GENERAL NOTES <br />1.PROVIDE A COMPLETE AND OPERABLE LIGHTING CONTROL SYSTEM AS SHOWN. CONTRACTOR <br />IS TO PROVIDE ALL REQUIRED EQUIPMENT, HARDWARE, SOFTWARE, SWITCHES, OCCUPANCY <br />SENSORS, ETC. FOR A COMPLETE AND TITLE 24 APPROVED CERTIFICATION. <br />2.THE MAXIMUM LENGTH OF A LOCAL DATALINE FROM EACH PANEL 1600ft USING FREE <br />TOPOLOGY WITHOUT A REPEATER. <br />3.CABLE RUNS ARE CONTINUOUS BETWEEN CONNECTED DEVICES, NO SPLICING ALLOWED. <br />4.ANALOG PHOTOCELLS AND OCCUPANCY SENSORS: (4) #18 AWG STRANDED Cu CONTROL <br />CONDUCTORS PER DEVICE, LABELED SPARE, +24V, COM. 1000 FEET MAXIMUM RUN <br />5.CONSULT MANUFACTURER FOR LOADING WITH EMERGENCY AND NORMAL CIRCUITS. <br />6.USE REMOTE LOW VOLTAGE INPUT CABINETS WHEN ADDITIONAL POWER FOR DIGITAL <br />CONTROLS IS REQUIRED, OR WHEN UP TO 16 ADDITIONAL LOCAL ANALOG INPUTS ARE <br />NECESSARY. <br />KEY NOTES <br />LIGHTING CONTROL PANEL SHOWN IS TO <br />BE CEC CERTIFIED. THE NETWORK CLOCK (DTC) IS TO BE ASTRONOMICAL. <br />VERIFY OVERRIDE SWITCH LOCATIONS WITH ARCHITECT. VERIFY QUANTITY, LAYOUT, AND <br />ORIENTATION WITH PLANS. SWITCHES SHALL BE COMPATIBLE WITH LIGHTING CONTROL <br />SYSTEM CONFIRM DEVICE FINISHES AND ALL SWITCH BUTTON ENGRAVINGS WITH THE <br />OWNER REPRESENTATIVE PRIOR TO ORDERING. <br />TYPICAL ELECTRICAL PANEL SHOWN. REFER TO SINGLE LINE DIAGRAM AND PANEL <br />SCHEDULES FOR ALL LIGHTING CIRCUITS TO BE CONTROLLED. <br />CONTROL POWER: 1 AMP, 120VAC -277VAC CONSTANT HOT DEDICATED SOURCE. IF <br />CONTROL IS REQUIRED UNDER EMERGENCY CONDITION, POWER SHOULD BE PROVIDED TO <br />THE CONTROL PROCESSOR IN BOTH NORMAL AND EMERGENCY CONDITIONS. <br />1 <br />2 <br />3 <br />4 <br />ELECTRICAL <br />PANEL(S) <br />3 <br />2 <br />1 <br />PC120 OR 277V CONTROL POWER4 <br />LOW VOLTAGE <br />CABLE PER MANF. <br />SPECS <br />EXTERIOR PHOTOCELL ON NORTH FACING BUILDING PARAPET <br />FOR EXTERIOR LIGHTING. MOUNT FACING NORTHERN SKY. <br />PROPERLY SEAL CONDUIT PENETRATION THROUGH CEILING. <br />LOW VOLTAGE ANALOG BUTTON STATION <br />LOW VOLTAGE CABLE PER MANF. SPECS <br />MAXIMUM 1000' RUN. <br />TYPICAL LIGHTING LOAD - ADDITIONAL ZONES <br />ON SAME CIRCUIT AS ZONE 1 <br />TYPICAL LIGHTING LOAD - ZONE 1 <br />HOT LINE <br />LOAD <br />LOCAL LINE <br />VOLTAGE SWITCH <br />(TYPICAL) <br />LIGHT FIXTURE <br />( LIGHT FIXTURE WITH <br />EM BATTERY) <br />N <br />LIGHTING <br />CONTROL PANEL <br />(TYP.) <br />LAMP <br />LAMP <br />ELECTRONIC <br />DIMMING <br />DRIVER <br />(0-10 VDC)YLW <br />YLW <br />GRY( - ) <br />VIO( + ) <br />RED <br />RED <br />BLU <br />BLUGND <br />GRN <br />GRY( - ) <br />VIO( + ) <br />BLU HOT <br />NEW <br />0-10V <br />DIMMER <br />SWITCH <br />* NOT USED <br />(CAP WITH WIRE NUT) <br />YLW* <br />HOT <br />NEUTRAL <br />DEVICE <br />SYMBOL DESCRIPTION OPERATION BASIS OF DESIGN <br />OEM/PART NO. <br />LOW VOLTAGE WALL MOUNTED SWITCHES <br />LOW VOLTAGE ON/OFF <br />SWITCH <br />USE WITH VACANCY AND OCCUPANCY SENSOR(S) FOR <br />MANUAL-ON OPERATION (AUTO-ON IN CORRIDORS AND <br />RESTROOMS). PROVIDES ON/OFF CAPABILITY AT ONE OR MORE <br />SWITCH LOCATIONS. <br />See control configurations below for more information. <br />LEVITON <br />LOW VOLTAGE ON/OFF & <br />RAISE/LOWER SWITCH <br />USE WITH VACANCY AND OCCUPANCY SENSOR(S) FOR MANUAL-ON <br />OPERATION. PROVIDES ON/OFF/RAISE/LOWER CAPABILITY AT <br />ONE OR MORE SWITCH LOCATIONS. <br />See control configurations below for more information. <br />LEVITON <br />LOW VOLTAGE ON/OFF & <br />RAISE/LOWER SWITCH, DUAL <br />TECH OCCUPANCY SENSOR <br />VACANCY SENSOR WITH MANUAL-ON AUTO OFF. USE WITH LOAD <br />CONTROLLER, 0-10V DIMMING (ON/OFF & RAISE/LOWER) <br />See control configurations below for more information. <br />LEVITON <br /> WALL MOUNTED SWITCHES/SENSORS <br />DUAL TECHNOLOGY WALL <br />SWITCH OCCUPANCY <br />SENSOR, 1-POLE <br />VACANCY SENSOR WITH MANUAL-ON AUTO OFF. <br />AUTO-ON IN CORRIDORS AND STAIRWELLS. <br />LEVITON <br />WALL SWITCH 0-10V DIMMING <br />OCCUPANCY SENSOR <br />VACANCY SENSOR, 0-10V DIMMING WITH MANUAL-ON AUTO OFF. <br />AUTO-ON PUBLIC REST ROOMS. <br />LEVITON <br />WALL SWITCH 0-10V DIMMING 0-10V DIMMING WITH MANUAL-ON AUTO OFF. <br />LEVITON <br />CEILING MOUNTED SENSORS <br />LOW VOLTAGE DUAL TECH <br />CEILING MOUNTED <br />OCCUPANCY SENSOR <br />VACANCY SENSOR (EXCEPT OCCUPANCY IN CORRIDORS AND <br />RESTROOMS) <br />Quantity of adjacent lower case letters indicates quantity of relays/ dimming <br />circuits required. See Sensor Configurations for more information. Exact <br />control function is determined by the ballast/ fixture type. <br />LEVITON <br />LOW VOLTAGE CEILING <br />MOUNT, AUTOMATIC DIMMING <br />CONTROL PHOTOCELL <br />DAYLIGHT SENSOR. PROVIDES ON/OFF AND AUTOMATIC DIMMING <br />CONTROL FOR DAYLIGHT HARVESTING. <br />Number in parenthesis indicates the average workplane "Target Illumination" <br />symbol value. Adjacent lower case letter(s) indicates switch leg(s) controlled. <br />Adjacent "*, ** and +" indicates portion of switchleg controlled by sensor <br />where" * " indicates Primary Sidelit Daylit Zone, " ** " Secondary Sidelit Daylit <br />Zone, and " + " indicates Skylit Daylit Zone. <br />LEVITON <br />NOTES: <br />LOW VOLTAGE SWITCH CONFIGURATIONS: <br />Adjacent lower case letters indicates quantity of switch legs to be controlled. <br />Exact control function is determined by the ballast/fixture type. Upper case <br />subscript "K" indicates Locking switch for the subsequent lower case letter. <br />Upper case subscript "V" indicates Vandal Resistant switch. Upper case <br />subscript "DM" indicates Dual Mode control switch. <br />SENSOR CONFIGURATIONS: <br />"y" indicates that switch leg "y" to be configured in a "Auto ON 100% / Auto <br />OFF" and be controlled (continuously dimmed) by the associated ceiling <br />sensor remote switch on the wall. <br />"y,(y)" indicates that switch leg "y" to be configured in a "Auto on 50% / Manual <br />ON 100% / Auto OFF" and be controlled (continuously dimmed) by the <br />associated distributed lighting controls. <br />"(y)" indicates that switch leg "y" is to be configured in a "Manual ON / Auto <br />OFF" (vacancy sensor) and be controlled by the associated distributed lighting <br />controls. <br />L <br />$ <br />LD <br />LD <br />$D <br />$D <br />OS <br />DS <br />y,(y) <br />(40) <br />y,(y) <br />LD <br />Ky <br />LD <br />Vy <br />LD <br />DM <br />y <br />(y) <br />y,(y) <br />OS <br />OS <br />OS <br />PC COMMENTS RESPONSE #1 01/29/2025A <br />al <br />l <br /> <br />i <br />d <br />e <br />a <br />s <br />, <br /> <br />d <br />e <br />s <br />i <br />g <br />n <br />s <br /> <br />a <br />n <br />d <br /> <br />p <br />l <br />a <br />n <br />s <br /> <br />r <br />e <br />p <br />r <br />e <br />s <br />e <br />n <br />t <br />e <br />d <br /> <br />b <br />y <br /> <br />t <br />h <br />i <br />s <br /> <br />d <br />r <br />a <br />w <br />i <br />n <br />g <br /> <br />a <br />r <br />e <br /> <br />t <br />h <br />e <br /> <br />e <br />x <br />c <br />l <br />u <br />s <br />i <br />v <br />e <br /> <br />p <br />r <br />o <br />p <br />e <br />r <br />t <br />y <br /> <br />o <br />f <br />Go <br />u <br />v <br />i <br />s <br /> <br />E <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />a <br />n <br />d <br /> <br />s <br />h <br />a <br />l <br />l <br /> <br />n <br />o <br />t <br /> <br />b <br />e <br /> <br />r <br />e <br />p <br />r <br />o <br />d <br />u <br />c <br />e <br />d <br /> <br />i <br />n <br /> <br />w <br />h <br />o <br />l <br />e <br /> <br />o <br />r <br /> <br />i <br />n <br /> <br />p <br />a <br />r <br />t <br /> <br />w <br />i <br />t <br />h <br />o <br />u <br />t <br /> <br />t <br />h <br />e <br /> <br />e <br />x <br />p <br />r <br />e <br />s <br />s <br /> <br />p <br />r <br />i <br />o <br />r <br /> <br />w <br />r <br />i <br />t <br />t <br />e <br />n <br /> <br />p <br />e <br />r <br />m <br />i <br />s <br />s <br />i <br />o <br />n <br /> <br />o <br />f <br /> <br />s <br />a <br />i <br />d <br /> <br />e <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />s <br />, <br /> <br />a <br />n <br />y <br /> <br />u <br />n <br />a <br />u <br />t <br />h <br />o <br />r <br />i <br />z <br />e <br />d <br /> <br />r <br />e <br />u <br />s <br />e <br /> <br />o <br />f <br /> <br />t <br />h <br />e <br />s <br />e <br /> <br />p <br />l <br />a <br />n <br />s <br /> <br />o <br />t <br />h <br />e <br />r <br /> <br />t <br />h <br />a <br />n <br /> <br />f <br />o <br />r <br /> <br />t <br />h <br />e <br /> <br />p <br />r <br />o <br />j <br />e <br />c <br />t <br /> <br />a <br />n <br />d <br /> <br />l <br />o <br />c <br />a <br />t <br />i <br />o <br />n <br /> <br />s <br />h <br />o <br />w <br />n <br /> <br />i <br />s <br /> <br />p <br />r <br />o <br />h <br />i <br />b <br />i <br />t <br />e <br />d <br />. <br />JOB NO. <br />SUBMITTAL <br />DATE <br />SHEET TITLE <br />SHEET NO. <br />CLIENT: <br />REVISION <br />DATE <br />21 <br />3 <br />0 <br /> <br />E <br /> <br />4 <br />T <br />H <br /> <br />S <br />T <br /> <br /># <br />2 <br />0 <br />0 <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />BSB: MR230056; Gouvis: 66467 <br />WATER REVISIONS <br />09/12/2025 <br />1ST PLAN CHECK SUBMITTAL 08/20/2024 <br />2ND PLAN CHECK SUBMITTAL 1/29/2025 <br />PC COMMENTS RESPONSE #2 04/17/2025B <br />3RD PLAN CHECK SUBMITTAL 04/17/2025 <br />PC COMMENTS RESPONSE #3 07/10/2025C <br />4TH PLAN CHECK SUBMITTAL 07/10/2025 <br />WATER REVISIONS 09/12/2025D <br />WATER REVISIONS 09/12/2025 <br />PC COMMENTS RESPONSE #4 10/10/2025E <br />CLIENT REVISIONS 10/10/20251 <br />OL <br />I <br />V <br />E <br /> <br />C <br />R <br />E <br />S <br />T <br /> <br />R <br />E <br />S <br />I <br />D <br />E <br />N <br />T <br />I <br />A <br />L <br />21 <br />5 <br />0 <br /> <br />E <br />. <br /> <br />F <br />O <br />U <br />R <br />T <br />H <br /> <br />A <br />N <br />D <br /> <br />2 <br />1 <br />6 <br />0 <br /> <br />E <br />. <br /> <br />F <br />O <br />U <br />R <br />T <br />H <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />OL <br />I <br />V <br />E <br /> <br />C <br />R <br />E <br />S <br />T <br />DATE SIGNED: 7/8/25 <br />E-0.3C <br />DETAILS <br />LIGHTING CONTROL WIRING DIAGRAM 1 <br />TYPICAL 0-10V DIMMING WIRING DIAGRAM 24LIGHTING CONTROL SYSTEM REQUIREMENTS <br />5OCCUPANCY CONTROL SPECIFICATIONS <br />1.OCCUPANCY SENSOR AND CONTROL ACCESSORIES SHALL BE U.L. AND C.E.C. CERTIFIED. <br />2.OCCUPANCY SENSOR AND CONTROL ACCESSORIES SHALL BE BY A SINGLE MANUFACTURER AND BE COMPLIANT WITH ALL APPLICABLE <br />FEDERAL, STATE AND LOCAL ENERGY CODES. <br />3.CEILING MOUNTED OCCUPANCY SENSORS (CONTINUOUS DIMMED) SHALL HAVE A LOW-PROFILE APPEARANCE. SENSOR SHALL UTILIZE <br />DUAL TECHNOLOGY (ULTRASONIC/PIR) WITH 360 DEGREE COVERAGE. THE USE OF MICROPHONES IS NOT AN ACCEPTABLE SENSING <br />TECHNOLOGY. INITIAL OCCUPANCY DETECTION SHALL BE BOTH PIR AND ULTRASONIC SENSORS. "STAY ON" DETECTION SHALL BE EITHER <br />PIR AND UTLRASONIC SENSORS. IN OFFICES WITH DESKTOP ACTIVITIES THE COVERAGE SHALL BE HAND MOTION AND SHALL NOT EXCEED <br />500 SQ.FT. AT A MAXIMUM CEILING HEIGHT OF 10 FT. IN CORRIDORS, STORAGE ROOMS AND NON-DESKTOP ACTIVITIES COVERAGE SHALL <br />BE HALF-STEP, WALKING MOTION AND SHALL NOT EXCEED 1200 SQ.FT. AT A MAXIMUM CEILING HEIGHT OF 10 FT. <br />4.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO LOCATE AND AIM SENSORS IN THE CORRECT LOCATION REQUIRED FOR COMPLETE <br />AND PROPER VOLUMETRIC COVERAGE PER THE MANUFACTURER'S RECOMMENDATIONS. ROOMS SHALL HAVE NINETY (90) TO ONE <br />HUNDRED (100) PERCENT COVERAGE AND SHALL ACCOMMODATE ALL HABITS OF SINGLE OR MULTIPLE OCCUPANTS AT ANY LOCATION <br />WITHIN THE ROOM. THE LOCATIONS AND QUANTITIES OF SENSORS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY <br />THE ROOMS THAT ARE TO BE PROVIDED WITH SENSORS. THE CONTRACTOR SHALL PROVIDE PROVIDE ADDITIONAL SENSORS AS <br />REQUIRED TO PROPERLY AND COMPLETELY COVER THE RESPECTIVE ROOM. ADDITIONALLY, IT MAY BE NECESSARY FOR THE <br />CONTRACTOR TO MAKE ADJUSTMENTS, CHANGE THE LOCATION OR TYPE OF SENSOR TO OBTAIN PROPER OPERATION IN A SPECIFIC <br />ROOM. THE USE OF FACTORY SUPPLIED INTERNAL MASKING (PIR) SHALL BE PROVIDED AND INSTALLED AS REQUIRED TO LIMIT DETECTION <br />TO WITHIN THE CONTROLLED SPACE ONLY. THE CONTRACTOR SHALL HAVE FINAL RESPONSIBILITY FOR PROPER OPERATION OF THE <br />SYSTEM IN EACH ROOM AND SHOULD THEREFORE MAKE LABOR ALLOWANCES FOR CHANGES AND ADJUSTMENTS. <br />5.CEILING MOUNTED SENSORS SHOULD BE LOCATED IN THE SPACE TO BE COVERED, A MINIMUM OF 4', PREFERABLY 5' AWAY FROM THE <br />LATCH SIDE OF THE DOOR, 2" TO 3" AWAY FROM THE WALL AND 3' TO 4' FROM AN AIR SUPPLY REGISTER. DO NOT MOUNT SENSORS OVER <br />A DOORWAY OR BEHIND A FULL HEIGHT DOOR. SENSORS SHALL BE AIMED IN THE DIRECTION OF THE SPACE TO BE COVERED. DO NOT AIM <br />SENSORS TOWARD A DOORWAY. <br />6.UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL SENSORS SHALL BE ADJUSTED FOR A TIME DELAY OF TWENTY (20) MINUTES. <br />7.PROPER JUDGEMENT MUST BE EXERCISED IN EXECUTING THE INSTALLATION SO AS TO ENSURE THE BEST POSSIBLE INSTALLATION IN <br />THE AVAILABLE SPACE AND TO OVERCOME LOCAL DIFFICULTIES DUE TO SPACE LIMITATIONS OR INTERFERENCE OF BUILDING <br />STRUCTURAL COMPONENTS. THE CONTRACTOR SHALL ALSO PROVIDE, AT THE PROJECT, THE TRAINING NECESSARY TO FAMILIARIZE THE <br />OWNER'S PERSONNEL WITH THE OPERATION, USE, MAINTENANCE, ADJUSTMENT AND PROBLEM SOLVING DIAGNOSIS OF THE OCCUPANCY <br />SENSING DEVISED AND SYSTEMS. <br />8.INTERCONNECT ALL DEVICES AS REQUIRED. UNLESS PROHIBITED BY LOCAL CODE, INTERCONNECTING SHALL BE MADE WITH <br />PLENUM-RATED CABLING ROUTED NEATLY INTO AND ABOVE THE ACCESSIBLE CEILING. CABLES SHALL BE SUPPORTED WITH DEDICATED <br />SUPPORT WIRES AND J-HOOKS. WHERE LOCAL CODE REQUIRES LOW VOLTAGE CABLING TO BE ROUTED IN CONDUIT, INCLUDE ALL COSTS <br />IN BASE BID TO PROVIDE APPROPRIATLEY-SIZED SYSTEM OF CONDUITS AND JUNCTION BOXES TO ROUTE INTERCONNECTION CABLING. <br />J-BOXES/CONTROLLERS SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS AND NEVER IN HARD-LID CEILING AREAS. <br />9.WHERE CODE OR LOCAL AHJ REQUIREMENTS REQUIRE THE INSTALLATION OF ALL LOW-VOLTAGE CONDUCTORS TO BE INSTALLED IN <br />CONDUIT - CONTRACTOR TO PROVIDE ALL REQUIRED MANUFACTURER SPECIFIC EQUIPMENT JUNCTION BOXES AND CONDUIT ADAPTORS <br />AS REQUIRED. <br />10.AS PART OF THE "RECORD DRAWINGS" INDICATE ON THE REFLECTED CEILING PLAN THE EXACT LOCATION (CEILING TILE OR ACCESS <br />PANEL) OF ANY ABOVE CEILING DEVICE. <br />11.OCCUPANCY SENSOR CONTROLLED RECEPTACLE BRANCH CIRCUIT RELAY SHALL BE CONNECTED TO CEILING MOUNTED OCCUPANCY <br />SENSOR. RELAY SHALL TURN ON WHEN THE ROOM IS OCCUPIED, REGARDLESS OF THE CONFIGURATION OF THE LIGHTING CONTROL <br />STATE. <br />12.LOW VOLTAGE WALL SWITCH CONTROLS SHALL BE DECORA STYLE, LOW-VOLTAGE, MOMENTARY SWITCHES WITH COLOR TO MATCH <br />OTHER WALL DEVICES AND SWITCHES. LOWER CASE LETTERS INDICATE SWITCHING CONFIGURATION. PROVIDE SWITCHING OR DIMMING <br />CONTROL DEVICES AS REQUIRED BY DRAWINGS. <br />13.OCCUPANCY SENSOR AND CONTROL ACCESSORIES SHALL BE MANUFACTURED BY COOPER CONTROLS, LUTRON, HUBBLE, LEVITON, AND <br />WATTSTOPPER. <br />14.THE OCCUPANTS SENSING CONTROLS WILL PROVIDE ON/OFF CONTROL AUTOMATICALLY TO REDUCE LIGHTING POWER BY AT LEAST 50% <br />WHEN THE AREAS ARE UNOCCUPIED FOR THE FOLLOWING AREAS AND CONTROLS NO OTHER AREAS. <br />1.THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE FURNISHING OF ALL MATERIAL, LABOR, EQUIPMENT, AND <br />SERVICES, IN CONNECTION WITH THE INSTALLATION OF A COMPLETE AND FULLY FUNCTIONING AND CODE <br />COMPLIANT INSTALLATION. <br />2.IT IS THE INTENT OF THE CONTRACT DOCUMENTS, WHICH ARE PRESENTED IN A DIAGRAMMATIC FORMAT, TO <br />PROVIDE CONTRACTOR INFORMATION THAT SUPPLEMENTS AND ENHANCES THE GENERALLY ACCEPTED <br />CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES EMPLOYED IN CONNECTION <br />WITH INSTALLATION OF THIS TYPE OF PRODUCT/SYSTEM. <br />3.THE CONTRACTOR SHALL ALSO INCORPORATE THE REQUIREMENTS OF THE MANUFACTURER'S INSTALLATION <br />INSTRUCTIONS/WARRANTY REQUIREMENTS AS PART OF THE REQUIREMENTS OF THE CONSTRUCTION <br />DOCUMENTS. IN THE EVENT OF A CONFLICT BETWEEN THE CONTRACT DOCUMENT REQUIREMENTS AND THE <br />MANUFACTURERS INSTALLATION REQUIREMENTS, THE MORE STRINGENT REQUIREMENTS SHALL APPLY - UNLESS <br />THE MORE STRINGENT REQUIREMENT VOIDS APPLICABLE WARRANTIES OR VIOLATES THE REQUIREMENTS OF <br />THE LOCAL AUTHORITY HAVING JURISDICTION. ANY SUCH CONFLICT SHALL IMMEDIATELY BE BROUGHT TO THE <br />ATTENTION OF THE ENGINEER IN WRITING THROUGH THE FORMAL RFI PROCESS. <br />4.REFER TO THE ASSOCIATED SCHEDULES, SCHEMATICS, DRAWINGS, AND SPECIFICATIONS FOR DETAILED <br />INFORMATION/REQUIREMENTS ON THIS PRODUCT/SYSTEM. <br />5.SHOP DRAWINGS SHALL BE SUBMITTED PER THE GENERAL SPECIFICATION REQUIREMENTS SHOWING ALL <br />COMPONENTS, WIRING CONFIGURATIONS AND PROGRAMMING SCHEDULES. SUBMITTALS SHALL BE MADE <br />SPECIFIC TO THE PROJECT - GENERIC SUBMITTALS SHALL BE REJECTED. <br />LIGHTING CONTROLS 3