<br />6/14/2024 1:40:48 AM
<br />BIM 360://007.3757.000 - Caribou Industries - 3rd & Broadway/228011-04_3RD-B_MECH_R20.rvt
<br />R2.M0.7
<br />ENERGY CALCULATIONS
<br />228011-04
<br />3rd & Broadway Residential
<br />Tower Tenant Interiors
<br />1103 North Broadway
<br />Santa Ana, CA 92701
<br />1
<br />06.13.2022 ISSUE FOR PLAN CHECK
<br />1 06.17.2024 REVISION TO PERMIT
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 19 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />L. DISTRIBUTION (DUCTWORK and PIPING)
<br />The answers to the questions below apply to the following duct systems:EXHAUST DUCT - TE & EA Duct leakage testing triggered for these systems?No
<br />11 No The scope of the project includes only duct systems serving healthcare facilities
<br />12 No Duct system provides conditioned air to an occupiable space for a constant volume, single zone, space-conditioning system.
<br />13 Yes The space conditioning system serves less than 5,000 ft2 of conditioned floor area.
<br />14 No The combined surface area of the ducts in the following locations is more than 25% of the total surface area of the entire duct system:
<br />Outdoors
<br />In a space directly under a roof that has a U-factor greater than the u-factor of the ceiling, or if the roof does not meet the
<br />requirements of §140.3(a)1B or if the roof has fixed vents or openings to the outside/ unconditioned spaces
<br />In an unconditioned crawl space
<br />In other unconditioned spaces
<br />15 No The scope of the project includes extending an existing duct system, which is constructed, insulated or sealed with asbestos.
<br />16 No The scope of the project includes an existing duct system that is documented to have been previously sealed as confirmed through field verification
<br />and diagnostic testing in accordance with procedures in the Reference Nonresidential Appendix NA2.
<br />17 Duct system shall be sealed in acordance with the California Mechanical Code
<br />M. COOLING TOWERS
<br />This section does not apply to this project.
<br />N. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION
<br />Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
<br />These documents must be provided to the building inspector during construction and can be found online at
<br />https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCI/
<br />Form/Title
<br />NRCI-MCH-01-E - Must be submitted for all buildings
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 20 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
<br />Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
<br />These documents must be provided to the building inspector during construction and can be found online at
<br />https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCA/
<br />Form/Title Systems/Spaces To Be Field
<br />Verified
<br />Studio Units ST_1 ( Flr 7 - 14);
<br />Studio Units ST_1 Flr 15; 1
<br />Bed Room Units 1BR_1 ( Flr 7
<br />- 14); 1 Bed Room Units
<br />1BR_2 ( Flr 7 - 14); 2 Bed
<br />Room Units 2BR_1 (Flr 7); 2
<br />Bed Room Units 2BR_2 (Flr
<br />7-14); 2 Bed Room Units
<br />2BR_1 (Flr 15); 2 Bed Room
<br />Units 2BR_2 (Flr 15); 1 Bed
<br />Room Units 1BR_1 (Flr 15);
<br />ACCU-R01, IDU-L01-04;
<br />ACCU-R01, IDU-L01-05;
<br />ACCU-R01, IDU-L01-03;
<br />ACCU-R03C, IDU-L01-01;
<br />ACCU-R03C, IDU-L01-02;
<br />ACCU-R06, IDU-L06-02;
<br />ACCU-R06, IDU-L06-01;
<br />ACCU-R06, IDU-L06-04;
<br />ACCU-R06, IDU-L06-05;
<br />ACCU-R06, IDU-L06-03;
<br />ACCU-R06, IDU-L06-C01 &
<br />C02; ACCU-R07B,
<br />IDU-L07-A03; ACCU-R07B,
<br />IDU-L07-A04; ACCU-R07A,
<br />IDU-L07-A01; ACCU-R07A,
<br />IDU-L07-A02A & A02B;
<br />ACCU-R07A & B, IDU-L07-C01
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 21 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
<br />Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
<br />These documents must be provided to the building inspector during construction and can be found online at
<br />https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCA/
<br />Form/Title Systems/Spaces To Be Field
<br />Verified
<br />NRCA-MCH-02-A - Outdoor Air must be submitted for all newly installed HVAC units. Note: MCH-02-A can be performed in conjunction with MCH-07-A
<br />Supply Fan VFD Acceptance (if applicable) since testing activities overlap.
<br />& C02; ACCU-R08A & B,
<br />IDU-L08-C01 & C02 (Typ. for
<br />Flr 8-14); ACCU-R15A & B,
<br />IDU-L15-C01,C02A & C02B
<br />NRCA-MCH-06-A Demand Control Ventilation Systems must be submitted for all systems required to employ demand controlled ventilation (refer to
<br />§120.1(c)3 ) can vary outside ventilation flow rates based on maintaining interior carbon dioxide (CO2) concentration setpoints.
<br />Level 6 - Game Room
<br />R06H16; Level 6 - Multi
<br />Function Assembly R06G14
<br />NRCA-MCH-19-A Occupancy Sensor Controls IDU-L07-AXXX (VRF INDOOR
<br />UNITS OF AMENITY SPACES
<br />ON 7TH FLR); IDU-L06-XX
<br />(VRF INDOOR UNITS OF
<br />AMENITY SPACES ON 6TH
<br />FLR); IDU-L06-CXX (VRF
<br />INDOOR UNITS FOR 6TH FLR
<br />CORRIODORS); IDU-L01-XX
<br />(VRF INDOOR UNITS ON 1ST
<br />FLR); ACCU-R01, IDU-L01-04;
<br />ACCU-R01, IDU-L01-05;
<br />ACCU-R01, IDU-L01-03;
<br />ACCU-R03C, IDU-L01-01;
<br />ACCU-R03C, IDU-L01-02;
<br />ACCU-R06, IDU-L06-04;
<br />ACCU-R06, IDU-L06-05;
<br />ACCU-R06, IDU-L06-03;
<br />ACCU-R07A, IDU-L07-A01;
<br />ACCU-R07A, IDU-L07-A02A &
<br />A02B
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 22 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
<br />Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
<br />These documents must be provided to the building inspector during construction and can be found online at
<br />https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCA/
<br />Form/Title Systems/Spaces To Be Field
<br />Verified
<br />NRCA-MCH-20 Multi-Family Ventilation Studio Units ST_1 ( Flr 7 - 14);
<br />Studio Units ST_1 Flr 15; 1
<br />Bed Room Units 1BR_1 ( Flr 7
<br />- 14); 1 Bed Room Units
<br />1BR_2 ( Flr 7 - 14); 2 Bed
<br />Room Units 2BR_1 (Flr 7); 2
<br />Bed Room Units 2BR_2 (Flr
<br />7-14); 2 Bed Room Units
<br />2BR_1 (Flr 15); 2 Bed Room
<br />Units 2BR_2 (Flr 15); 1 Bed
<br />Room Units 1BR_1 (Flr 15)
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 23 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />P. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION
<br />Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
<br />These documents must be completed by a HERS Rater and provided to the building inspector during construction. The final documents must be created by a HERS Provider's registry, but
<br />drafts can be found online at https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCV/
<br />Form/Title Systems/Spaces To Be Field
<br />Verified
<br />NRCV-MCH-24 Enclosure Air Leakage Worksheet NOTE: Must be completed by a HERS Rater Studio Units ST_1 ( Flr 7 - 14);
<br />Studio Units ST_1 Flr 15; 1
<br />Bed Room Units 1BR_1 ( Flr 7
<br />- 14); 1 Bed Room Units
<br />1BR_2 ( Flr 7 - 14); 2 Bed
<br />Room Units 2BR_1 (Flr 7); 2
<br />Bed Room Units 2BR_2 (Flr
<br />7-14); 2 Bed Room Units
<br />2BR_1 (Flr 15); 2 Bed Room
<br />Units 2BR_2 (Flr 15); 1 Bed
<br />Room Units 1BR_1 (Flr 15)
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 24 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />P. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION
<br />Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
<br />These documents must be completed by a HERS Rater and provided to the building inspector during construction. The final documents must be created by a HERS Provider's registry, but
<br />drafts can be found online at https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCV/
<br />Form/Title Systems/Spaces To Be Field
<br />Verified
<br />NRCV-MCH-27 High-rise Residential NOTE: Must be completed by a HERS Rater Studio Units ST_1 ( Flr 7 - 14);
<br />Studio Units ST_1 Flr 15; 1
<br />Bed Room Units 1BR_1 ( Flr 7
<br />- 14); 1 Bed Room Units
<br />1BR_2 ( Flr 7 - 14); 2 Bed
<br />Room Units 2BR_1 (Flr 7); 2
<br />Bed Room Units 2BR_2 (Flr
<br />7-14); 2 Bed Room Units
<br />2BR_1 (Flr 15); 2 Bed Room
<br />Units 2BR_2 (Flr 15); 1 Bed
<br />Room Units 1BR_1 (Flr 15)
<br />NRCV-MCH-32 Local Mechanical Exhaust NOTE: Must be completed by a HERS Rater Studio Units ST_1 ( Flr 7 - 14);
<br />Studio Units ST_1 Flr 15; 1
<br />Bed Room Units 1BR_1 ( Flr 7
<br />- 14); 1 Bed Room Units
<br />1BR_2 ( Flr 7 - 14); 2 Bed
<br />Room Units 2BR_1 (Flr 7); 2
<br />Bed Room Units 2BR_2 (Flr
<br />7-14); 2 Bed Room Units
<br />2BR_1 (Flr 15); 2 Bed Room
<br />Units 2BR_2 (Flr 15); 1 Bed
<br />Room Units 1BR_1 (Flr 15)
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 25 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />Q. MANDATORY MEASURES DOCUMENTATION LOCATION
<br />This table is used to indicate where mandatory measures are documented in the plan set or construction documentation.
<br />01 02
<br />Compliance with Mandatory Measures documented through MCH
<br />Mandatory Measures Note Block
<br />No
<br />03 04
<br />Mandatory Measure Plan sheet or construction document location
<br />Heating Equipment Efficiency per §110.1 Refer to Core & Shell Mechanical Drawing R1-M0.3
<br />Cooling Equipment Efficiency per §110.1 Refer to Core & Shell Mechanical Drawing R1-M0.3
<br />Furnace Standby Loss Control per §110.2(d) N/A
<br />Duct Insulation per §120.4 Refer to Tenant Interior Mechanical Dwg R2-M0.1 &
<br />Specification Section 23 07 13 Duct Insulation
<br />Heat Pump with Supplemental electric Resistance Heater Controls per §110.2(b) N/A
<br />The air duct and plenum system is designed per §120.4(a) -(f)Refer to Specification Section 23 07 13 Duct Insulation
<br />Kitchen range hoods shall be rated for sound in accordance with Section 7.2 of ASHRAE 62.2 N/A
<br />STATE OF CALIFORNIA
<br />Mechanical Systems
<br />NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
<br />CERTIFICATE OF COMPLIANCE NRCC-MCH-E
<br />Project Name: 3rd & Broadway West Building Report Page: (Page 26 of 26)
<br />Project Address: Date Prepared: 2024-06-14T02:27:10-04:00
<br />Registration Number:Generated Date/Time:Documentation Software: Energy Code Ace
<br />CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
<br />Schema Version: rev 20200601
<br />Compliance ID: 206053
<br />Report Generated: 2024-06-13 23:27:15
<br />DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
<br />I certify that this Certificate of Compliance documentation is accurate and complete.
<br />Documentation Author Name:
<br />Rashmi Holla
<br />Documentation Author Signature:
<br />Company:Signature Date:
<br />Address:CEA/ HERS Certification Identification (if applicable):
<br />City/State/Zip:Phone:
<br />RESPONSIBLE PERSON'S DECLARATION STATEMENT
<br />I certify the following under penalty of perjury, under the laws of the State of California:
<br />1.The information provided on this Certificate of Compliance is true and correct.
<br />2.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer)
<br />3.The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements
<br />of Title 24, Part 1 and Part 6 of the California Code of Regulations.
<br />4.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations,
<br />plans and specifications submitted to the enforcement agency for approval with this building permit application.
<br />5.I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
<br />inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
<br />Responsible Designer Name:Responsible Designer Signature:
<br />Company:Date Signed:
<br />Address:License:
<br />City/State/Zip:Phone:
<br />COSENTINI ASSOCIATES INC.
<br />1 S. WACKER DRIVE, 37TH FLOOR
<br />CHICAGO/ILLINOIS/60606
<br />RASHMI V. HOLLA
<br />+1-312-201-7437
<br />06/14/2024
<br />COSENTINI ASSOCIATES INC.
<br />498 SEVENTH AVENUE
<br />NEW YORK/NY/10018
<br />06/14/2024
<br />27670
<br />+1-212-615-3602
<br />DOUGLAS MASS
<br />1/15/2025
|