IN (F) OUT (F)
<br />GWH-2 ROOF 32"W x 54"D x 70"H 60 140 16 120 1 800 N/A 23.6 760 INTELLIHOT iQ751, Gen II
<br />GWH-3 ROOF 32"W x 54"D x 70"H 60 140 16 120 1 800 N/A 23.6 760 INTELLIHOT iQ751, Gen II
<br />GWH-1 ROOF 32"W x 54"D x 70"H 60 140 16 120 1 800 N/A 23.6 760 INTELLIHOT iQ751, Gen II CSA CERTIFIED, RATED FOR OUTDOOR INSTALLATION, WITH MAINTENANCE-FREE POWERED
<br />ANODE, 120V FOR CONTROLS, IGNITER AND BLOWER, POWER DIRECT VENTING, REMOTE
<br />MONITORING, LEAK DETECTION AND FAULT ALERT, FLAME ROD, THERMAL FUSE, OVERHEAT
<br />PREVENTION DEVICE, FAN SPEED MONITOR, FLUE TEMPERATURE MONITOR, BLOCKED VENT
<br />DETECTOR, DUAL FLAME SENSING, CONDENSATE NEUTRALIZATION KIT, ALARM BELL, COMPLETE
<br />WITH ALL OPTIONS AND ACCESSORIES FOR OPTIMUM PERFORMANCE. PROVIDE WITH
<br />APPROVED SEISMIC RESTRAINT, WEATHER-PROOF FLUE CAP, AND 6"H HOUSEKEEPING PAD.
<br />COORD. ELECTRICAL REQUIREMENTS WITH ELECT. CONTR. INSTALL PER MFR'S
<br />RECOMMENDATIONS. COORDINATE STATUS MONITORING WITH BMS CONTRACTOR.
<br />GAS WATER HEATER SCHEDULE (RES. BLDG.)
<br />NOTES:
<br />1. INSTALL ALL UNITS PER MANUFACTURER'S RECOMMENDATIONS.
<br />2. PROVIDE APPROVED SEISMIC BRACING, 6"H HOUSE-KEEPING PAD.
<br />3. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR PRIOR TO START OF WORK.
<br />4. COORDINATE BMS MONITORING WITH BMS CONTRACTOR PRIOR TO START OF WORK.
<br />5. PROVIDE LISTED MANUFACTURER OR EQUAL.
<br />MARK NO. LOCATION DIMENSIONS
<br />TEMPERATURE
<br />KW FLA VOLT PHASE OP. WT.
<br />(LBS)
<br />STORAGE CAP
<br />(GAL)
<br />RECOVERY
<br />RATE AT 60
<br />DEG-F RISE
<br />(GPH)
<br />GAS INPUT
<br />(CFH)MAKE MODEL REMARKS
<br />EWH-L06
<br />ZONED HOT WATER
<br />REHEAT WATER
<br />HEATERS
<br />LEVEL-06 20"DIA. x38"H 100 140 9 11 460 3 450 30 62 BRADFORD
<br />WHITE
<br />MODEL #
<br />30A-30-3
<br />NOTES:
<br />1. INSTALL ALL UNITS PER MANUFACTURER'S RECOMMENDATIONS.
<br />2. PROVIDE APPROVED SEISMIC BRACING, 6"H HOUSE-KEEPING PAD.
<br />3. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR PRIOR TO START OF WORK.
<br />4. COORDINATE BMS MONITORING WITH BMS CONTRACTOR PRIOR TO START OF WORK.
<br />5. PROVIDE LISTED MANUFACTURER OR EQUAL.
<br />IWH-1
<br />TANKLESS
<br />INSTANTANEOUS
<br />WATER HEATER
<br />FOR L-1
<br />LEVEL-01 6-1/4"H x 9-5/8" x 2-3/4” 60 104 5.6 - 277 1 8 - - CHRONOMITE SR-20L/277 SERVING SINGLE LAVATORY, TANKLESS, UL LISTED, PROVIDE WITH APPROVED SEISMIC
<br />RESTRAINT, RUGGED STEEL HOUSING.
<br />IWH-2
<br />TANKLESS
<br />INSTANTANEOUS
<br />WATER HEATER
<br />FOR MS-1
<br />LEVEL-01 6-1/4"H x 17-1/4" x 2-3/4" 60 120 8.3 - 277 1 8 - - CHRONOMITE M-30L/277 SERVING JANITOR'S FAUCET. TANKLESS, UL LISTED, PROVIDE WITH APPROVED SEISMIC
<br />RESTRAINT, RUGGED STEEL HOUSING.
<br />IN (F) OUT (F)
<br />EWH-L14
<br />ZONED HOT WATER
<br />REHEAT WATER
<br />HEATERS
<br />LEVEL-15 20"DIA. x38"H 100 140 9 11 460 3 450 30 62 BRADFORD
<br />WHITE
<br />MODEL #
<br />30A-30-3 CSA CERTIFIED, REMOTE MONITORING, LEAK DETECTION AND FAULT ALERT, COMPLETE WITH ALL
<br />OPTIONS AND ACCESSORIES FOR OPTIMUM PERFORMANCE. PROVIDE WITH APPROVED SEISMIC
<br />RESTRAINT. COORD. ELECTRICAL REQUIREMENTS WITH ELECT. CONTR. INSTALL PER MFR'S
<br />RECOMMENDATIONS. COORDINATE STATUS MONITORING WITH BMS CONTRACTOR.
<br />ELECTRIC WATER HEATER SCHEDULE (RES. BLDG.)
<br />MARK NO. DESCRIPTION LOCATION DIMENSIONS
<br />TEMPERATURE
<br />KW FLA VOLT PHASE OP. WT.
<br />(LBS)
<br />STORAGE CAP
<br />(GAL)
<br />RECOVERY
<br />RATE AT 60
<br />DEG-F RISE
<br />(GPH)
<br />MAKE MODEL REMARKS
<br />HP KW RPM VOLTS PHASE
<br />DWBP-1
<br />DOM. WATER
<br />TRIPLEX
<br />BOOSTER PUMPS
<br />1 LOT ---BSMT P1 60 HP (20
<br />HP EA.)3500 460 3PH 522 GPM
<br />TOTAL 156 PSIG SYNCRO
<br />FLO
<br />65TG20XXX-6V-XX-
<br />SWF55-1
<br />SYNCROFLO IRONHEART, ANSI/NSF STANDARD 61 ANNEX G CERTIFIED, ULQCZJ.E189340 LISTED, IN STRICT COMPLIANCE WITH LOS
<br />ANGELES MECHANICAL TESTING LABORATORY RR4682. THE PACKAGE SYSTEM SHALL BE THE PRODUCT OF A SINGLE
<br />MANUFACTURER, CONSISTING OF STAINLESS STEEL VERTICAL MULTISTAGE PUMPS, SKID-MOUNTED WITH 304 STAINLESS STEEL
<br />MANIFOLDS, BUTTERFLY AND WAFER CHECK VALVES; ALL BRANCH AND HEADER CONNECTIONS SHALL BE FLANGED OR WELDED,
<br />SECURED WITH ADEQUATE BRACING AND SUPPORTS, SUCTION & SYSTEM DISCHARGE DIGITAL PRESSURE TRANSDUCERS. NEMA
<br />12 CONTROL PANEL WITH MAIN NON-FUSED DISCONNECT, TOUCH SAFE, RATED FUSES FOR EACH VFD, PROGRAMMABLE LOGIC
<br />CONTROLLER (PLC) BASED OPERATION, SEQUENCING BY HORSEPOWER AND/OR PRESSURE-VFD SPEED PROGRAMMING,
<br />CUSTOMER ACCESSIBLE DATA AND FAULT LOGS, DISCRETE VARIABLE FREQUENCY DRIVES, ENCLOSURE-MOUNTED, ALARM HORN,
<br />5.7" HDMI COLOR TOUCHSCREEN WITH REMOVABLE MEMORY CARD AND DATA PORT, MINIMUM 10,000 AMP SCCR RATING,
<br />VENTILATED AND FAN-COOLED ENCLOSURE WITH POSITIVE CABINET PRESSURE. SYSTEM STARTUP BY FACTORY AUTHORIZED
<br />SERVICE AGENT. PROVIDE FIELD-MOUNTED ASME HYDROPNEUMATIC TANK 106 GAL 300 PSIG ASME TO BE LOCATED ON THE ROOF
<br />EQUAL TO WESSELS MODEL FXA-400-HP. COORDINATE BMS MONITORING WITH BMS CONTRACTOR. PROVIDE 6"H CONCRETE
<br />HOUSEKEEPING PAD AND SEISMIC BRACING AS REQUIRED.
<br />BOOSTER PUMP SCHEDULE (RES. BLDG.)
<br />NOTES:
<br />1. INSTALL ALL UNITS PER MANUFACTURER'S RECOMMENDATIONS.
<br />2. PROVIDE APPROVED SEISMIC BRACING, 6"H HOUSE-KEEPING PAD.
<br />3. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL CONTRACTOR PRIOR TO START OF WORK.
<br />4. COORDINATE BMS MONITORING WITH BMS CONTRACTOR PRIOR TO START OF WORK.
<br />5. PROVIDE LISTED MANUFACTURER OR EQUAL.
<br />MARK NO. DESCRIPTION QTY.ON
<br />EMERG.LOCATION
<br />MOTOR DATA CAPACITY
<br />(GPM)
<br />HEAD
<br />EXTERNAL (PSI)
<br />OP. WT.
<br />(LBS)MAKE MODEL REMARKS
<br />© Gensler
<br />Date Description
<br />Project Name
<br />Project Number
<br />Description
<br />Scale
<br />Seal / Signature
<br />2015
<br />NOT FOR
<br />CONSTRUCTION
<br />Tel 949.863.9434
<br />Fax 949-553-1676
<br />4675 MacArthur Court
<br />Suite 100
<br />Newport Beach, CA
<br />92600
<br />USA
<br />Job No.:
<br />Contact:
<br />www.glumac.com
<br />18200 Von Karman Ave., Suite 100
<br />Irvine, CA 92612
<br />T. 949.833.8190
<br />12" = 1'-0"
<br />6/12/2024 7:39:09 PM
<br />BIM 360://007.3757.000 - Caribou Industries - 3rd & Broadway/3RD-B_MEP_WEST_R20.rvt
<br />R1-P0.3
<br />PLUMBING SCHEDULES
<br />21US00608
<br />3rd & Broadway West
<br />1103 North Broadway
<br />Santa Ana, CA 92701
<br />21US00608
<br />TG
<br />1 9/21/2021 REISSUE FOR PLAN CHECK
<br />2 01/18/2022 REISSUE FOR PLAN CHECK
<br />4 06/17/2024 REVISION TO PERMIT
<br />4
<br />EOR: SEAN AGUON
<br />LIC#: M41274
<br />10/11/2024
|