<br /> <br /> <br /> <br /> <br /> <br /> <br /> <br />This document is a Property of BTCPower Inc. and shall not be <br />copied, reproduced, or used as the basis for sale or manufacture <br />of apparatus without written permission. <br />23-Sep-22 Rev D <br /> <br />360kW High Power DC Charger <br />INSTALLATION AND USER’S MANUAL <br />Page 88 of 89 <br />APPENDIX <br /> <br />Case 1: Tank is prefilled (standard at delivery) <br />• Tank is prefilled to operate one cable with a maximal total length of 8m. <br />Coolant level before connecting the cable is visible in the venting tube (refer <br />to figure 1, number 2). <br />• Starting up the cooling system for 5min. <br />• Check: Coolant level must be as shown in figure 2. <br />• If coolant level is below 100mm, refill coolant according to the instruction <br />case 2. <br /> <br />Case 2: Refill coolant to have the right amount of coolant in cooling system <br />• General amount of coolant is 1.1dl per meter cable. <br /> <br />Refilling Coolant in Cooling Unit: <br />• Open cap no.1 and no.2 (figure 1, no.1 and no.2) <br />• Use a funnel to avoid spillage. Connect the funnel to tube no.1 (refer to figure 1, <br />no. 1). <br />• Tube no.1 (figure 1, no.1) => fill in coolant <br />• Tube no.2 (figure 1, no.2) => venting hole <br />• Coolant level must be minimum 100mm and maximum 150mm according to the <br />viewing pipe (refer to figure 2). <br />• Close cap no.1 and no.2 (refer to figure 1) <br />• Start up the cooling system for 5min. <br />• Check: Coolant level must be as shown in figure 2. If coolant level is below <br />100mm, refill according to instruction in case 2. <br /> <br /> <br /> <br /> <br /> <br /> <br />