<br />R2.M0.6
<br />ENERGY CALCULATIONS
<br />228011-04
<br />3rd & Broadway Residential
<br />Tower Tenant Interiors
<br />1103 North Broadway
<br />Santa Ana, CA 92701
<br />1
<br />06.13.2022 ISSUE FOR PLAN CHECK
<br />1 06.17.2024 REVISION TO PERMIT
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 10 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />Level 6 -
<br />Conference
<br />Room R06F16
<br />Conference/ meeting 244 8 122
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor
<br />NA: System < 2kW
<br />demand + manual
<br />shutoff per
<br />§120.2(e)3 exception
<br />17 Total System Required Min OA CFM 122 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R06, IDU-L06-04 System Design OA CFM
<br />Airflow1 450 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 6 -
<br />Game Room
<br />R06H16
<br />Multipurpose assembly 900 20 450
<br />DCV Provided per
<br />§120.1(d)4
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 450 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R06, IDU-L06-05 System Design OA CFM
<br />Airflow1 480 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 11 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 6 - Multi
<br />Function
<br />Assembly
<br />R06G14
<br />Multipurpose assembly 954 30 477
<br />DCV Provided per
<br />§120.1(d)4
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 477 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R06, IDU-L06-03 System Design OA CFM
<br />Airflow1 95 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 6 -
<br />Business
<br />center
<br />R06G16
<br />Office space 630 6 94.5
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 94.5 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R06, IDU-L06-C01 & C02 System Design OA CFM
<br />Airflow1 245 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 12 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 6 -
<br />Corridor
<br />R06G16
<br />Corridor 1382 5 207.3
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor NA: Not required
<br />space type
<br />17 Total System Required Min OA CFM 207.3 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R07B, IDU-L07-A03 System Design OA CFM
<br />Airflow1 45 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 7 -
<br />Corridor
<br />R07H12 &
<br />R07J11A
<br />Corridor 300 2 45
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor
<br />NA: System < 2kW
<br />demand + manual
<br />shutoff per
<br />§120.2(e)3 exception
<br />17 Total System Required Min OA CFM 45 18 Ventilation for this System Complies?Yes
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 13 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />04 05 06 07
<br />System Name ACCU-R07B, IDU-L07-A04 System Design OA CFM
<br />Airflow1 315 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 7 - Club
<br />House
<br />R07J11B
<br />Office space 1157 20 300
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor NA: Not required
<br />space type
<br />17 Total System Required Min OA CFM 300 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R07A, IDU-L07-A01 System Design OA CFM
<br />Airflow1 235 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 7 - Yoga
<br />Studio
<br />R07H13
<br />Gym/ sports arena (play area)470 10 235 235 235
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 14 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />17 Total System Required Min OA CFM 235 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R07A, IDU-L07-A02A & A02B System Design OA CFM
<br />Airflow1 470 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 7 -
<br />Fitness Studio
<br />R07J13
<br />Gym/ sports arena (play area)935 10 467.5 467.5 470
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor Provided per
<br />§120.1(d)5
<br />17 Total System Required Min OA CFM 467.5 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R07A & B, IDU-L07-C01 & C02 System Design OA CFM
<br />Airflow1 255 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 15 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />Level 7 -
<br />Circulation
<br />R07G13
<br />Corridor 1239 1 185.85
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor NA: Not required
<br />space type
<br />17 Total System Required Min OA CFM 185.85 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R08A & B, IDU-L08-C01 & C02
<br />(Typ. for Flr 8-14)
<br />System Design OA CFM
<br />Airflow1 255 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 08-14
<br />Circulation Corridor 1362 1 204.3
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor NA: Not required
<br />space type
<br />17 Total System Required Min OA CFM 204.3 18 Ventilation for this System Complies?Yes
<br />04 05 06 07
<br />System Name ACCU-R15A & B, IDU-L15-C01,C02A
<br />& C02B
<br />System Design OA CFM
<br />Airflow1 320 System Design
<br />Transfer Air CFM 0
<br />Air Filtration per §120.1(c) and §141.0(b)2 2
<br />Provided per §120.1(c) (NR and
<br />Hotel/Motel))
<br />08 09 10 11 12 13 14 15 16
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 16 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />Space Name
<br />ot item Tag
<br />Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
<br />DCV or Sensor Controls per §120.1(d)3,
<br />§120.1(d)5, and §120.1(e)3 6Occupancy Type4
<br />Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Shower
<br />heads/
<br />toilets
<br /># of
<br />people5
<br />Required
<br />Min OA
<br />CFM
<br />Required
<br />Min CFM
<br />Provided per Design
<br />CFM
<br />Level 15 -
<br />Circulation Corridor 1700 2 255
<br />DCV
<br />NA: Area < 150ft2 or
<br />design occupancy <
<br />10 people
<br />Occ Sensor NA: Not required
<br />space type
<br />17 Total System Required Min OA CFM 255 18 Ventilation for this System Complies?Yes
<br />1 FOOTNOTES: System CFM should include both mechanical and natural ventilation for the zone/system
<br />2 Air filtration requirements apply to the following three system types per §120.1(c)1A : space conditioning systems utilizing ducts to supply air to occupiable space; supply-only
<br />ventilation systems providing outside air to occupiable space; supply side of balanced ventilation systems including heat recovery and energy recovery ventilation systems providing
<br />outside air to occupiable space.
<br />3 Uniform Mechanical Code may have more stringent ventilation requirements; the most stringent code requirement takes precedence.
<br />4 See Standards Tables 120.1-A and 120.1-B.
<br />5 For lecture halls with fixed seating, the expected number of occupants shall be shall be determined in accordance with the California Building Code.
<br />6 §120.2(e)3 requires systems serving rooms that are required by §130.1(c) to have lighting occupancy sensing controls to also have occupancy sensing zone controls for ventilation.
<br />Examples of spaces which require lighting occupancy sensors include offices 250ft2 or smaller, multipurpose rooms less than 1,000 ft2, classrooms, conference rooms, restrooms, aisles
<br />and open areas in warehouses, library book stack aisles, corridors, stairwells, parking garages, and loading and unloading zones, unless excepted by §130.1(c).
<br />High-rise Residential Dwelling Unit Ventilation Systems
<br />Check the box if the system is using continuous ventilation to meet the ventilation requirements per §120.1(b)2Aivb
<br />19 20 21 22 23 24 25 26 27
<br />Space Name
<br />or Item Tag
<br />Mechanical Ventilation Required per §120.1(b) Ventilation per
<br />Design
<br />Local Exhaust Air Filtration per §120.1(b) 3Conditioned
<br />Floor Area
<br />(ft2)
<br /># of Bedrooms # of Dwelling
<br />Units
<br />Required
<br />Min OA
<br />CFM1
<br />Supply Air
<br />CFM
<br />Exhaust
<br />CFM
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 17 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />Studio Units
<br />ST_1 ( Flr 7 -
<br />14)
<br />480 0 1 21.9 355 50
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />Studio Units
<br />ST_1 Flr 15 480 0 1 21.9 530 50
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />1 Bed Room
<br />Units 1BR_1 (
<br />Flr 7 - 14)
<br />1047 1 1 46.41 675 50
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />1 Bed Room
<br />Units 1BR_2 (
<br />Flr 7 - 14)
<br />1054 1 1 46.62 705 50
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />2 Bed Room
<br />Units 2BR_1
<br />(Flr 7)
<br />1533 2 1 68.49 845 100
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />2 Bed Room
<br />Units 2BR_2
<br />(Flr 7-14)
<br />1041 2 1 53.73 1690 100
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />2 Bed Room
<br />Units 2BR_1
<br />(Flr 15)
<br />1494 2 1 67.32 1030 100
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />2 Bed Room
<br />Units 2BR_2
<br />(Flr 15)
<br />1038 2 1 53.64 2520 100
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />1 Bed Room
<br />Units 1BR_1
<br />(Flr 15)
<br />1446 1 1 58.38 1030 50
<br />Bathroom IAQ
<br />Provided per §120.1(b) Bathroom IAQ and Vent.
<br />Kitchen Range Hood2
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 18 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />J. VENTILATION AND INDOOR AIR QUALITY
<br />28 Is this a balanced system4 29 Meeting Outside Air Requirements?Yes
<br />1 FOOTNOTES: Uniform Mechanical Code may have more stringent ventilation requirements; the most stringent code requirement takes precedence.
<br />2 Kitchen range hood will be verified per NA7.18.1 to confirm model is rated by HVI.
<br />3 Air filtration requirements apply to the following three system types per §120.1(c)1A : space conditioning systems utilizing ducts to supply air to occupiable space; supply-only
<br />ventilation systems providing outside air to occupiable space; supply side of balanced ventilation systems including heat recovery and energy recovery ventilation systems providing
<br />outside air to occupiable space.
<br />4 A balanced ventilation system provides ventilation airflow to each dwelling-unit at a rate equal to or greater than the required minimum rate, but not more than twenty percent.
<br />K. TERMINAL BOX CONTROLS
<br />This section does not apply to this project.
<br />L. DISTRIBUTION (DUCTWORK and PIPING)
<br />This table is used to show compliance with mandatory pipe insulation requirements found in §120.3 and prescriptive requirements found in §140.4(l) for duct leakage testing.
<br />Duct Leakage Sealing
<br />The answers to the questions below apply to the following duct systems:SUPPLY & RETURN AIR DUCT
<br />- SA & RA Duct leakage testing triggered for these systems?No
<br />11 No The scope of the project includes only duct systems serving healthcare facilities
<br />12 Yes Duct system provides conditioned air to an occupiable space for a constant volume, single zone, space-conditioning system.
<br />13 Yes The space conditioning system serves less than 5,000 ft2 of conditioned floor area.
<br />14 No The combined surface area of the ducts in the following locations is more than 25% of the total surface area of the entire duct system:
<br />Outdoors
<br />In a space directly under a roof that has a U-factor greater than the u-factor of the ceiling, or if the roof does not meet the
<br />requirements of §140.3(a)1B or if the roof has fixed vents or openings to the outside/ unconditioned spaces
<br />In an unconditioned crawl space
<br />In other unconditioned spaces
<br />15 No The scope of the project includes extending an existing duct system, which is constructed, insulated or sealed with asbestos.
<br />16 No The scope of the project includes an existing duct system that is documented to have been previously sealed as confirmed through field verification
<br />and diagnostic testing in accordance with procedures in the Reference Nonresidential Appendix NA2.
<br />17 Duct system shall be sealed in acordance with the California Mechanical Code