CITY OF SANTA ANA <br />Planning and Building Agency <br />Substrate: 20 gauge metal roof simulation in field l Fastener. (60) #14-14 x 2 in. s4rews n 1 <br />FOR PERMIT ISSUANCE <br />Dynamic Strength Testing of Anchorage Connector <br />Requirements per Manufacturer Established OSHA Anchor Testing <br />(Figure 1 ) <br />Master ID: <br />1. Determine drop height required to create a 3,600 lb. <br />Requirement <br />S <br />m le <br />Sample <br />Sample <br />#2 <br />#3 <br />or 5,000 lb. test load. <br />#1 <br />2. Install anchorage connector according to manufac- <br />turer's instructions. <br />Tested to load (lbs.) <br />5,000 <br />5,000 <br />5,000 <br />Anchorage connector <br />withstands applied load? <br />Pass <br />Pass <br />Pass <br />3. Make sure that the anchorage connector is oriented <br />so that the test load is applied in the intended direc- <br />tion of use. <br />4. Release load. <br />COMPLIANT <br />Yes <br />Yes <br />Yes <br />Dynamic Strength Testing of Anchorage Connectors <br />Requirements per Manufacturer Established OSHA Anchor Testing <br />(Figure 2) <br />1. Determine drop height required to create a 3,600 lb. <br />Requirement <br />Sample <br />Sample <br />Sample <br />or 5,000 lb. test load. <br />#1 <br />#2 <br />#3 <br />2. Install anchorage connector according to manufac- <br />turer's instructions. <br />Tested to load (lbs.) <br />5,000 <br />5,000 <br />5,000 <br />Anchorage connector <br />withstands applied load? <br />Pass <br />Pass <br />Pass <br />3. Make sure that the anchorage connector is oriented <br />so that the test load is applied in the intended direc- <br />tion of use. <br />4. Release load. <br />COMPLIANT <br />Yes <br />Yes <br />Yes <br />Page 3 of 3 <br />