALL BE MINIMUM 20 AMP SPECIFICATION GRADE. HUBBELL, LEVITON, AND PASS-SEYMORE ARE ACCEPTABLE EQUIVALENTS. ALL <br />OUTLETS, SWITCHES, SPECIAL RECEPTACLES AND GROUND FAULT PROTECTION DEVICES SHALL BE PERMANENTLY MARKED WITH ENGRAVED COVER PLATES, <br />STATING PURPOSE, CIRCUIT AND SOURCE PANEL AND VOLTAGE. <br />4.7. COVER PLATES SHALL BE NYLON (IVORY) IN OFFICE/COMMERCIAL/OR LIVING AREAS, AND GALVANIZED STEEL IN WAREHOUSE/INDUSTRIAL/MANUFACTURING <br />AREAS OR AREAS SUBJECT TO PHYSICAL ABUSE. INDUSTRIAL COVERS ARE REQUIRED FOR ALL MOUNTING APPLICATIONS. <br />4.8. ALL RACEWAYS AND CABLES ARE TO BE CONCEALED EXCEPT TO SURFACE MOUNTED PANELS AND AT THE CEILING OF EXPOSED STRUCTURE AREAS. CONDUITS <br />WILL BE RUN PARALLEL OR PERPENDICULAR TO BUILDING LINES. <br />4.9. THE USE OF MC CABLE IS ACCEPTABLE IN ACCORDANCE WITH NEC ARTICLE 330, BUT LIMITED TO USE FOR BRANCH CIRCUITS ONLY. MC CABLE MAY NOT BE <br />USED FOR HOME RUNS, WHERE SUBJECT TO PHYSICAL DAMAGE, IN DIRECT BURIAL (IN EARTH OR CONCRETE) SITUATION UNLESS UL LISTED AND SUITABLE FOR <br />THE APPLICATION. MC CABLE MAY NOT BE RUN EXPOSED. <br />4.10. P.V.C. CONDUIT MAY BE USED ONLY IN OR UNDER SLABS AND IN CONCRETE OR MASONRY WALLS. INSTALLATIONS BELOW GRADE SHALL BE BURIED 24" (MIN) <br />DEEP OR GREATER. <br />4.11. FUSES SHALL BE BUSSMAN, LITTLE FUSES, GOULD-SHAWMUT OR ENGINEER APPROVED EQUAL. <br />4.12. CONDUCTORS UP TO AND INCLUDING #10 AWG SHALL BE SOLID WITH CONTINUOUSLY COLOR CODED INSULATION. COLOR CODING SHALL COMPLY WITH THE NEC <br />AND/OR LOCAL CODES OR POLICIES. <br />4.13. CONDUCTORS #8 AWG AND #6 AWG SHALL BE STRANDED WITH CONTINUOUS COLOR CODED INSULATION. COLOR CODING SHALL COMPLY WITH THE NEC AND/OR <br />LOCAL CODES OR POLICIES. <br />4.14. SPLICING OF GROUNDING ELECTRODE CONDUCTORS, WATER AND BUILDING STEEL BONDS SHALL ONLY BE ALLOWED WITH EXOTHERMIC WELDING. <br />4.15. NEW CONDUCTORS SHALL BE CONTINUOUS AND WITHOUT SPLICE EXCEPT AT JUNCTION OR PULL BOXES. <br />4.16. ALL CONDUIT SUPPORT SYSTEMS SHALL BE INSTALLED ON THE BUILDING STRUCTURE. UNISTRUT, BEELINE, OR CADDY MOUNTING SYSTEMS ARE ACCEPTABLE. <br />NO CONDUIT OR CABLE WILL BE SUPPORTED BY WIRES UTILIZED TO SUPPORT SUSPENDED CEILINGS OR BY "SLACK" WIRES USED AT LUMINAIRES OR AIR <br />TERMINALS. PERFORATED STRAPS OR OTHER PIPING AND CONDUIT STRAPS ARE NOT ACCEPTABLE SUPPORTS. <br />4.17. ACCEPTABLE MANUFACTURES FOR SWITCH GEAR RELATED COMPONENTS ARE: SQUARE D, CHALLENGER, GENERAL ELECTRIC, SIEMENS, AND CUTLER-HAMMER. <br />4.18. CONDUCTORS SHALL BE COLOR CODED FOR BRANCH CIRCUITS IN ACCORDANCE WITH THE NEC AND LOCAL REQUIREMENTS. CONDUCTORS SHALL BE <br />IDENTIFIED AS FOLLOWS EXCEPT AS AMENDED BY LOCAL AMENDMENTS: <br />●120/240 VOLT SINGLE PHASE: UNGROUNDED CONDUCTORS A-PHASE; BLACK, B-PHASE; RED, GROUNDED CONDUCTOR; WHITE. <br />● 120/208 VOLT THREE PHASE GROUNDED AND UNGROUNDED SYSTEMS: UNGROUNDED CONDUCTORS, A-PHASE; BLACK, B-PHASE; RED, C-PHASE; BLUE, <br />GROUNDED CONDUCTOR; WHITE (WHERE USED). <br />● 120/240 VOLT THREE PHASE GROUNDED AND UNGROUNDED SYSTEMS: UNGROUNDED CONDUCTORS, A-PHASE; BLACK, B-PHASE; ORANGE, C-PHASE; BLUE, <br />GROUNDED CONDUCTOR; WHITE. <br />● 277/480 VOLT THREE PHASE GROUNDED AND UNGROUNDED SYSTEMS: UNGROUNDED CONDUCTORS, A-PHASE; BROWN, B-PHASE; ORANGE, C-PHASE; <br />YELLOW, GROUNDED CONDUCTOR; GRAY. <br />● EQUIPMENT GROUNDING OR BONDING CONDUCTORS SHALL BE GREEN OR BARE. ISOLATED GROUNDING CONDUCTORS SHALL BE GREEN WITH A YELLOW <br />STRIPE. <br />4.19. INSTALLATIONS FOR EQUIPMENT SUBJECT TO VIBRATION, SUCH AS MOTORS AND TRANSFORMERS, SHALL HAVE CONDUCTORS INSTALLED IN 'SEAL TIGHT' OR <br />LIQUID TIGHT FLEXIBLE CONDUIT WITH GASKETED CONNECTORS AND FITTINGS. <br />4.20. PROVIDE RUBBER VIBRATION DAMPENING PADS FOR ALL MOTORS AND TRANSFORMERS, AND ALL VIBRATION PRODUCING EQUIPMENT. <br />4.21. ALL CONDUITS, RACEWAYS AND CABLES, REGARDLESS OF VOLTAGE, SHALL HAVE AN INSULATED BOND WIRE, SIZED BY EITHER NEC TABLE 250.66 (LINE SIDE) OR <br />250.122 (LOAD SIDE), WHERE APPLICABLE, INSTALLED AND PROPERLY TERMINATED WITH THE PHASE CONDUCTORS. CONDUIT IS NOT AN ACCEPTABLE <br />GROUNDING OR BONDING METHOD PER THESE DOCUMENTS. <br />4.22. ALL DIMMERS AND DIMMER SWITCHES SHALL BE OF THE SLIDE TYPE AND RATED FOR CONTINUOUS DUTY OF 1000 WATTS MINIMUM. THE CONTRACTOR SHALL <br />VERIFY IN THE FIELD, THE ACTUAL LOAD OF THE LIGHTING (SPECIFICALLY, BUT NOT LIMITED TO, TRACK LIGHTING) AND INSTALL DIMMERS OF PROPER WATTAGE. <br />4.23. ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL CIRCUIT NUMBERS AT JUNCTION, OUTLET, SWITCH OR PULL BOXES WITH PERMANENT MARKER ON THE INSIDE OF <br />THE BOX COVER OR TRIM PLATE. <br />5.SUBMITTALS <br />5.1. SUBMIT 6 SETS OF SHOP DRAWINGS AND SAMPLES FOR ALL EQUIPMENT PRIOR TO ORDERING AND IN A TIMELY MANNER. SUBMITTALS SHALL INCLUDE LIGHT <br />FIXTURES (INCLUDING LIGHT POLES), SWITCHBOARDS, PANELBOARDS, STARTERS, HVAC ELECTRICAL EQUIPMENT AND TRANSFORMERS. DESIGN BUILD ARE <br />EXEMPT FROM SUBMITTAL REQUIREMENTS. <br />5.1.1. SHOP DRAWINGS SHALL INCLUDE LAYOUT DIMENSIONS AND IDENTIFICATION OF SPECIFIC EQUIPMENT FOR INSTALLATION, MINIMUM NEC CLEARANCES (E.G. <br />110.26) SHALL BE INDICATED. <br />5.1.2. THE CONTRACTOR SHALL INCLUDE COMPARISON DATA AND SAMPLES FOR BOTH THE SUBSTITUTE AND SPECIFIED ITEMS WHEN SUBSTITUTIONS ARE PROPOSED. <br />THE CONTRACTOR REMAINS RESPONSIBLE TO PROVIDE THE ORIGINALLY SPECIFIED EQUIPMENT IN ACCORDANCE WITH THE ORIGINAL DELIVERY DATE (AT THEIR <br />COST) WHEN SUBSTITUTIONS ARE NOT APPROVED. <br />5.2. THE CONTRACTOR SHALL PROVIDE PROOF OF PERFORMANCE BOND WITH HIS INITIAL SUBMITTALS (E.G. SHOP DRAWINGS) TO INCLUDE A WARRANTY FOR THE <br />WARRANTY PERIOD (2 YEARS). <br />5.3. THE CONTRACTOR SHALL SUBMIT COMPLETE AND ACCURATE "AS BUILT" DRAWING TO THE OWNER AND ENGINEER WITHIN 2 WEEKS OF OWNER ACCEPTANCE. <br />PROVIDE (4) SETS OF BLUE LINES OR REPRODUCIBLE OF SAID PLANS. <br />5.4. PROVIDE A LETTER TO THE OWNER AND ENGINEER CERTIFYING ALL EQUIPMENT AND TERMINATION'S ARE TORQUED PER THE LISTING OF THE EQUIPMENT. THIS <br />CERTIFICATION SHALL BE EXECUTED BY A LICENSED CONTRACTOR, AND WRITTEN CERTIFICATION PROVIDED ON COMPANY LETTERHEAD. <br />5.5. PROVIDE COPIES OF ALL MANUFACTURER/SUPPLIER WARRANTIES AND GUARANTEES TO THE OWNER WITHIN 2 WEEKS OF FINAL ACCEPTANCE BY THE OWNER. <br />6.TESTING <br />6.1. SUBMIT A COPY OF ALL TEST RESULTS FOR THE ELECTRICAL POWER DISTRIBUTION SYSTEM AS A COMPLETE PACKAGE TO THE OWNER AND ENGINEER. <br />PACKAGE MUST PROVIDE SPECIFIC VALUES OF TEST DATA OBTAINED AGAINST ACCEPTANCE CRITERIA (SIMPLE PASS/FAIL ALONE IS INADEQUATE). TESTING <br />PERSONAL SHALL BE CERTIFIED BY INTERNATIONAL ELECTRIC TESTING ASSOCIATION (NETA) OR NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING <br />TECHNOLOGIES (NICET). <br />6.2. GROUNDING SYSTEM FALL-OF-POTENTIAL (RESISTANCE TO GROUND) SHALL PROVIDE LESS THAN 25 OHMS RESISTANCE TO GROUND AND LESS THAN .5 OHMS <br />POINT TO POINT BETWEEN THE MAIN GROUNDING ELECTRODE SYSTEM AND MAJOR ELECTRICAL EQUIPMENT FRAMES, SYSTEM NEUTRAL, AND/OR DERIVED <br />NEUTRAL POINTS. (REF IEEE STANDARD 81-1991 AND 142). SHALL NOT BE PERFORMED WITHIN 96 HOURS OF RAIN FALL. <br />6.3. OVER POTENTIAL (HIGH POTENTIAL) TESTING ON BUSSES GREATER THAN 1000 AMPS (OR MODIFICATION OF SERVICES) GREATER THAN 400 AMPS AND EACH <br />PHASE TO GROUND IN ACCORDANCE WITH SWITCH GEAR / SWITCH BOARD MANUFACTURES RECOMMENDATIONS FOR ONE MINUTE. THE INSULATION SHALL <br />WITHSTAND THE OVER POTENTIAL TEST VOLTAGE APPLIED. <br />6.4. GROUND-FAULT PROTECTION SYSTEM SHALL BE TESTED USING PRIMARY INJECTION FOR PICK UP TESTS. RELAY TIMING SHALL BE IN ACCORDANCE WITH <br />MANUFACTURERS SPECIFICATIONS. <br />6.5. PROVIDE TWO COPIES OF ACCEPTANCE OF FIRE ALARM SYSTEM BY LOCAL FIRE AUTHORITY. <br />6.6. INSULATION RESISTANCE (MEGGER) (AC AND DC (1000v) FOR ONE MINUTE) SHALL PROVIDE 50 MEGOHMS OR GREATER. TESTING MAY BE PERFORMED BY <br />CONTRACTOR, WITH WRITTEN CERTIFICATION BY LICENSED CONTRACTOR. <br />7.WARRANTY <br />7.1. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FURNISHED BY THEM UNDER THIS CONTRACT FOR A PERIOD OF (2) YEARS FROM THE <br />DATE OF FINAL ACCEPTANCE OF THE WORK BY THE OWNER. ANY DEFECTS DEVELOPING DURING THE WARRANTY PERIOD TRACEABLE TO MATERIALS OR <br />WORKMANSHIP SHALL BE CORRECTED AT THE CONTRACTORS EXPENSE. <br />7.2. THE ENGINEER AND OWNER RETAIN THE RIGHT TO REQUIRE REMOVAL AND INSTALLATION OF ANY MATERIAL OR EQUIPMENT NOT IN COMPLIANCE WITH THE <br />PROVISIONS AND STANDARDS OF THESE DRAWINGS AND SPECIFICATIONS. NO CLAIM FOR ADDITIONAL COMPENSATION WILL BE ALLOWED FOR WORK <br />PERFORMED IN THIS REGARD. <br />7.3. THE CONTRACTOR AGREES TO TRANSFER ALL MANUFACTURERS/SUPPLIERS WARRANTIES AND GUARANTEES TO THE OWNER. THIS INCLUDES COMPLETION OF <br />ALL DOCUMENTATION FOR THE MANUFACTURER/SUPPLIER. <br />8.SERVICE <br />8.1. PROVIDE AND INSTALL NEW SERVICE SECTION AS SHOWN ON DRAWINGS. SES SHALL BEAR U.L. LABEL, HAVE COPPER BUSSING - SILVER PLATED AND AMPERAGE <br />RATING AS SHOWN ON DRAWINGS. METERING AND PRIMARY PULL SECTION SHALL BE BARRIERED FROM OTHER WORK AND APPROVED BY BOTH THE LOCAL <br />UTILITY COMPANY AND AUTHORITY HAVING JURISDICTION. <br />8.2. GROUND FAULT PROTECTION SHALL BE PROVIDED FOR SERVICES RATED 150 VOLTS TO GROUND OR GREATER ON ALL SERVICE DISCONNECTS GREATER THAN <br />1000A. <br />8.3. GROUND FAULT PROTECTION ON MAINS AND SUB-MAINS MUST HAVE AUDIBLE/VISIBLE ALARMS. <br />8.4. ENCLOSURES SHALL MEET UL & PUBLIC UTILITY REQUIREMENTS BARRIERED BETWEEN SECTIONS, LINE AND LOAD, BOTH BARRIERED. <br />8.5. NO COVERS GREATER THAN 1/3 HEIGHT OF EQUIPMENT. <br />8.6. FULL SIZED NEUTRAL BUSSING AND NON-TAPERED BUSSING WILL BE STANDARD. ALL SPACE WILL BE FULLY BUSSED FOR FUTURE. ALL BUSSING WILL BE <br />PHYSICALLY BARRIERED. <br />8.7. ENCLOSURES SHALL MEET UL & PUBLIC UTILITY REQUIREMENTS BARRIERED BETWEEN SECTIONS, LINE AND LOAD, BOTH BARRIERED. <br />8.8. ALL SERVICES SHALL BE PROVIDED WITH A PERMANENTLY ATTACHED, ENGRAVED PLATE SHOWING S.E.S. BUSSING TO INCLUDE ALL TORQUE VALUES FOR <br />PREVENTATIVE MAINTENANCE PURPOSES. <br />8.9. ALL SERVICES SHALL BE LISTED FOR FRONT ACCESSIBILITY ONLY, WHERE LOCATED ON WALLS, ALL OTHERS SHALL BE FRONT. <br />8.10. ALL SERVICE DOORS SHALL BE HINGED AND LOCKABLE. <br />8.11. NEW SERVICE INSTALLATIONS FOR MULTI TENANT FACILITIES WITH MULTIMETER SERVICES, SHALL HAVE ALL UNDERGROUND CONDUITS INSTALLED IN THE <br />APPROPRIATE SERVICE SECTION. DO NOT INSTALL CONDUITS WHERE THERE EXISTS A POSSIBILITY OF IMPROPER CABLE ROUTING TO OTHER SECTIONS. <br />9.DISTRIBUTION <br />9.1. PANELBOARDS (EXISTING): ADD CIRCUIT BREAKERS AS REQUIRED FOR CIRCUITING. MATCH PRECISELY BRAND AND A.I.C. RATING. TANDEM AND PIGGY-BACK <br />BREAKERS ARE NOT PERMITTED. ALL LUGS OR CONNECTORS TO BE 90 DEGREE C RATED. <br />9.2. PANELBOARDS (NEW): TO BE RATED AS SHOWN ON DRAWINGS. PROVIDE NEMA ENCLOSURES AS REQUIRED BY CODE. CUTOUT BOXES TO BE ENLARGED FOR <br />DOUBLE NEUTRALS AND LUGS AND SHALL BE SIZED TO ACCOMMODATE ISOLATED GROUND BUSS AND NORMAL GROUND BUSS. ALL TERMINATIONS OR <br />CONNECTORS TO BE RATED 75 DEGREE CENTIGRADE MINIMUM. <br />9.3. CIRCUIT BREAKERS WILL BE SWITCH RATED AND AMBIENT COMPENSATED FOR ALL CIRCUITS. PROVIDE SWITCHED NEUTRALS ON ALL CIRCUIT BREAKERS <br />FEEDING CLASS 1 AND CLASS 2 AREAS WITH NEUTRALS. GFCI ON CIRCUITS WITH NEUTRALS TO DEVICES ABOVE CLASSIFIED AREAS. ALL LIGHTING <br />PANELS/CIRCUIT BREAKERS SHALL BE RATED FOR CONTINUOUS DUTY. <br />9.4. ALL EQUIPMENT (PANELS, DISCONNECT SWITCHES, STARTERS, ETC.) WILL BE MARKED WITH BLACK ENGRAVERS STOCK TAGS EMBOSSED WITH 1/4" HIGH LETTERS <br />DESCRIBING EACH ITEM. CONDUCTORS WILL BE MARKED AT ALL TERMINATION AND JUNCTION POINTS (PANELS, JUNCTION BOXES, SPLICES, ETC.) WITH LABELS <br />BEARING THE PANEL AND CIRCUIT NUMBER WHICH FEEDS EACH CONDUCTOR (PER NEC 210.4, 300.3). <br />9.5. ALL PANELBOARDS WILL HAVE TYPED DIRECTORY CARDS IDENTIFYING ALL CIRCUITS AND SPACES REVISED, IF NECESSARY, FOR THIS WORK. EXISTING <br />PANEL/PANELBOARDS SHALL HAVE EACH EXISTING CIRCUIT TRACED AND VERIFIED. UPDATE PANEL DIRECTORY AS NEEDED. <br />9.6. TRANSFORMERS 15 KVA AND ABOVE SHALL BE 150 DEGREE CENTIGRADE TEMPERATURE RISE ABOVE 40 DEGREE CENTIGRADE AMBIENT. ALL INSULATING <br />MATERIALS TO BE IN ACCORDANCE WITH NEMA ST20-1972 STANDARDS FOR A 220 DEGREE C. UL COMPONENT RECOGNIZED INSULATION SYSTEM. SINGLE PHASE <br />TRANSFORMERS 15 KVA THROUGH 167 KVA, AND THREE PHASE TRANSFORMERS THROUGH 112.5 KVA SHALL BE DESIGNED SO THEY CAN BE EITHER FLOOR OR <br />WALL MOUNTED. THE TRANSFORMER SHALL BE LISTED BY UNDERWRITERS LABORATORY FOR THE SPECIFIED TEMPERATURE RISE. <br />9.7. LABEL ALL PANELS/TRANSFORMERS/DISCONNECTS WITH "WARNING" - ELECTRICAL EQUIPMENT - DANGER - QUALIFIED PERSONNEL ONLY TO OPERATE AND OPEN <br />EQUIPMENT. <br />9.8. ALL ELECTRICAL EQUIPMENT INCLUDING SWITCHBOARDS, PANELBOARDS, INDUSTRIAL CONTROL PANELS AND MOTOR CONTROL CENTERS SHALL BE MARKED IN <br />ACCORDANCE WITH NEC ARTICLE #110.16 FOR FLASH HAZARD. (REFERENCE NFPA #70E-2000 AND ANSI #Z535.4-1998). <br />9.9. DISCONNECT SWITCHES SHALL BE HEAVY-DUTY, QUICK-MAKE, QUICK-BREAK, HORSEPOWER RATED, NEMA 1 INDOOR, NEMA 3R GASKETED, (4X) NEMA 12, OR <br />NEMA 7 AS APPLICABLE WITH CLASS RK-1 BUSSMAN FUSES AND REJECTION CLIPS, SIZED OR AS SHOWN ON DRAWINGS. PROPER DISCONNECTS PER N.E.C. WILL <br />BE PROVIDED FOR EACH PIECE OF ELECTRICAL EQUIPMENT. <br />9.10. MANUAL MOTOR STARTERS WITH THERMAL OVERLOADS WILL BE PROVIDED FOR MOTORS 1/2 HP TO 1 HP. SQUARE 'D' CLASS 2510, 2511, 2512 OR EQUAL, AMBIENT <br />COMPENSATED AS REQUIRED. <br />9.11. MAGNETIC MOTOR STARTERS WITH THERMAL OVERLOADS, (2) AUXILIARY CONTACT SWITCHES, INTERNAL LINE VOLTAGE TO 24 VOLT TRANSFORMER (250VA. MIN) <br />WITH PROPER PRIMARY/SECONDARY PROTECTION, AMBIENT COMPENSATED, GREEN RUNNING LIGHT, HAND-OFF-AUTO, ACROSS THE LINE STARTERS TO 25HP. <br />WILL BE PROVIDED WITH EACH MOTOR AS SHOWN ON THE DRAWING (ONE HORSEPOWER TO 25 H.P.). <br />9.12. ALL PANELBOARDS SHALL HAVE HINGED, LOCKABLE COVERS. ALSO SEE SECTION 7.4. <br />10.LUMINAIRES <br />10.1. FURNISH AND INSTALL ALL LUMINAIRES COMPLETE WITH LAMPS, WHIPS AND ACCESSORIES. ALL RECESSED LUMINAIRES WILL BE RATED FOR USE IN ANY CEILING <br />APPLICATIONS AND BE THERMALLY PROTECTED. <br />10.2. MOUNTING TYPE AND VOLTAGE OF LUMINAIRES IS THE RESPONSIBILITY OF THE CONTRACTOR. (4) EARTHQUAKE CLIPS WILL BE INSTALLED ON EACH FIXTURE <br />MOUNTED IN GRID OR FLANGE TYPE CEILINGS. FLUORESCENT FIXTURE LENSES WILL BE 100% ACRYLIC, .125" THICK MINIMUM. <br />10.3. ALL LUMINAIRES TO BE INSTALLED IN SYMMETRICAL MANNER FREE FROM LIGHT LEAKS AND DIRTY LENSES OR REFLECTORS. <br />10.4. ALL LAY-IN LUMINAIRES IN ACOUSTICAL CEILING SYSTEMS WILL BE INSTALLED PER ASTM STANDARDS C635, C635M, C636, C636M, AND UBC STANDARD 25-2 VERIFY <br />WITH LOCAL BUILDING AUTHORITY. <br />10.5. SUPPORT LUMINAIRES PER UBC-1507 WITH TWO LOOSE SIZE 9 WIRES TO STRUCTURES ON OPPOSITE CORNERS AND 2 TAUGHT SIZE 9 WIRE TO STRUCTURES AT <br />CORNERS OR TO GRID WITHIN 3" OF FIXTURE. ALL H.I.D. OR FLUORESCENT LUMINAIRES WILL HAVE GREATER THAN .9 POWER FACTOR BALLASTS. <br />11.TELEPHONE SYSTEM <br />11.1. PROVIDE AND INSTALL A COMPLETE SYSTEM OF EMPTY RACEWAYS (WITH PULL STRING). PROVIDE REQUIRED/REQUESTED INFORMATION TO TELEPHONE <br />COMPANY PRIOR TO INSTALLATION. <br />12.DATA/INFORMATION SYSTEMS <br />12.1. PROVIDE AND INSTALL A COMPLETE SYSTEM OF RACEWAYS (CABLE TRAYS, J-HOOKS, CONDUIT SLEEVES) OF PREFERABLY OPEN CONSTRUCTION WITH PULL LINE. <br />RACEWAYS TO BE CONTINUOUS. <br />13.FIRE ALARM SYSTEM <br />13.1. PROVIDE AND INSTALL A COMPLETE AND WORKING FIRE ALARM SYSTEM, POWER LIMITED BY NEC DEFINITION. ALL WIRING TO BE CLASS "A" OR "B" WITH DEVICES <br />AND CONDUCTORS TO BE U.L., F.M., OR C.S.A. LISTED AND APPROVED (LABELS ON EQUIPMENT). <br />13.2. ALL WIRING TO BE #14 A.W.G. CU., STRANDED, 105 DEGREE INSULATED, PLENUM RATED. INSTALLED IN CONDUIT OR RACEWAY WITH SIX (6) FEET SPACING <br />BETWEEN OUTPUT/INPUT PER N.F.P.A. <br />13.3. SYSTEM INSTALLATION AND DEVICES WILL BE IN ACCORDANCE WITH ALL PERTINENT AND THE MOST STRINGENT REQUIREMENTS (ONLY POWER LIMITED <br />SYSTEMS WILL BE ACCEPTED) OF: <br />13.3.1. NATIONAL FIRE PROTECTION AGENCY (NFPA) NFPA 70 - NATIONAL ELECTRICAL CODE <br />13.3.2. NFPA 72 <br />13.3.3. NFPA 71 - CENTRAL STATION SIGNALING <br />13.3.4. ARS TITLE 26, CHAPTERS 2-3 (ARIZONA STATE FIRE CODE) <br />13.3.5. ADA AND ARIZONA HANDICAPPED REGULATIONS <br />13.3.6. INTERNATIONAL CONSTRUCTION BUILDING AND FIRE CODES <br />13.3.7. WORK SHALL BE INSTALLED BY UL CERTIFIED INSTALLERS <br />13.4. DO NOT POSITION SMOKE DETECTORS WITHIN 36" OF ANY AIR HANDLING GRILLES (SUPPLY OR RETURN) OR WITHIN 12" OF FACILITY LIGHTING FIXTURES. <br />13.5. ALL DEVICE BACK BOXES TO BE MOUNTED FLUSH, PERPENDICULAR TO FINISH WALLS AND CEILING SURFACES USING STANDARD "TRADE" MOUNTING HARDWARE. <br />13.6. CONTRACTOR WILL COMPLY WITH PROJECT SPECIFICATIONS, AND SUPPLY SHOP DRAWINGS, CUTS, SAMPLES, ETC. TO THE ENGINEER WITHIN 5 DAYS OF <br />CONTRACT AS REQUIRED. <br />13.7. SYSTEM MONITORED AT ACM, U.L. APPROVED MONITORING STATION LOCATED IN CITY OF PROJECT. <br />13.8. EXTEND EXISTING SYSTEM TO NEW DEVICES. LOADS ON EACH ZONE, OR RUN TO BE CALCULATED (RESULTS TO ENGINEER) PRIOR TO INSTALLATION. ADDITIONAL <br />RUNS, ZONES, CONTROL CARDS, ETC., REQUIRED FOR FACP/FAANN TO BE INCLUDED IN BID. <br />13.9. GAMEWELL IS AN ACCEPTABLE MANUFACTURER. <br />13.10. ALL SPRINKLER SYSTEMS WITH GREATER THAN 100 HEADS SHALL HAVE MINIMUM 4 ZONE CLASS B FIRE ALARM CONTROL PANEL WITH AUTO DIALER. (UNLESS <br />COMPLETE CLASS A FIRE ALARM SYSTEM IS INDICATED ON PLANS). SPRINKLER SYSTEMS WITH LESS THAN 100 HEADS REQUIRE ONLY CONNECTION TO WATER <br />FLOW AND TAMPER SWITCH. (UNLESS OTHERWISE NOTED OR INDICATED) <br />14.ELEVATORS <br />14.1. ALL INSTALLATIONS AND EQUIPMENT SHALL COMPLY WITH N.E.C. ARTICLE 620 AND ASME/ANSI STANDARDS A17.1. <br />14.2. SPECIFIC REQUIREMENTS INCLUDE BUT ARE NOT LIMITED TO: <br />14.2.1. A SEPARATE BRANCH CIRCUIT WITH DISCONNECT (CAPABLE OF BEING LOCKED IN THE OPEN POSITION, LOCATED IN THE MACHINE ROOM)(BRADY NO. 2AF98 OR <br />EQUAL.) PROVIDED FOR EACH ELEVATOR CAR FOR LIGHTS, FANS AND/OR ACCESSORIES. <br />14.2.2. HVAC SYSTEMS SHALL BE PROVIDED WITH SEPARATE BRANCH CIRCUIT. (CAPABLE OF BEING LOCKED IN THE OPEN POSITION LOCATED IN THE MACHINE ROOM) <br />(BRADY NO. 2AF98 OR EQUAL.) HVAC TAPS WITH OTHER UNITS). <br />14.2.3. A SEPARATE BRANCH CIRCUIT FOR EQUIPMENT ROOM LIGHTING AND GFCI PROTECTED OUTLET (REQUIRED). <br />14.2.4. DEDICATED BRANCH CIRCUITS FOR HOIST WAY PIT LIGHTING AND GFCI OUTLET (REQUIRED). MINIMUM LIGHTING SHALL BE 4'-0" FLUORESCENT STRIP, (2) LAMPS <br />AND WIRE GUARD. <br />14.2.5. NO CONDUITS, PIPES, DUCTS OR OTHER RACEWAY SYSTEMS SHALL PASS INTO OR THROUGH THE ELEVATOR EQUIPMENT ROOM OR HOIST WAY WHICH IS NOT <br />DIRECTLY RELATED TO ELEVATOR OPERATION. (THIS DOES NOT INCLUDE REQUIRED SPRINKLER PIPING). <br />14.2.6. IF SPRINKLERS ARE PRESENT, IN EITHER OR BOTH ELEVATOR EQUIPMENT ROOM AND ELEVATOR HOIST WAY, THE CONTRACTOR SHALL PROVIDE A SHUNT TRIP <br />MECHANISM AS A MEANS OF DISCONNECTING POWER TO THE AFFECTED ELEVATOR AND CONTROLLER PRIOR TO THE APPLICATION OF WATER. (SPRINKLER <br />ACTIVATION OUTSIDE OF ELEVATOR EQUIPMENT ROOM OR HOIST WAY SHALL NOT DISCONNECT POWER). <br />14.2.7. INSTALL 165° RATE OF RISE HEAT DETECTORS IN THE ELEVATOR EQUIPMENT ROOM, TOP OF HOIST WAY AND BOTTOM OF HOIST WAY - ALL WITH AUX. CONTACTS <br />FOR CONNECTION TO BOTH FIRE ALARM CONTROL PANEL AND SHUNT TRIP MECHANISM IN EQUIPMENT ROOM. ANY DETECTOR ACTIVATION WILL SHUNT TRIP THE <br />EQUIPMENT. <br />14.2.8. INSTALL SMOKE DETECTORS IN ELEVATOR EQUIPMENT ROOM, TOP OF HOIST WAY AND BOTTOM OF HOIST WAY AND CONNECT TO FIRE ALARM CONTROL PANEL <br />AS A MEANS OF PRELIMINARY SHUT DOWN WARNING, AND TO ELEVATOR CONTROLLER FOR RECALL FUNCTION. <br />14.2.9. PROVIDE SMOKE DETECTORS IN ALL ELEVATOR LOBBIES. PROVIDE AUXILIARY CONTACTS AT EACH SMOKE DETECTOR FOR CONNECTION TO ELEVATOR <br />CONTROLLER FOR ALTERNATE FLOOR RECALL MODE DURING A FIRE. <br />THESE SPECIFICATIONS ARE BASED UPON THE 2020 NEC. THE CODE(S) ADOPTED BY THE AUTHORITY HAVING JURISDICTION SUPERCEDE THE SECTIONS LISTED BELOW BUT ONLY IF THOSE REQUIREMENT(S) ARE MORE STRINGENT. <br />ELECTRICAL SPECIFICATIONS <br />NE <br />W <br /> <br />2 <br />0 <br />0 <br />0 <br />A <br /> <br />S <br />E <br />R <br />V <br />I <br />C <br />E <br />10 <br />0 <br />1 <br /> <br />S <br />. <br /> <br />G <br />R <br />A <br />N <br />D <br /> <br />A <br />V <br />E <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />ARCHITECT: <br />CONSULTANTS: <br />SEAL & SIGNATURE: <br />ISSUED FOR: <br />DESCRIPTION:DATE: <br />KEY PLAN <br />SHEET NAME: <br />PROJECT NO.: <br />DRAWN BY: <br />CHECKED BY: <br />SCALE: <br />SHEET NO.: <br />Copyright 120DEGREEZ 2019c <br />NORTH <br />San Diego | Los Angeles <br />www.120degreez.com <br />619.323.1515 | 310.364.5228 <br />Mechanical | Electrical | Plumbing <br />MEP Project No.: 25−070