<br />ENERGY CALCULATIONS
<br />228011-04
<br />3rd & Broadway Residential
<br />Tower Tenant Interiors
<br />1103 North Broadway
<br />Santa Ana, CA 92701
<br />06.13.2022 ISSUE FOR PLAN CHECK
<br />1 06.17.2024 REVISION TO PERMIT
<br />2 10.04.2024 REVISION TO PERMIT REVIEW
<br />2
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />This document is used to demonstrate compliance for mechanical systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive
<br />path outlined in §140.4, or §141.0(b)2 for alterations.
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 1 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />A. GENERAL INFORMATION
<br />01 Project Location (city)Santa Ana 04 Total Conditioned Floor Area 176200
<br />02 Climate Zone 8 05 Total Unconditioned Floor Area 205000
<br />03 Occupancy Types Within Project:06 # of Stories (Habitable Above Grade)10
<br />Office (B)Retail (M)Non-refrigerated Warehouse (S)
<br />Hotel/ Motel Guest Rooms (R-1)School (E)Healthcare Facility (I)
<br />High-Rise Residential (R-2/R-3)Relocatable Class Bldg (E)Other (Write In)
<br />B. PROJECT SCOPE
<br />This table Includes mechanical systems or components that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in
<br />§140.4, or §141.0(b)2 for alterations.
<br />01 02 03
<br />Air System(s)Wet System Components Dry System Components
<br />Heating Air System Water Economizer Air Economizer
<br />Cooling Air System Pumps Electric Resistance Heat
<br />Mechanical Controls System Piping Fan Systems
<br />Mechanical Controls (existing to remain, altered
<br />or new)Cooling Towers Ductwork (existing to remain, altered or new)
<br />Chillers Ventilation
<br />Boilers Zonal Systems/ Terminal Boxes
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 3 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
<br />This table is used to demonstrate compliance for mechanical equipment with mandatory requirements found in §110.1 and §110.2(a) and prescriptive requirements found in §140.4(a),
<br />§140.4(b) and §140.4(k) or §141.0(b)2 for alterations.
<br />Dry System Equipment Sizing (includes air conditioners, condensers, heat pumps, VRF, furnaces and unit heaters)
<br />01 02 03 04 05 06 07 08 09 10 11
<br />Name or Item
<br />Tag
<br />Equipment Category per
<br />Tables 110.2
<br />Equipment Type per Tables 110.2 / Title
<br />20
<br />Smallest Size
<br />Available1
<br />§140.4(a)
<br />Equipment Sizing per Mechanical Schedule (kBtu/h)
<br />§140.4 (a&b)
<br />Heating Output2,3 Cooling Output2,3 Load Calculations3,4
<br />Per Design
<br />(kBtu/h)
<br />Rated
<br />(kBtu/h)
<br />Supp.
<br />Heating
<br />Output
<br />(kBtu/h)
<br />Sensible
<br />Per Design
<br />(kBtu/h)
<br />Rated
<br />(kBtu/h)
<br />Total
<br />Heating
<br />Load
<br />(kBtu/h)
<br />Total
<br />Sensible
<br />Cooling
<br />Load
<br />(kBtu/h)
<br />ACCU-R01 Variable Refrigerant Flow VRF heat pump, air cooled Yes 189 189 0 168 168 88.3 159.6
<br />ACCU-R03C Variable Refrigerant Flow VRF heat pump, air cooled Yes 81 81 0 72 72 32.8 55.9
<br />ACCU-R07A Variable Refrigerant Flow VRF heat pump, air cooled Yes 216 216 0 192 192 75.9 76.5
<br />ACCU-R07B Variable Refrigerant Flow VRF heat pump, air cooled Yes 162 162 0 216 216 120.9 137.1
<br />ACCU-R08A
<br />THRU
<br />ACCU-R14A
<br />(TYP.)
<br />Variable Refrigerant Flow VRF heat pump, air cooled Yes 162 162 0 144 144 100.4 134
<br />ACCU-R08B
<br />THRU
<br />ACCU-R14B
<br />(TYP.)
<br />Variable Refrigerant Flow VRF heat pump, air cooled Yes 216 216 0 192 192 135.4 161.1
<br />ACCU-R15A &
<br />15B Variable Refrigerant Flow VRF heat pump, air cooled Yes 216 216 0 192 192 129.6 191.8
<br />1FOOTNOTES: Equipment shall be the smallest size, within the available options of the desired equipment line, necessary to meet the design heating and cooling loads of the building per
<br />§140.4(a). Healthcare facilities are excepted.
<br />2It is common practice to show rated output capacity on the equipment schedule. Sensible cooling output comes from specification sheet tables.
<br />3 If equipment is heating only, leave cooling output and load blank. If equipment is cooling only, leave heating output and load blank.
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 4 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
<br />Dry System Equipment Sizing (includes air conditioners, condensers, heat pumps, VRF, furnaces and unit heaters)
<br />01 02 03 04 05 06 07 08 09 10 11
<br />4 Authority Having Jurisdiction may ask for load calculations used for compliance per §140.4(b).
<br />Dry System Equipment Efficiency (other than Package Terminal Air Conditioners (PTAC) and Package Terminal Heat Pumps (PTHP))
<br />01 02 03 04 05 06 07 08 09
<br />Name or Item
<br />Tag
<br />Size Category
<br />(Btu/h)
<br />Heating Mode Cooling Mode
<br />Rating
<br />Condition
<br />( °F)
<br />Efficiency Unit
<br />Minimum
<br />Efficiency
<br />Required per
<br />Tables 110.2 /
<br />Title 20
<br />Design Efficiency Efficiency Unit
<br />Minimum
<br />Efficiency
<br />Required per
<br />Tables 110.2 /
<br />Title 20
<br />Design Efficiency
<br />ACCU-R01 >=135,000 and <240,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.2 3.2 EER
<br />IEER
<br />10.6
<br />13.9
<br />11.1
<br />21.9
<br />ACCU-R03C >=65,000 and <135,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.3 3.48 EER
<br />IEER
<br />11
<br />14.6
<br />13
<br />23.6
<br />ACCU-R07A >=135,000 and <240,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.2 3.53 EER
<br />IEER
<br />10.6
<br />13.9
<br />11
<br />23
<br />ACCU-R07B >=135,000 and <240,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.2 3.53 EER
<br />IEER
<br />10.6
<br />13.9
<br />11.1
<br />21.9
<br />ACCU-R08A
<br />THRU
<br />ACCU-R14A
<br />(TYP.)
<br />>=135,000 and <240,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.2 3.84 EER
<br />IEER
<br />10.6
<br />13.9
<br />12.1
<br />23
<br />ACCU-R08B
<br />THRU
<br />ACCU-R14B
<br />(TYP.)
<br />>=135,000 and <240,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.2 3.75 EER
<br />IEER
<br />10.6
<br />13.9
<br />11
<br />23
<br />ACCU-R15A &
<br />15B >=135,000 and <240,000 47 °Fdb/ 43
<br />°Fwb OSA HSPF 3.2 3.75 EER
<br />IEER
<br />10.6
<br />13.9
<br />11
<br />23
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 5 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />G. PUMPS
<br />This section does not apply to this project.
<br />H. FAN SYSTEMS & AIR ECONOMIZERS
<br />This section does not apply to this project.
<br />I. SYSTEM CONTROLS
<br />This table is used to demonstrate compliance with mandatory controls in §110.2 and §120.2 and prescriptive controls in §140.4(f) and (n) or requirements in §141.0(b)2E for altered
<br />space conditioning systems.
<br />01 02 03 04 05 06 07 08 09
<br />System Name System
<br />Zoning
<br />Conditioned
<br />Floor Area
<br />Being Served
<br />(ft2)
<br />Thermostats
<br />§110.2(b) & (c)1,
<br />§120.2(a)or §141.0(b)2E
<br />Shut-Off
<br />Controls
<br />§120.2(e)
<br />Isolation
<br />Zone
<br />Controls
<br />§120.2(g)
<br />Demand Response
<br />§110.12 and §120.2(b)
<br />Supply Air
<br />Temp. Reset
<br />§140.4(f)
<br />Window Interlocks per
<br />§140.4(n)
<br />IDU-LXX-RXXX (VRF
<br />INDOOR UNITS -DWELLING
<br />UNITS)
<br />Single zone <= 25,000 ft2 Setback NA: HRR
<br />dwelling unit
<br />NA: Single
<br />Zone DR Tstat per §110.12 NA: Single
<br />Zone NA: HRR dwelling unit
<br />IDU-LXX-CXX (VRF INDOOR
<br />UNITS FOR RESIDENTIAL
<br />CORRIODORS FLR 7-15)
<br />Single zone <= 25,000 ft2 Setback NA: HRR
<br />dwelling unit
<br />NA: Single
<br />Zone DR Tstat per §110.12 NA: Single
<br />Zone NA: HRR dwelling unit
<br />IDU-L07-AXXX (VRF
<br />INDOOR UNITS OF
<br />AMENITY SPACES ON 7TH
<br />FLR)
<br />Single zone <= 25,000 ft2 Setback Occ. Sensor Occ. Sensor DR Tstat per §110.12 NA: Single
<br />Zone NA: No operable windows
<br />IDU-L06-XX (VRF INDOOR
<br />UNITS OF AMENITY SPACES
<br />ON 6TH FLR)
<br />Single zone <= 25,000 ft2 Setback Occ. Sensor Occ. Sensor DR Tstat per §110.12 NA: Single
<br />Zone NA: No operable windows
<br />IDU-L06-CXX (VRF INDOOR
<br />UNITS FOR 6TH FLR
<br />CORRIODORS)
<br />Single zone <= 25,000 ft2 Setback Occ. Sensor NA: Single
<br />Zone DR Tstat per §110.12 NA: Single
<br />Zone NA: No operable windows
<br />IDU-L01-XX (VRF INDOOR
<br />UNITS ON 1ST FLR)Single zone <= 25,000 ft2 Setback Occ. Sensor Occ. Sensor DR Tstat per §110.12 NA: Single
<br />Zone NA: No operable windows
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 7 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />04 05 06 07
<br />System Name ACCU-R01, IDU-L01-05 System Design OA CFM
<br />Airflow1 60 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 1 - Mail
<br />Room
<br />R01G17
<br />Corridor 371 3 55.65
<br />DCV NA: Not required per
<br />§120.1(d)3
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 55.65 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R01, IDU-L01-03 System Design OA CFM
<br />Airflow1 535 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 1 - West
<br />Lobby
<br />R01H16
<br />Lobbies 1070 5 535
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 535 18 Ventilation for this System Complies?Yes
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 8 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />04 05 06 07
<br />System Name ACCU-R03C, IDU-L01-01 System Design OA CFM
<br />Airflow1 480 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 1 - East
<br />Lobby
<br />R01H08
<br />Lobbies 955 5 477.5
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 477.5 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R03C, IDU-L01-02 System Design OA CFM
<br />Airflow1 35 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 1 -
<br />Elevator
<br />Lobby
<br />R01H10
<br />Corridor 232 1 34.8
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 9 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />17 Total System Required Min OA CFM 34.8 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R06, IDU-L06-02 System Design OA CFM
<br />Airflow1 125 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 6 -
<br />Conference
<br />Room R06F15
<br />Conference/ meeting 243 8 121.5
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor
<br />NA: System < 2kW
<br />demand + manual
<br />shutoff per
<br />§120.2(e)3 exception
<br />17 Total System Required Min OA CFM 121.5 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R06, IDU-L06-01 System Design OA CFM
<br />Airflow1 125 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 2 of 26)
<br />Project Address: Date Prepared: 2024-09-27T16:57:22-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-09-27 13:57:29
<br />C. COMPLIANCE RESULTS
<br />Table C will indicate if the project data input into the compliance document is compliant with mechanical requirements. This table is not editable by the user. If this table says "DOES
<br />NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D., or the table indicated as not compliant for guidance.
<br />01
<br />AND
<br />02
<br />AND
<br />03
<br />AND
<br />04
<br />AND
<br />05
<br />AND
<br />06
<br />AND
<br />07
<br />AND
<br />08 09
<br />System
<br />Summary
<br />§110.1,
<br />§110.2,
<br />§140.4
<br />Pumps
<br />§140.4(k)
<br />Fans/
<br />Economizers
<br />§140.4(c),
<br />§140.4(e)
<br />System
<br />Controls
<br />§110.2,
<br />§120.2,
<br />§140.4(f)
<br />Ventilation
<br />§120.1
<br />Terminal Box
<br />Controls
<br />§140.4(d)
<br />Distribution
<br />§120.3,
<br />§140.4(l)
<br />Cooling Towers
<br />§110.2(e)2 Compliance Results
<br />(See Table F)(See Table G)(See Table H)(See Table I)(See Table J)(See Table K)(See Table L)(See Table M)
<br />Yes AND AND AND Yes AND Yes AND AND Yes AND COMPLIES
<br />Mandatory Measures Compliance (See Table Q for Details)COMPLIES
<br />D. EXCEPTIONAL CONDITIONS
<br />This table is auto-filled with uneditable comments because of selections made or data entered in tables throughout the form.
<br />Table J indicates continuous ventilation is being used as an alternative to a balanced systems. However, Table J also indicates that both supply and exhaust fans are being used. Please
<br />verify the same ventilation type is being used in all dwelling units.
<br />E. ADDITIONAL REMARKS
<br />This table includes remarks made by the permit applicant to the Authority Having Jurisdiction.
<br />{General Remarks} This form is being submitted under Tenant Interior scope only. Only VRF Indoor units (IDU) are part of Tenant Interior scope. All the Condensing units listed on the
<br />form (ACCU) are under Core & Shell scope, submitted under Permit No. B-101107990, B-101107992 & B-101107993. For Core and shell NRCC compliance forms, refer to the Core &
<br />Shell Mechanical Drawings.
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 6 of 26)
<br />Project Address: Date Prepared: 2024-09-27T16:57:22-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-09-27 13:57:29
<br />I. SYSTEM CONTROLS
<br />1FOOTNOTES: Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non-central electric heaters, fireplaces or decorative gas appliances, wood stoves are not required to
<br />have setback thermostats.
<br />*Notes: Controls with a * require a note in the space below explaining how compliance is achieved. EX: system 1: SA Temp Reset: Exempt because zones compliant with §140.4(d) ;
<br />EXCEPTION 1 to §140.4(f)
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />This table is used to demonstrate compliance with mandatory ventilation requirements in §120.1 and §120.2(e)3B for all nonresidential, high-rise residential and hotel/motel
<br />occupancies. For alterations, only ventialtion systems being altered within the scope of the permit application need to be documented in this table. In lieu of this table, the required
<br />outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented in a spreadsheet.
<br />01 Check the box if the project is showing ventilation calculations on the plans, or attaching the calculations instead of completing this table.
<br />02 Check this box if the project included Nonresidential or Hotel/Motel spaces
<br />Check this box if the project included new or altered high-rise residential dwelling units.
<br />03 Check the box if the project is using natural ventilation in any nonresidential or hotel/motel spaces to meet required ventilation rates per §120.1(c)2.
<br />Nonresidential and Hotel/ Motel Ventilation Systems
<br />04 05 06 07
<br />System Name ACCU-R01, IDU-L01-04 System Design OA CFM
<br />Airflow1 45 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 1 -
<br />Leasing Office
<br />R01G16
<br />Office space 300 3 45
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 45 18 Ventilation for this System Complies?Yes